m100m proportional motor actuator - johnson...

21
Installation Sheets Manual 121 Motor Actuators Section M Technical Bulletin M100M Issue Date 0493 © 1993 Johnson Controls, Inc. 1 Part No. 34-636-127 RevFigure 1: M100 Motor Actuator The design of the M100M is to provide direct interface with the following Honeywell Controllers: 1. All Series 90 135 ohm slidewire controllers. 2. W973 and W7100 Series Controllers for modulating valves in heating, cooling and water source economizer applications. In addition, W973 and W7100 Series Controllers can be accommodated in air-to-air economizer damper applications when using a diode (1N4002) and resistor (620 ohm, 1/2 watt). Note: The M100M is not a direct replacement for air side economizers with minimum position and outside air changeover logic as Honeywell wiring diagrams indicate. Refer to the wiring section for logic connections. The following table lists the torque rating for each model (MXXXMYZ—where X = Model No.): Table 1: Torque Rating MODEL DESCRIPTION M110 25 in·lb (2.8 N·m) Torque with Spring Return M120 35 in·lb (4.0 N·m) Torque, Non-Spring Return M130 50 in·lb (5.6 N·m) Torque with Spring Return M100M Proportional Motor Actuator R81M Interface Board Application Details Torque

Upload: vutuyen

Post on 14-Feb-2019

232 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

Installation Sheets Manual 121Motor Actuators Section M

Technical Bulletin M100MIssue Date 0493

© 1993 Johnson Controls, Inc. 1Part No. 34-636-127Rev—

Figure 1: M100 Motor Actuator

The design of the M100M is to provide direct interface with the followingHoneywell Controllers:

1. All Series 90 135 ohm slidewire controllers.

2. W973 and W7100 Series Controllers for modulating valves in heating,cooling and water source economizer applications.

In addition, W973 and W7100 Series Controllers can be accommodated inair-to-air economizer damper applications when using a diode (1N4002)and resistor (620 ohm, 1/2 watt).

Note: The M100M is not a direct replacement for air side economizerswith minimum position and outside air changeover logic asHoneywell wiring diagrams indicate. Refer to the wiring sectionfor logic connections.

The following table lists the torque rating for each model(MXXXMYZ—where X = Model No.):

Table 1: Torque RatingMODEL DESCRIPTION

M110 25 in·lb (2.8 N·m) Torque with Spring Return

M120 35 in·lb (4.0 N·m) Torque, Non-Spring Return

M130 50 in·lb (5.6 N·m) Torque with Spring Return

M100M Proportional Motor Actuator R81M Interface Board

Application Details

Torque

Page 2: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

2 M Motor Actuators—M100M Proportional Motor Actuator

M140 75 in·lb (8.5 N·m) Torque, Non-Spring Return

M150 150 in·lb (17 N·m) Torque, Non-Spring Return

Page 3: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 3

The following table lists the input voltage options available(MXXXMYZ—where Y = Power Source Option):

Table 2: Input Voltage OptionsOPTION DESCRIPTION

A 120 VAC

D 240 VAC

G 24 VAC

H 24 VAC 1:1Isolation

The following table lists the factory mounted accessories available(MXXXMYZ—where Z = Accessory Option):

Table 3: Factory Mounted AccessoriesOPTION DESCRIPTION

A No auxiliary switch

B One SPDT switch S91DJ-1 installed on auxiliary end of M100

C Two SPDT switches S91EJ-1 installed on auxiliary end of M100

D S91 Potentiometer (1000 ohm) installed on auxiliary end of M100

The M100M horizontal terminal board is divided into two sections,Series 90 and W7100/W973.

The labeling of the Series 90 section contains Honeywell terminaldesignations R, B, and W. The wiring for a Series 90 Controller is colorfor color in heating applications and reversing W and B in coolingapplications.

For heating applications, as the wiper arm R on the Series 90 Controllermoves toward terminal B, the motor drives clockwise as viewed from theload end. As the wiper arm moves towards terminal W, the motor drivescounterclockwise. All Series 90 overrides and minimum positionnetworks are applicable.

The labeling of the W7100/W973 section is with terminal designationsR1/T1 and W1. The labels of the W973 terminals are RH and WH forheating, RC and WC for cooling, and R and W for economizerapplications. The labels of the W7100 terminals are R and W for heating,cooling and economizer applications. Terminals R1/T1 and W1 respondto the control signal generated by the W973/W7100.

Note: The M100M must be the master motor actuator. It is not to be aslave.

Power Source

Factory MountedAccessories

Control Input

Page 4: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

4 M Motor Actuators—M100M Proportional Motor Actuator

The M100M can slave up to ten M100J slave actuators. Each slaveactuator must have a separate transformer. Do not mix Johnson Controlsand Honeywell actuators in a master/slave application. All slave actuatorsmust be of the same manufacturer as the master actuator.

The voltage between terminals T and X (when jumpered from XD or XR)is approximately 6 VDC at zero rotation of the output shaft. Full rotationof the output shaft occurs when the voltage between T1 and X isapproximately 10 VDC.

The M100M Motor Actuator travel is factory set at 90 degrees and isadjustable from 65 to 270 degrees.

The timing of the actuator is 38 seconds for 90 degree rotation and60 seconds for 160 degree rotation.

Travel and Timing

Page 5: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 5

LOAD END

10° (AX)

Direction ofDrive Rotation

COM to CCW Shorted

Drive Shaft

Y20A1-15

KeywayZero Reference Position

Direction of DriveRotation COM to CW Shorted

Figure 2: Direction of Rotation

All reference to the direction of rotation is when viewing the load end asstamped on the actuator housing shown in Figure 2. From this view, theCCW limit is the zero reference.

The actuators are factory set at zero position which is 10 degreesclockwise from vertical (see Figure 2) and for 90 degrees clockwise travel.When using Y20 linkage kits, each 15 degrees of actuator rotation resultsin 0.1 inch (2.54 mm) of linear movement of the rack assembly.

1.6943

4 Mounting Slots

.87522.23

5.64143 4.88

124

4.00102

4.81122

.5614

.2666.76

7.28185

.4512

1.5038

1.3133

3.3184

4.65118

.297

.3810

.03

.76

5.81148

1.7545

.164

4.38111

2.5064

1.2532

4 Holes

1.2732

.9725

.5113

5.13130

2.5665

Top View

Load End Auxiliary End

Side ViewM100PB13.drw

Figure 3: M100 with Spring Return Dimensions

Direction ofRotation

Dimensions

Page 6: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

6 M Motor Actuators—M100M Proportional Motor Actuator

Figure 3 shows the dimensions for a standard M100 Series MotorActuator. Additional space is to be allowed for options such as a switchkit (two inches additional length at auxiliary end).

Installation Procedures

screwdriver, Phillips-head (No. 1 or 2 tip)

screwdriver, flat-blade, 1/8 inch tip

Note: All Series M100 Motor Actuators are for use only as operatingcontrols. Where an operating control failure would result in personalinjury and/or loss of property, it is the responsibility of the user to adddevices (safety, limit controls) or systems (alarm, supervisory systems)that protect against and/or warn of control failure.

• Follow NEC and local electrical codes.

• Disconnect all power supplies.

• Observe the following ranges and limitations:

Power Requirements 24 VAC at 50/60 Hz, 25 VA spring return, 20 VA non-spring return

Ambient OperatingConditions

-40° to 125°F (-40° to 52°C), 90% RH non-spring return

-35° to 125°F (-37° to 52°C), 90% RH spring return

Ambient StorageConditions

-40° to 125°F (-40° to 52°C), 90% RH

• Do not install the motor actuator in atmospheres with explosive vaporsor escaping gases, or where vapors having deteriorating propertiesmight attack the actuator’s metal parts.

• Wiring into return air systems should be sealed to prevent aspiration ofcorrosive air into the actuator.

Upright mounting of the motor actuator is required.

When mounting on a valve, do not mount below the horizontal plane ofthe valve piping to prevent damage to the motor actuator if the valve leaksor develops condensation.

Valve medium temperatures above 250°F (121°C) are permissible only ifthe maximum ambient temperature at the motor actuator is less than 105°F(41°C).

Locate the motor actuator where the shaft and wiring terminals are accessible.

Follow installation procedures for the linkage kit used to couple the motoractuator and the controlled device.

Tools Needed

Precautions andCodeRequirements

Mounting

Page 7: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 7

When not utilizing a damper or valve linkage kit, use four 1/4 x 1 inchbolts for mounting the motor actuator.

Perform travel adjustments as described in the Travel Adjustment section.

To install the R81 interface kit in a Series M100X Base Motor Actuator orremove and/or replace the electronic circuit boards in an existing SeriesM100 Motor Actuator, proceed as follows:

! CAUTION: Disconnect the electrical power supply beforeattempting to remove the wiring connections and theboards to prevent possible electrical shock or damageto the equipment.

1. Remove the motor actuator’s top cover by loosening the two coverscrews.

2. Verify that power is removed from the unit and disconnect all wiringconnections to the terminal board.

3. Loosen the bracket screw and remove the bracket.

4. Pull the vertical board straight upward. Be careful not to bend ordamage the pin terminals.

5. Remove the two screws from the terminal board.

6. Remove the terminal board by grasping the receptacles and liftingstraight upward being careful not to bend or damage the pin terminals.

1. Install the terminal board by carefully placing the terminal receptaclesonto the pin terminals.

TerminalBoard

Terminal Board Screws

Receptacles

Pin Terminals

M100C01

R81 Installation

Removing Boards

Installing Boards

Page 8: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

8 M Motor Actuators—M100M Proportional Motor Actuator

Figure 4: Terminal Receptacles

2. Fasten the board in place using the screws that are supplied with theR81 kit.

Vertical Boardwith Attached Cover

M100FO1

TerminalReceptacles

PinTerminals

Figure 5: Installing Vertical Board

3. Install the vertical board by carefully placing the terminal receptaclesonto the pin terminals as shown in Figure 5.

Note: Align all pins within the receptacle.

M100F02

Bracket

Figure 6: Installing Bracket

Page 9: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 9

4. Place the bracket, supplied with the motor actuator, over the verticalboard and fasten the bracket in place with captive screw as shown inFigure 6.

MODEL NO.

M150 X GA-1Base Actuator

Requires R81 Electronic Board Kit

MThis Model Contains

R81MAA-I Electronic Board Kit

Identification Label

M100M01.drw

Figure 7: Installing Identification Label

5. Install the adhesive backed label supplied in the R81 kit.

IMPORTANT: As shown in Figure 7, locate the label on the insulationbarrier. The letter on the R81 label will complete thenumber that identifies the Series M100 with the R81installed.

6. Install the motor actuator.

7. Make control and 24 VAC wiring connections.

8. Turn on power supply.

9. Adjust, and check operation.

! CAUTION: Disconnect the electrical power supply before wiringthe motor actuator to avoid possible electrical shockor damage to the equipment. Always disconnect the24 VAC power supply before attempting to make anywiring connections.

Control Wiring

Page 10: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

10 M Motor Actuators—M100M Proportional Motor Actuator

Make all wiring connections using copper conductors only. Wire inaccordance with National Electric Code and local regulations.

M100F04

WiringCompartment

Figure 8: Attaching Wiring Junction Box To M100

Make all splices in junction boxes using approved solderless connectors,or by soldering and then taping the connections. Locate all splicing andexcess wiring outside the motor actuator wiring compartment. If desired,add a standard electrical box to the wiring compartment of the motoractuator as shown in Figure 8.

Runs less than 50 feet (15 m) long require no shielded cable for theVDC/mA control wiring. Avoid running low voltage control wiring in thesame conduit as line voltage wiring or other conductors that supply highlyinductive loads (contactors, coils, motors, generators, etc.).

If the control wiring is over 50 feet (15 m) long, run in a common conduit,or near inductive loads, we recommend the use of shielded cable. Use 22AWG gauge, Beldfoil 8761 or equivalent for runs up to 250 feet (76 m).For 250 feet (76 m) to 500 feet (152 m) runs, use 18 AWG gauge Beldfoil8760 or equivalent. Connect the shield only at the controller. Do notconnect shield to any other point.

Page 11: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 11

24 VAC

M100MMotor

ActuatorPowerSupply

B R W WI

B R W

Series 90

Transformer

R1T1

T2

M100M02.drw

Figure 9: Typical Heating Application with Series 90 Controller

24 VAC

M100MMotor

ActuatorPowerSupply

B R W WI

B R W

Series 90

Transformer

R1T1

T2

M100M03.drw

Figure 10: Typical Cooling Application with Series 90 Controller

To connect the wires:

1. Loosen the two screws securing the top cover and remove the topcover for access to the wiring terminals.

2. Use a hammer and punch to drive out one of the access hole plugs.

3. Install the conduit connector to the motor actuator and secure using theconduit nut provided with the connector.

4. Connect the controller to the terminals located in the wiringcompartment.

5. Connect 24 VAC to terminals T1 and T2.

Note: To avoid potential miswiring or control signal problems, the use ofseparate transformers on each M100 is required.

Note: For further information on any of the controllers illustrated,reference the applicable controller literature.

Wiring Diagrams

Page 12: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

12 M Motor Actuators—M100M Proportional Motor Actuator

24 VAC

M100MMotor

ActuatorPowerSupply

B R W WI

B R W

Series 90

Low Limit

BRW

Transformer

280 ohm minimumT991T915

135 ohmsT921

T92T991T915

Note: 100% Override Limit drives motor CW.

R1T1

T2

24 VAC

M100MMotor

ActuatorPowerSupply

B R W WI

B R W

Series 90

Transformer

280 ohm minimumT991T915

Note: 67% Override Hi Limit drives motor CCW, Low Limit drives motor CW.

135 ohmsT961

T92T991T915

280 ohm minimumT991T915

1

2

1 2

If not using HI Limit,connect wire as shown.If not using LO Limit,connect wire as shown.

LOW Limit

B R W

B R W

HI Limit

R1T1

T2

M100M04.drw

Figure 11: Proportional Override with Series 90 Controller

24 VAC

M100MMotor

ActuatorPowerSupply

B R W

Series 90

Minimum Position

BRW

Transformer150 or 300 ohmQ209B, Q209C

135 ohmsT921

T92T991T915

Note: 50% Override with 150 ohm controllers 67% Override with 300 ohm controllers

R1T1

T2

B R W WI

M100M05.drw

Figure 12: Minimum Positioning with Series 90 Controller

Page 13: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 13

24 VAC

M100MMotor

ActuatorPowerSupply

Transformer

B R W WI

B R W

Series 90

R1T1

T2

PowerSupply

Transformer

98

10X

M100J

T1

T2

24VAC

PowerSupply

Transformer

98

10X

M100J

T1

T2

24VAC

M100M06.drw

Figure 13: Typical Master/Slave Heating Application

Note: Slave actuators must be equipped with R81JAA-1 boards. Up toten slaves may be accommodated by a single 135 ohm controller.Use separate transformers for each actuator.

Figure 14: Typical Heating/Cooling with W7100 Controller

24 VAC

M100MHeating

MotorActuator

PowerSupply

Transformer

B R W WI

R1T1

T2

HTG/CLG

24 VAC

M100MCoolingMotorActuator

B R W WI

R1T1

T2

PowerSupply

Transformer

1

2

3Changeover Control DPDT(Not all contacts shown)

PowerSupply

Transformer

24 VAC

B RWY

TR

TR GND

W7100

M100M07

Page 14: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

14 M Motor Actuators—M100M Proportional Motor Actuator

ECON

24 VAC

M100MCoolingMotorActuator

B R W WI

R1T1

T2

PowerSupply

Transformer

WR

BChangeover Control SPDT

GNDW7100

TR

TR

B R WY

M100M08

Figure 15: Typical Water Economizer with W7100 Controller

Figure 16: Air-Side Economizer with Remote Minimum Positioning andChangeover with W7100 Controller

ECON

12

3 Changeover Control SPDT

TR

TR GNDW7100

24 VACPowerSupply

Transformer

M100MMotorActuator

B R W WI

R1T1

T2

B R WY

TimeClock

24 VACPowerSupply

Transformer

620 ohm, 1/2W IN4002

PowerSupply

Transformer 98

10X

M100J

T1

T2

24VAC

B R W

Minimum Position

M100MA09

Page 15: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 15

Note: Slave actuators must be equipped with R81JAA-1 boards. Up toten slaves may be accommodated by a single 135 ohm controller.Use separate transformers for each actuator.

HTG/CLG

TR

TRGND

W973 24 VACPowerSupply

Transformer

M100MMotor

Actuator

B R W WI

R1T1

T2

Transformer

24 VACPowerSupply

BRWPowerSupply

Transformer

9810X

M100J

T1

T2

24VAC

PowerSupply

Transformer

98

10X

M100J

T1

T2

24VAC

M100M10.drw

Figure 17: Master/Slave Valve Control with W973 Controller

Note: Slave actuators must be equipped with R81JAA-1 boards. Up toten slaves may be accommodated by a single 135 ohm controller.Use separate transformers for each actuator.

ECON

12

3 Changeover Control SPDT

TR

TRGNDW973

24 VACPowerSupply

Transformer

M100MMotorActuator

B R W WI

R1T1

T2

B R WY

TimeClock

B R W

Minimum Position

Transformer

24 VAC

PowerSupply

620 ohm, 1/2W IN4002

R W

Y

PowerSupply

Transformer 98

10X

M100J

T1

T2

24VAC

W974B

M100M11.drw

Figure 18: Air-Side Economizer with Remote Minimum Positioning andChangeover with W973 Controller

Page 16: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

16 M Motor Actuators—M100M Proportional Motor Actuator

Note: Slave actuators must be equipped with R81JAA-1 boards. Up toten slaves may be accommodated by a single 135 ohm controller.Use separate transformers for each actuator.

Calibration Procedures

The travel adjustment potentiometer mounted on the R81M horizontalterminal board enables positioning the M100 Actuator from 65 to270 degrees rotation. Changing the travel adjustment affects the clockwiselimit. Turn the adjustment clockwise to increase travel andcounterclockwise to reduce total travel.

To make adjustments, use the following procedure or refer to theappropriate valve or damper linkage instruction.

1. Set the travel adjustment potentiometer fully counterclockwise.

2. Remove all control wires.

! CAUTION: Disconnect the electrical power supply beforeattempting to remove the wiring connections and theboards to prevent possible electrical shock or damageto the equipment.

3. Apply 24 VAC between R1/T1 and T2.

4. Jumper terminals R and B to drive the motor to the fully clockwiseposition as viewed from the load end.

5. Slowly rotate the travel adjustment potentiometer clockwise toincrease motor rotation until the corresponding valve or damper is inthe desired position.

6. Remove the jumper between terminals R and B, enabling the motor toreturn to the full counterclockwise position as viewed from the loadend.

7. Repeat steps four through six to provide proper stroking.

8. Turn off the 24 VAC and remove the 24 VAC from terminals R1/T1and T2. Connect all control wires.

Travel Adjustment

Page 17: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 17

Page 18: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

18 M Motor Actuators—M100M Proportional Motor Actuator

Troubleshooting Procedures

M100MMotorActuator

B R W WI

R1T1

T2

DPDTRelay

W973/W7100CCW Override

M100MMotorActuator

B R W WI

R1T1

T2

SPDTRelay

W973/W7100CW Override

SPDTRelay

M100MMotorActuator

B R W WI

R1T1

T2

Series 90CCW Override

M100MMotorActuator

B R W WI

R1T1

T2

SPDTRelay

Series 90CW Override

M100M12.drw

Figure 19: Configurations for Remote Relay Override

Before manually overriding the motor actuator, disconnect any controlwiring and then jumper terminals R and B for CW direction, andR and W for CCW direction.

To checkout the system:

1. Connect all control wiring and apply 24 VAC.

2. Adjust the controller setpoint above and below the ambienttemperature, making sure that the motor correctly drives open andclosed. Refer to Honeywell’s controller checkout procedure ifnecessary.

3. If the motor does not drive correctly, check the motor operation withSteps 4 through 10. If the motor drives correctly, proceed to Step 11.

4. Remove all control wiring.

Remote RelayOverride Wiring

Checkout Series90 Controller

Page 19: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 19

! CAUTION: Disconnect the electrical power supply beforeattempting to remove the wiring connections and theboards to prevent possible electrical shock or damageto the equipment.

5. Apply 24 VAC between R1/T1 and T2.

6. Jumper terminals R and B to drive the motor to the fully clockwiseposition as viewed from the load end.

7. Remove the jumper from between terminals R and B enabling themotor to return to the full counterclockwise position as viewed fromthe load end.

8. If the motor does not drive, check the 24 VAC power supply betweenR1/T1 and T2.

9. If the supply power wiring checks out, replace the R81M board andrepeat the checkout procedure.

10. If the motor still does not drive properly, replace the base actuator.

11. If the motor drives properly, proceed to the controller checkoutprocedure. Refer to Honeywell’s Series 90 literature.

To check system (motor and controller) operation, proceed as follows:

1. Connect all control wiring and apply 24 VAC.

2. Adjust the controller set point above and below the ambienttemperature, making sure that the motor drives open and closedcorrectly. Refer to Honeywell’s controller checkout procedure ifnecessary.

3. Set a voltmeter to the 10 VDC scale and place the leads acrossterminals R1/T1 (-) and W1 (+).

4. Check for nominal 0.5 to 1.4 VDC. At 0.5 VDC or less, the motorshould be fully clockwise. At 1.4 VDC or more, the motor should befully clockwise.

5. If 1.4 VDC is present and the motor does not drive, check the motoroperation.

6. Remove all wiring.

! CAUTION: Disconnect the electrical power supply beforeattempting to remove the wiring connections and theboards to prevent possible electrical shock or damageto the equipment.

CheckoutW7100/W973Controllers

Page 20: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

20 M Motor Actuators—M100M Proportional Motor Actuator

7. Apply 24 VAC to R1/T1 and T2.

8. Jumper terminals R and B to drive the motor to the fully clockwiseposition as viewed from the load end.

9. Remove the jumper from between terminals R and B enabling themotor to return to the full counterclockwise position as viewed fromthe load end.

10. If the motor does not drive, check the 24 VAC power supply betweenR1/T1 and T2.

11. If the supply power wiring checks out, replace the R81M board andrepeat the checkout procedure.

12. If the motor still does not drive properly, replace the base actuator.

13. If the motor drives properly, proceed to the controller checkoutprocedure. Refer to Honeywell’s W7100/W793 literature.

The drive motor and gear train are immersed in oil and sealed in a die castcase. Therefore, maintenance is not necessary.

Make no field repairs except for replacement of R81 plug-in interface kits.For repair parts or replacement, contact the nearest Johnson ControlsCommercial Systems wholesaler or Systems and Services Division branchoffice.

Replacement

Page 21: M100M Proportional Motor Actuator - Johnson Controlscgproducts.johnsoncontrols.com/met_pdf/121357.pdf · Installation Sheets Manual 121 Motor Actuators Section M ... M100M Proportional

M Motor Actuators—M100M Proportional Motor Actuator 21

Notes

Controls Group FAN 121507 E. Michigan Street Installation Sheets ManualP.O. Box 423 Printed in U.S.A.Milwaukee, WI 53201