louvers - pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head)...

20
ACOUSTICAL BRICK VENT COMBINATION DRAINABLE EQUIPMENT SCREENS FEMA FLORIDA BUILDING CODE FORMED METAL MIAMI-DADE CERTIFIED NON-DRAINABLE OPERABLE PENTHOUSE SAND LOUVER WIND-DRIVEN RAIN LOUVERS

Upload: doanmien

Post on 20-May-2018

234 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

ACOUSTICAL • BRICK VENT • COMBINATION • DRAINABLE • EQUIPMENT SCREENSFEMA • FLORIDA BUILDING CODE • FORMED METAL • MIAMI-DADE CERTIFIED

NON-DRAINABLE • OPERABLE • PENTHOUSE • SAND LOUVER • WIND-DRIVEN RAIN

LOUVERS

Page 2: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

POTTORFF IS:

PRODUCT SELECTION GUIDE

Innovation, quality, performance and service are what differentiate Pottorff’s products among the competition. Founded in 1928, we are one of the most respected suppliers in the industry today. It is our experience, versatility, and ability to react quickly to our customer’s needs which makes us the choice for architects and engineers.

1

HOW WE ARE DIFFERENT FROM THE COMPETITION:■■ Ongoing commitment to personal and technical service■■ Wide range of quality products ■■ Products delivered on time and on budget■■ Louver Information and Selection Tool■■ Innovative solutions for your design requirements■■ Skilled engineering staff for structural design analysis■■ Quick ship - when you need it FAST!■■ Industry leading 5-year warranty■■ Member of the US Green Building Council

––––●

––––––

–●

INTAKE-EXHAUSTEXHAUST

JJ

HIGH PERFORMANCE JHIGH PERFORMANCE J

JKK

INVERTED YINVERTED Y

–64.5%46.9%56.9%56.3%56.3%50.0%56.9%50.0%38.2%38.8%

FLORIDA BUILDING CODEECD-545ECV-645EFD-437EFD-637EFJ-437EFJ-445EFK-437EFK-445

5"6"4"6"4"4"4"4"

4"4"2"4"4"6"6"4"6"2"4"

45°45°

37.5°37.5°37.5°45°

37.5°45°

30°30°45°30°

37.5°37.5°45°30°

37.5°45°45°

HORIZONTALVERTICAL

HORIZONTALHORIZONTALHORIZONTALHORIZONTALHORIZONTALHORIZONTAL

125012509031113721689721689

925092508398

102426547554965475549

MODEL DEPTHBLADEANGLE

BLADESTYLE

46.3%46.0%58.1%57.5%56.9%50.0%56.9%50.0%

MIAMI-DADE LOUVERSECD-545-MDECV-645-MDEFD-637-MDEXA-645-MDMIAMI-DADE ACOUSTIC LOUVEREAJ-1235-MD

5"6"6"6"

12"

4"6"2"4"4"6"6"

2"4"6"7"2"4"5"7"9"

45°45°

37.5°37.5°– 45°

35°

45°37.5°45°35°45°45°45°

45°45°35°45°45°45°45°45°37 °

HORIZONTALVERTICAL

HORIZONTALCOMBINATION

INSULATED J

DUAL DRAINABLEDUAL DRAINABLE

DRAINABLEDRAINABLEDRAINABLEDRAINABLE

RECESSED-DRAINABLE

HORIZONTALHORIZONTALHORIZONTALHORIZONTAL

VERTICALVERTICALVERTICAL

HORIZONTAL JHORIZONTAL J

1250125011001076

924

8388925096008281

4528

41.9%46.0%54.6%48.1%

30.6%

FREEAREA

VELOCITY(fpm)

AMCACERT

AIRVOLUME

(cfm)PAGE

NON-DRAINABLE LOUVERSEEI-430 (DRAINABLE HEAD)EFE-430-HP (DRAINABLE HEAD)EFJ-245EFJ-430EFJ-437-HP (DRAINABLE HEAD)EFJ-637-HP (DRAINABLE HEAD)EFJ-645EFK-430EFK-637EFY-245EFY-445DRAINABLE LOUVERSEDD-445EDD-637EFD-245EFD-435EFD-445EFD-645ERD-645WIND-DRIVEN RAIN LOUVERSECD-245ECD-445ECD-635ECD-745ECV-245ECV-445ECV-545EFJ-745EFJ-937

–1158583889912915800889832383745

––

437380908220822664168090667323364589

50.4%57.5%42.5%58.1%50.4%54.6%50.6%

10261113955966

10261009990

83111024264948984831188118059

41.3%42.7%53.8%50.6%41.5%42.9%41.9%43.8%53.9%

117212501217121812501250125012501250

77448538

1050898668299857583758755

10755

444444444444

77777777788888

8

555555556666666666

Page 3: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

PRODUCT SELECTION GUIDE (CONT)

2

––––●

––●

–––––––––––––

–––

MODEL DEPTHBLADEANGLE

BLADESTYLE

FREEAREA

VELOCITY(fpm)

AIRVOLUME

(cfm)PAGE

OPERABLE LOUVERSEOD-445EOD-637EOJ-445EOJ-637EOJ-690SOJ-445

4"6"4"6"6"4"

4"4"6"4"6"

2"4"4"4"6"2"4"4"6"6"4"6"4"

6"8"

12"4"6"

12"8"

12"

4"6"4"

2.25"2.5"4"4"5"

1.5"4"4"

4"

5.5"8"

45°37.5°45°

37.5°90°45°

45°45°

37.5°– 45°37.5°

37.5°– 45°

45°45°45°45°35°45°30°45°30°45°45°45°45°

45°45°45°37°37°45°35°35°

45°45°22°

45°

45°45°

45°45°

–45°

––––

OPERABLE–DRAINABLEOPERABLE–DRAINABLE

OPERABLE–JOPERABLE–JOPERABLE–J

FORMED OPERABLE–J

J-BD-EXHAUSTJ-BD-INTAKE

COMBINATIONCOMBINATIONCOMBINATION

J-BD-EXHAUSTJ-BD-EXHAUST

J-BD-INTAKEDRAINABLEDRAINABLE

JJJJJKK

CHEVRON

AIRFOILAIRFOILAIRFOIL

JJ

FORMED AIRFOILFORMED-JFORMED-J

30.0%37.9%26.3%33.8%32.5%26.3%33.1%30.6%

980649999740890999808924

47043931419639964637419642934528

–●

––––●

JJ

VERTICAL

J

HORIZONTAL-INVERTED-VHORIZONTAL-INVERTED-V

1024990683810748775

709691085396728283255813

––––––––

––––––––

––––––––

43.1%57.5%49.4%56.3%68.5%46.9%

41.0%46.9%46.9%53.1%61.7%42.0%51.0%48.0%65.2%50.0%48.0%50.0%38.0%

383775775715815603847775825800775800600

2528581358136092804440406945599185806400599164003648

50.6%50.0%60.0%19.4%24.4%21.0%38.8%53.8%

AMCACERT

COMBINATION LOUVERSEBE-445EBI-445EXA-645EXD-437EXD-645FORMED METAL LOUVERSSBE-245SBE-445SBI-445SFD-445SFD-635SFJ-245SFJ-430SFJ-445SFJ-630SFJ-645SFK-445SFK-645SFV-445ACOUSTICAL LOUVERSEAA-645EAA-845EAA-1245EAJ-437EAJ-637FAA-1245SAJ-835SAJ-1235SPECIALTY LOUVERSEBV-145EBV-445EVS-422PENTHOUSEEPJ-445FEMA GRILLESXAV-545XSV-845SIGHT SCREENSHJ-445HJ-645HT-401HZ-200VT-250VT-654VV-400VV-500

HORIZONTAL-INVERTED-JHORIZONTAL-INVERTED-J

HORIZONTAL AIRFOILHORIZONTAL CLADDING

VERTICAL-CLADDINGVERTICAL-CLADDING

VERTICAL-VVERTICAL-V

––

15.6%

50.0%

46.8%58.5%

––

1250

––

3125

689

555–

5549

4151–

49.4%49.4%50.4%43.0%44.4%

689689

108511721050

53965396875681347455

111111111111111212121212121313131313131313131313131313141414141414141414151515151515151515161616161616161616

Top Left: Campbell Landings | St. Petersburg, Florida | ECD-545

Top Center: Methodist Hospital for Surgery | Addison, Texas | EFD-445

Top Right: Wilshire Grand Center | Los Angeles, California | EFD-445

Middle Left: T-Mobile | Irvine, California | SFJ-445

Cover Photos:Center: Bank of America | Richmond, Virginia | EFD-637-MD

Bottom Left: DuPont Fabros | Ashburn, Virginia | ECD-545

Bottom Center: Oakmonte Village | St. Mary, Florida | ECD-645-MD, EFD-637-MD

Bottom Right: Detail, Methodist Hospital for Surgery | Addison, Texas | EFD-445

Page 4: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

ANATOMY OF A LOUVERA louver is a device comprised of multiple blades that, when mounted in an opening, permits flow of air but inhibits the entrance of other elements. Louvers are typically fabricated from formed steel or extruded aluminum.

3

DRAINABLE BLADE

HEAD

DRIP

JAMB

SILL

BLADE

BLADE ANGLE

K BLADEJ BLADE INVERTED Y BLADECHEVRON BLADE

The K blade has an offset step in its profile acting as a rain trap. The K style blade can be drainable or non-drainable.

A drainable blade is equipped with a gutter to channel water toward the jambs of the louver and away from the airflow.

The J Blade has a smooth flat profile devoid of a gutter on the leading edge.

An Inverted Y or V blade is intended for sight proof applications. With the closed sight-lines, sacrifices in free area performance and greater pressure drop are made.

The Chevron blade combines closed sight lines and drainability. With a C shaped hook at the top, it is the primary choice to stop wind-driven rain.

Top of the louver and completes the connection between the jambs

Top of the louver that fills the gap between head and top blade. Equipped with a drainable channel

Structural support for the blades as well as channels water for drainable louvers

The lower or flatter the blade angle, the easier it is to get air into the building

Varies in shapes, sizes and blade angles to serve different purposes

Base of the louver

BLADE STYLES

Page 5: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

4" 6"4"2"4" 4"

6"2" 6"

2"

6"

4" 4"

NON-DRAINABLE LOUVERSAvailable in a wide array of blade shapes and frame depths, non-drainable louvers offer value and economy for exhaust applications or intake conditions where protection against water infiltration is not critical. Optional hidden mullions provide a continuous blade appearance on multiple section assemblies. Ideally suited for special shapes and transitional designs.

EFJ-437-HP EFJ-637-HPEFY-245EFY-445

EFJ-245EFJ-430EFK-430 EFJ-645

EFK-637

45° 30°

EEI-430 EFE-430-HP

4

––––●

––––––

AMCACERT.

EEI-430EFE-430-HPEFJ-245EFJ-430EFJ-437-HPEFJ-637-HPEFJ-645EFK-430EFK-637EFY-245EFY-445

4"4"2"4"4"6"6"4"6"2"4"

30°30°45°30°

37.5°37.5°45°30°

37.5°45°45°

VARIES64.5% 10.346.9% 7.556.9% 9.156.3% 9.056.3% 9.050.0% 8.056.9% 9.150.0% 8.038.2% 6.138.8% 6.2

––

583889912915800889832383745

––

437380908220822664168090667323364589

––

0.060.090.140.120.100.090.050.060.18

MODEL DEPTHBLADEANGLE

INTAKE-EXHAUSTEXHAUST

JJ

HIGH PERFORMANCE-JHIGH PERFORMANCE-J

JKK

INVERTED YINVERTED Y

BLADESTYLE

FREE AREA(%) (Sq. Ft.) VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. Wg.)

BEGINNING POINT OF WATER PENETRATION RATINGS

DRAINABLE HEADNON-DRAINABLEINTAKE/EXHAUST(DRAINABLE HEAD)

Certified Ratings:Pottorff certifies that model EFJ-437-HP, shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.

Page 6: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

6"4" 6" 4"6"2"

EFD-245EFD-645

DRAINABLE LOUVERSDrainable blade louvers are designed to prevent water penetration in non-wind-driven rain applications by collecting water in frame and blade gutters and channeling it into downspouts and away from airflow. These models are available in a wide array of anodized and painted finishes including custom color matching.

Certified Ratings:Pottorff certifies that models EDD-445, EDD-637, EFD-435, EFD-445, and EFD-645, shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48" x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

EFD-435 ERD-645EDD-637EDD-445EFD-445

5

EDD-445EDD-637EFD-245EFD-435EFD-445EFD-645ERD-645

4"6"2"4"4"6"6"

45°37.5°45°35°45°45°45°

50.4% 8.157.5% 9.242.5% 6.858.1% 9.350.4% 8.154.6% 8.750.6% 8.1

10261113955966

10261009990

83111024264948984831188118059

0.160.150.140.120.160.130.11

MODEL DEPTH ANGLEDUAL-DRAINABLEDUAL-DRAINABLE

DRAINABLEDRAINABLEDRAINABLEDRAINABLE

RECESSED-DRAINABLE

BLADESTYLE

FREE AREA(%) (Sq. Ft.) VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. W

g.)BEGINNING POINT OF WATER

PENETRATION RATINGS

–●

AMCACERT.

Page 7: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

PLAN VIEW

2" 4"

7"

7"

PLAN VIEW

7"2"4"6"

5"

9"

9"

PLAN VIEW

WIND–DRIVEN RAIN LOUVERSOur wind-driven rain louvers offer exceptional protection under the most severe conditions and are available in frame depths from 2" to 7". The closely spaced vertical blade design of the ECV-545 provides wind-driven rain performance with 99.6% effectiveness at wind velocities up to 50 mph and rainfall up to

8 in/hr. When aesthetic requirements demand a more conventional louver profile, our EFJ-745 is the ideal solution. Its horizontal blades, vertically bladed rear screen, and 99.3% effectiveness at 3in/hr as per the AMCA 500-L wind-driven rain test, offer the best of both worlds.

Certified Ratings:Pottorff certifies that models ECD-245, ECD-445, ECD-635, ECD-745, ECV-245, ECV-445, ECV-545, EFJ-937 and shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to water penetration, air performance and wind-driven rain ratings.

Certified Ratings:Pottorff certifies that model EFJ-745 shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and wind-driven rain ratings.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48”x 48” louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind-driven Rain Ratings based upon a test louver size having 39-3/8” x 39-3/8” core area.

ECV-245 ECV-445

ECV-245 ECV-445

ECV-545

VERTICAL BLADES DUAL MODULE

ECV-545ECD-245ECD-445ECD-635

EFJ-745J BLADE WITH VERTICAL

BLADE REAR SECTION

EFJ-937J BLADE WITH VERTICAL

BLADE REAR SECTION

ECD-745

6

ECD-245ECD-445ECD-635ECD-745ECV-245ECV-445ECV-545EFJ-745EFJ-937

2"4"6"7"2"4"5"7"9"

41.3% 6.642.7% 6.853.8% 8.650.6% 8.141.5% 6.642.9% 6.941.9% 6.743.8% 7.053.9% 8.6

29/5029/50

2929/5029/5029/5029/50

2929/50

3/83/83

3/83/83/83/83

3/8

117212501217121812501250125012501250

77448538

1050898668299857583758755

10755

0.370.320.290.570.420.300.250.470.48

A/BA/BBAAAAAA

CLASSMODEL DEPTHHORIZHORIZHORIZHORIZVERTVERTVERT

HORIZ JHORIZ J

BLADESTYLE

WIND

VELOCITY

(mph)

RAINFALL

(In/Hr)FREE AREA

(%) (Sq. Ft.) VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. Wg.)

BEGINNING POINT OF WATER PENETRATION RATINGS

AMCACERT.

45°45°35°45°45°45°45°45°

37.5°

BLADEANGLE

2123/30114062/4323

19986260/53126371/43007343/43507356/9485

721110640/9599

AIRFLOW

(cfm)

99.0/95.099.0/95.0

96.699.6/99.299.6/99.399.5/99.499.9/99.6

99.3100/99.0

EFFECTIVENESS

RATIO (%)

AMCA 500L TEST

Certified Listing:Pottorff certifies that the model EFJ-937 herein is licensed to bear this AMCA listing label.

Page 8: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

6"4" 4"

6"

PLAN VIEW

5"

ECD-545

ECV-645AMCA 540/550 LISTED

7

EFD-437EFD-637

EFJ-437EFJ-445EFK-437EFK-445

Certified Ratings:Pottorff certifies that model ECD-545, and ECV-645 shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance, water penetration, and wind-driven rain ratings.

Certified Ratings:Pottorff certifies that models EFD-437, EFD-637, EFJ-437, EFJ-445, EFK-437 and EFK-445 shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind-driven Rain Ratings based upon a test louver size having 39-3/8" x 39-3/8" core area.

MODELECD-545ECV-645EFD-437EFD-637EFJ-437EFJ-445EFK-437EFK-445

5"6"4"6"4"4"4"4"

45°45°

37.5°37.5°37.5°45°

37.5°45°

HORIZVERTHORIZHORIZHORIZHORIZHORIZHORIZ

WIND DRVN RAINWIND DRVN RAIN

DRAINABLEDRAINABLE

NON-DRAINABLENON-DRAINABLENON-DRAINABLENON-DRAINABLE

46.3% 7.446.0% 7.458.1% 9.357.5% 9.256.9% 9.150.0% 8.056.9% 9.150.0% 8.0

125012509031113721689721689

925092508398

102426547554965475549

0.240.150.130.150.070.080.070.08

DEPTHBLADEANGLE

BLADESTYLE

FREE AREA(%) (Sq. Ft.)

LOUVERDESIGNATION

FLORIDABUILDING

CODEVELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. Wg.)

BEGINNING POINT OF WATER PENETRATION RATINGS

AMCACERT.

187200200200187200187200

DESIGNLOAD (psf)

–●

––––––

AMCA540

–●

––––––

AMCA550

Certified Listing:Pottorff certifies that the model ECV-645 herein is licensed to bear this AMCA listing label.

FLORIDA BUILDING CODEThe Florida Building Code is a single statewide code developed and maintained by the Florida Building Commission. The code establishes accountability for licensed contractors and designers. It also establishes building code education requirements for all licensees, uniform procedures and quality control in a product approval system.

Page 9: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

5" 6"

ANCHORLESS INSTALLATIONThe ECD-545-MD and ECV-645-MD feature an installation system option that secures the louver to the wall without the need for anchors.

6"

PLAN VIEW

6" 6"

ECD-545-MD ECV-645-MD EFD-637-MD EXA-645-MD EAJ-1235-MD

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48"x 48" louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions. AMCA Wind-driven Rain Ratings based upon a test louver size having 39-3/8" X 39-3/8" core area.

*Applies when the CD-55 damper option is utilized and the damper is in the closed position.

8

FLORIDABUILDING

CODEMODEL

ECD-545-MDECV-645-MDEFD-637-MDEXA-645-MDACOUSTIC LOUVEREAJ-1235-MD

5"6"6"6"

12"

45°45°

37.5°37.5°–45°

35°

HORIZVERTHORIZ

COMBO

HORIZ

WIND DRVN RAINWIND DRVN RAIN

DRAINABLECOMBINATION

ACOUSTICAL

41.9% 6.746.0% 7.454.6% 8.748.1% 7.7

30.6% 4.9

1250125011001076

8388925096008281

0.210.150.140.12

DEPTHBLADEANGLE

BLADESTYLE

FREE AREA(%) (Sq. Ft.)

LOUVERDESIGNATION VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. Wg.)

BEGINNING POINT OF WATER PENETRATION RATINGS

–●

AMCA540

––

AMCA550

AMCACERT.

150150150120

150

DESIGNLOAD (psf)

NOISE REDUCTION 125 250 500 1K 2K 4K12 14 18 21 19 16

*

Certified Ratings:Pottorff certifies that models ECD-545-MD and ECV-645-MD shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance, water penetration and wind-driven rain ratings.

Certified Ratings:Pottorff certifies that models EFD-637-MD and EXA-645-MD shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.

Certified Listing:Pottorff certifies that the models ECD-545-MD* and ECV-645-MD herein are licensed to bear this AMCA listing label.

MIAMI-DADE CERTIFIED LOUVERSOur Miami-Dade/Florida Building Code certified louvers are engineered and tested to withstand extreme loads, debris impact and cyclic fatigue associated with the severe weather effects of hurricanes. Our ECD-545-MD and ECV-645-MD are also listed for Impact Resistance (AMCA 540) and High Velocity Wind-Driven Rain (AMCA 550) as required by the Florida Building Code.

Certified Ratings:Pottorff certifies that model SAJ-1235-MD, shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to water penetration, soundand air performance.

Certified Listing:Pottorff certifies that the model EAJ-125-MD herein is licensed to bear this AMCA listing label.

Page 10: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

VENTILATION FAN Has the ability to produce up to 24,000 cfm of airflow for use in water penetration and air performance tests

LOUVER TESTING LABORATORYPottorff's wind-driven rain and water penetration lab features a 48" vane axial tubular fan providing 55,000 CFM. In front of the outlet is a system of nozzles which are programmed to sequence the pattern of spray. In front of this is a ventilation chamber with

ductwork running to an exhaust fan featuring an airflow nozzle to measure ventilation airflow. Our setup will test louvers per AMCA 500 and 511 with eventual approval for the AMCA CRP program.

■■ Wind-Driven Rain Test – Rates the ability of a louver to protect openings behind it from water directed at the louver of speeds up to 50 mph. Published ratings are a statement of the louver's ability to reject simulated rain including wind velocity, effectiveness, penetration class and discharge loss coefficient class.

■■ Water Penetration Test – The Water Penetration test rates the ability of a louver to protect openings behind it from water that cascades down a wall or falls vertically in front of it. This determines the point of water penetration which AMCA defines as at least 0.01 ounces of water during a 15 minute test. The sample tested is also tested for air performance.

■■ Air Performance – Published ratings include a graph for the pressure loss to the louver's free area, the mode tested (intake or exhaust) and a table of the free area based on its size.

9

MANIFOLD Allows water to fall in front or down the wall of the louver to simulate conditions in the Water Penetration Test

WET WALL MANIFOLD Allows water to fall down the wall to the face of the louver at a prescribed 4 in. per hour

FAN AND NOZZLES Five nozzles along with the fan, simulate rain, to suit the spread of rain required

AIRFLOW REGULATION A series of chambers that regulate airflow

WATER PRESSURE NOZZLESReleases water to simulate WDR rain rates which are tested at 3 and 8 in. rainfall/hr.

LOUVER Louvers are fabricated to a uniform 48" × 48" and placed in an appropriate opening in the drainage chamber wall where tests are performed

DRAINAGE CHAMBERWater collected to provide readings for water penetration test

Page 11: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

HUMAN MACHINE INTERFACEAll of our testing in our Pottorff Wind-Driven Rain and Water Penetration Laboratory is able to be automated. For this purpose we use a new HMI (Human Machine Interface) which is designed to run any test and continually store the data in our database.

■■ Plot the desired points for testing

■■ Start and stop tests automatically

■■ Live view of all data being retrieved at any point during testing. For example: wind speed, differential pressure, etc.

■■ Control any aspect of a test; for example: fan speed, rain nozzle intervals, etc.

■■ Tests automations at our desired data points

10

WIND FAN Has the ability to produce up to 55,000 cfm of airflow for use in wind-driven rain testing

THE HMI SOFTWARE ALLOWS US TO:

Page 12: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

6"4" 4" 6" 4"6"

OPERABLE LOUVERSOperable blade louvers provide weather protection for open and positive shutoff when no airflow is required. These units incorporate center pivoted blades that can be controlled manually with a pull chain, hand quadrant, or hand crank. They can also be controlled automatically with electric or pneumatic actuators.

EOJ-445EOD-445 EOD-637 EOJ-637 SOJ-445EOJ-690

11

––––●

AMCACERT.

EOD-445EOD-637EOJ-445EOJ-637EOJ-690SOJ-445

4"6"4"6"6"4"

45°37.5°45°

37.5°90°45°

43.1% 6.957.5% 9.249.4% 7.956.3% 9.0

68.5% 10.9646.9% 7.5

1024990683810748775

709691085396728283255813

0.160.110.100.120.190.14

MODEL DEPTHBLADEANGLE

EXTRUDED ALUMINUMEXTRUDED ALUMINUMEXTRUDED ALUMINUMEXTRUDED ALUMINUMEXTRUDED ALUMINUMGALVANNEALED STEEL

MATERIALOPERABLE-DRAINABLEOPERABLE-DRAINABLE

OPERABLE-JOPERABLE-JOPERABLE-JOPERABLE-J

STYLEFREE AREA

(%) (Sq. Ft.) VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. W

g.)BEGINNING POINT OF WATER

PENETRATION RATINGS

Certified Ratings:Pottorff certifies that the model EOJ-690 shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performance ratings

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48”x 48” louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

OPERABLE EXTRUDED ALUMINUM OPERABLE FORMED

Page 13: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

4"

4"6.125"

4"

6"

COMBINATION LOUVERSCombination Louvers feature stationary front blades and operable rear blades to ensure proper weather protection when open as well as a consistent appearance in both the open and closed positions. Optional low leakage seals provide further environmental protection in the closed position. These units incorporate center pivoted blades

that can be controlled manually with a pull chain, hand quadrant or hand crank. They can also be controlled automatically with electric or pneumatic actuators. The EBE-445 and the EBI-445 incorporate an integral gravity operated backdraft damper to protect exhaust or intake air openings in exterior walls.

Certified Ratings:Pottorff certifies that models EXA-645 and EXD-437 shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performance and water penetration ratings.

Certified Ratings:Pottorff certifies that the model EXA-645 shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air leakage ratings.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48”x 48” louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

EBE-445 EBI-445 EXD-437 EXD-645EXA-645

12

VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. W

g.)BEGINNING POINT OF WATER

PENETRATION RATINGS

––●

AMCACERT.

EBE-445EBI-445EXA-645EXD-437 EXD-645

4"4"6"4"6"

45°45°

37.5°– 45°37.5°

37.5°– 45°

49.4% 7.949.4% 7.950.4% 8.143.0% 6.944.4% 7.1

689689108511721050

53965396875681347455

0.100.100.110.170.19

MODEL DEPTHBLADEANGLE

J-BD-EXHAUSTJ-BD-INTAKE

COMBINATIONCOMBINATIONCOMBINATION

BLADESTYLE

FREE AREA(%) (Sq. Ft.)

Page 14: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

4"4"6"

4"2"

6"4"2"4"

4" 6"

FORMED METAL LOUVERSTypically formed from galvannealed steel, these louvers accent building architecture while withstanding corrosion in caustic environments. The SBE-245, SBE-445 and SBI-245 incorporate an integral gravity operated backdraft damper to protect exhaust or intake openings in exterior walls.

SFV-445SFJ-430SFJ-630

SFJ-245SFJ-445 SFJ-645SFK-445SFK-645

SFD-445 SFD-635

13

SBE-245SBE- 445SBI - 445SFD - 445SFD - 635SFJ-245SFJ- 430SFJ- 445SFJ- 630SFJ- 645SFK- 445SFK- 645SFV- 445

2"4"4"4"6"2"4"4"6"6"4"6"4"

45°45°45°45°35°45°30°45°30°45°45°45°45°

41.0% 6.646.9% 7.546.9% 7.553.1% 8.561.7% 9.942.0% 6.751.0% 8.248.0% 7.7

65.2% 10.450.0% 8.048.0% 7.750.0% 8.038.0% 6.1

383775775715815603847775825800775800600

2528581358136092804440406945599185806400599164003648

0.080.130.140.110.080.060.130.130.080.090.130.090.25

MODELJ-BD-EXHAUSTJ-BD-EXHAUST

J-BD-INTAKEDRAINABLEDRAINABLE

JJJJJKK

CHEVRON

VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. W

g.)BEGINNING POINT OF WATER

PENETRATION RATINGS

DEPTHBLADESTYLE

FREE AREA(%) (Sq. Ft.)

BLADEANGLE

SBE-245SBE-445SBI-445

Page 15: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

12"6"8"

8"12"

4"6"

ACOUSTICAL LOUVERSAcoustical louvers provide low static pressure loss and reliable noise reduction over a wide range of frequencies. Ideally suited for intake or exhaust applications where maximum noise reduction is required.

Certified Ratings:Pottorff certifies that models EAA-845, SAJ-1235 and SAJ-835, shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.

Certified Ratings:Pottorff certifies that model SAJ-1235, shown herein are licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to water penetration, soundand air performance.

AMCA defines the beginning point of water penetration as the free area velocity at the intersection of a simple linear regression of test data and the line of 0.01 ounces of water per square foot of free area and is measured through a 48”x 48” louver during a 15 minute period. The AMCA water penetration test provides a method for comparing louver models and designs as to their efficiency in resisting the penetration of rainfall under specific lab conditions. Pottorff recommends that intake louvers are selected with a reasonable margin of safety below the beginning point of water penetration in order to avoid unwanted penetration during severe storm conditions.

SAJ-835SAJ-1235

EAJ-437EAJ-637

EAA-645EAA-845

EAA-1245FAA-1245

14

45°45°45°37°37°45°35°35°

BLADEANGLE

EAA-645EAA-845EAA-1245EAJ-437EAJ-637FAA-1245SAJ-835SAJ-1235

6"8"12"4"6"12"8"12"

30.0% 4.837.9% 6.126.3% 4.233.8% 5.432.5% 5.226.3% 4.233.1% 5.330.6% 4.9

118

131110131312

118

141010141314

1310171212171918

1614191722192621

1815181820182819

1713171719172316

980649999740890999808924

47043931419639964637419642934528

0.100.030.090.060.150.090.070.08

MODEL DEPTH 125 250 500 1K 2K 4KAIRFOILAIRFOILAIRFOIL

JJ

FORMED - AIRFOILFORMED - JFORMED - J

BLADESTYLE

FREE AREA(%) (Sq. Ft.) VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. W

g.)BEGINNING POINT OF WATER

PENETRATION RATINGS

NOISE REDUCTION

–●

––––●

AMCACERT.

Page 16: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

4"

4".25"

15

SAND LOUVER PENTHOUSE FEMA GRILLESBRICK VENTS

EVS-422EBV-145EBV-445

FREE AREA(%) (Sq. Ft.)

EBV-145EBV-445EVS-422

1.5"4"4"

––

15.6% 2.5

––

1250

––

3125

––

1.00

MODEL DEPTHBLADEANGLE

JJ

VERTICAL

BLADESTYLE VELOCITY

(fpm)

AIRFLOW

(cfm) PRESSURE

DROP (In. Wg.)

BEGINNING POINT OF WATER PENETRATION RATINGS

PENTHOUSEEPJ-445 4" 45° 50.0% 8.0 689 5549 0.08J-BLADE

FEMA GRILLESXAV-545XSV-845

5.5"8"

45°45°

46.8% 7.558.5% 9.4

–––

–555–

4151–

0.09–

INVERTED VINVERTED V

45°45°22°

AMCACERT.

SPECIALTY PRODUCTS

EPJ-445

MITERED CORNER

BOXED CORNER

Brick vents are used primarily on renovation projects and provide a permanent means of gravity ventilation for crawl spaces, hung ceilings, foundations, pipe spaces and corridors. Our EVS-422 is ideally suited for high wind areas that are sensitive

to wind-driven sand penetration. The EPJ-445 penthouse serves frequently as a gravity ventilator, fan discharge cap, fresh air intake cap, sight shield or pressure relief ventilator.

8"5.5"

XSV-845

Certified Ratings:Pottorff certifies that the model XAV-545 shown herein is licensed to bear the AMCA seal. The ratings shown are based on test and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings seal applies to air performance ratings.

XAV-545MEETS ICC-500 2014

The XAV-545 and XSV-845 were designed to FEMA 320 or FEMA 361 guidelines for shelters or safe rooms. They have been designed to withstand design loads of ± 300 PSF produced by extreme wind phenomena such as tornadoes and hurricanes. They have been tested with impacts of 15lb 2" x 4"s traveling at 100 MPH per ICC 500. This makes both the XAV-545 and XSV-845 compliant for wind borne debris in all tornado or hurricane regions in the United States.

Page 17: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

PLAN VIEW

4"

HZ-200

VT-250

HT-401

VT-654 VV-500VV-400

HJ-445HJ-645

PLAN VIEW

2.5"

6"4"

2.25"4"

PLAN VIEW

4"

PLAN VIEW

5"

Whether the design calls for total sight concealment, partial screening, high volume airflow, specialty shapes, or thermal shading, our sight screens are engineered to meet the most stringent project parameters while satisfying our customer’s aesthetic requirements.

SIGHT SCREENS

50.6% 8.150.0% 8.060.0% 9.619.4% 3.124.4% 3.921.0% 3.438.8% 6.253.8% 8.6

45°45°–

45°––––

BLADEANGLE

FREE AREA(%) (Sq. Ft.)

HJ-445HJ-645HT-401HZ-200VT-250VT-654VV-400VV-500

4"6"4"

2.25"2.5"4"4"5"

MODEL DEPTHHORIZONTAL - INVERTED JHORIZONTAL - INVERTED J

HORIZONTAL - AIRFOIL TUBEHORIZONTAL - CLADDING

VERTICAL - CLADDINGVERTICAL - CLADDING

VERTICAL - VVERTICAL - V

BLADE

16

Page 18: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

www.pottorff.com/LIST

LIST™ (LOUVER INFORMATION AND SELECTION TOOL)

17

Pottorff’s Louver Information and Selection Tool is a state-of-the-art computer based program that puts key information for louver selection at your fingertips. LIST™ allows engineers and architects to choose the right louver based on application and performance criteria.

LIST™ GIVES YOU THE ABILITY TO: � View model, catalog pages

and installation instructions � Access REVIT models � Drop louver selections

into a schedule � Automatically save your work

when interruptions arise � Create custom CSI

formatted specifications

SELECT LOUVERS BASED ON: � Material � Louver Type � Blade Type � Airflow Velocities � Airflow Direction � Opening Size � Pressure Loss � Beginning Point of

Water Penetration � Free Area � AMCA, FBC, Miami-Dade,

and FEMA Certifications

Page 19: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

LOUVER OPTIONS

18

Pottorff offers a complete line of louver options. Whether your project requires special architectural shapes, security burglar bars, flange or frame options, we have the accessories you need. See the back cover for finish options.

SHAPE

ATrapezoid Right Triangle Triangle Double Slope Top Diamond 1/4 Round Radius Top Round 1/2 Round

B C D E F G H J LK M

LOUVER SHAPES

BURGLAR BARS

OPTIONS

GLAZING FRAME

SILL/HEAD FLASHING

LOUVER HINGE

STUCCO FLANGE

VARIABLE FLANGE

FILTER RACK

BEST WARRANTY IN THE INDUSTRYTo reinforce our reputation for high quality products and dependable service, Pottorff offers an industry leading 5-year warranty on our entire line of louver products.

"By backing every product we ship with a 5-year warranty, we reinforce the depth of our commitment to providing customers quality products the first time and every time" says Pat Cockrum, president of Pottorff.

18

Page 20: LOUVERS - Pottorff · efe-430-hp (drainable head) efj-245 efj-430 efj-437-hp (drainable head) efj-637-hp (drainable head) efj-645 efk-430 efk-637 efy-245 efy-445 drainable louvers

5101 Blue Mound Road • Fort Worth, Texas 76106 • tel: 817-509-2300 • fax: 817-831-3110 • www.pottorff.com

Our premier finish for extruded aluminum. Tough, long lasting, environmentally friendly powder coating has superior color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.

Environmentally friendly powder coating has good color retention and abrasive properties. Resists chalking, fading, chemical abrasion and weathering.

Electrochemically deposited inorganic color pigment which is sealed to convert an aluminum oxidation into a corrosion resistant finish. Some shade variation will occur.

Electrochemically oxidized aluminum surface for uniform clear finish. More resistant to natural oxidizing. Improved luster and less glossy than mill finish.

Preparation for field applied epoxy, vinyl, urethane, or other heavy-duty coatings. Must be finished within 6 months of application. Contamination can occur in transit and in the field; requires field cleaning prior to painting.

Aluminum or Galvanized Steel. Normal weathering will occur.

2-coat 100% Fluoropolymer Powder Coat meets AAMA 2605. Dry film thickness 2 mil. Equivalent to Kynar 500®/Hylar5000®,Duranar®, Fluoropon®

2-coat Polyester Powder Coat meets AAMA 2604. Dry film thickness 2 mil. Equivalent to Baked Enamel

Integral Color AnodizeAA-M10C22A42 (>0.7 mil)

Clear Anodize 215 R-1AA-M10C22A41 (>0.7 mil)

Alkyd Prime Coat

Mill

Standard Colors: 20 standard colors plus Premium Pearl finishes. Custom colors are available. Consult factory.

20 standard colors for aluminum products and acoustical louvers, 18 colors for steel. Custom colors are available. Consult factory.

Champagne; Light, Medium or Dark Bronze; Black

Clear

N/A

N/A

10 Years (consult factory for availability of extended warrantyup to 20 years).

5 Years

5 Years

5 Years

N/A

N/A

FINISH TYPE DESCRIPTION/APPLICATION

FINISHES OPTIONSCOLOR SELECTION WARRANTY

To request a standard color sample or anodized variation sample, please contact customer service.

PBL – APRIL 2018