M-25 GRADE CONCRETE MIX DESIGNDATAS REQUIRED:
1. Characteristics compressive strength @ 28 days=25 N/mm22. Maximus size of Aggregate
=20mm
3. Required slump
=100mm
4. Type of exposure
=severe
5. Chemical Admixture
=Nil
6. Absorption
a. 20mm
=0.6 %
b. NRS
=1.5 %7. Specific gravitya. Cement
=3.15
b. 20mm
=2.79c. NRS
=2.65 Zone III1. Target mean strength
fck=fck + 1.65s
=30 + 1.65(4)fck=36.6 N/mm22. Selection of Water-Cement ratio
From IS:456-2000 table 5, max. free w/c for M25 = 0.53. Selection of Water content
From IS:10262-2009 table 2, max water content = 186 Kg
For 100mm slump water content to be increased by 6 % = 197 Kg
4. Calculation of Cement content
Cement content = 197/0.5 = 388 Kg.
From table 5, min. cement content for M25 = 300 Kg.
388 > 300 Kg.
5. Proportion of volume of CA and FA
From IS:10262-2009 table 3,
vol of CA per unit vol of total aggregate for zone III = 0.64
vol of FA = 1-0.64 = 0.36
6. Mix calculations
a) Vol of Concrete=1 m3b) Vol of Cement
=0.123 m3c) Vol of water
=0.197 m3d) Vol of all in aggregate=0.68 m3e) Mass of CA
=1214 Kg
f) Mass of FA
=650 Kg
Mix proportion for 1 m3
Correction for AbsorptionCement= 388 Kg
388 Kg
Water
= 197 Kg
201 Kg20mm
= 1214 Kg
1207 KgNRS
= 650 Kg
640 Kg