lv junction touchproof preinsulated sleeve · 2015. 6. 16. · ensuring class ii according to en...

1
2 Non-contractual photos and drawing. MICHAUD Export reserves the right to modify characteristics without any prior notice. Low Voltage Energy LV connection Non-contractual photos and drawing. MICHAUD Export reserves the right to modify characteristics without any prior notice. 3 Lv connection 173 215 Application Code Designation Leading-in and output colour Weight (kg) Sales unit K 522 PREINSULATED SLEEVE (E173) 25mm² TOUCHPROOF ORANGE 0.064 40 K 523 PREINSULATED SLEEVE (E173) 50mm² TOUCHPROOF YELLOW 0.062 40 K 524 PREINSULATED SLEEVE (E215) 95mm² TOUCHPROOF GREY 0.059 40 K 525 PREINSULATED SLEEVE (E215) 120mm² TOUCHPROOF PINK 0.058 40 References Implementation Touchproof preinsulated sleeve for double layer A.B.C. LV junction This preinsulated sleeve is used for the connection of low voltage double layer A.B.C. (Aerial Bundled Conductors) from AMOKABEL. It offers an additional layer on the barrel, ensuring class II according to EN 60950-1 . The product is IK07 according to EN 62262 and its dielectric strength is 8kV (1 minute into water according to EN 50483-4). Preparation of the conductor to be connected: - Cut the cable using a device that does not scratch the core. - Strip the conductors over the length indicated on the sleeve. - Brush the conductors to be connected using neutral grease to remove the oxide film. Do not wipe the conductors cleaned in this way. - Insert the conductors fully into the sleeve bores. Crimping: - Use a tool equipped with an E173 hexagonal crimping die (25mm² and 50mm²) or an E215 hexagonal crimping die (95mm² or 120mm²). - Crimp in the indicated area starting from the centre and working towards the end of the sleeve. - Both conductors do not need to be inserted before the crimping operation. You can insert one, crimp it, insert the second one and crimp it. 15.05 15.05 PATENTED SYSTEM by Description Crimping pin stops Barrel bore brushed with conductive grease at the factory Barrel anchor in the insulation permitting to totally crimp one side without having to insert the other cable 1 050A conductive aluminium barrel Coloured cap according to the section of the cable to connect 2 nd layer made of black compound-filled insulation Black elastomer gasket with seal wall protecting the barrel bore Ultrasonic weld 1 st layer made of elastomer white compound insulation

Upload: others

Post on 09-Aug-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LV junction Touchproof preinsulated sleeve · 2015. 6. 16. · ensuring class II according to EN 60950-1. EN 62262 and its dielectric strength is 8kV (1 minute into water according

2 Non-contractual photos and drawing. MICHAUD Export reserves the right to modify characteristics without any prior notice.

Low Voltage Energy

LV c

onnecti

on

Non-contractual photos and drawing. MICHAUD Export reserves the right to modify characteristics without any prior notice. 3

Lv c

onnecti

on

173

215

Application

Code Designation Leading-in and output colour

Weight (kg)

Sales unit

K 522 PREINSULATED SLEEVE (E173) 25mm² TOUCHPROOF ORANGE 0.064 40

K 523 PREINSULATED SLEEVE (E173) 50mm² TOUCHPROOF YELLOW 0.062 40

K 524 PREINSULATED SLEEVE (E215) 95mm² TOUCHPROOF GREY 0.059 40

K 525 PREINSULATED SLEEVE (E215) 120mm² TOUCHPROOF PINK 0.058 40

References

ImplementationTouchproof preinsulated sleeve for double layer A.B.C.

LV junction

This preinsulated sleeve is used for the connection of low voltage double layer A.B.C. (Aerial Bundled Conductors) from AMOKABEL.It offers an additional layer on the barrel, ensuring class II according to EN 60950-1.The product is IK07 according to EN 62262 and its dielectric strength is 8kV (1 minute into water according to EN 50483-4).

Preparation of the conductor to be connected:- Cut the cable using a device that does not scratch the core.- Strip the conductors over the length indicated on the sleeve.- Brush the conductors to be connected using neutral grease to remove the oxide film. Do not wipe the

conductors cleaned in this way.- Insert the conductors fully into the sleeve bores.

Crimping:- Use a tool equipped with an E173 hexagonal crimping die (25mm² and 50mm²) or an E215 hexagonal

crimping die (95mm² or 120mm²).- Crimp in the indicated area starting from the centre and working towards the end of the sleeve.- Both conductors do not need to be inserted before the crimping operation. You can insert one, crimp it, insert

the second one and crimp it.

15.05 15.05

PATENTED

SYSTEM

Créateur en équipement électrique

by

Description

Crimping pin stops

Barrel bore brushed with conductive grease at the factory

Barrel anchor in the insulation permitting to totally crimp one side without having to insert the other cable

1 050A conductive aluminium barrel

Coloured cap according to the section of the cable to connect

2nd layer made ofblack compound-filled insulation

Black elastomer gasket with seal wall protecting the barrel bore

Ultrasonic weld

1st layer made of elastomerwhite compound insulation