low voltage electrical distribution easypact sps

62
Low voltage electrical distribution EasyPact SPS Circuit breakers and switch-disconnectors 800 to 1600 A User manual 03/2013 Released for Manufacturing Printed on 2018/04/12

Upload: others

Post on 16-Nov-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Low voltage electrical distribution EasyPact SPS

Low voltage electrical distribution

EasyPact SPSCircuit breakers and switch-disconnectors800 to 1600 A

User manual03/2013

Released for ManufacturingPrinted on 2018/04/12

Page 2: Low voltage electrical distribution EasyPact SPS

HRB75971

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

This document has been printed on ecological paper

Design: Schneider ElectricPhotos: Schneider ElectricPrinted:

Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F - 92506 Rueil Malmaison Cedex

RCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com

© 2

013

- Sch

neid

er E

lect

ric -

Tous

dro

its ré

serv

és

03-2013 Released for ManufacturingPrinted on 2018/04/12

Page 3: Low voltage electrical distribution EasyPact SPS

User manual for circuit breakers and switch-disconnectors Easypact SPS

1HRB75971 - 03/2013HRB75971 - 03/2013

Contents

Identifying EasyPact SPS 2Rating plate 2Discovering EasyPact SPS 3Components 3Using EasyPact SPS 7Understanding the controls and indications 7Charging the circuit breaker 8Closing the circuit breaker 9Opening the circuit breaker 10Resetting after a fault trip 11Locking the controls 12Using the EasyPact SPS drawout chassis 14Identifying the circuit breaker positions 14Racking 15Locking the switchboard door 18Locking the circuit breaker in position 19Locking the safety shutters 21Discovering Microprocessor based ET Trip System 22Identifying Microprocessor based ET Trip System Designations 22Overview of functions 24Setting procedure 26Setting Microprocessor based ET Trip System 27Setting the Microprocessor based ET2.0 Trip System 27Setting the Microprocessor based ET6G Trip System 28Selecting the type of neutral protection 29Fault and status indications 30Resetting the fault indications and checking battery status 30Testing the ground-fault functions 31Technical appendix 32Tripping curves 32Thermal memory 34Identifying the electrical auxiliaries 35Identification of the connection terminals 35Operation 36Electrical diagrams 37Discovering EasyPact SPS accessories 39ET Trip system 39Indication contacts 40Auxiliaries for remote operation 41Device mechanical accessories 44Chassis accessories 46Inspecting and testing before use 48Initial tests 48What to do when the circuit breaker trips 49Maintaining EasyPact SPS performance 50Recommended maintenance program 50Maintenance operations 51Ordering replacement parts 52Troubleshooting and solutions 53Checking EasyPact SPS operating conditions 55Environmental conditions 55

Released for ManufacturingPrinted on 2018/04/12

Page 4: Low voltage electrical distribution EasyPact SPS

2 HRB75971- 03/2013

EasyPact

UiUimp

Ue(V)220/440~

Ics=100%Icucat.B

12kV

Icu(kA) Icw(kA/1s)50 42

50/60HzIEC / EN 60947-2

SPS 12F

1000V

Rated current (x 100 A)

Suitability f or isolation

P erf or mance le ve l

Rated insulation le ve l

Rated short-time withstand current

Rated operational voltage

Icu - ultimate breaking capacity

Impulse withstand vo ltage

Ics - rated service breaking capacity

T ype of de vice: circuit break er or sw itch-disconnector

F requency

Standards

DB

1193

13

DB

1193

14

Rating plateIdentifying EasyPact SPS

Released for ManufacturingPrinted on 2018/04/12

Page 5: Low voltage electrical distribution EasyPact SPS

3HRB75971 - 03/2013

Discovering EasyPact SPS

EasyPact circuit breakers are available in drawout and fixed versions.The drawout version is mounted on a chassis and the fixed version is installed using fixing brackets.

Drawout version

Fixed version

E51

321A

E51

322A

Components

Released for ManufacturingPrinted on 2018/04/12

Page 6: Low voltage electrical distribution EasyPact SPS

4 HRB75971- 03/2013

Chassis

DB

1193

15

Carr ying gr ip

Dr aw out gr ip

Carr iage sw itch ter minal s

Te rm inals f or control-unit and f ault-tr ip indication contacts

Door inter lo ck

Arc-chute co ve r

Disconnecting-contact cluster

A uxilia ry ter minal shiel d

Control auxilia ry ter minal s

ON/OFF indication contact ter minal s Carr iage sw itch ter minal s

Saf ety shutters

Shutter lo ck ing bl oc ks

"Connected", "test" or "disconnected" position indicator

Loc king by key lo ck s

Crank storage

Crank so cke t

P osition release b utton

Loc king by padloc ks

Crank

Discovering EasyPact SPS Components

Released for ManufacturingPrinted on 2018/04/12

Page 7: Low voltage electrical distribution EasyPact SPS

5HRB75971 - 03/2013

Drawout circuit breaker / switch-disconnector

DB

1193

16

MCH gear motor fo r electr ical charging of the operating mechanism

Operating-mechanism charging handl e

PF "ready to close" contact Te rm inals f or control unit, f aul t indication contacts , control auxilia ri es and auxilia ry contacts

MN under vo ltage release

XF closing release

MX opening release

Closing pushb utton

Carr ying gr ip

SDE "fault-tr ip" indication contact

Arc chute

Control unit*

OF "ON/OFF" indication contacts

Opening pushb utton

Ke yloc k f or lo ck ing in open position

Side plate fo r dr aw out de vice

Discovering EasyPact SPS Components

* Switch disconnector is without control unit

Released for ManufacturingPrinted on 2018/04/12

Page 8: Low voltage electrical distribution EasyPact SPS

6 HRB75971- 03/2013

DB

1193

17

MCH gear motor forelectrical charging of theoperating mechanism

Operating-mechanismcharging handle

PF "ready to close" contactTerminals for control unit and faultindication contacts

MN undervoltage release

XF closing release

MX opening release

Closing pushbutton

Carrying grip

SDE "fault-trip" indication contact

Control unit*

OF "ON/OFF" indication contacts

Opening pushbutton

Side plate for fixeddevice

Auxiliary contact terminals

Control auxiliary terminals

Arc chute

Keylock for lockingin open position

Fixed circuit breaker / switch-disconnector

DB

1193

18

Indicator f or position of the main contacts

"Spr ings charged" and "Ready to close" indicato r

Loc king by padloc k, lead-seal co ve r or scre ws f or pushb uttons

Rating plate

Tr ip indication b utton used to reset bef ore closing

Front

Discovering EasyPact SPS Components

* Switch disconnector is without control unit

Released for ManufacturingPrinted on 2018/04/12

Page 9: Low voltage electrical distribution EasyPact SPS

7HRB75971 - 03/2013

Understanding the controls and indications

Circuit breaker open and discharged

Circuit breaker closed and discharged

Circuit breaker open, charged and not "ready to close"

Circuit breaker closed, charged and not "ready to close"

Circuit breaker open, charged and "ready to close"

DB

1193

19

Push OFFOI

Push ON

Push OFFOI

Push ON

Push OFFOI

Push ON

Push OFFOI

Push ON

E51

488A

E51

489A

E51

490A

E51

491A

E51

492A

Push OFFOI

Push ON

Using EasyPact SPS

Released for ManufacturingPrinted on 2018/04/12

Page 10: Low voltage electrical distribution EasyPact SPS

8 HRB75971- 03/2013

The charge status is indicated as follows. The springs in the circuit breaker operating mechanism must be charged to store the energy required to close the main contacts. The springs may be charged manually using the charging handle or automatically by the optional MCH gear motor.

Manual charging.Pull the handle down six times until you hear a "clack".

Automatic charging.If the MCH gear motor is installed, the spring is automatically recharged after each closing.

DB

1193

20

DB

1193

37

E46

790A

Charging the circuit breaker

Push OFFOI

Push ON

or

Using EasyPact SPS

Released for ManufacturingPrinted on 2018/04/12

Page 11: Low voltage electrical distribution EasyPact SPS

9HRB75971 - 03/2013

Using EasyPact SPS Closing the circuit breaker

Closing conditionsClosing (i.e. turning the circuit ON) is possible only if the circuit breaker is "ready to close". The prerequisites are the following:

b device open (OFF) b springs charged b no opening order present.

The circuit breaker will not close unless it is "ready to close" when the order is given.

Closing the circuit breakerLocally (mechanical)Press the mechanical ON pushbutton.

Remotely

Anti-pumping functionThe purpose of the mechanical anti-pumping function is to ensure that a circuit breaker receiving simultaneous opening and closing orders does not open and close indefinitely. If there is a continuous closing order, after opening the circuit breaker remains open until the closing order is discontinued. A new closing order is required to close the circuit breaker. A new order is not required if the closing release is wired in series with the PF "ready to close" contact.

When connected to a remote control panel, the XF closing release can be used to close the circuit breaker remotely.

XF

Push OFFOI

E51

291A

E51

292A

E60

047A

E51

493A

DB

1193

21

E51

294A

Device not "ready to close"

Device "ready to close"

EasyPact

Released for ManufacturingPrinted on 2018/04/12

Page 12: Low voltage electrical distribution EasyPact SPS

10 HRB75971 - 03/2013

Opening the circuit breaker

LocallyPress the OFF pushbutton.

RemotelyUse one of the following solutions:

b one MX opening release b one MN undervoltage release b one MN undervoltage release with a delay unit.

When connected to a remote control panel, these releases can be used to open the circuit breaker remotely.

E60

047A

DB

1193

21

E51

294A

E51

296A

E51

499A

3 6

MNUVR

1012

100/130 V

AC/DC

S

0.5 1

3 1.5

Retardateur de MN

Time delay for UVR

4 5 6

1 2 3

1 2 3

MX / MN Delay unit

Using EasyPact SPS

Released for ManufacturingPrinted on 2018/04/12

Page 13: Low voltage electrical distribution EasyPact SPS

11HRB75971 - 03/2013HRB75971 - 03/2013

Using EasyPact SPS

The circuit breaker signals a fault trip by: b a mechanical indicator on the front b one SDE "fault-trip" indication contacts.

LocallyIf the circuit breaker is not equipped with the automatic reset option, reset it manually.

Resetting after a fault tripE

6004

7A

DB

1193

22

RESET

Released for ManufacturingPrinted on 2018/04/12

Page 14: Low voltage electrical distribution EasyPact SPS

12 HRB75971 - 03/2013

Locking the controlsDisabling circuit-breaker local closing and opening

Pushbutton locking using a padlock (shackle diameter 5 to 8 mm), a lead seal or screws.

DB

1193

23

UnlockingRemove the padlock, lead seal or screws.

DB

1193

24

DB

1193

25

DB

1193

27

DB

1193

238

Padlock. Lead seal.

LockingClose the covers. Insert the padlock

shackle, lead seal or screws.

DB

1193

28

DB

1193

29

DB

1193

30

Lift the covers and swing them down.

The pushbuttons are no longer locked.

Push OFF

OPush ON

I

Push OFF

OPush ON

I

DB

1193

26

Screws.

Using EasyPact SPS

Released for ManufacturingPrinted on 2018/04/12

Page 15: Low voltage electrical distribution EasyPact SPS

13HRB75971 - 03/2013HRB75971 - 03/2013

CheckThe closing control is inoperative.

E51

446A

UnlockingInsert the key.

Two types of keylocks are available

E60

008A

E60

009A

E60

010A

DB

1184

79

Turn the key. The key cannot be removed.

RONIS PROFALUX

Locking the controls with a keylockLockingOpen the circuit breaker.

E51

499A

E51

448A

E51

449A

Turn the key. Remove the key.

E51

270A

Using EasyPact SPS Locking the controlsDisabling local and remote closing

Released for ManufacturingPrinted on 2018/04/12

Page 16: Low voltage electrical distribution EasyPact SPS

14 HRB75971 - 03/2013

Using the EasyPact SPS drawout chassis

Identifying the circuit breaker positions

b "connected" position

DB

1193

41

The indicator on the front signals the position of the circuit breaker in the chassis.

E51

453A

b "test" position

E51

454A

DB

1193

42

b "disconnected" position

E51

455A

DB

1193

43

Test

Test

10.9 mm

Test

32.2 mm

DB

1193

44

Released for ManufacturingPrinted on 2018/04/12

Page 17: Low voltage electrical distribution EasyPact SPS

15HRB75971 - 03/2013HRB75971 - 03/2013

Racking

PrerequisitesTo connect and disconnect EasyPact, the crank must be used. The locking systems and padlocks all inhibit use of the crank.

Withdrawing the circuit breaker from the "connected" to "test" position, then to "disconnected" position

The circuit breaker is in "connected" position.

The circuit breaker is in "test" position.

DB

1197

17

The circuit breaker is in "test" position. Remove the crank or continue to "disconnected" position.

The circuit breaker is in "disconnected" position.

These operations require that all chassis-locking functions be disabled (see page 19).

Using the EasyPact SPS drawout chassis

Released for ManufacturingPrinted on 2018/04/12

Page 18: Low voltage electrical distribution EasyPact SPS

16 HRB75971 - 03/2013

Using the EasyPact SPS drawout chassis

Racking

Position the circuit breaker on the rails.Check that it rests on all four supports.

DB

1193

48

Open the circuit breaker (in any case, it opens automatically during connection).

E51

499A

Push the circuit breaker into the chassis, taking care not to push on the control unit.

For complete information on EasyPact handling and mounting, see the installation manual(s).

Before mounting the circuit breaker, make sure it matches the chassis.

Inserting EasyPact

DB

1193

49

DB

1193

50

Removing the railsPress the release tabs and pull the rails out.

Press the release tabs to push the rails in.

DB

1193

47

DB

1193

46

1

2 3

DB

1193

51

Released for ManufacturingPrinted on 2018/04/12

Page 19: Low voltage electrical distribution EasyPact SPS

17HRB75971 - 03/2013HRB75971 - 03/2013

Racking the circuit breaker from the "disconnected" to "test" position, then to "connected" position

The device is in "disconnected" position.

The device is in "test" position.

The device is in "test" position. Remove the crank or continue to "connected" position.

The device is in "connected" position.

Using the EasyPact SPS drawout chassis

Racking

DB

1197

18

Released for ManufacturingPrinted on 2018/04/12

Page 20: Low voltage electrical distribution EasyPact SPS

18 HRB75971 - 03/2013

Locking the switchboard door

Disabling door openingClose the door.

DB

1193

57

Enabling door openingPut the EasyPact in "disconnected" position.

E51

469A

The door is unlocked.

The locking device is installed on the left or right-hand side of the chassis. b When the circuit breaker is in "connected" or "test" position, the latch is lowered

and the door is locked b When the circuit breaker is in "disconnected" position, the latch is raised and the

door is unlocked.

DB

1193

54E

5146

5A

DB

1193

55

DB

1193

56

Put the EasyPact in "test" or "connected" position.

The door is locked.

Using the EasyPact SPS drawout chassis

Released for ManufacturingPrinted on 2018/04/12

Page 21: Low voltage electrical distribution EasyPact SPS

19HRB75971 - 00 - 03/2013

Using the EasyPact drawout chassis

Locking the circuit breaker in positionUsing padlocks

Circuit breaker in "disconnected" position.

DB

1193

58Pull out the tab.

DB

1193

60

DB

1193

59

Insert the shackle (max. diameter 5 to 8 mm) of the padlock(s).

DB

1193

64

DB

1193

61

Padlocks and keylocks may be used together.Padlocks are not supplied.

UnlockingRelease the tab.

The crank can be inserted.

The crank cannot be inserted.

DB

1193

62

DB

1193

63

Test

1 2

3

1 2

3 4

Combination of locking systemsTo disable connection of the circuit breaker in "disconnected" position in thechassis, use as needed:

b one to three padlocks b one keylock b a combination of the two locking systems.

Disabling connection when the circuit breaker is in "disconnected" position, using one to three padlocks (maximum shackle diameter 5 to 8 mm)Locking

Remove the padlock(s).

If specified when ordering the chassis, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.

Released for ManufacturingPrinted on 2018/04/12

Page 22: Low voltage electrical distribution EasyPact SPS

20 HRB75971 - 00 - 03/2013

1 3

Unlocking

Two types of keylocks are available

DB

1193

69

The crank can be inserted.

Insert the key(s).

DB

1193

70

DB

1193

71

Turn the key(s).

E51

270A

RONIS

DB

1187

49

PROFALUX

2

Padlocks and keylocks may be used together.Padlocks are not supplied.

Remove the key(s). The crank cannot be inserted.

DB

1193

67

DB

1193

68 44

Disabling connection when the circuit breaker is in "disconnected" position, using one or two keylocks.Locking

DB

1193

65

Circuit breaker in "disconnected" position.

DB

1193

66

Turn the key(s).

T est

1 22

Using the EasyPact drawout chassis

Locking the circuit breaker in positionUsing Keylocks

33

Released for ManufacturingPrinted on 2018/04/12

Page 23: Low voltage electrical distribution EasyPact SPS

21HRB75971 - 00 - 03/2013

Locking the safety shuttersPadlocking inside the chassis

Four locking possibilities: using one or two padlocks (maximum shackle diameter 5 to 8 mm) for each shutter

DB

1193

75D

B11

9376

Top and bottom shutters not locked.

Top shutter not locked.Bottom shutter locked.

Top shutter locked.Bottom shutter not locked.

Top and bottom shutters locked.

Using the EasyPactdrawout chassis

Padlocks are not supplied.

Released for ManufacturingPrinted on 2018/04/12

Page 24: Low voltage electrical distribution EasyPact SPS

22 HRB75971 - 03/2013

Identifying Microprocessor basedET Trip System Designations

DiscoveringMicroprocessor basedET Trip System

.

A25315E

Microprocessor based ET2.0 Trip System: basic protection

Long time + Instantaneous

0 Ir Isd I

t

Microprocessor based ET6G Trip System: selective + ground-fault protection

A45315E

A59315E

0 Ir I

t

IiIsd

Long time + Short time+ Instantaneous

Ground-fault protection

0 I

t

I2t off

I2t on

Ig

ET2I Trip System

.98

instantaneous

long timealarm

.512

48

121620

tr(s)

at 6 Ir24.4

.5

.6.7 .8 .9

.95

1

Ir

x In

x Ir

22.5

3 4 568

101.5

setting

Isd

x Ir

22.5

3 4 568

10

Isd

1.5

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

4 8 121620

tr

24

long time alarm(s)

6xIr

setting

instantaneous

ET2.0 Trip System

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

A 2

.2

.3.4 .4

.1

.2.3

.10

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

6xIr

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

All EasyPact SPS Air Circuit Breakers are equipped with icroprocessor based ET Trip System.Microprocessor based ET Trip Systems are designed to protect power circuits and connected loads

Released for ManufacturingPrinted on 2018/04/12

Page 25: Low voltage electrical distribution EasyPact SPS

Identifying Microprocessor basedET Trip System Designations

DiscoveringMicroprocessor basedET Trip System

1 top fastener2 bottom fastener3 protective cover4 cover opening point5 lead-seal fixture for protective cover6 long-time rating plug7 screw for long-time rating plug8 connection with circuit breaker

Adjustment dials

14 long-time current setting Ir15 long-time tripping delay tr16 short-time pickup Isd17 short-time tripping delay tsd18 instantaneous pick-up Ii19 LED indicating an overload-alarm

23 test connector

20 ground-fault pick-up Ig21 ground-fault tripping delay tg

Test

22 test button for ground-fault

Microprocessor based ET Trip System description

Microprocessor based ET2.0 Trip System

Microprocessor basedET6G Trip System

ET2I Trip System

.98

instantaneous

long timealarm

.512

48

121620

tr(s)

at 6 Ir24.4

.5

.6.7 .8 .9

.95

1

Ir

x In

x Ir

22.5

3 4 568

101.5

setting

Isd

x Ir

22.5

3 4 568

10

Isd

1.5

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

4 8 121620

tr

24

long time alarm(s)

6xIr

setting

instantaneous

ET2.0 Trip System

19

23

16

14

15

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I

2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

6xIr

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

19

18

22

23

21

20

17

14

15

16

9 long-time trip indicator light10 short-time or instantaneous trip indicator light11 self-protection indicator light12 reset button for battery status check and trip indicator LED13 ground-fault trip indicator light

.4.5.6

.7.8 .9

.95

.981

.512

48 12

1620

24

long time

alarm

Irtr(s)

x In@ 6 Ir

1

5

3

7

6

4

2 8

13

9

1012

11

ET6G Trip System

23HRB75971 - 03/2013 Released for ManufacturingPrinted on 2018/04/12

Page 26: Low voltage electrical distribution EasyPact SPS

24 HRB75971 - 03/2013

Overview of functionsCurrent protecton

DiscoveringMicroprocessor basedET Trip System

Protection settingsDepending on the type of installation, it is possible to set the tripping curve of yourMicroprocessor based ET Trip System using the parameters presented below.

Thermal memoryThe thermal memory continuously accounts for the amount of heat in the cables,both before and after tripping, whatever the value of the current (presence of anoverload or not). The thermal memory optimises the long-time protection functionof the circuit breaker by taking into account the temperature rise in the cables.The thermal memory assumes a cable cooling time of approximately 20 minutes.

Long-time current setting Ir and standard tripping delay tr

A85315E

Microprocessor basedET2.0 Trip System

1. current setting Ir(long time)2. tripping delay tr(long time) for 6 x Ir3. pick-up Isd(instantaneous)

1. current setting Ir (long time)2. tripping delay tr (long time) for 6 x Ir3. pick-up Isd (short time)4. tripping delay tsd (short time)5. pick-up Ii (instantaneous)

Microprocessor basedET6G Trip System

A95315E

Microprocessor based ET Trip Systemcurrent setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1tripping betweeen 1.05 and 1.20 Ir

time setting 0,5 1 2 4 8 12 16 20 24time delay (s) tr at 1.5 x Ir 0 to - 30% 12.5 25 50 100 200 300 400 500 600

tr at 6 x Ir 0 to - 20% 0.7 (1) 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

(*) In: circuit breaker rating(1) 0 to - 40%(2) 0 to - 60%

This LED signals that the long-time current setting Irhas been overrun.

0 Ir Isd I

t1

2

3

1

2

34

5

0 Ir Isd I

t

Ii

I2t off

I2t on

Long-time protectionThe long-time protection function protects cables (phases and neutral) againstoverloads. This function is based on true rms measurements.

Microprocessor basedET6G Trip System

1. pick-up Ig (groundfault)2. tripping delay tg(ground fault)

0

t

1

2

I2t off

I2t on

Ig

Overload LED

alarm

6xIr

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

x Ir

22.5

3 4 568

10

Isd

1.5

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

4 8 121620

tr

24

long time alarm(s)

6xIr

setting

instantaneous

2.0 and 6G

Accuracy

Released for ManufacturingPrinted on 2018/04/12

Page 27: Low voltage electrical distribution EasyPact SPS

Short-time protection1. the short-time protection function protects the distribution system against

impedant short-circuits.2. the short-time tripping delay can be used to ensure discrimination with

a downstream circuit breaker.3.

4.

the I2t ON and I2t OFF options enhance discrimination with downstreamprotection devices.

use of I2t curves with short-time protection:a. I2t OFF selected: the protection function implements a constant time curveb. I2t ON selected: the protection function implements an I2t inverse-time curve up to

10 Ir. Above 10 Ir, the time curve is constant.Short-time pick-up Isd and tripping delay tsd

Microprocessor based ET Trip System 6Gpick-up Isd = Ir x … accuracy± 10% 1.5 2 2.5 3 4 5 6 8 10time delay (ms) setting I2t Off 0 0.1 0.2 0.3 0.4

IrI01ta 2t On 0.1 0.2 0.3 0.4I2 0530320410802)emitelbatteserxam(dstronOtI2 00502300204108)emitkaerbxam(dstffOt

Instantaneous protection the instantaneous-protection function protects the distribution systemagainst solid short-circuits. Contrary to the short-time protection function,the tripping delay for instantaneous protection is not adjustable.The tripping order is sent to the circuit breaker as soon as current exceedsthe set value, with a fixed time delay of 20 milliseconds.Instantaneous pick-up Isd

Microprocessor based ET Trip System 2.0pick-up Isd = Ir x ... accuracy± 10 % 1.5 2 2.5 3 4 5 6 8 10time delay (ms) tsd (max resettable time) 20

tsd (max break time) 80

Instantaneous pick-up IiMicroprocessor based ET Trip System 6G

pick-up li = In (*) x … accuracy± 10 % 2 3 4 6 8 10 12 15 OFFtime delay (ms) tsd (max resettable time) 20 tsd (max break time) 50

Ground-fault pick-up Ig and tripping delay tgThe pick-up and tripping-delay values can be set independently.

Microprocessor based ET Trip System

time delay settings I2 4.03.02.01.00FFOt(ms) at 10 In (*) I2 4.03.02.01.0NOtI2 t ON or tg (max resettable time) 20 80 140 230 350I2 00502300204108)emitkaerbxam(gtFFOt

* In: circuit-breaker rating

Protection of the fourth pole on four-pole circuit breakers (Refer page 29)Type of neutral Description.

Ground-fault protection on ET6G Trip System A ground fault in the protection conductors can provoke local temperature riseat the site of the fault or in the conductors.The purpose of the ground-fault protection function is to eliminate this type of fault.Type Description

1. ground-fault and neutral protection are independent and can therefore becombined.

Neutral protection for three-pole devicesNeutral protection is not available on three-pole devices.

6G

Residual 1. the function determines the zero-phase sequencecurrent, i.e. the vectorial sum of the phase and neutralcurrents2. it detects faults downstream of the circuit breaker.

Neutral protection The cross-sectional area of the neutral conductor is equalat In to that of the phase conductors.

1. the long-time current setting Ir for the neutral is equalto the setting value

2. the short-time pick-up Isd for the neutral is equal tothe setting value

3. the instantaneous pick-ups Isd and Ii for the neutralare equal to the setting value.

2. ground-fault protection in 3P+N system is activated by installing a external sensor(CT) in the neutral conductor and connecting to Microprocessor based ET Trip System.

(Refer page 31)

Pick-up (A) Ig = In x … A B C D E F G H JAccuracy: ±10 % In y 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In y 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In u 1250 A 500 640 720 800 880 960 1040 1120 1200

Overview of functionsCurrent protecton

DiscoveringMicroprocessor basedET Trip System

25HRB75971 - 03/2013 Released for ManufacturingPrinted on 2018/04/12

Page 28: Low voltage electrical distribution EasyPact SPS

26 HRB75971 - 03/2013

Setting procedureSettingMicroprocessor basedET Trip System

Setting procedure

Using the adjustment dials

A36315E

A46315E

A56315E

Open the protectivecover.

Select the desiredsetting.

Close the protectivecover and, if necessary,install a lead seal toprotect the settings.

ET2.0 Trip System

1 2

ET2.0 Trip System

3

ET2.0 Trip System

Fault indications

Signals tripping due to anoverrun of the long-timecurrent setting Ir.

Signals tripping dueto an overrun of theshort-time pick-up Isdor the instantaneouspick-up Isd / Ii.

Signals tripping due to anoverrun of the ground-fault pick-up Ig

Signals tripping due tothe auto-protection, Apfunction of the Microprocessor basedET Trip System

.

ET6G Trip SystemET6G Trip System

ET6G Trip SystemET6G Trip SystemET6G Trip SystemET6G Trip System

ET6G Trip SystemET6G Trip System

The auto-protection function (excessive temperature or short-circuit higher than circuit-break er capacity) opens the circuit breaker capacity) opens the circuit breaker and turns on the Ap LED.

Caution.If the circuit breaker remains closed and the Ap LED remains on, contact the Schneider after-sales support department.

Caution.The battery maintains the fault indications.If there are no indications, check the battery.

Released for ManufacturingPrinted on 2018/04/12

Page 29: Low voltage electrical distribution EasyPact SPS

SettingMicroprocessor basedET Trip System

Setting the Microprocessor based ET2.0 Trip System

Set the threshold values

A86315E

Set the tripping delay

A07315E

Ir = 0.7 x In = 700 A

Isd = 3 x Ir = 2100 A

0 I

tIr

Isd

tr = 1 second

0 I

t

tr

The rating of the circuit breaker in this example is 1000 A.

See pages 24 and 25 for informationon the available setttings.

1

In = 1000 A

x Ir

22.5

3 4 568

10

Isd

1.5

.4.5.6

.7 .8 .9.95.98

1

Ir

x In

long time alarm

setting

instantaneous

Ir

.512

4 8 121620

tr

24

long time alarm(s)

6xIr

In = 1000 A

27HRB75971 - 03/2013 Released for ManufacturingPrinted on 2018/04/12

Page 30: Low voltage electrical distribution EasyPact SPS

28 HRB75971 - 03/2013

SettingMicroprocessor basedET Trip System

Setting the Microprocessor based ET6G Trip System

The rating of the circuit breakerin this example is 1000 A.

See pages 24 and 25 for informationon the available settings.

1

In = 1000 A

In = 1000 A

t on I

Set the threshold values

A37315E

A27315E

Ir

Isd

Ii

0 I

tIr

Isd

Ii

0 I

t

I2t ON curve I2t OFF curve

Set the tripping delay

A67315E

A57315E

tr

tsd

0 I

t

tr

tsd

0 I

t

A61415E

A51415E

A91415E

A81415E

t

tg

t

tg

In = 1000 A

Ir = 0.7 x In = 700 A

Ii = 3 x In = 3000 A

Isd = 2 x Ir = 1400 A

B Ig = 300 A

0 I

t

Ig

0 I

t

Ig

tr = 1 s

tsd = 0.2 s

tg = 0.2 s

I2 2t off

Thresholds

Tripping delays

I2t ON curve I2t OFF curve

alarm

ground fault

testoff off

long time

short time instantaneous

alarm

6xIr

ground fault

test

on off

on off

(s)

(s)

(s)

long time

short time

Released for ManufacturingPrinted on 2018/04/12

Page 31: Low voltage electrical distribution EasyPact SPS

SettingMicroprocessor basedET Trip System

29HRB75971 - 03/2013

Selecting the type of neutral protection

To test the Microprocessor based ET Trip System, connect the portable test kit via the test connector

A36315E

A77315E

Testing the Microprocessor basedET Trip System

Micrologic 2.0

1

Micrologic 2.0

2

Micrologic 2.0

2

1. neutral unprotected (4P 3D);2. neutral protection at 0.5 In (3D + N/2);3. neutral protection at In (4P 4D).

A38315E

4P 3D

3D+N/24P 4D

On four-pole circuit breakers, it is possible to select the type of neutral protection forthe fourth pole using the three-position dial on the circuit breaker:

The factory default setting is 3D + N/ 2.

Caution!With the 4P 3D setting, the current in the neutral mustnot exceed the rated current of the circuit breaker.

See the user manualfor the portable test kit.

Released for ManufacturingPrinted on 2018/04/12

Page 32: Low voltage electrical distribution EasyPact SPS

30 HRB75971 - 03/2013

Fault and statusindications

Resetting the fault indicationsand checking battery status

Resetting the fault indications1. determine why the circuit breaker tripped. The fault indication is maintained until it is reset on the control unit.a. press the fault-trip reset button.

b. check the parameter settings of the control unit.

ET6G Trip SystemET6G Trip System

Changing the control-unit battery(only ET6G)

1. Remove the batterycover.

2. Remove the battery.

A24415E

A34415E

3. Insert a new battery.Check the polarity.

4. Put the cover back inplace. Press the battery-test button to check thenew battery.

A44415E +

A54415E

Checking the battery

Press the battery-test button (same as the fault-trip reset button) to checkthe battery status by the luminance of trip indicator light.

If trip indicators became dim or no luminance,the battery should be changed.

ET6G Trip SystemET6G Trip System

If the battery needs to be changed, order anew battery with the Schneider cataloguenumber 33593.

1. lithium battery 2. 1.2 AA, 3.6 V, 850 mA/h 3. SAFT LS3 SONNENSCHEIN TEL-S

The procedure for closing the circuitbreaker following a fault trip is presentedin the circuit-breaker user manual.

Applicable only on ET6G Trip System

Released for ManufacturingPrinted on 2018/04/12

Page 33: Low voltage electrical distribution EasyPact SPS

Fault and statusindications

Testing the ground-fault functions

Charge and close the circuit breaker.Using a screwdriver, press the test button for ground-faultprotection. The circuit breaker should open.

B65415E

ET6G Trip System

me

If the circuit breaker does not open, contact the Schneider after-salessupport department.

31HRB75971 - 03/2013

Applicable only on ET6G Trip System

Released for ManufacturingPrinted on 2018/04/12

Page 34: Low voltage electrical distribution EasyPact SPS

32 HRB75971 - 03/2013

Technical appendix Tripping curves

Long-time and instantaneous protection (Microprocessor based ET2.0 Trip System)

A96306E

.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300

I / Ir

10 0005 000

2 0001 000

500

200100

50

2010

5

21

.5

.2

.1.05

.02

.01.005

.002

.001

t(s)

tr = 0.5…24 s

Isd = 1.5…10 x Ir

Ir = 0.4…1 x In

Released for ManufacturingPrinted on 2018/04/12

Page 35: Low voltage electrical distribution EasyPact SPS

Technical appendix

33HRB75971 - 03/2013

Tripping curves

Long-time, short-time and instantaneous protection(Microprocessor based ET6G Trip System )

A07306E

0

0.40.3

0.20.1

t(s)

.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30

10 0005 000

2 0001 000

500

20010050

20105

21

.5

.2

.1.05

.02

.01.005

.002

.001

x In

tr = 0.5…24 s

Isd = 1.5…10 x Ir

Ir = 0.4…1 x In

Ii = 2…15 x In . OFF (1)

I2t OFF

x Ir

0.40.3

0.20. 1

I2t ON

0

Ground-fault protection (Microprocessor based ET6G Trip System)

A66264E

Ig = A…J x In (1) 1200 A max.

t(s)

I / In

10 0005 000

2 0001 000

500

20010050

20105

21

.5

.2

.1.05

.02

.01.005

.002

.001.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300

I2t OFF

0.40.30.20.1

I2t ON

0.40.30.20.1

0 0

Released for ManufacturingPrinted on 2018/04/12

Page 36: Low voltage electrical distribution EasyPact SPS

34 HRB75971 - 03/2013

Technical appendix Thermal memory

Thermal memoryThe thermal memory is a means to simulate temperature rise and cooling causedby changes in the flow of current in the conductors.

These changes may be caused by:1. repetitive motor starting;2. loads fluctuating near the protection settings;3. repeated circuit-breaker closing on a fault.Microprocessor based ET Trip System without a thermal memory (contrary to bimetal strip thermalprotection) do not react to the above types of overloads because they do notlast long enough to cause tripping.However, each overload produces a temperature rise and the cumulative effectcan lead to dangerous overheating.

Microprocessor based ET Trip System with a thermal memory record the temperature rise causedby each overload. Even very short overloads produce a temperature risethat is stored in the memory.This information stored in the thermal memory reduces the tripping time.

Microprocessor based ET Trip System and thermal memoryAll Microprocessor based ET Trip System are equipped as standard with a thermal memory.

1. for all protection functions, prior to tripping, the temperature-rise and cooling timeconstants are equal and depend on the tripping delay in question:a. if the tripping delay is short, the time constant is low;b. if the tripping delay is long, the time constant is high.

2. for long-time protection, following tripping, the cooling curve is simulatedby the Microprocessor based ET Trip System.Closing of the circuit breaker prior to the end of the timeconstant (approximately 20 minutes) reduces the tripping time indicatedin the tripping curves.

Short-time protection and intermittent faultsFor the short-time protection function, intermittent currents that do no provoketripping are stored in the Microprocessor based ET Trip ystem memory.This information is equivalent to the long-time thermal memory and reducesthe tripping delay for the short-time protection.Following a trip, the short-time tsd tripping delay is reduced to the value ofthe minimum setting for 20 seconds.

Ground-fault protection and intermittent faultsThe ground-fault protection implements the same function as the short-timeprotection.

Released for ManufacturingPrinted on 2018/04/12

Page 37: Low voltage electrical distribution EasyPact SPS

35HRB75971 - 00 - 03/2013

CD1814812811

CE1 CT1314 914312 912311 911

OF4444241

OF3343231

OF2 OF124 1422 1221 11

MXC2C3C1

MND2

D1

XFA2A3A1

PF254252251

UC1 UC2 SDEZ5Z3Z1

Z4Z2

T3T1

T4T2

848281

MCHB2B3B1

MXC2C3C1

XFA2A3A1

PF254252251

UC1 UC2 SDEZ5Z3Z1

Z4Z2

T3T1

T4T2

848281

MCHB2B3B1

OF4444241

OF3343231

OF2 OF124 1422 1221 11

MND2

D1

SDE

DB

1193

77

Identifying the electrical auxiliaries

Identification of the connection terminalsLayout of terminal blocks

Key: Only for ET6G

SDE, OF1, OF2 supplied as standard and OF3,OF4 optional

Released for ManufacturingPrinted on 2018/04/12

Page 38: Low voltage electrical distribution EasyPact SPS

36 HRB75971 - 00 - 03/2013

DB

1193

78Operation

Circuit breaker

closed

completely closed completely open

main contacts

OF: ON/OFF (closed/open)indication changeover contacts

open

closed open

open closed

test position

separation of the auxiliary circuits

separation of the main circuits

completely connected

open

closed

closed

open

closed

open

CE: connected-positioncarriage switch

CT: test-position carriageswitch

CD: disconnected-positioncarriage switch

closed

open open

closed

completely disconnected

DB

1193

79

The ON/OFF indication contacts signal the status of the device main contacts.

ChassisFor information on the separation distance of the main circuits in the "test" and "disconnected" positions, see page 14.

The carriage switches indicate the "connected", "test" and "disconnected" positions.

Identifying the electrical auxiliaries

Released for ManufacturingPrinted on 2018/04/12

Page 39: Low voltage electrical distribution EasyPact SPS

37HRB75971 - 00 - 03/2013

2.0 6G

Identifying the electrical auxiliaries

Electrical diagramsFixed and drawout devices

b

b

E60

062A

The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position.

E60

063A

E60

064A

E60

067A

Power

UC1: Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault)

UC2: T1, T2, T3, T4 = external neutral;

Control unit

Control unit Remote operation

SDE: Fault-trip indication contact (supplied as standard)

MN: Undervoltage release

MX: Shunt release XF: Closing release

PF: "Ready to close" contact

MCH : Gear motor

2.0: Basic Protection6G: 2.0 + Isd + Ig

Ope

n Clos

e Rea

dy-

to-c

lose

Cha

rged

E60

065A

E46

136A

E46

137A

E60

066A

T4T3T2T1Z4

ET Trip System

Z4Z3Z2Z1Z5 Z1 Z2N L3L2L1

Q

Powerupstream cb downstream

cb

Z5

Z3Z2Z1 Z3 Z4 Z5

I

SG

1

SG

2

X1

X2

Remote operation

Remote operation SDE MN MX1 XF PF MCH

84 D2 C2 A2 254 B2 82 252 B3 81 D1 C1 A1 251 B1

Control unit UC1 UC2

Z5 Z3 Z4 T3 T4 Z1 Z2 T1 T2

Faul

t

Stop

Note: Z1...Z5 & T1..T4 are available only in ET6G trip system

Released for ManufacturingPrinted on 2018/04/12

Page 40: Low voltage electrical distribution EasyPact SPS

38 HRB75971 - 00 - 03/2013

E60

068A

E60

069A

E60

070A

E60

076A

Indication contacts

(*) 440/480 V AC gear motor for charging(380 V motor + additional resistor)

CD1: Disconnected-position

CT1: Test-positioncontacts

CE1: Connected-position

12 1411

22 2432 3431 21

OF4

42 4441

OF3 OF2 OF1

open closed

Key: Drawout device only

SDE,OF1, OF2, supplied as standard Interconnected connections (only one wire per connection point)

914

912

911

CT1

test

Chassis contacts

Chassis contacts

B1

CN2 - 440/480 V

9 11

MCH380V

CH

B3 B2

R440/480 V"charged LED"

CN1 - 440/480 V

XXX

E60

075A

Indication contacts

CD1 CE1 CT1 814 314 914

812 312 912

811 311 911

Indication contacts OF4 OF3 OF2 OF1 44 34 24 14

42 32 22 12

41 31 21 11

Contacts châssis

Identifying the electrical auxiliaries

Electrical diagramsFixed and drawout devices

812

814

811

CD1

disconnected

311

312

314

CE1

connected

Released for ManufacturingPrinted on 2018/04/12

Page 41: Low voltage electrical distribution EasyPact SPS

39HRB75971 - 00 - 03/2013

Discovering EasyPact SPS accessories

ET Trip System

E51

329A

E46

108A

.4.5.6

.7.8 .9

.95

.981

.512

48 12

1620

24

long time

alarm

Irtr(s)

x In@ 6 Ir

ET6G Trip System

ET trip system

Long-time rating plugs

b Standard equipment, one per device

b Part numbers (long-time rating plug and connectors not included, see below):ET 2.0: MVS15514ET 6G: 67479Part numbers for connectors for ET6G

v for fixed device: 47065 v for drawout device: 47066

b Depending on the model, control units offer in addition:

v fault indications v Earth-fault protection

b Standard equipment, one per control unit

b Part numbers for setting options:

v standard 0.4 to 1 x Ir setting: 64888

b The plugs determine the setting range for the long-time protection.

Released for ManufacturingPrinted on 2018/04/12

Page 42: Low voltage electrical distribution EasyPact SPS

40 HRB75971 - 03/2013

Indication contacts

ON/OFF indication contacts (OF) b 4 changeover contacts b Breaking capacity at

cos ϕ = 0.3 (AC12 / DC12 as per 60947-5-1)

v standard, minimum current 10 mA / 24 VV AC 240/380 6 A (rms)

480 6 A (rms)V DC 24/48 2.5

125 0.5250 0.3

"Fault-trip" indication contact (SDE) b Standard equipment on

circuit breakers, one SDE contact per device

b Not available for switch-disconnector versions.

b Changeover contact b Breaking capacity at

cos ϕ = 0.3 (AC12 / DC12 as per 60947-5-1)

v standard, minimum current 10 mA / 24 VV AC 240/380 5 A (rms)

480 5 A (rms)V DC 24/48 3 A

125 0.3 A250 0.15 A

b Standard equipment, 2 OF per device

b Part numbers: v standard: 47076 b Part numbers for

connectors: v for fixed device: 47074 v for drawout device: 33098

b The contact provides a remote indication of device opening due to an electrical fault.

b OF contacts indicate the position of the main contacts

b They trip when the minimum isolation distance between the main contacts is reached.

Discovering EasyPact SPS accessories

E51

332A "Ready to close" contact (PF)

b Optional equipment, one PF contact per device

b Part numbers (connectors not included, see below):

v standard: 47080 b Part numbers for

connectors: v for fixed device: 47074 v for drawout device: 33098

b The contact indicates that the device may be closed because all the following are valid:

v circuit breaker is open v spring mechanism is

charged v a maintained closing

order is not present v a maintained opening

order is not present.

b Changeover contact b Breaking capacity at

cos ϕ = 0.3 (AC12 / DC12 as per 60947-5-1)

v standard, minimum current 10 mA / 24 VV AC 240/380 5 A (rms)

480 5 A (rms)V DC 24/48 3 A

125 0.3 A250 0.15 A

E51

332A

Released for ManufacturingPrinted on 2018/04/12

Page 43: Low voltage electrical distribution EasyPact SPS

41HRB75971 - 03/2013HRB75971 - 03/2013

Discovering EasyPact SPS accessories

Auxiliaries for remote operation

Gear motor (MCH) b The gear motor

automatically charges the spring mechanism.

b Power supply: v V AC 50/60 Hz: 48/60

100/130 - 200/240 -277 400/440-480

v V DC: 24/30 - 48/60 100/125 - 200/250

b Operating threshold:0.85 to 1.1 Un

b Consumption:180 VA or W

b Inrush current:2 to 3 In for 0.1 second

b Charging time: 3 seconds max.

b Operating rate: maximum 3 cycles per minute.

E51

294A

E51

294A

Closing release XF

Opening releases MX

b Optional equipment, XF release per device

b The function (XF) is determined by where the coil is installed

b Part numbers (connectors not included, see below)V AC 50/60 Hz, V DC:

v standard version:24AC 24/30DC: 3365948AC 48/60DC: 33660100/130 AC/DC: MVS15511200/250 AC/DC: MVS15512380/480 AC: MVS15513

b Part numbers for connectors:

v for fixed device v for drawout device.

b Optional equipment, 1 MX release per device

b The function (MX) is determined by where the coil is installed

b Part numbers (connectors not included, see below)V AC 50/60 Hz, V DC:

v standard version:24AC 24/30DC: 3365948AC 48/60DC: 33660100/130 AC/DC: 33661200/250 AC/DC: 33662380/480 AC: 33664

b Part numbers for connectors:

v for fixed device: 47074 v for drawout device: 33098

b The XF release instantaneously closes the circuit breaker when energised, if the device is "ready to close".

b The MX release instantaneously opens the circuit breaker when energised

b Optional equipment, one MCH gear motor per device

b Part numbers (connectors not included, see below):

v AC 50 / 60 Hz:48: 33186100/130: 33176200/240: 33177277/415: 33179440/480 +Resistor: 33179 + 33193

v DC24/30: 3318548/60: 33186100/125: 33187200/250: 33188

b Part numbers for connectors:

v for fixed device: 47074 v for drawout device: 33098

b Power supply: v V AC 50 / 60 Hz:

24 48 - 100/130 - 200/250 -240/277 - 380/480

v V DC: 24/30 - 48/60 - 100/130 - 200/250

b Operating threshold: v XF: 0.85 to 1.1 Un b Consumption: v pick-up: 200 VA or W

(80 ms) v hold: 4.5 VA or W b Circuit-breaker

response time at Un: v XF: 55 ms ± 10.

b Power supply: v V AC 50 / 60 Hz:

24 48 - 100/130 - 200/250 -240/277 - 380/480

v V DC: 24/30 - 48/60 - 100/130 - 200/250

b Operating threshold: v MX: 0.7 to 1.1 Un b Consumption: v pick-up: 200 VA or W

(80 ms) v hold: 4.5 VA or W b Circuit-breaker

response time at Un: v MX: 50 ms ± 10.

E46

790A

Released for ManufacturingPrinted on 2018/04/12

Page 44: Low voltage electrical distribution EasyPact SPS

42 HRB75971 - 03/2013

Discovering EasyPact SPS accessories

Instantaneous undervoltage releases (MN) b Optional equipment,

1 MN per device b Part numbers (connectors

not included, see below)V AC 50/60 Hz, V DC:24AC 24/30DC: 3366848AC 48/60DC: 33669100/130 AC/DC: 33670200/250 AC/DC: 33671380/480 AC: 33673

b Part numbers for connectors:

v for fixed device: 47074 v for drawout device: 33098

b The MN release instantaneously opens the circuit breaker when its supply voltage drops.

b Power supply: v V AC 50/60 Hz: 24/48

100/130 - 200/250 240/277 - 380/480

v V DC: 24/30 - 48/60 100/130 - 200/250

b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W

(80 ms) v hold: 4.5 VA or W b Circuit-breaker

response time at Un: 40 ms ± 10.

Auxiliaries for remote operationE

5129

4AE

5129

6A

b Optional equipment, 1 MN with delay unit per device

b Delay-unit part numbers V AC 50/60 Hz, V DC:

v non adjustable:100/130 AC/DC: 33684200/250 AC/DC: 33685

v adjustable:48/60 AC/DC: 33680100/130 AC/DC: 33681200/250 AC/DC: 33682380/480 AC/DC: 33683

Delay unit for MN releases b The unit delays

operation of the MN release to eliminate circuit-breaker nuisance tripping during short voltage dips

b The unit is wired in series with the MN and must be installed outside the circuit breaker.

b Power supply V AC 50/60 Hz, V DC:

v non adjustable:100/130 - 200/250

v adjustable:48/60 - 100/130200/250 - 380/480

b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W

(80 ms) v hold: 4.5 VA or W b Circuit-breaker

response time at Un: v non adjustable:

0.25 second v adjustable: 0.5 - 0.9 -

1.5 - 3 seconds.

3 6

MNUVR

1012

100/130 V

AC/DC

S

0.5 1

3 1.5

Retardateur de MN

Time delay for UVR

4 5 6

1 2 3

1 2 3

Released for ManufacturingPrinted on 2018/04/12

Page 45: Low voltage electrical distribution EasyPact SPS

43HRB75971 - 03/2013HRB75971 - 03/2013

Wiring of control auxiliariesUnder pick-up conditions, the level of consumption is approximately 150 to 200 VA.Consequently, for low supply voltages ( 24, 48 V), cables must not exceed a maximum length determined by the supply voltage and the cross-section of the cables.Indicative values for maximum cable lengths (in meters)

24 V 48 V2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2

MN 100 % source voltage 58 36 280 16585 % source voltage 16 10 75 45

MX-XF 100 % source voltage 115 70 550 33085 % source voltage 75 44 350 210

Note: The indicated length is that for each of the two supply wires.

Discovering EasyPact SPS accessories

Auxiliaries for remote operation

Released for ManufacturingPrinted on 2018/04/12

Page 46: Low voltage electrical distribution EasyPact SPS

44 HRB75971 - 03/2013

Discovering EasyPact SPS accessories

Device mechanical accessoriesE

6049

9A Escutcheon (CDP) b Optional equipment,

one CDP per device b Part numbers: v for fixed device: 33718 v for drawout device:

33857.

b The CDP increases the degree of protection to IP 40 and IK 07 (fixed and drawout devices).

E60

498A

E60

498A

Transparent cover (CCP)

Blanking plate (OP)

b Optional equipment, one CCP per device equipped with a CDP

b Part number: 33859 (for drawout devices).

b Optional equipment, one OP per device

b Part number: 33858.

b Mounted with a CDP, the CCP increase the degree of protection to IP 54 and IK 10 (fixed and drawout devices).

b Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.

Released for ManufacturingPrinted on 2018/04/12

Page 47: Low voltage electrical distribution EasyPact SPS

45HRB75971 - 03/2013HRB75971 - 03/2013

E60

347A Transparent cover for pushbutton locking using a

padlock, lead seal or screws b Optional equipment, one

locking cover per device b Part number: 33897

b The transparent cover blocks access (together or separately) to the pushbuttons used to open and close the device

b Locking requires a padlock, a lead seal or two screws.

Device OFF position locking kit for keylocks b Optional equipment:

one locking kit (without keylock) per device

b Part numbers: v for Profalux:

MVS31117 v for Ronis: MVS31113 b Optional equipment,

one locking system per device.

b The kit inhibits local or remote closing of the device

b Mounted on the chassis and accessible with the door closed, this system locks the circuit breaker in "disconnected" position using one or two keylocks.

E60

348A

Ronis

Profalux

Keylocks required for the device OFF position b One or two keylocks

per locking kit b Part numbers: v Profalux:

1 keylock.: 428882locks+1key: 42878

v Ronis:1lock+1key: 419402locks+1key: 41950

E51

286A

DB

1191

80

Discovering EasyPact SPS accessories

Device mechanical accessories

Released for ManufacturingPrinted on 2018/04/12

Page 48: Low voltage electrical distribution EasyPact SPS

46 HRB75971 - 03/2013

Discovering EasyPact SPS accessories

Chassis accessories

Safety shutters b Optional equipment b Part numbers (set of

shutters for top and bottom) drawout, front/rear connection:

v 3 poles: 33765 v 4 poles: 33766

b Mounted on the chassis, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the "disconnected" or "test" positions.

b IP 20 for chassis connections

b IP 40 for the disconnecting contact cluster.

E60

030A

Ronis

Profalux

Keylocks required with the "disconnected" position locking system

b One keylock per locking system

b Part numbers: v Profalux:

1keylock: 428882locks+1key: 42878

v Ronis:1keylock: 419402locks+1key: 41950

E51

286A

E51

273A

DB

1191

80

DB

1191

91

Top shutter closed Bottom shutter closed

E60

031A

Circuit breaker locking in "disconnected" position b Optional equipment,

one locking system per device

b Part numbers (keylocks not included):

v for Profalux keylocks: 33769

v for Ronis keylocks: 33770

b Mounted on the chassis and accessible with the door closed, this system locks the circuit breaker in "disconnected" position using one or two keylocks.

If specified when ordering the chassis, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.

Released for ManufacturingPrinted on 2018/04/12

Page 49: Low voltage electrical distribution EasyPact SPS

47HRB75971 - 03/2013HRB75971 - 03/2013

Door interlock b Optional equipment,

one door interlock per chassis

b Part number: 33172

b This device inhibits opening of the cubicle door when the circuit breaker is in "connected" or "test" position.

b It may be mounted on the left or right-hand side of the chassis.

E60

011A

Opush OFF

O OFF

Auxiliary terminal shield (CB) b Optional equipment,

one CB shield per chassis b Part numbers:

3 poles: 33763 4 poles: 33764

b The shield prevents access to the terminal block of the electrical auxiliaries.

E60

345A

"Connected", "disconnected" and "test" position carriage switches (CE, CD, CT)

b Optional equipment, one to three carriage switches

b Standard configuration, 0 to 1 CE, 0 to 1 CD, 0 to 1 CT

b Part numbers: v standard: 33170

b The carriage switches indicate the three positions:CE: connected positionCD: disconnected position (when the minimum isolation distance between the main contacts and the auxiliary contacts is reached) CT: test position.

b Changeover contact b Breaking capacity at

cos ϕ = 0.3 (AC12 / DC12 as per 60947-5-1)

v standard, minimum current 10 mA / 24 VV AC 240 8 A (rms)

380 8 A (rms)480 8 A (rms)

V DC 24/48 2.5 A125 0.8 A250 0.3 A

E46

095A

Discovering EasyPact SPS accessories

Chassis accessories

Released for ManufacturingPrinted on 2018/04/12

Page 50: Low voltage electrical distribution EasyPact SPS

48 HRB75971 - 03/2013

Inspecting and testing before use

Initial testsProcedure

A general check of the circuit breaker takes only a few minutes and avoids any risk of mistakes due to errors or negligence.A general check must be carried out:

b prior to initial use b following an extended period during which the circuit breaker is not used.

A check must be carried out with the entire switchboard de-energised. In switchboards with compartments, only those compartments that may be accessed by the operators must be de-energised.

Electrical testsInsulation and dielectric-withstand tests must be carried out immediately after delivery of the switchboard. These tests are precisely defined by international standards and must be directed and carried out by a qualified expert.

Prior to running the tests, it is absolutely necessary to: b disconnect all the electrical auxiliaries of the circuit breaker (MCH, MX, XF, MN) b remove the long-time rating plug on the 2.0, 6G control units.

Switchboard inspectionCheck that the circuit breakers are installed in a clean environment, free of any installation scrap or items (tools, electrical wires, broken parts or shreds, metal objects, etc.).

Conformity with the installation diagramCheck that the devices conform with the installation diagram:

b breaking capacities indicated on the rating plates b identification of the control unit (type, rating) b presence of any optional functions (remote ON/OFF with motor mechanism,

auxiliaries, measurement and indication modules, etc.) b protection settings (long time, short time, instantaneous, earth fault) b identification of the protected circuit marked on the front of each circuit breaker.

Condition of connections and auxiliariesCheck device mounting in the switchboard and the tightness of power connections.Check that all auxiliaries and accessories are correctly installed:

b electrical auxiliaries b terminal blocks b connections of auxiliary circuits.

OperationCheck the mechanical operation of the circuit breakers:

b opening of contacts b closing of contacts.

Check on the control unitIdentify the control unit of each circuit breaker Please refer page no. 22

These operations must be carried out in particular before using a EasyPact device for the first time.

Released for ManufacturingPrinted on 2018/04/12

Page 51: Low voltage electrical distribution EasyPact SPS

49HRB75971 - 03/2013HRB75971 - 03/2013

Note the faultFaults are signalled locally and remotely by the indicators and auxiliary contacts installed on circuit breakers (depending on each configuration). See page 11 in this manual and the user manual of the control unit for information on the fault indications available with your circuit breaker.

Identify the cause of trippingA circuit must never be reclosed (locally or remotely) before the cause of the fault has been identified and cleared.A fault may have a number of causes:

b depending on the type of control unit, fault diagnostics are available. See the user manual for the control unit.

b depending on the type of fault and the criticality of the loads, a number of precautionary measures must be taken, in particular the insulation and dielectric tests on a part of or the entire installation. These checks and test must be directed and carried out by qualified personnel.

Inspect the circuit breaker following a short-circuit b Check the arc chutes (see page 51) b Check the contacts (see page 51) b Check the tightness of connections (see the device installation manual) b Check the disconnecting-contact clusters (see page 51).

Reset the circuit breakerThe circuit breaker can be reset locally or remotely. See page 11 in this manual for information on how the circuit breaker can be reset.

What to do when the circuit breaker trips

Inspecting and testing before use

Released for ManufacturingPrinted on 2018/04/12

Page 52: Low voltage electrical distribution EasyPact SPS

50 HRB75971 - 03/2013

Interval Operation ProcedureEach year b Open and close the device locally

and remotely, successively using the various auxiliaries

b Test the operating sequences b Test the control unit using the mini

test kit

v see pages 9 and 10

v see pages 9 and 10 v see the user manual of the

control unitEvery two years b Check the arc chutes

b Check the main contacts b Check the tightness of

connections

v see page 51 v see page 51 v see the device installation

manual

Maintaining EasyPact SPS performance

Recommended maintenance program

Periodic inspections required

Type of circuitbreaker

Maximumservice life

Service life of various parts

Arc chutes,main contacts

Connecting-rod springs, MCH,interlockingsystems

MX / XF / MNreleases

SPS08 to 16Type F

12500 440 V: 6000 12500 12500

Recommended program for devices used under normal operating conditions:Ambient temperature: -5 °C / +70 °CNormal atmosphere

Part Intervening entity Description or procedure

Arc chutes b User v see page 51Main contacts b Inspection: user

b Replacement: Schneider After Sales Support

v see page 51

MCH gear motor b User v see page 8Mechanical interlocks b UserConnecting-rod springs

b Schneider After Sales Support

MX/MN/XF b User v see pages 9 and 10

Parts requiring replacement, depending on the number of operating cyclesThe following parts must be replaced periodically to lengthen the service life of the device (maximum number of operating cycles).

Part replacement must be programmed on the basis of the data below, listing the service life of the various parts in numbers of O/C cycles at the rated current.

Number of O/C cycles at the rated current

Released for ManufacturingPrinted on 2018/04/12

Page 53: Low voltage electrical distribution EasyPact SPS

51HRB75971 - 03/2013HRB75971 - 03/2013

Arc chutes b Remove the fixing screws

Maintenance operations

Before undertaking any maintenance work, de-energise the installation and fit locks or warnings in compliance with all applicable safety standards.

22

E60

045A

If the control unit has a maintenance indicator, there is no need to systematically check the contacts.

If the contacts are worn, have the concerned poles replaced by the Schneider service centre.

1

E60

000A

33

E60

001A

E60

002A

Wear of main contacts b Remove the arc chutes b Visually check the contacts.

If necessary, contact Schneider After-sales support.

b Check the arc chutes: v chamber intact v separators not corroded.

If necessary, replace the arc chutes.

b Refit the arc chutes and secure with a tightening torque of 1.5 Nm.

Disconnecting-contact clusters b Grease the contacts using the grease listed on page 52, supplied by Schneider

Electric b Check the contacts as follows: v open the circuit breaker v de-energise the busbars v disconnect the circuit breaker v remove the circuit breaker v check the contact fingers (no sign of copper should be visible).

Replace any worn clusters.

Maintaining EasyPact SPS performance

Released for ManufacturingPrinted on 2018/04/12

Page 54: Low voltage electrical distribution EasyPact SPS

52 HRB75971 - 03/2013

Maintaining EasyPact SPS performance

Ordering replacement parts

Electrical accessoriesThe electrical accessories that may require replacement are the following:

b MCH gear motor b MX opening release(s) b XF closing release b MN undervoltage release.

See pages 41 and 42 in the "Auxiliaries for remote operation" section for their characteristics and part numbers.

E60

002A

E60

349A

Arc chutes b Part numbers

(1 arc chute): v type F: 47095

b One chute per pole.

Front b Part number: MVS31114 b 1 per 3- or 4-pole device.

Crank b Part number (1 crank):

47098 b 1 per device.E

5133

6A

b 1 per device.Charging handle

E60

496A

b Part number (1 handle): 47092

Support for MX / XF / MN releases b Part number: 47093 b 1 per device.

Disconnecting-contact clusters b Part number (1 cluster):

64906

Grease for disconnecting-contact clusters b Part number (1 can):

33160

E46

237A

Released for ManufacturingPrinted on 2018/04/12

Page 55: Low voltage electrical distribution EasyPact SPS

53HRB75971 - 03/2013HRB75971 - 03/2013

Maintaining EasyPact SPS performance

Troubleshooting and solutions

Problem Probable causes SolutionsCircuit breaker cannot be closed locally or remotely b Circuit breaker padlocked or keylocked in the

"open" position

b Circuit breaker interlocked mechanically in a source changeover system

b Circuit breaker not completely connected

b The reset button signalling a fault trip has not been reset

b Stored energy mechanism not charged

b MX opening shunt release permanently supplied with power

b MN undervoltage release not supplied with power

b XF closing release continuously supplied with power, but circuit breaker not "ready to close" (XF not wired in series with PF contact)

v disable the locking fonction

v check the position of the other circuit breaker in the changeover system

v modify the situation to release the interlock v terminate racking in (connection) of the

circuit breaker

v clear the fault v push the reset button on the front of the

circuit breaker v charge the mechanism manually v if it is equipped with a an MCH gear motor,

check the supply of power to the motor. If the problem persists, replace the gear motor (MCH)

v there is an opening order. Determine the origin of the order. The order must be cancelled before the circuit breaker can be closed

v there is an opening order. Determine the origin of the order.

v check the voltage and the supply circuit (U > 0.85 Un). If the problem persists, replace the release

v cut the supply of power to the XF closing release, then send the closing order again via the XF, but only if the circuit breaker is "ready to close"

Circuit breaker cannot be closed remotely but can be opened locally using the closing pushbutton

b Closing order not executed by the XF closing release

v check the voltage and the supply circuit (0.85 - 1.1 Un). If the problem persists, replace the XF release

Unexpected tripping without activation of the reset button signalling a fault trip

b MN undervoltage release supply voltage too low b Load-shedding order sent to the MX opening

release by another device

b Unnecessary opening order from the MX opening release

v check the voltage and the supply circuit (U > 0.85 Un)

v check the overall load on the distribution system

v if necessary, modify the settings of devices in the installation

v determine the origin of the order

Unexpected tripping with activation of the reset button signalling a fault trip

A fault is present : b overload b earth fault b short-circuit detected by the control unit

v determine and clear the causes of the fault

v check the condition of the circuit breaker before putting it back into service

Instantaneous opening after each attempt to close the circuit breaker with activation of the reset button signalling a fault trip

b Thermal memory

b Transient overcurrent when closing

b Closing on a short-circuit

v see page 34 v press the reset button v modify the distribution system or the control-

unit settings v check the condition of the circuit breaker

before putting it back into service v press the reset button v clear the fault v check the condition of the circuit breaker

before putting it back into service v press the reset button

Released for ManufacturingPrinted on 2018/04/12

Page 56: Low voltage electrical distribution EasyPact SPS

54 HRB75971 - 03/2013

Maintaining EasyPact SPS performance

Troubleshooting and solutions

Problem Probable causes SolutionsCircuit breaker cannot be opened remotely, but can be opened locally

b Opening order not executed by the MX opening release

b Opening order not executed by the MN undervoltage release

v check the voltage and the supply circuit (0.7 - 1.1 Un). If the problem persists, replace the MX release

v drop in voltage insufficient or residual voltage (> 0.35 Un) across the terminals of the undervoltage release. If the problem persists, replace the MN release

Circuit breaker cannot be opened locally b Operating mechanism malfunction or welded contacts

v contact a Schneider service centre

Circuit breaker cannot be reset locally but not remotely b Insufficient supply voltage for the MCH gear motor

v check the voltage and the supply circuit (0.7 - 1.1 Un). If the problem persists, replace the MCH

Nuisance tripping of the circuit breaker with activation of the reset button signalling a fault trip

b Reset button not pushed-in completely v push the reset button in completely

Impossible to insert the crank in connected, test or disconnected position

b A padlock or keylock is present on the chassis or a door interlock is present

v disable the locking function

Impossible to turn the crank b The reset button has not been pressed v press the reset button Circuit breaker cannot be removed from chassis b Circuit breaker not in disconnected position

b The rails are not completely out

v turn the crank until the circuit breaker is in disconnected position and the reset button out

v pull the rails all the way outCircuit breaker cannot be connected (racked in) b Cradle/circuit breaker mismatch protection

b The safety shutters are locked b The disconnecting-contact clusters are

incorrectly positioned b Cradle locked in disconnected position b The reset button has not been pressed,

preventing rotation of the crank b The circuit breaker has not been sufficiently

inserted in the cradle

v check that the cradle corresponds with the circuit breaker

v remove the lock(s) v reposition the clusters

v disable the cradle locking function v press the reset button

v insert the circuit breaker completely so that it is engaged in the racking mechanism

Circuit breaker cannot be locked in disconnected position b The circuit breaker is not in the right position

b The cranck is still in the cradle

v check the circuit breaker position by making sure the reset button is out

v remove the crank and store itCircuit breaker cannot be locked in connected, test or disconnected position

b Check that locking in any position is enabled b The circuit breaker is not in the right position

b The cranck is still in the cradle

v contact a Schneider Electric service centre

v check the circuit breaker position by making sure the reset button is out

v remove the crank and store it

Released for ManufacturingPrinted on 2018/04/12

Page 57: Low voltage electrical distribution EasyPact SPS

55HRB75971 - 03/2013HRB75971 - 03/2013

Checking EasyPact SPSoperating conditions

E60

004A

E60

005A

E60

003A Ambient temperature

Easypace SPS devices can operate under the following temperature conditions: b the electrical and mechanical characteristics are stipulated for an ambient

temperature of -5 °C to +70 °C b circuit-breaker closing is guaranteed down to -35 °C b the control unit can be stored in an ambient temperature of -25 °C to +85 °C

Extreme atmospheric conditionsEasypace SPS devices have successfully passed the tests defined by the following standards for extreme atmospheric conditions:

b IEC 68-2-1: dry cold at -55 °C b IEC 68-2-2: dry heat at +85 °C b IEC 68-2-30: damp heat (temperature +55 °C, relative humidity 95 %) b IEC 68-2-52 level 2: salt mist.

Easypace SPS devices can operate in the industrial environments defined by standard IEC 60947 (pollution degree up to 4).

It is nonetheless advised to check that the devices are installed in suitably cooled switchboards without excessive dust.

VibrationsEasypace SPS devices resist electromagnetic or mechanical vibrations.Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):

b 2 to 13.2 Hz: amplitude ±1 mm b 13.2 to 100 Hz: constant acceleration 0.7 g.

Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.

Environmental conditions

Released for ManufacturingPrinted on 2018/04/12

Page 58: Low voltage electrical distribution EasyPact SPS

56 HRB75971 - 03/2013

E60

006A

2000

m

Altitude Easypace SPS devices are designed for operation at altitudes under 2000 metres.At altitudes higher than 2000 metres, the modifications in the ambient air (electrical resistance, cooling capacity) lower the following characteristics.

Altitude (m) 2000 3000Dielectric withstand 3500 3150 voltage (V)Rated insulation level (V) 1000 900Rated operational 440 440 voltage (V)Rated current (A) at 40 °C 1 x In 0.99 x In

E60

007A Electromagnetic disturbances

Easypace SPS devices are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by an atmospheric disturbance or by a distribution-system

outage (e.g. failure of a lighting system) b devices emitting radio waves (radios, walkie-talkies, radar, etc.) b electrostatic discharges produced by users.

Easypace SPS devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards:

b IEC 60947-2, appendix F

The above tests guarantee that: b no nuisance tripping occurs b tripping times are respected.

Checking EasyPact SPSoperating conditions

Environmental conditions

Cleaning b Non-metallic parts:

never use solvent, soap or any other cleaning product. Clean with a dry cloth only b Metal parts:

clean with a dry cloth whenever possible. If solvent, soap or any other cleaning product must be used, make sure that it does not come into contact with non-metallic parts.

Released for ManufacturingPrinted on 2018/04/12

Page 59: Low voltage electrical distribution EasyPact SPS

57HRB75971 - 03/2013HRB75971 - 03/2013

Notes

Released for ManufacturingPrinted on 2018/04/12

Page 60: Low voltage electrical distribution EasyPact SPS

58 HRB75971 - 03/2013

Notes

Released for ManufacturingPrinted on 2018/04/12

Page 61: Low voltage electrical distribution EasyPact SPS

59HRB75971 - 03/2013HRB75971 - 03/2013

Notes

Released for ManufacturingPrinted on 2018/04/12

Page 62: Low voltage electrical distribution EasyPact SPS

60 HRB75971 - 03/2013

Notes

Released for ManufacturingPrinted on 2018/04/12