loss of 1,365 mw followed by 59.7 hz load...

22
Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss of generation occurred at 03:29 totaling 1,365 MW. Frequency declined to 59.694 HZ, ERCOT load was 30,071 MW. 59.6 59.7 59.8 59.9 60.0 60.1 1 2 3 4 5 6 7 8 9 10 Minutes On 11/29/11, a sudden loss of generation occurred at 03:29 totaling 1,365 MW. Frequency declined to 59.694 HZ, ERCOT load was 30,071 MW. 59.6 59.7 59.8 59.9 60.0 60.1 2 2.1 2.2 2.3 Minutes Zoom

Upload: others

Post on 14-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Loss of 1,365 MW Followed by 59.7 Hz Load Shedding

On 11/29/11, a sudden loss of generation occurred at 03:29 totaling 1,365 MW. Frequency declined to 59.694 HZ, ERCOT load was 30,071 MW.

59.6

59.7

59.8

59.9

60.0

60.1

1 2 3 4 5 6 7 8 9 10

Minutes

On 11/29/11, a sudden loss of generation occurred at 03:29 totaling 1,365 MW. Frequency declined to 59.694 HZ, ERCOT load was 30,071 MW.

59.6

59.7

59.8

59.9

60.0

60.1

2 2.1 2.2 2.3

Minutes

Zoom

Page 2: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 1 of 11

West Texas Voltage Phase Angle wrt UT Austin

-36

-35

-34

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

20

21

22

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

01

02

03

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.90

59.95

60.00

0 10 20 30 40 50 60

Seconds

Event 1. Jan. 03, 2012. 01:44 GMT

370 miles

280 miles

100 miles

Straight-Line Miles

No unit tripped.

Steady-state angle rises.

No wind generation. West Texas is importing power.

Conclusion – line trip or opening of series caps to South Texas. Easily visible throughout ERCOT.

Page 3: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 2 of 11

West Texas Voltage Phase Angle wrt UT Austin

28

29

30

31

32

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

17

18

19

20

21

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

06

07

08

09

10

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 2. Jan. 03, 2012. 13:14 GMT

No unit tripped.

Good wind.

Strong ringdown, but steady-state angle does not change.

Conclusion – South Texas event, cause unknown.

Page 4: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 3 of 11

West Texas Voltage Phase Angle wrt UT Austin

20.5

21.5

22.5

23.5

24.5

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

23

24

25

26

27

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

08

09

10

11

12

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

60.00

60.05

60.10

0 10 20 30 40 50 60

Seconds

Event 3. Jan. 03, 2012. 18:06 GMT

Moderate wind. Steady-state angle rises.

Frequency a bit high, but no unit trip.

Small drop in steady-state angle. Less power flowing from south to central.

Small steady-state angle rise in the short distance between Waco and Austin. More power flowing from north to central.

Conclusion – possible line trip to West Texas.

Page 5: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 4 of 11

West Texas Voltage Phase Angle wrt UT Austin

27

28

29

30

31

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

-01

00

01

02

03

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

06

07

08

09

10

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.90

59.95

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 4. Jan. 07, 2012. 08:55 GMT

Unit trip. Poor frequency recovery.

Conclusion – unit trip in West Texas.

Good wind. Sudden drop in steady-state angle.

Page 6: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 5 of 11

West Texas Voltage Phase Angle wrt UT Austin

34

35

36

37

38

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

01

02

03

04

05

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

05

06

07

08

09

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 5. Jan. 09, 2012. 09:25 GMT

Unit trip. Poor frequency recovery.

Conclusion – unit trip in South Texas.

Strong wind. Small steady-state angle drops.

Steady state angle drops.

Page 7: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 6 of 11

West Texas Voltage Phase Angle wrt UT Austin

35.5

36.5

37.5

38.5

39.5

30 40 50 60 70 80 90

South Texas Voltage Phase Angle wrt UT Austin

00

01

02

03

04

30 40 50 60 70 80 90

Waco Voltage Phase Angle wrt UT Austin

05

06

07

08

09

30 40 50 60 70 80 90

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

30 40 50 60 70 80 90

Seconds

Event 6. Jan. 09, 2012. 09:31-32 GMT

Abrupt load shedding?

Conclusion – load shedding. Shedding was not in South Texas, and was not in West Texas.

Strong wind. West Texas steady-state angle drops slightly.

Slight angle drop in South Texas.

Slight drop in steady-state angle, and power flowing south.

Page 8: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 7 of 11

West Texas Voltage Phase Angle wrt UT Austin

35.5

36.5

37.5

30 50 70 90 110

South Texas Voltage Phase Angle wrt UT Austin

21

22

23

30 50 70 90 110

Waco Voltage Phase Angle wrt UT Austin

09

10

11

30 50 70 90 110

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

30 50 70 90 110

Seconds

Event 7. Jan. 10, 2012. 13:42 GMT

South Texas Voltage Phase Angle wrt UT Austin

21

22

45 46 47 48 49 50

Zoom-In Shows ≈ 0.6 Hz Oscillation

Initially not a frequency event. Undamped oscillation clearly visible in frequency as well as angle.

Strong wind. West Texas sees a bump, followed by a 10-15 sec. of undamped oscillation.

Conclusion – Strong ERCOT-wide undamped oscillation, freq ≈ 0.6 Hz, lasting 20 seconds, then restarting after a pause. Most significant in South Texas, but visible everywhere. Cause unknown.

Zoom

Small unit trip?

Page 9: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 8 of 11

West Texas Voltage Phase Angle wrt UT Austin

24.5

25.5

26.5

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

12

13

14

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

06

07

08

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.90

59.95

60.00

0 10 20 30 40 50 60

Seconds

Event 8. Jan. 11, 2012. 00:59 GMT

No unit tripped.

No significant steady-state angle change.

Good wind. Steady-state angle rises.

Conclusion – line trip to West Texas

Slight steady-state angle rise.

Page 10: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 9 of 11

West Texas Voltage Phase Angle wrt UT Austin

26

27

28

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

12

13

14

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

02

03

04

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 9. Jan. 12, 2012. 03:49 GMT

Load shed?

No significant change in steady-state angle.

Good wind. Steady-state angle drops slightly.

Conclusion – possible load shedding

Slight steady-state angle drop.

Page 11: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 10 of 11

West Texas Voltage Phase Angle wrt UT Austin

-19.5

-18.5

-17.5

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

24

25

26

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

-01

00

01

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 10. Jan. 12, 2012. 22:24 GMT

Unit trip.

Steady-state angle rises slightly.

Poor wind. Steady-state angle drops slightly.

Conclusion – Unit trip in North or West Texas

Steady-state angle drops slightly.

Page 12: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_1_thru_15_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 11 of 11

To run the program, unzip and place the hourly files and program in one folder. When you execute the program,

• Pick your hour • Pick your minute (default is one minute, but you can also display two or more

consecutive minutes • Include the PMUs – in these graphs we show McDonald, UT Pan Am, and Waco. • Note the line below the graph “Above graph saved as XXX.” That file has the

points, suitable for plotting in Excel. • Top right buttons do auto screen. Presently, the program takes about 30 minutes

to screen one day, flagging the events of interest in an output text file. Re-run the program (no auto-screen) to view those events and create the saved text files.

• Have fun.

PMU Waveform Analyzer Display for Event 7

Page 13: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_15_thru_21_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 1 of 5

West Texas Voltage Phase Angle wrt UT Austin

43.5

44.5

45.5

46.5

40 50 60 70 80 90 100

South Texas Voltage Phase Angle wrt UT Austin

02

03

04

05

40 50 60 70 80 90 100

Waco Voltage Phase Angle wrt UT Austin

08

09

10

11

40 50 60 70 80 90 100

West Texas, South Texas, Waco Frequency

59.85

59.90

59.95

60.00

40 50 60 70 80 90 100

Seconds

370 miles

280 miles

100 miles

Straight-Line Miles

Event 1. Jan. 15, 2012. 20:04 GMT

Conclusion –

Page 14: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_15_thru_21_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 2 of 5

West Texas Voltage Phase Angle wrt UT Austin

33

34

35

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

17

18

19

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

06

07

08

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.85

59.90

59.95

60.00

0 10 20 30 40 50 60

Seconds

Event 2. Jan. 16, 2012. 16:48 GMT

Conclusion –

Page 15: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_15_thru_21_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 3 of 5

West Texas Voltage Phase Angle wrt UT Austin

-24.5

-23.5

-22.5

40 50 60 70 80 90 100

South Texas Voltage Phase Angle wrt UT Austin

35

36

37

40 50 60 70 80 90 100

Waco Voltage Phase Angle wrt UT Austin

-05

-04

-03

40 50 60 70 80 90 100

West Texas, South Texas, Waco Frequency

59.95

60.00

60.05

40 50 60 70 80 90 100

Seconds

Event 3. Jan. 18, 2012. 09:50 GMT

Conclusion –

Page 16: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_15_thru_21_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 4 of 5

West Texas Voltage Phase Angle wrt UT Austin

6.5

7.5

8.5

9.5

10.5

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

09

10

11

12

13

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

06

07

08

09

10

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

60.00

60.05

0 10 20 30 40 50 60

Seconds

Event 4. Jan. 18, 2012. 19:15 GMT

Conclusion –

Page 17: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_15_thru_21_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer

Page 5 of 5

West Texas Voltage Phase Angle wrt UT Austin

-30

-29

-28

-27

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

-12

-11

-10

-09

-08

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

02

03

04

05

06

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.75

59.80

59.85

59.90

59.95

60.00

0 10 20 30 40 50 60

Seconds

Event 5. Jan. 21, 2012. 19:34 GMT

Conclusion –

Page 18: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

On 01/21/12, a sudden loss of generation occurred at 13:34 totaling 584 MW. Frequency declined to 59.752 HZ, ERCOT load was 31,275 MW.

59.7

59.8

59.9

60.0

60.1

0 1 2 3 4 5 6 7 8 9 10

Minutes

It is amazing what 584 MW can do when there is little reserve.More fallout from the Texas Nodal Market?

Page 19: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Jan_25_2012.doc

Page 1 of 1

West Texas Voltage Angle Oscillation, Beginning Jan. 25, 2012, 07:35 GMTOscillation Continued for About 20 Minutes

26.5

27.5

28.5

300 310 320 330 340 350 360

Seconds

Undamped Oscillation, Approx. 1.8 Hz

South Texas Voltage Angle Oscillation, Beginning Jan. 25, 2012, 07:35 GMT

13.5

14.5

15.5

300 310 320 330 340 350 360

Seconds

Control action

Page 20: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_25.doc. Events automatically detected by our PMU_Waveform_Analyzer. Data from 120V Wall Outlets.

Page 1 of 2

370 miles

280 miles

100 miles

Straight-Line Miles

Event 1. Jan. 15, 2012. 20:04 GMT

West Texas Voltage Phase Angle wrt UT Austin

18

19

20

21

22

50 60 70 80 90 100 110

South Texas Voltage Phase Angle wrt UT Austin

04

05

06

07

08

50 60 70 80 90 100 110

Waco Voltage Phase Angle wrt UT Austin

-01

00

01

02

03

50 60 70 80 90 100 110

West Texas, South Texas, Waco Frequency

59.80

59.85

59.90

59.95

60.00

60.05

50 60 70 80 90 100 110

Seconds

West Texas Voltage Phase Angle wrt UT Austin

18

19

20

21

22

55 56 57 58 59 60 61 62 63 64 65

West Texas, South Texas, Waco Frequency

59.80

59.85

59.90

59.95

60.00

60.05

55 56 57 58 59 60 61 62 63 64 65

Seconds

Zoom

Zoom

Comments – We believe there are two, possibly three events here. The first is a unit trip, where the frequency drop begins. The second is at the frequency minimum, where frequency immediately ramps up at the same rate it ramped down. Now, see the Waco and South Texas phase angle curves (these are with respect to U.T. Austin). The first angle ringdown starts at the unit trip, but is then interrupted at the frequency minimum, where a second angle ringdown begins. West Texas phase angle does not show much. However, the undamped West Texas 1.8 Hz oscillation pointed out on an earlier Jan. 25 event is visible in both phase angle and frequency.

Jan. 25, 2012. 18:22 GMT

Page 21: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Events_Jan_25.doc. Events automatically detected by our PMU_Waveform_Analyzer. Data from 120V Wall Outlets.

Page 2 of 2

West Texas Voltage Phase Angle wrt UT Austin

00

01

02

03

04

0 10 20 30 40 50 60

South Texas Voltage Phase Angle wrt UT Austin

04

05

06

07

08

0 10 20 30 40 50 60

Waco Voltage Phase Angle wrt UT Austin

-02

-01

00

01

02

0 10 20 30 40 50 60

West Texas, South Texas, Waco Frequency

59.85

59.90

59.95

60.00

60.05

60.10

0 10 20 30 40 50 60

Seconds

West Texas, South Texas, Waco Frequency

59.80

59.85

59.90

59.95

60.00

60.05

5 6 7 8 9 10 11 12 13 14 15

Seconds

Comments – About the same situation as 18:22 GMT. There appear to be two events. Rate of frequency drop is less. Less 1.8 Hz visible in West Texas.

Zoom

Jan. 25, 2012. 20:29 GMT

370 miles

280 miles

100 miles

Straight-Line Miles

Page 22: Loss of 1,365 MW Followed by 59.7 Hz Load Sheddingusers.ece.utexas.edu/~grady/Texas_Synchrophasor... · Loss of 1,365 MW Followed by 59.7 Hz Load Shedding On 11/29/11, a sudden loss

Texas_Synchrophasor_Network_Jan_26_2012.doc. Events automatically detected by our PMU_Waveform_Analyzer. Data from 120V Wall Outlets.

Page 1 of 1

West Texas Voltage Phase Angle wrt UT Austin

-53-52-51-50-49-48-47-46-45

0 60 120 180 240 300 360 420 480 540 600

South Texas Voltage Phase Angle wrt UT Austin

101112131415161718

0 60 120 180 240 300 360 420 480 540 600

Waco Voltage Phase Angle wrt UT Austin

-09-08-07-06-05-04-03-02-01

0 60 120 180 240 300 360 420 480 540 600

West Texas, South Texas, Waco Frequency

59.85

59.90

59.95

60.00

60.05

60.10

60.15

0 60 120 180 240 300 360 420 480 540 600

Seconds

370 miles

280 miles

100 miles

Straight-Line Miles

Jan. 26, 2012. 04:04 GMT

Comments – Zero wind, West Texas angle less than −50º. Unit trip, likely in Central Texas, drops frequency to 59.87 Hz. After a rocky start, frequency climbs past 60.10 Hz in eight minutes. Wind, or other West Texas generation, ramps up then levels out.