  • 8/3/2019 LV Switch Gear Assemblies

    1/24

    Type-tested

    low voltage switchgear

    assembliesup to 7300 A

    Product informationas at: 6/2005

    Industrial Electrical Power Distribution Systems

    NEW! SAS low voltage switchgear assemblieswith HENCONNECT plug-in technology

    for power functional units

  • 8/3/2019 LV Switch Gear Assemblies

    2/242

    Type-tested quality

    The market lead which we and our partners are able to command

    tests on a solid foundation of a consistently high standard of quality.

    Hensel meets the highest demands of ISO 9001 with all its operating

    areas.

    It is both a requirement and a promise to do everythingnot only to ensure the high level of quality of our products

    in the future but also to extend it.

    It can be taken for granted that we are working on the

    continued optimisation of operating processes

    on all levels.

    Your competent partner

    Temperature rise test IPH in Berlin

    2

    Lennestadt-Altenhundern factory

    Grimma factory

    Competencein low voltage switchgear assemblies

    Hensel has been producing high quality low voltage switchgear

    assemblies for industry, commerce and functional buildings

    for more than 40 years.

    Innovative systems made from insulating material and sheet steel have made

    us into a leading supplier in the distribution of electrical energy.

    Our switchgear manufacturing plants in Lennestadt and Grimma offer a high

    level of flexibility and guarantee a reliable standard of quality.

    Contents

    System overview and technical data

    Mi 1000

    SV 250

    MC 630

    SAS 600/600i

    SAS 2000/2000i

    SAS 5000

    SAS low voltage switchgear assemblies with

    HENCONNECT plug-in technology for power functional units

    SMC 7000

    References

    Pages 4 - 5

    Page 6

    Page 7

    Page 8

    Page 9

    Pages 10

    Page 11

    Pages 12 - 17

    Page 18

    Pages 19 - 24

    NEW!

  • 8/3/2019 LV Switch Gear Assemblies

    3/243

    Type-tested switchgear assemblies

    Technical features:

    Rated current: up to 7300 A

    Rated voltage: 690 V AC

    Rated peak withstand current: up to IPK = 330 kA

    Network systems: TN, TT, IT

    Protection class: II totally insulated up to 2500 A

    I with protective conductor up to 7300 A

    Degree of protection: IP 30 to IP 65

    During the development stage,

    we place particular value on a

    simple and time-saving installation

    of the switchgear assembly on siteas well as sufficiently large

    wiring compartments.

    Our servicesOur understanding of partner-based co-operation extends

    beyond the supply of products.

    We are pleased to advise you on the creation of concepts for the

    distribution of electrical energy.

    - Calculations within the network (short-circuit currents, selectivity etc.)

    can be offered by us if required

    - Configuration of the low voltage switchgear assemblies

    according to your ideas and local conditions

    - Factory inspections and customer acceptance tests after consultation

    Your competent partner

  • 8/3/2019 LV Switch Gear Assemblies

    4/244

    Mi 1000 SV 250 MC 630

    Protection class II (totally insulated) II (totally insulated) I (earthed)

    Material Insulating material Sheet steel Sheet steel

    Type of assembly Box-type Single cabinet Modular cabinet

    Colour RAL 7032, slate grey IP 41/43 = RAL 9016,

    traffic whiteIP 54 = RAL 9002,

    greyish white

    RAL 7032, slate grey

    Operating and ambient conditions

    For indoor use x x x

    For outdoor use with protection against

    ambient conditions

    Ambient temperature

    Average value over 24 hours + 35 C + 35 C + 35 C

    Maximum value + 40 C + 40 C + 40 C

    Minimum value - 5 C - 5 C - 5 C

    Relative humidity 50% at 40C 50% at 40C 50% at 40C

    short-time 100% at 25C 100% at 25C 100% at 25C

    Dimensions

    Width mm in 300 mm grid 300, 550, 800, 1050,

    1300*(*wall-mounted cabinet only)

    350, 600

    Height (wall-mounted cabinet/wall-mounted distribution board) mm in 300 mm grid 650, 800, 950, 1100,

    1250, 1400

    650, 850, 1050

    Height (floor-mounted cabinet with base) mm in 300 mm grid 1980

    Height (floor-mounted cabinet without base) mm in 300 mm grid 1850 1400, 1750

    Depth mm 170, 214, 255, 299

    + mounting frame =

    62,5

    IP 41 = 160 (up to 63

    A),

    IP 41 = 210,

    IP 54 = 225

    250

    + mounting frame =

    62,5

    Combinable In all directions No Laterally and at the top

    Busbars Rated current [Ie] / Rated peak withstand current [IPK] / Rated short-time withstand current [ICW]

    250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA)

    400 A (IPK 30 kA/ICW 15 KA) 400 A (IPK 30 kA/ICW 15 KA)

    630 A (IPK 45 kA/ICW 21 KA) 630 A (IPK 45 kA/ICW 21 KA)1000 A (IPK 75 kA/ICW 36 KA)

    N/PEN conductor

    EMC compliant in the area of phase conductors Standard Standard Standard

    Same current carrying capacity as phase conductors Standard Standard Standard

    Higher current carrying capacity than phase conductors

    Circuit-breaker 160-630 A

    Fixed part x x x

    Removable part

    Withdrawable part

    Circuit-breaker 800 A up to maximum rated current

    Fixed part

    Withdrawable part

    Switch-disconnector with strip type HRC fuse

    Removable part

    Voltage values

    Rated operating voltage [Ue] AC 690 V AC 400 V AC 690 V

    Rated insulation voltage [Ui] AC 690 V AC 400 V AC 690 V

    Degree of pollution 3 3 3

    Overvoltage category III III III

    Standards and regulations

    IEC 60 439-1/EN 60 439-1 Type-tested low voltage switchgear and control-

    gear assembly (TTA)

    x x x

    IEC 439-3/EN 60 439-3 Type-tested low voltage switchgear and controlgear

    assembly to which unskilled persons have access for their operation

    x x x

    IEC 60 439-1/EN 60 439-1 supplement 1 Personal protection in the eventof internal arcing currents

    IEC 60 529 Degrees of protection provided by enclosure (IP-Code) x x x

    DIN 43 880 Built-in equipment for electrical installations; overall dimensi-

    ons and related mounting dimensions

    x x x

    IEC 999/EN 60 999 Screw-type and screwless-type clamping units for

    electrical copper conductors

    x x x

    DIN EN 0100 Part 534 Tested lightning conductors x x x

    System overview and technical data

  • 8/3/2019 LV Switch Gear Assemblies

    5/245

    SAS 600 SAS 600i SAS 2000 SAS 2000i SAS 5000 SMC 7000

    I (earthed) II (totally insulated) I (earthed) II (totally insulated) I (earthed) I (earthed)

    Sheet steel Sheet steel Sheet steel Sheet steel

    Cabinet system Cabinet system Cabinet system Cabinet system

    RAL 7032, slate grey RAL 7032, slate grey RAL 7032, slate grey RAL 7032, slate grey

    x x x x

    + 35 C + 35 C + 35 C + 35 C

    + 40 C + 40 C + 40 C + 40 C

    - 5 C - 5 C - 5 C - 5 C

    50% at 40C 50% at 40C 50% at 40C 50% at 40C

    100% at 25C 100% at 25C 100% at 25C 100% at 25C

    350, 600, 850, 1100 400, 600, 650, 850, 1000 400, 600, 650,

    850, 1000

    250, 350, 450, 650

    1000*, 1100*, 1150(*in case of combination)

    2200 2200 2200 2200/2350

    2050 2050 2050

    275 500 750, 1250*, 1500*(*in case of combination)

    600, 1000*, 1200*,

    1400*(*in case of combination)

    Laterally Laterally Laterally Laterally

    250 A (IPK 30 kA/ICW 15 KA) 250 A (IPK 30 kA/ICW 15 KA) 2000 A (IPK 130 kA/ICW 59 KA) 1900 A (IPK 110 kA/ICW 50 KA)

    400 A (IPK 30 kA/ICW 15 KA) 400 A (IPK 30 kA/ICW 15 KA) 2500 A (IPK 130 kA/ICW 59 KA) 2500 A (IPK 176 kA/ICW 80 KA)

    630 A (IPK 45 kA/ICW 21 KA) 630 A (IPK 45 kA/ICW 21 KA) 2500 A (IPK 160 kA/ICW 72 KA) 3200 A ( IPK 220 kA/ICW 100 KA)1000 A (IPK 75 kA/ICW 36 KA) 3200 A (IPK 160 kA/ICW 72 KA) 4000 A ( IPK 220 kA/ICW 100 KA)

    1250 A (IPK 100 kA/ICW 45 KA) 4000 A (IPK 220 kA/ICW 100 KA) 4500 A (IPK 220 kA/ICW 100 KA)

    1600 A (IPK 130 kA/ICW 59 KA) 5000 A (IPK 220 kA/ICW 100 KA) 5800 A (IPK 220 kA/ICW 100 KA)

    2000 A (IPK 130 kA/ICW 59 KA) 7300 A (IPK 330 kA/ICW 150 KA)

    2500 A (IPK 130 kA/ICW 59 KA)

    Standard Option Option Standard

    Standard Option Option Standard

    Option Option Option

    x x x x

    x x x

    x x x

    x x

    x x x

    x x x

    AC 690 V AC 690 V AC 690 V AC 690 V

    AC 690 V AC 1000 V AC 1000 V AC 1000 V

    3 3 3 3

    III III III IV

    x x x x

    x

    x x

    x x x x

    x x x x

    x x x x

    x x x x

  • 8/3/2019 LV Switch Gear Assemblies

    6/24

    Mi 1000

    up to 1000 A, degree of protection IP 65

    Wall fixing with fastening tags. Wall fixing with mounting rai ls Wall fixing with stable mounting

    frame

    System benefits:

    As standard with N conductor:

    - with the same current carrying capacity as

    the phase conductors

    - EMC-compliant in the area of the phase

    conductors

    Also available as preassembled or partially

    extended. The degree of expansion can be

    agreed.

    Mi-Distribution boards are also offered as

    combinable type-tested boxes for self

    assembly.

    Incoming supply up to

    1000 A with integrated

    current and voltage

    measurement

    Easily accessible and

    sufficient wiring compart-

    ment even for parallel

    cables. The separable

    flange makes it easier to

    insert the cable

    Protection cover with

    captive labelling strips

    Box lid with quick-release

    lock can be operated

    manually or with a tool,

    depending on the inte-

    grated function

    Assembled, insulation-enclosed, totally insulated, low voltage switchgear assembly in

    a box-type assembly as a type-tested switchgear and controlgear assembly TTA in

    accordance with IEC 60 439 -1/EN 60 439 -1, for surface mounting on walls, floor-

    mounted distribution board or floor-mounted distribution board with covering,

    degree of protection IP 65.

    Box-type system consisting of combinable boxes of the same design, grid spacing

    300 x 300 mm which can be extended in all directions.

    - Standardised and type-tested modules enable the creation of all circuit variants of

    a modern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    Built-in devices:Main busbar system:

    As standard

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    Fixed-mounted switchgear:- Circuit-breaker 100-1000 A

    - Switch-disconnector 100-1000 A

    - Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)

    - DIN rail equipment in accordance with DIN 43 880

    - KWH meter mounting boards

    Bus-mounted switchgear:

    - Fuse switch-disconnector HRC 00 (160 A), HRC 1 (250 A)

    - Screw-in fuse bases D02, DII, DIII

    Reactive current compensation:

    - Fixed part

    Connection:

    - Cable from top and/or bottom

    Areas of application:Main distribution board or subdistribution board

    For the reliable supply of energy particularly in a harsh industrial environment with a

    high volume of dust and high degree of humidity

    - of industrial, commercial and trade buildings

    - of railway companies, particularly in technical areas of all commercial departments

    - Suitable for the protected outdoor use.

    6

  • 8/3/2019 LV Switch Gear Assemblies

    7/247

    SV 250

    up to 250 A, degree of protection IP 41/54

    Assembled, totally insulated, low voltage switchgear assembly as a type-tested switch-

    gear and controlgear assembly TTA in accordance with IEC 60 439/EN 60 439 -1, in

    cabinet form as a wall-mounted or floor-mounted distribution board,

    degree of protection IP 41/54.

    - Standardised and type-tested modules enable the creation of all circuit variants of amodern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    Built-in devices:Main busbar system:

    As standard

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    Fixed-mounted switchgear:

    - Circuit-breaker 100-250 A

    - Switch-disconnector 100-250 A

    - Fuse switch-disconnector HRC 00 (160 A) - HRC 1 (250 A)

    - DIN rail equipment in accordance with DIN 43 880

    - KWH meter mounting boards

    Bus-mounted switchgear:

    - Fuse switch-disconnector HRC 00 (160 A)

    - Screw-in fuse bases D02, DII, DIII

    Connection:

    - Cable from top and/or bottom

    Areas of application:Subdistribution board for the reliable supply of energy

    - of industrial and commercial buildings

    - of administration buildings and hospitals

    Circuit-breaker board for DIN rail

    equipment in accordance with

    DIN 43 880

    Termination panel with modular

    terminal blocks

    Fuse bases D02 on busbar 250 A

    Incoming circuit-breaker and fuse

    switch-disconnector HRC 1 wired

    onto busbar system

    Fuse switch-disconnector HRC 00

    bus-mounted onto busbar system

    250 A

    Empty panel with mounting plate,

    height adjustable

    System benefits:

    As standard with N conductor:

    - with the same current carrying capacity as the

    phase conductors- EMC-compliant in the area of the phase

    conductors

  • 8/3/2019 LV Switch Gear Assemblies

    8/24

    MC 630

    up to 630 A, degree of protection IP 55

    Assembled, metal-enclosed, low voltage switchgear assembly in modular cabinet form

    as a type-tested switchgear and controlgear assembly TTA in accordance with

    IEC 60 439/ EN 60 439 -1, as a wall-mounted or floor-mounted cabinet,

    degree of protection IP 55.

    Cabinet system consisting of extendable, individual panels of the same design inwidths of 350 and 600 mm, extendable on both sides and at the top and bottom.

    - Standardised and type-tested modules enable the creation of all circuit variants of a

    modern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    Built-in devices:Main busbar system:

    As standard

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    Fixed-mounted switchgear- Circuit-breaker 160-630 A

    - Switch-disconnector 160-630 A

    - Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)

    - DIN rail equipment in accordance with DIN 43 880

    - KWH meter mounting boards

    Bus-mounted switchgear:

    - Fuse switch-disconnector HRC 00 (160 A)

    - Fuse switch-disconnector in strip type HRC 00 (160 A)

    - Screw-type fuse bases D02 D02, DII, DIII

    Reactive current compensation:

    - Fixed part

    Connection:

    - Cable from top and/or bottom

    Areas of application:Main distribution board or subdistribution board for the reliable supply of energy

    particularly in a harsh industrial environment

    - of industrial, commercial and trade buildings

    - of railway companies, particularly in technical areas of all commercial departments

    Due to the modular design, can be adapted to any local conditions without special components

    System benefits:

    Modular system can be extended in all

    directions

    Also available as preassembled or partially

    extended. The degree of expansion can be

    agreed.

    MC 630 are also offered as a kit system for

    self assembly.

    Comprehensive range of accessories for fixing onto the unit

    Wall-mounted Wall-mounted Floor-mounted Floor-mounted

    distribution board distribution board distribution board distribution board,

    with covering back to back

    8

  • 8/3/2019 LV Switch Gear Assemblies

    9/249

    SAS 600 / SAS 600i

    up to 630 A, degree of protection IP 30/40/54

    System benefits:

    As standard with N conductor:

    - with the same current carrying capacity as

    the phase conductors

    - EMC-compliant in the area of the phase

    conductors

    Also available as preassembled or partially

    extended.

    Door panels

    Sufficient wiring compart-

    ment in the incoming

    panel

    Cabinet base enables

    transport with a fork-lift

    truck

    Fixing parts available for

    floor-mounting

    Door panel for totally insulated location of

    built-in equipment for doors

    Cabinet labelling

    Areas can be identified

    using different colours

    Lifting eyes with dual function

    1. Assembly of the cabinet panels externally

    using centring elements2. Crane transport

    Assembled, metal-enclosed (totally insulated) low voltage switchgear assembly in

    cabinet form as a free-standing unit as a type-tested switchgear and controlgear

    assembly TTA in accordance with IEC 60 439/ EN 60 439 -1,

    degree of protection IP 30/40/54.

    Cabinet system consisting of extendable, individual panels of the same design in widthsof 350, 600, 850 and 1100 mm

    - Standardised and type-tested modules enable the creation of all circuit variants of a

    modern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    - Totally insulated switchgear assemblies up to a rated busbar current of 630 A

    Built-in devices:Main busbar system:

    As standard

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    Fixed-mounted switchgear:

    - Circuit-breaker 100-630 A

    - Switch-disconnector 100-630 A

    - Fuse switch-disconnector HRC 00 (160 A) - HRC 3 (630 A)

    - DIN rail equipment in accordance with DIN 43 880

    - KWH meter mounting boards

    Bus-mounted switchgear:

    - Fuse switch-disconnector HRC 00 (160 A) and HRC 1 (250 A)

    - Fuse switch-disconnector in strip type HRC 00 (160 A)

    - Screw-type fuse bases D02, DII, DIII

    Reactive current compensation:

    - Fixed part

    Cablinet for 90 extension, 350 x 350 mm: Connection:- with turn around of the busbars - Cable from top and/or bottom

    Areas of application:Main distribution board or subdistribution board

    for the reliable supply of energy

    - of industrial, commercial and trade buildings

    - of railway companies, particulary in technical areas of all commercial departments

    - of administration buildings, hospitals, exhibition halls etc.

  • 8/3/2019 LV Switch Gear Assemblies

    10/24

    Sufficient wiring compartment in

    the incoming panel

    Cabinet base enables transport

    with a fork-lift truck

    Elements available for false floor-

    mounting without bore holes

    SAS 2000 / SAS 2000i

    up to 2500 A, degree of protection IP 30/40/54

    Assembled, metal-enclosed (totally insulated) low voltage switchgear assembly in cabi-

    net form as a free-standing unit as a type-tested switchgear and controlgear assembly

    TTA in accordance with IEC 60 439/EN 60 439 -1, degree of protection IP 30/40/54.

    Cabinet system consisting of extendable, individual panels of the same design in widths

    of 400, 600, 650, 850 and 1000 mm- Standardised and type-tested modules enable the creation of all circuit variants of a

    modern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    - Totally insulated switchgear up to a rated busbar current of 2500 A

    Built-in devices:Main busbar system:

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors

    (if required)

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    or higher (if required)

    Circuit-breaker 160-630 A: Circuit-breaker 800-2500 A:- Plug-in - Withdrawable part

    technology - Fixed part

    - Withdrawable part

    - Fixed part

    Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:

    - Plug-in technology

    Fuse switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:

    - Fixed part

    Reactive current compensation:

    - Fixed part linked to the main busbar via group back-up fuse

    Cabinet for 90 extension, Connection:

    600 x 600 mm: - cable from top and/or bottom

    - with turn around of the busbars - with busbar trunking system

    from top or bottom

    Areas of application:Main distribution board or subdistribution board

    for the reliable supply of energy

    - of industrial, commercial and trade buildings

    - of railway companies, particulary in technical areas of all commercial departments

    - of administration buildings, hospitals, exhibition halls etc.System benefits:

    If required with N conductor:

    - with the same current carrying capacity as

    the phase conductors or higher

    - EMC-compliant in the area of the phase

    conductors

    Cabinet labelling

    Areas can be identified using different colours

    Lifting eyes with

    dual function

    1. Crane transport

    2. Assembly of the

    cabinet panels externally

    using centring elements

    Cabinets with 90 extension enable

    installation even in small-sized

    rooms

    10

    newwith HENCONNECT plug-in technology

    for power functional units

  • 8/3/2019 LV Switch Gear Assemblies

    11/2411

    SAS 5000

    up to 5000 A, degree of protection IP 30

    Sufficient wiring compartment in

    the incoming panel

    System benefits:

    If required with N conductor:

    - with the same current carrying capacity as

    the phase conductors or higher

    - EMC-compliant in the area of the phase

    conductors (option, following agreement)

    Busbar system

    The busbar system lies in the rear part of the

    cabinet.

    The busbar system can change in heights of

    cabinets in the course of the installation which

    simplifies the use of bus-couplers.

    Depending on the design up to form 4a can be

    used.

    Assembled, metal-enclosed, low voltage switchgear assembly in cabinet form as a

    free-standing unit as a type-tested switchgear and controlgear assembly TTA in

    accordance with IEC 60 439/EN 60 439 -1, degree of protection IP 30.

    Cabinet system consisting of extendable, individual panels of the same design in widths

    of 400, 600, 650, 850 and 1000 mm- Standardised and type-tested modules enable the creation of all circuit variants of

    a modern and reliable energy supply

    - Generous wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    Built-in devices:Main busbar system:

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors (if required)

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    (if required)

    Circuit-breaker 160-630 A: Circuit-breaker 800-5000 A:

    - Plug-in technology - Withdrawable part

    - Fixed part

    - Withdrawable part

    - Fixed part

    Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:

    - Plug-in technology

    Fuse switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:

    - Fixed part

    Reactive current compensation:

    - Plug-in technology (via distribution busbar)

    Cabinet for 90 extension, 850 x 850 mm:

    - with turn around of the busbars

    Connection:

    - cable from top or bottom

    - with busbar from top or bottom

    Areas of application:Main distribution board

    for the reliable supply of energy

    - of industrial, commercial and trade buildings

    - of railway companies, particulary in technical areas of all commercial departments

    - of administration buildings, hospitals, exhibition halls etc.

    Access from

    one side

    Back-to-back

    with a central

    busbar system

    Back-to-back with

    two separate central

    busbar systems

    Cabinets with

    90 extension

    including busbars

    In assemblies

    with several trans-

    formers, a busbar

    link can be set up

    with a 250 mm

    deep cabinet

    Plan view:

    Space for busbars

    wiring space

    Space for equipment

    newwith HENCONNECT plug-in technology

    for power functional units

  • 8/3/2019 LV Switch Gear Assemblies

    12/24

    SMC 7000

    up to 7300 A, degree of protection IP 31

    System benefits:

    If required with N conductor:

    With the same current carrying capacity as the

    phase conductors,

    EMC-compliant in the area of the phase con-

    ductors.

    Outgoing feeder cabinet with switch-

    disconnector with strip type HRC

    fuse, sizes HRC 00 - HRC 3

    bus-mounted onto distribution busbar and exchangeable under voltage.

    Cable entry from top or bottom via a separate termination cabinet

    available in the widths 350, 450, 650 mm

    Connection with busbar from above Cabinet base enables transport

    with a fork-lift truck

    The outgoing circuits up to 630 A can be replaced during operation (without disconnecting the switchgear assembly)

    Assembled, metal-enclosed, low voltage switchgear assembly in cabinet form as a free-

    standing unit as a type-tested switchgear and controlgear assembly TTA in accordance

    with IEC 60 439-1/EN 60 439 -1, degree of protection IP 31.

    Cabinet system consisting of extendable, individual panels of the same design in widths

    of 250, 350, 450 and 650 mm- Standardised and type-tested modules enable the creation of all circuit variants of a

    modern and reliable energy supply

    - Sufficient wiring compartments save time when connecting the cables

    - Practical devices for transport and installation make it easier to work on site

    Built-in devices:Main busbar system:

    - EMC-compliant, with N/PEN conductor in the area of the phase conductors (if required)

    - N/PEN conductor with the same current carrying capacity as the phase conductors

    (if required)

    Circuit-breaker 160-630 A: Circuit-breaker 800-6300 A:

    - Removable part - Withdrawable part

    - Withdrawable part- Fixed part

    Switch-disconnector with strip type HRC fuse, size HRC 00 HRC 3:

    - Removable part

    Reactive current compensation:

    - Removable part

    (via distribution busbar)

    (no cable connection required))

    Connection:

    - cable from top, bottom or from the rear side

    - with busbar from top or bottom

    Areas of application:

    Main distribution board for the reliable supply of energy- of industrial, commercial and trade buildings

    - of railway companies, particulary in technical areas of all commercial departments

    - of administration buildings, hospitals, exhibition halls etc.

    Power functional unit NS 250/630

    in polyfast as plug-in technology

    Power functional unit NS 250/630

    with polyfast as withdrawable part

    Power functional unit as

    removable part

    Power functional unit NS 250/630

    in polyfast as plug-in technology

    12

  • 8/3/2019 LV Switch Gear Assemblies

    13/2413

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Replacement or removement of individual power functional units

    entirely from the assembly even though the circuit to which it is

    connected may be live.

    Switchgear

    switch-disconnector with fuse

    circuit-breaker

    in plug-in technology

    newwith HENCONNECT

    plug-in technology

    for power functional units

    13

  • 8/3/2019 LV Switch Gear Assemblies

    14/2414

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Switch-disconnector with strip type HRC fuse

    Sizes: HRC 00 / 160 A up to HRC 3 / 630 A

    Main incoming circuit: disconnecable

    Main outgoing circuit: fixed connection

    - Replacement or removement of the switchgear or connecting the cable even though

    the circuit to which it is connected may be live increases the availability of electrical

    energy in production lines and buildings and saves costs.

    - Switch-disconnectors with HRC fuse including double disconnection (before and after

    the HRC fuse *) increase personal safety during switching operation and removing the

    HRC fuse (replacing of the fuse is possible because all parts are not live).

    Remote interrogation of all electrical va-

    lues, fuse monitoring and remote operati-

    on via motor drive are possible with a

    BUS system (Type: SASIL).

    Individual power function units can be re-

    placed or removed even though the circuit

    to which it is connected may be live.

    The power functional units are bus-

    mounted onto a distribution busbar,

    centreline spacing 185 mm..

    The distribution busbar up to 2000 A

    is covered (IP XXB).

    The connections can be realized in

    form 4a.

    It is possible to carry out connections

    safely without interrupting the other

    outgoing circuits.

    Horizontal layout: Vertical layout:

    Switch-disconnector with fuse in plug-in

    technology

    SAS 2000

    operation

    behind the

    door:

    protection

    class I

    and

    protectionclass II

    up to IP 54

    SAS 2000/5000

    operation

    from the front:

    protection class I

    IP 30

    SAS 2000

    operationbehind the door:

    protection class I

    and

    protection class II

    up to IP 54

    14

    *

  • 8/3/2019 LV Switch Gear Assemblies

    15/2415

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Circuit-breaker 80 - 630 A

    Main incoming circuit: disconnecable

    Main outgoing circuit: fixed connection

    - Replacement or removement of the switchgear or connecting the cable even though

    the circuit to which it is connected may be live increases the availability of electrical

    energy in production lines and buildings and saves costs.

    - The incoming parts of circuit-breakers up to 630 A are linked with the distribution

    busbar in plug-in technology. The plugged parts are removable even though the circuit

    to which it is connected may be live.

    Control wiring is linked via plug-in contacts.

    Power functional units up to 80 A in plug-

    in technology, 3- or 4-pole.

    Main incoming circuit: disconnectable.Main outgoing circuit: fixed.

    Power functional units up to 160-630 A in

    plug-in technology, 3- or 4-pole.

    Main incoming circuit: disconnectable.Main outgoing circuit: fixed.

    The power functional units are bus-

    mounted onto a distribution busbar,

    centreline spacing 70 mm.

    The distribution busbar up to 2000 A

    is covered (IP XXB).

    Individual power function units can be re-

    placed or removed even though the circuit

    to which it is connected may be live.

    Current transformers can be mounted on

    the power functional unit.

    Control wiring is connected via easily

    accessible control terminals.

    Circuit-breaker in HENCONNECT

    plug-in technology

  • 8/3/2019 LV Switch Gear Assemblies

    16/2416

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Circuit-breaker 80 630 A

    Main incoming and outgoing circuits: disconnecable

    - Replacement or removement of the switchgear or connecting the cable even though

    the circuit to which it is connected may be live increases the availability of electrical

    energy in production lines and buildings and saves costs.

    - The incoming parts of circuit-breakers up to 630 A are linked with the distribution

    busbar in plug-in technology. The plugged parts are removable even though the circuit

    to which it is connected may be live.

    Control wiring is linked via plug-in contacts.

    Power functional units up to 160-630 A in

    plug-in technology, 3- or 4-pole.

    Main incoming and outgoing circuits:

    disconnectable

    The plugged part is wear-resistant and re-

    movable even though the circuit to which

    it is connected may be live.

    The power functional units are bus-

    mounted onto a distribution busbar,

    centreline spacing 70 mm.The distribution busbar up to 2000 A

    is covered (IP XXB).

    Individual power function units can be re-

    placed or removed even though the circuit

    to which it is connected may be live.

    Current transformers can be installed

    within the termination compartment.

    The connections can be realized in

    form 4a.

    It is possible to carry out connections

    safely without interrupting the other

    outgoing circuits.

    Circuit-breaker in HENCONNECT

    plug-in technology

    16

  • 8/3/2019 LV Switch Gear Assemblies

    17/241717

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Termination cabinet

    - Termination cabinet in 3 widths (400, 600, 850 mm)

    Can be combined left or right or between cabinets with outgoing circuits

    (refer to combination examples on page 18)

    -The cabinet width is selectable depending on the number of connecting cables .

    and the maximum dimensions on site.

    The use of cable fixing rails on two levels

    enables a larger number of outgoing

    cables to be fixed in position.

    Termination cabinet

    400 mm wide

    The N (PEN) and PE connecting bars are

    designed with EMC compliance.

    Termination cabinet600 mm wide

    The connections can be realized in

    form 4a.

    It is possible to carry out connections

    safely without interrupting the other

    outgoing circuits.

    Termination

    cabinet

    850 mm wide

    Termination cabinet

  • 8/3/2019 LV Switch Gear Assemblies

    18/2418

    SAS

    with HENCONNECT plug-in technology

    for power functional units

    Combination examples

    SAS 5000

    Left:Switch-disconnector

    with fuse,

    main incoming circuit in

    HENCONNECT

    plug-in technology,

    cabinet 650 mm wide

    Right:

    Termination cabinet

    400 mm wide

    SAS 2000

    Left:Termination cabinet

    600 mm wide

    Right:

    Switch-disconnector

    with fuse,

    main incoming circuit

    in HENCONNECT

    plug-in technology,

    cabinet 650 mm wide

    SAS 2000

    Left:

    Circuit-breaker,

    main incoming and

    outgoing circuit in

    HENCONNECT

    plug-in technology,

    cabinet 650 mm wide

    Right:

    Termination cabinet

    600 mm wide

    SAS 5000

    Left:

    Switch-disconnector

    with fuse,

    main incoming circuit

    in HENCONNECT

    plug-in technology,

    cabinet 650 mm wide

    Centre: Termination

    cabinet 600 mm wide

    Right:

    Switch-disconnector

    with fuse,

    main incoming circuit

    in HENCONNECT

    plug-in technology,

    cabinet 650 mm wide

    SAS 5000

    Left:

    Circuit-breaker,

    main incoming circuit

    in HENCONNECT

    plug-in technology;

    cabinet 650 mm wide

    Right:

    Termination cabinet

    850 mm wide

    SAS 5000Left:

    Circuit-breaker,

    main incoming

    and outgoing

    circuit in

    HENCONNECT

    plug-in technology,

    cabinet 850 mm

    wide

    Centre:

    Termination

    cabinet

    850 mm wide

    Right:

    Switch-disconnector with fuse, main incoming circuit in HENCONNECT

    plug-in technology, cabinet 650 mm wide

  • 8/3/2019 LV Switch Gear Assemblies

    19/2419

    References

    Examples

    Zwischentitel

    folgt

  • 8/3/2019 LV Switch Gear Assemblies

    20/24

    Mi 1000

    up to 1000 A, degree of protection IP 65

    Low voltage switchgear assembly:

    Mi 1000

    Mi 1000 switchgear assembly installed in the protective

    cabinet for controlling and monitoring railway platform

    lighting with remote signalling device.

    Low voltage switchgear assembly:

    Mi 1000

    Railway company

    Subdistribution board

    Low voltage switchgear assembly:

    Mi 1000

    Wind power station

    Mi installed in cable distribution cabinet

    20

  • 8/3/2019 LV Switch Gear Assemblies

    21/2421

    SAS 600 / SAS 600i

    up to 630 A, degree of protection IP 30/40/54

    Low voltage switchgear assembly:

    SAS 600

    Car dealer

    SAS 600, main distribution board with 3 cabinets,

    rated busbar current 250 A,circuit-breaker 160 A

    Cabinet 1: Measurement of consumption from the power

    supply company

    Cabinet 2: Low voltage main distribution board

    Low voltage switchgear assembly:

    SAS 600

    Historical hotel site

    Low voltage switchgear assembly:

    SAS 600

    Exhibition centre

    Subdistribution boards SAS 600, SAS 2000 and

    SV-Wall-mounted distribution boards for halls,

    main entrances and auxiliaries for general power supply

  • 8/3/2019 LV Switch Gear Assemblies

    22/24

    SAS 2000 / SAS 2000i

    up to 2500 A, degree of protection IP 30/40/54

    Low voltage switchgear assembly:

    SAS 2000

    Office and administrative building

    Low voltage switchgear assembly:

    SAS 2000

    Shopping centre

    Low voltage switchgear assembly:

    SAS 2000

    Hospital

    Distribution board for supplying the medical area

    22

  • 8/3/2019 LV Switch Gear Assemblies

    23/2423

    SAS 5000

    up to 5000 A, degree of protection IP 30

    Low voltage switchgear assembly:

    SAS 5000

    Hospital

    Low voltage switchgear assembly:

    SAS 5000

    Hospital

    Low voltage switchgear assembly:

    SAS 5000

    Broadcast and telestation, Inselberg

  • 8/3/2019 LV Switch Gear Assemblies

    24/24

    X0

    6.0

    5/?/??

    Gustav Hensel GmbH & Co. KGIndustrial Electrical Power Distribution System

    HENSEL products are available from MARYLAND METRICS

    P.O. Box 261 Owings Mills, MD 21117 USAph: (410)358-3130 (800)638-1830 fx: (410)358-3142 (800)872-9329

    web: http://mdmetric.com email: [email protected]