lv switchgear sen plus - minor elektromaterijali plus presentation za sajt2.pdf · sen plus (tta) a...
TRANSCRIPT
LV SG Type-Tested AssemblySEN Plus (TTA)
Rated operational voltage: Ue 690 V AC 40-60 Hz, 600 V DC
Rated insulation voltage : Ui 1000 V
Rated current horizontal busbar: Ie 1000 A - 7600 A (3P, 4P)Rated current vertical busbar: 850 A - 1900 A (3P, 4P)Peakwithstand currrent: Ipk 220 kAShorttime withstand current: Icw 100 kA, 1 seс
Arc proof design Test Voltage 420V, Prospective short circuit current 50kA,Test duration 100ms MCC / 200ms Power Center
Standards: IEC 61439-2, IEC 60439-1, МЭК 60439-1, ГОСТ Р 51321.1-2000, VDE 660 teil 500,IEC/TR 61641:2008-01, МЭК 61641
Electrical parameters
3 /GE /
Dimensions: height: 2000, 2200 mmwidth: 400, 500, 600, 800, 1000, 1200 mmdepth: 600, 800, 1200 mm
Degree of protection: IP30 - IP54 IEC 60529Form of internal separation: up to 4b IEC 60439-1Color: RAL 7035
Mechanical parameters
LV SG Type-Tested AssemblySEN Plus (TTA)
4b
4 /GE /
5 /GE /
Motor Control CenterMCC
Type A, C
Power Center
MCCType B
Empty panel
LV SG Type-Tested AssemblySEN Plus (TTA)
6 /GE /
Main Distribution Board(Power center)
EntelliGuard, M-Pact, Record Plus, Dilos,2 breakers up to 2500 A per columnBuscoupler up to 6400ACable entry from bottom or topMeasurement instruments mounting plates3 separate or one big compartment door
Empty panels
full height mounting platewith or without horizontal busbarscorner panelwidth 600 or 800mm (400, 500 optionally)
LV SG Type-Tested AssemblySEN Plus (TTA)
7 /GE /
Plug-in modules:Height 4E - 36E (E = 25mm)Max. 20 modules in a panelMax. nominal current of a module 800A
Auxiliary plug 16 poles
Withdrawable modulesModule height 5E - 36EMax. 16 modules in a panelMax. nominal current of module 630AIncoming plug withdrawable, outgoing
pluginAuxiliary plug 24 polesAll positions (On, Test, Stand-By) possible when door is closed
Fuesed Load Break Switches type HSE
LV SG Type-Tested AssemblySEN Plus (TTA)
Motor Control Center (MCC)
8 /GE /
Fixed modules:Module height 5E - 36E (E = 25mm)Max. 16 modules in a panelMax. nominal current of module 630A
VPS (plug-in)For modular DIN-rail devicesModule height 24E, 36E, 48E
Motor Control Center (MCC)
LV SG Type-Tested AssemblySEN Plus (TTA)
Busbars system - overview
LV SG Type-Tested AssemblySEN Plus (TTA)
Panel depth: 600 mm 800 mm 1200 mm
BB position:
Top
Middle
Bottom
Rated current: up to 2500A up to 4000A up to 7600A
10 /GE /
11 /GE /
Busbars system - overview
LV SG Type-Tested AssemblySEN Plus (TTA)
Current Cross-Section Icw
A mm kA
1000 50x10 50
1250 60x10 65
1600 80x10 80
2000 100x10 100
2500 2/80x10 100
3200 2/100x10 100
4000 3/100x10 100
5000 (3+3)x100x10 100
7600 (3+4)x100x10 100
12 /GE /
Panel derating
LV SG Type-Tested AssemblySEN Plus (TTA)
PanelkVA A kA Rated current frame W/D
@ 400V @ 6% A size [mm] 35°C 50°C630 914 15 1000 1 500/600 1000 1000
800 1200 19 1250 1 500/600 1250 1100
1000 1450 24 1600 1 500/600 1600
1000 1450 24 2000 1 500/600 1600
1250 1800 30 2000 1 500/600 1900
1250 1800 30 2500 2 600/600 1850
1600 2350 38 2500 2 600/600 2350
1600 2350 38 3200 2 800/800 2550
2000 2900 48 3200 2 800/800 2800
2000 2900 48 4000 2 1000/800 3600
2500 3600 60 4000 2 1000/800 3900 3600
3000 4350 72 5000 3 1000/1200 5000 4700
3600 5250 87 6300 3 1000/1200 6000 5400
4000 5800 96 6300 3 1000/1200 6000
ambient temperatureTransformer derating @
IP30, ventilated panel, withdrawable breaker, 3 pole
Circuit Breaker
13 /GE /
Impossible to open doors if a breaker is ON
Impossible to withdraw or put in a module if an incoming plug is ON or TEST
Impossible to switch ON a breaker if an incoming plug is in OFF position
Impossible to operate a wormgear if the door is open (оption)
Up to tree padlocks on a wormgear
Optimum of Safety and AvailabilityWithdrawable modules – interlocks
LV SG Type-Tested AssemblySEN Plus (TTA)
1
23
4
5
6
7
89
10
14 /GE /
LV SG Type-Tested AssemblySEN Plus (TTA)
SafetyWithdrawable module – position of a plug and a module
On On On On
Off On On On
Off On On Off
Off Off Off Off
Off Off Off Off
ON
Stand-by
OFF
Removed
TEST
inserted
inserted
withdrawn
rejected
inserted
Main circuit plugs Control InterlockIncoming Outgoing plug on wormgear
15 /GE /
Type tests
All tests in independent, certified test laboratoriesTested standard configurations of switchgears
All motor starter combinations are testedaccording coordination type II requirementsSummary of test resultsDegree of protection tested up to IP 54
LV SG Type-Tested AssemblySEN Plus (TTA)
16 /GE /
Seismic qualification
LV SG Type-Tested AssemblySEN Plus (TTA)
qualification according to UBC 97Arig = 0.4g / 0.30g hor. / vert.A flex = 1.0g / 0.75g hor. / vert.
SEN Plus fulfills GE Energy global specs for electrical equipment for Gas Turbines
qualification according to IEEE 344(Seismic design for Nuclear Power Generation Stations)RRS = 2.80g horizontal & vertical
Test result exceeds requirements for UBC 97 -seismic zone 4(>7 Richter magnitude,>IX MSK)
Smart simple design
installation of all main components from the frontminimized number of different screws (only one screw driver)use of snap-in technology (e.g. IP20 shroud)pre-punched cut-outs (e.g. cubicle to cubicle wiring)use of „simple connections“ (e.g. fixation of module separation plate)Modules from 4E to 12E produced out of 1 sheet metal plateone basic MCC column for all outgoing functionssimple interlocking of plug-in modules...
LV SG Type-Tested AssemblySEN Plus (TTA)
17 /GE /
Technical documentation
Brochure
18 /GE /
User manual
Overview –Type test reports
LV SG Type-Tested AssemblySEN Plus (TTA)
Assembly Documentation