luck common mistakes in electrical grounding and bonding

103
BOARD OF ELECTRICAL ENGINEERING PROFESSIONAL REGULATION COMMISSION Common Mistakes in Electrical Grounding and Bonding Jaime V. Mendoza, PEE, MTM Member- Board of Electrical Engineering member-Technical Committee, PEMCI Chairman-Distribution Management Committee

Upload: cs110510

Post on 20-Jan-2016

114 views

Category:

Documents


20 download

DESCRIPTION

electrical common mistake

TRANSCRIPT

Page 1: Luck Common Mistakes in Electrical Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERING

PROFESSIONAL REGULATION COMMISSION

Common Mistakes in Electrical Grounding

and Bonding

Jaime V. Mendoza, PEE, MTMMember- Board of Electrical Engineeringmember-Technical Committee, PEMCIChairman-Distribution Management Committee

Page 2: Luck Common Mistakes in Electrical Grounding and Bonding

2

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

May – Electrical Safety Month

Page 3: Luck Common Mistakes in Electrical Grounding and Bonding

3

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

1. It is important to ground metal parts to a suitable grounding electrode, so that in the event of a ground fault, dangerous ground-fault current will be shunted into the earth away from persons, thereby protecting them against electric shock.

2. Electrical equipment must be grounded to ensure that dangerous voltage on metal parts resulting from a ground fault can be reduced to a safe value.

3. Electrical equipment must be grounded so that sufficient fault current will flow through the circuit protection device to quickly open and clear the ground fault. For example, a 20 A circuit breaker will trip and de-energize a 240 V ground fault to a metal pole that is grounded to a 25 ohm ground rod.

4. When electrical current is given multiple conductive paths on which to flow, current will only take the path of least resistance.

Page 4: Luck Common Mistakes in Electrical Grounding and Bonding

4

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Introduction

Why Electrical Grounding and Bonding?

The most controversial and misunderstood concepts in the Code.

The most neglected subject by electrical practitioners.

When improperly installed, it may results to physical injuries, costly damage to electrical facilities or even death to individual.

Each utility (power, telephone, cable TV) has its own grounding electrodes.

Electrical Grounding and Bonding circuit follows the basic laws of electricity.

Page 5: Luck Common Mistakes in Electrical Grounding and Bonding

5

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

What is the difference between grounded

conductor and grounding conductor???

Page 6: Luck Common Mistakes in Electrical Grounding and Bonding

6

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded conductor – a system or circuit conductor that is intentionally grounded.

Grounding Conductor – a conductor used to connect equipment or the grounded circuit of a wiring system to a grounding electrode conductor.

From PEC 2009

Page 7: Luck Common Mistakes in Electrical Grounding and Bonding

7

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Definition of Grounded Conductor

PEC 1.0.1

Page 8: Luck Common Mistakes in Electrical Grounding and Bonding

8

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Definition of Grounding Conductor

Page 9: Luck Common Mistakes in Electrical Grounding and Bonding

9

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Conductor

Not a “neutral” because it is not a 3 0r 4 wire system.

Page 10: Luck Common Mistakes in Electrical Grounding and Bonding

10

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Identifying Grounded Neutral Conductors of Different Systems

Page 11: Luck Common Mistakes in Electrical Grounding and Bonding

11

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

120/240 –V, Single Phase

208Y/120 –V, Three-Phase

480Y/277-V, Three-Phase

Phase A Black Black Brown

Phase B Red Red Orange

Phase C Blue Yellow

Neutral Conductor

White White with red Stripe

Gray

Equipment Grounding Conductor

Green Green Green

Proper Wiring Starts with the Right Color Used in Conductor Wiring

Page 12: Luck Common Mistakes in Electrical Grounding and Bonding

12

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Service Equipment

The necessary equipment, usually consisting of a circuit breaker(s) or switch(es) and fuse(s) and their accessories, connected to the load end of the of service conductors to a building or other structure, or an otherwise designated area, and intended to constitute the main control and cutoff of the supply.

Page 13: Luck Common Mistakes in Electrical Grounding and Bonding

13

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Service

Page 14: Luck Common Mistakes in Electrical Grounding and Bonding

14

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Service

Article 100 ● Definitions

National Electrical Code Handbook 2011 35

EXHIBIT 100.18 Conductors in an overhead service.

Service-drop conductors

Service-entranceconductors

Service point

voltaic systems, provided they “have no direct electrical

connection” to another source. This definition was revised

for the 2011 Code to clarify the interconnection between

separately derived systems and service derived electrical

systems. The earth, metal enclosures, metal raceways, and

equipment grounding conductors may provide incidental

connection between systems. However, the grounded circuit

conductors are not intended to be directly connected.

Service. The conductors and equipment for delivering elec-

tric energy from the serving utility to the wiring system of

the premises served.

A service can only be supplied by the serving utility. If elec-

tric energy is supplied by other than the serving utility, the

supplied conductors and equipment are considered feeders,

not a service.

Service Cable. Service conductors made up in the form of

a cable.

Service Conductors. The conductors from the service

point to the service disconnecting means.

Service conductors is a broad term and may include service

drops, service laterals, and service-entrance conductors.

This term specifically excludes, however, any wiring on the

supply side (serving utility side) of the service point. Simply

put, the service conductors originate at the service point

(where the serving utility ends) and end at the service dis-

connect. These service conductors may originate only from

the serving utility.

If the utility has specified that the service point is at the

utility pole, the service conductors from an overhead distri-

bution system originate at the utility pole and terminate at

the service disconnecting means.

If the utility has specified that the service point is at the

utility manhole, the service conductors from an underground

distribution system originate at the utility manhole and ter-

minate at the service disconnecting means. Where utility-

owned primary conductors are extended to outdoor

pad-mounted transformers on private property, the service

conductors originate at the secondary connections of the

transformers only if the utility has specified that the service

point is at the secondary connections.

See Article 230, Part VIII, and the commentary follow-

ing 230.200 for service conductors exceeding 600 volts,

nominal.

Service Conductors, Overhead. The overhead conductors

between the service point and the first point of connection

to the service-entrance conductors at the building or other

structure.

Service Conductors, Underground. The underground

conductors between the service point and the first point of

connection to the service-entrance conductors in a terminal

box, meter, or other enclosure, inside or outside the building

wall.

Informational Note: Where there is no terminal box, meter, or other enclosure, the point of connection is considered to be the point of entrance of the service conductors into the building.

Service Drop. The overhead conductors between the utility

electric supply system and the service point.

The definition of service drop was revised for the 2011

Code. This revision correlates with the changes to the defini-

tions of the term service lateral conductors. Service drop

and service lateral conductors are conductors on the line side

of the service point and are not subject to the NEC. Over-

head conductors on the load side of the service point are

overhead service conductors.

In Exhibit 100.18, the service-drop conductors run from

the utility pole and connect to the service-entrance conduc-

tors at the service point. Conductors on the utility side of the

service point are not covered by the NEC. The utility speci-

fies the location of the service point. Exact locations of the

service point may vary from utility to utility, as well as from

occupancy to occupancy.

Service-Entrance Conductors, Overhead System. The

service conductors between the terminals of the service

Service

equipment

Page 15: Luck Common Mistakes in Electrical Grounding and Bonding

15

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Proper Electrical Installation

Page 16: Luck Common Mistakes in Electrical Grounding and Bonding

16

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Panelboard Located in theKitchen – Is this readily accessible?

Missing Service

Equipment

Existing Practice???

Page 17: Luck Common Mistakes in Electrical Grounding and Bonding

17

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Service Equipment-Disconnecting Means

A – The service disconnecting means shall be installed at a readily accessible

location of a building or a structure. 2.30.6.1(a)(1)

It may be located either outside wall or inside, nearest the point of the

Service Conductors.

Page 18: Luck Common Mistakes in Electrical Grounding and Bonding

18

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Page 19: Luck Common Mistakes in Electrical Grounding and Bonding

19

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Page 20: Luck Common Mistakes in Electrical Grounding and Bonding

20

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Not Located in Bathrooms

Overcurrent protection devices must not be locatedin the bathrooms of dwelling units, or in guest roomsor guest suites of hotels or motels.(2.40.2.5

Page 21: Luck Common Mistakes in Electrical Grounding and Bonding

21

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Accessible, Readily

Accessible, Readily

Page 22: Luck Common Mistakes in Electrical Grounding and Bonding

22

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

No Grounded Service at the Customer Side

Page 23: Luck Common Mistakes in Electrical Grounding and Bonding

23

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

250.24 (A)(2) Outdoor Transformer

Where the transformer supplying the service is located outside the building, at least one additional grounding connection is required to be made from the grounded service conductor to a grounding electrode, either at the transformer or elsewhere outside the building.

WHY?

Page 24: Luck Common Mistakes in Electrical Grounding and Bonding

24

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Earth Return Prohibited

Page 25: Luck Common Mistakes in Electrical Grounding and Bonding

25

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Earth is Not an Effective Ground-Fault Current Path

Page 26: Luck Common Mistakes in Electrical Grounding and Bonding

26

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Proper Wiring Installation

Page 27: Luck Common Mistakes in Electrical Grounding and Bonding

27

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Each Utilities has its Own Grounding Electrode

Page 28: Luck Common Mistakes in Electrical Grounding and Bonding

28

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Low-Voltage & Intersystem Grounding and Bonding

Page 29: Luck Common Mistakes in Electrical Grounding and Bonding

29

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Each Utilities has its Own Grounding Electrode

Page 30: Luck Common Mistakes in Electrical Grounding and Bonding

30

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Single Point Ground

Page 31: Luck Common Mistakes in Electrical Grounding and Bonding

31

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Low-Voltage & Intersystem Grounding and Bonding

Intersystem bonding and grounding

Page 32: Luck Common Mistakes in Electrical Grounding and Bonding

32

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

The Same Grounding Electrode for Lightning and Power Supply

Page 33: Luck Common Mistakes in Electrical Grounding and Bonding

33

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Proper Grounding

PEC Art. 250.5.17 Lightning Protection System. The bonding of a system grounding electrode and a lightning rod grounding electrode.

Page 34: Luck Common Mistakes in Electrical Grounding and Bonding

34

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Streetlight Grounded System to Ground Rod Only

Page 35: Luck Common Mistakes in Electrical Grounding and Bonding

35

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

2.50.3.5 Auxiliary grounding electrodes

But the earth shall NOT be used as an

effective ground-fault current path

2.50.3.5 Auxiliary Grounding Electrodes

Page 36: Luck Common Mistakes in Electrical Grounding and Bonding

36

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

No Auxiliary Electrode for Remote Metering

Page 37: Luck Common Mistakes in Electrical Grounding and Bonding

37

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

2.50.5.3(b) Method of Bonding at the Service

(b)(1)Bonding remote meter enclosures onon supply side of service

Page 38: Luck Common Mistakes in Electrical Grounding and Bonding

38

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Potential Difference

Potential difference between a grounded

Water pipe and an ungrounded motor.

Page 39: Luck Common Mistakes in Electrical Grounding and Bonding

39

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Potential Difference

Motor ground-fault. A hazard now exists.

Page 40: Luck Common Mistakes in Electrical Grounding and Bonding

40

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Potential Difference

The hazard results in an electric shock.

Page 41: Luck Common Mistakes in Electrical Grounding and Bonding

41

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Potential Difference

Another shock hazard exists.

Page 42: Luck Common Mistakes in Electrical Grounding and Bonding

42

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Earth Return Prohibited

Page 43: Luck Common Mistakes in Electrical Grounding and Bonding

43

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Properly

Page 44: Luck Common Mistakes in Electrical Grounding and Bonding

44

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Earth is Not an Effective Ground-Fault Current Path

Page 45: Luck Common Mistakes in Electrical Grounding and Bonding

45

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Objectionable Current

If current is regularly flowing over equipment grounding conductors, it would be considered “ objectionable current” as covered in Sec. 2.50.1.6

It is intended that fault current will flow over equipment grounding conductors only while a ground fault exists.

Page 46: Luck Common Mistakes in Electrical Grounding and Bonding

46

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Equipment Grounding Conductor

Page 47: Luck Common Mistakes in Electrical Grounding and Bonding

47

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 48: Luck Common Mistakes in Electrical Grounding and Bonding

48

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 49: Luck Common Mistakes in Electrical Grounding and Bonding

49

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 50: Luck Common Mistakes in Electrical Grounding and Bonding

50

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 51: Luck Common Mistakes in Electrical Grounding and Bonding

51

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 52: Luck Common Mistakes in Electrical Grounding and Bonding

52

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 53: Luck Common Mistakes in Electrical Grounding and Bonding

53

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 54: Luck Common Mistakes in Electrical Grounding and Bonding

54

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 55: Luck Common Mistakes in Electrical Grounding and Bonding

55

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Grounded Improperly

Page 56: Luck Common Mistakes in Electrical Grounding and Bonding

56

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Receptacles

A. Tamper-Resistant Receptacles in Dwellings Unit (NEC 2008 - 406.11)

Why do you think it is a tamper-

resistant receptacle?

…..To increase safety for children.

…..maybe that your son, daughter, or

grandchildren that you will save…

Page 57: Luck Common Mistakes in Electrical Grounding and Bonding

57

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Tamper-Resistant Receptacles

Insertion of an object in any one side does not open the shutter(left), but a two-bladed plug or grounding plug compresses the Spring and simultaneously opens both shutters (right)

Page 58: Luck Common Mistakes in Electrical Grounding and Bonding

58

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Electric Shock

Electric Shock Severity

1. Path of Current through Body

2. Length of Time Current Flows

3. Amount of Current through Body

Page 59: Luck Common Mistakes in Electrical Grounding and Bonding

59

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Electric Shock

Current flow through body tissues delivers energy in the form of heat. The magnitude of energy may be approximated by

J = I2Rt

where J = energy, joules

I = current, amperes

R = resistance of the current path through

the body, ohms

t = time of current flow, seconds

Page 60: Luck Common Mistakes in Electrical Grounding and Bonding

60

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Effects of AC Electric Shock

Level (in milliamperes) of current through the body

ELCB!!!

Page 61: Luck Common Mistakes in Electrical Grounding and Bonding

61

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Ground Fault Circuit Interrupter

GFCI – A device intended for the protection of personnel that functions to deenergize a circuit or portion thereof within an established period of time when a current to ground exceeds the values established for a device.

The GCFI does not protect someone against receiving a electrical shock, but it does limit the time hazards exists. Hazard exist only during period of time fault is there.

Page 62: Luck Common Mistakes in Electrical Grounding and Bonding

62

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Ground Fault Circuit Interrupter

The circuitry and components of a typical GFCI

240 V

load

240 V line source

Page 63: Luck Common Mistakes in Electrical Grounding and Bonding

63

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Ground Fault Circuit Interrupter

Page 64: Luck Common Mistakes in Electrical Grounding and Bonding

64

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Ground Fault Circuit Interrupter

Page 65: Luck Common Mistakes in Electrical Grounding and Bonding

65

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Ground Fault Circuit Interrupter

A GFCI is designed to protect persons against electric shock.It operates on the principles of monitoring the unbalanced currentBetween the ungrounded and the grounded neutral conductor.

Page 66: Luck Common Mistakes in Electrical Grounding and Bonding

66

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GCFI CAN ELIMINATE THIS!

Ground Fault Circuit Interrupter

Page 67: Luck Common Mistakes in Electrical Grounding and Bonding

67

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

1. Dwelling Bathroom Receptacle

and /or 250 V

Page 68: Luck Common Mistakes in Electrical Grounding and Bonding

68

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

2. Dwelling Garage Receptacle

Page 69: Luck Common Mistakes in Electrical Grounding and Bonding

69

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

2. Dwelling Garage Receptacle

All 15 and 20 A, 125/250 V receptacles in accessorybuildings and similar work areas must be GFCI protected.

Page 70: Luck Common Mistakes in Electrical Grounding and Bonding

70

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

3. Dwelling Outdoor Receptacle

Page 71: Luck Common Mistakes in Electrical Grounding and Bonding

71

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel4. Dwelling Basement Receptacle

Page 72: Luck Common Mistakes in Electrical Grounding and Bonding

72

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

5. Dwelling Unfinished Basement

Page 73: Luck Common Mistakes in Electrical Grounding and Bonding

73

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

6. Kitchens for Countertop Appliances

Page 74: Luck Common Mistakes in Electrical Grounding and Bonding

74

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

6. Dwelling Laundry or Utility Sink

Page 75: Luck Common Mistakes in Electrical Grounding and Bonding

75

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

GFCI Protection for Personnel

7. Dwelling Wet Bar Sinks

Page 76: Luck Common Mistakes in Electrical Grounding and Bonding

76

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

PEC-2.10.1.8 (a)

a) Dwelling Units1. Bathrooms2. Garages3. Outdoors4. Crawl spaces at or

below grade level5. Unfinished

basements6. Kitchens for

countertopappliances

7. Wet bar sinks

GFCI Protection for Personnel

Page 77: Luck Common Mistakes in Electrical Grounding and Bonding

77

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Outdoor Receptacles Outlets –One Family Dwelling

Page 78: Luck Common Mistakes in Electrical Grounding and Bonding

78

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

New Provision

Row Housing with GFCI-protected receptacles located at the front and the back of each one family dwelling, as required by 210.52(E)

Page 79: Luck Common Mistakes in Electrical Grounding and Bonding

79

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

New Provision

2.10.1.8(b)(2) –GFCI Protection Other than Dwelling

Commercial and institutional kitchens –for the purposes of this section, a kitchen is an area with a sink and permanent facilities for food preparation and cooking. (Culinary Schools)

Page 80: Luck Common Mistakes in Electrical Grounding and Bonding

80

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

New Provision

2.10.1.8(b)(4) –GFCI Protection Other than Dwelling

Outdoor in Public Spaces – for the purpose of this section a public space is defined as any space that is for use by, or is accessible to the public.

Page 81: Luck Common Mistakes in Electrical Grounding and Bonding

81

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

New Provision

2.10.1.8(c)Boat Hoists

GFCP for personnel shall be provided for outlets that supply boat hoists installed in dwelling unit locations

Page 82: Luck Common Mistakes in Electrical Grounding and Bonding

82

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

2.10.1.8(b)(5) –GFCI Protection Other than Dwelling

(5)Outdoor , where installed to comply with 2.10.3.14 Heating, Air-conditioning, and Refrigeration Outlet

New Provision

Page 83: Luck Common Mistakes in Electrical Grounding and Bonding

83

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

The general philosophy behind Code articles is that circuit protection will shut down equipment before letting the supply conductors melt from overload.

Art. 6.95 Fire Pumps depart from this philosophy.

The idea is that the fire pump motor must run, no matter what; it supplies water to facility’s fire protection piping, which in turn supplies water to the sprinkler system and fire hoses.

6.95 Fire Pumps

Page 84: Luck Common Mistakes in Electrical Grounding and Bonding

84

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Introduction

Art. 6.95 contains many requirements to keep that supply of water uninterrupted.

For example:

1. Locating the pump so as to minimize its exposure to fire.

2. Ensuring that the fire pump and its jockey pump have a reliable source of power.

3. It makes sense to keep fire pump wiring independent.

Page 85: Luck Common Mistakes in Electrical Grounding and Bonding

85

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Introduction

Other requirements seem wrong at first glance, until you remember why the fire pump is there in the first place.

For example:

1. The disconnect must be lockable in the closed position.

2. Fire pumps power circuits cannot have automatic protection against overload.

Page 86: Luck Common Mistakes in Electrical Grounding and Bonding

86

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Introduction

“ It’s better to run the fire pump until its winding melt, than to save the fire pump and lose the facility”

And the intent of Article 6.95 is to save the facility.

Page 87: Luck Common Mistakes in Electrical Grounding and Bonding

87

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.1 Scope

a) Covered

1) Electric power sources and interconnecting circuits

2) Switching and control equipment dedicated to fir pump drivers

b) Not Covered

1) The performance, maintenance, and acceptance testing of the fire pump system, and the internal wiring of the components of the system

2) Pressure maintenance (jockey or makeup) pumps

Page 88: Luck Common Mistakes in Electrical Grounding and Bonding

88

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

a) Individual Source

1) Electric Utility Service. A separate service from a connection located ahead of but not within the service disconnecting means.

2) On-Site Power. An on-site power supply, such as generator, located and protected to minimize damage by fire is permitted to supply a fire pump.

Page 89: Luck Common Mistakes in Electrical Grounding and Bonding

89

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection

Page 90: Luck Common Mistakes in Electrical Grounding and Bonding

90

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

a) Electric-Utility Service Connection

Page 91: Luck Common Mistakes in Electrical Grounding and Bonding

91

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

2) On-Site Power Production Facility

Page 92: Luck Common Mistakes in Electrical Grounding and Bonding

92

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

b) Multiple Sources

1) Generator Capacity. Shall have sufficient capacity to allow normal starting and running 0f the motor(s) driving the fire pump(s) while supplying other simultaneously operated load.

2) Feeder Sources.

3) Arrangement. The power sources shall be arranged so that a fire at one will not cause an interruption at the other source.

Page 93: Luck Common Mistakes in Electrical Grounding and Bonding

93

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.3 Power Sources for Electric-Motor Driven Fire Pumps

2) Feeder Sources

Page 94: Luck Common Mistakes in Electrical Grounding and Bonding

94

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Dedicated transformer and overcurrent protection sizing can be broken down into three requirements.

1. The transformer must be size to at least 125% of the sum of the loads.

2. The transformer primary overcurrent device must be at least a specified minimum size.

3. The transformer secondary must not contain any overcurrent device whatsoever.

6.95.1.5 Transformers

Page 95: Luck Common Mistakes in Electrical Grounding and Bonding

95

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.5 Transformers

The overcurrent device in the primary of a transformer supplying

a fire pump installation. The device is required to be sized to carry

the locked-rotor current motor(s) and associated fire pump

accessory equipment indefinitely.

Page 96: Luck Common Mistakes in Electrical Grounding and Bonding

96

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.6 Power Wiring

a) Service and Feeder Conductors.

Supply conductors must be physically routed outside buildings and must be installed in accordance with Article 2.30. Where supply conductors cannot be routed outside buildings, they must be encased in 2 inches or 50 mm of concrete or brick.

Page 97: Luck Common Mistakes in Electrical Grounding and Bonding

97

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.6 Power Wiring

b) Circuit Conductors.

Fire pump supply conductors on the load side of the final disconnecting means and overcurrent device(s) must be kept entirely independent of all other wiring. They can be routed through a building using one of the following methods:1) Be encased in a minimum 2 inches or 50 mm of

concrete

2) Be within an enclosed construction dedicated to the fire pump circuit(s) and having a minimum of a 1-hour fire-resistant rating

3) Be listed electrical circuit protective system with a minimum 1-hour fire rating.

Page 98: Luck Common Mistakes in Electrical Grounding and Bonding

98

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.6(c)(2) BC Conductor Size

Fire Pump Motor

Branch Circuit Conductor Size

Branch circuit conductors to a single fire pump

motor must have a rating not less than 125% of the

motor

FLC as listed in Table 4.30.14.2 or 4.30.14.4

From Table

4.30.14.5(b)

Page 99: Luck Common Mistakes in Electrical Grounding and Bonding

99

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.7 Voltage Drop

The voltage drop at the line terminals of the controller

when the motor starts (locked-rotor current), must not

drop more than 15% below the controller’s rated voltage.

Page 100: Luck Common Mistakes in Electrical Grounding and Bonding

100

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.7 Voltage Drop

Fire Pump Motor – Voltage Drop

Page 101: Luck Common Mistakes in Electrical Grounding and Bonding

101

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

6.95.1.7 Voltage Drop

Fire Pump Conductor Size – Voltage Drop

Page 102: Luck Common Mistakes in Electrical Grounding and Bonding

102

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

1. It is important to ground metal parts to a suitable grounding electrode, so that in the event of a ground fault, dangerous ground-fault current will be shunted into the earth away from persons, thereby protecting them against electric shock.

2. Electrical equipment must be grounded to ensure that dangerous voltage on metal parts resulting from a ground fault can be reduced to a safe value.

3. Electrical equipment must be grounded so that sufficient fault current will flow through the circuit protection device to quickly open and clear the ground fault. For example, a 20 A circuit breaker will trip and de-energize a 240 V ground fault to a metal pole that is grounded to a 25 ohm ground rod.

4. When electrical current is given multiple conductive paths on which to flow, current will only take the path of least resistance.

Page 103: Luck Common Mistakes in Electrical Grounding and Bonding

103

Common Mistakes in Electrical

Grounding and Bonding

BOARD OF ELECTRICAL ENGINEERINGPROFESSIONAL REGULATION COMMISSION

Jaime V. Mendoza, MTM

Member, Board of Electrical Engineering

Chairman, Distribution Management Committee

Email: [email protected]