IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 1 Installation Instructions IQL16/xxx, /AHU LONMARK ® Terminal Unit Controllers Important: Retain these instructions 3 Installation - Mounting CONTENTS 1 Unpacking................................................ 1 2 Storage .................................................... 1 1 Unpacking IQL16/xxx, /AHU Installation Instructions TG200453 HO 2 +50 °C (122 °F) 0 -10 °C (14 °F) 90 %RH 1 6 L L A N N I D S t r a t e g y : : : : : O / S S e r i a l N o 2 3 0 V a c ~ 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 1 2 3 2 4 V a c 1 2 3 5 4 6 7 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 1 2 3 4 5 L O N 2 9 3 0 3 1 3 2 129 mm (5.08”) 75 mm (3”) 205 mm (8.07”) Dimensions 63 mm (2.48”) 1 3 Installation - Mounting ............................. 1 4 Installation - Configuration...................... 6 5 Disposal ................................................. 12 1 6 L : : : : : b a Requirements 2 Note that this product may involve LONWORKS ® system integration as referred to in section 4 step 4: this procedure should only be performed by an installer with LONWORKS engineering expertise. 2 Storage It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

Upload: others

Post on 22-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 1

Installation InstructionsIQL16/xxx, /AHU

LONMARK® Terminal Unit Controllers

Important: Retain these instructions

3 Installation - Mounting

CONTENTS

1 Unpacking................................................12 Storage ....................................................1

1 Unpacking

IQL16/xxx, /AHU Installation Instructions TG200453

H O2

+50 °C(122 °F)

0-10 °C(14 °F)

90 %RH

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

129

mm

(5.0

8”)

75 mm (3”)

205 mm (8.07”)

Dimensions

63 mm (2.48”)

1

3 Installation - Mounting .............................14 Installation-Configuration ......................65 Disposal .................................................12

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

ba

Requirements2

Note that this product may involve LONWORKS ® system integration as referred to in section 4 step 4: this procedure should only be performed by an installer with LONWORKS engineering expertise.

2 StorageIt is recommended that the instal lat ion should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations

1989, USA National Electric Code).

These instructions shall be used by trained service personnel onlyIftheequipmentisusedinamannernotspecifiedbytheseinstructions,theprotectionprovidedbytheequipment may be impaired.

Page 2: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

2 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

3 Requirements (continued)

3 Installation - Mounting (continued)

4 holes� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

∅ 6 mm(0.24”)

Mounting

114

mm

(4

.49”

)

3

Lift Hinged Cover4

189 mm (7.44”)

LAN

NID

Strategy

::

::

:

O/S

Serial No

1 1 +

L

LAN

NID

Strategy

::

::

:

O/S

Serial No

1 1 +

L

LAN

NID

Strategy

::

::

:

O/S

Serial No

1 1 +

L

a

b c

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

either surface mount

or DIN rail mount

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

a b c d

WARNING: Failure to use a screwdriver to open the cover will cause damage to the unit.

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

c� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

dH O

2

+45 °C(113 °F)

0

0 °C(32 °F)

90 %RH

1 3+

LLAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

21 22 23 24 25 26 27 281 2 3

COM

1 2 3 54 6 7

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5

~24V

LON

29 30 31 32

LONOK

SRVPIN

C

24 Vac

e

Protection: IP20, NEMA 1

Altitude: <2000 m

f

g

Avoid locations where corrosive fumes or explosive vapours are present. Avoid electrical noise interference.

This unit must be installed in an enclosure conforming to EN61010-1

1 3 +

LLAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

21 22 23 24 25 26 27 281 2 3

COM

1 2 3 54 6 7

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5

~24V

LON

29 30 31 32

LONOK

SRVPIN

C

13+

LLAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24VCOM

21 22 23 24 25 26 27 28 1 2 3

COM

1235 467

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

12345

~24V

LON

29 30 31 32

LONOK

SRVPIN

C

13

+LLA

N

NID

Stra

tegy

: : : : :

O/S

Se

rial N

o

23

0 V

ac

~ 24

VC

OM

21

22

23

24

25

26

27

28

1 2

3

CO

M

12

35

46

7

6 7

8 9

10 1

1 1

2 1

3 1

4 1

5 1

6 1

7 1

8 1

9 2

0

12

34

5

~ 24

V

LO

N

29

30

31

32

LO

NO

K

SR

VP

IN

C

13

+ LLA

N

NID

Str

ate

gy

: : : : :

O/S

Se

ria

l N

o

23

0 V

ac

~24

VC

OM

21

2

2

23

2

4

25

2

6

27

2

81

2

3

CO

M

12

35

46

7

6 7

8

9

1

0 11 1

2 1

3 1

4 1

5 1

6 1

7 1

8 19 20

12

34

5

~24

V

LO

N

29

3

0

3

1

32

LO

NO

K

SR

VP

IN

C

DIN rail end stop!

Page 3: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 3

Installation Instructions IQL16/xxx, /AHU

Connect Power5

DO NOT APPLY POWER

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

3 Installation - Mounting (continued)

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

6

� � � � � � � � � �

� � � � � � � � � �

� � � � � � � � � �

LON - FTT (free topology)

Star topology Bus topology Loop topology*Terminate LONWORKS bus at one end only

polarity independent

Connect LONWORKS LON

29 30 31 32

L W

network

ON ORKS L W

network

ON ORKS

** *

Do not allow wires to cross on a loop

100 � F, 50 V min

100 � F, 50 V min

Terminatore.g.LONTERMINATOR

LonASCN LonB LonASCN LonB

LINC

A

IQLROUTER

B

IQL

x y

A

IQLROUTER

B

zw

IQL

x y zw

T

T T

4 5 6 7 8 9 10 11

4 5 6 7 8 9 10 11

L N E

230 Vac

1 2 3

Clean earths, grounds, consisting of short (<300 mm, 12”) stranded copper wire (>=1.5 mm2, 16 AWG) to a substantial earthed, grounded, metal part (e.g. cable tray) are recommended

Terminal size 0.5 to 2.5 mm2

(14 to 20 AWG)

24 Vac

1 2 3

24Vac

Earth, ground, 24 Vac supply neutral at transformer

/24VAC option /230 optionIQL consumption

<= 12.1 VA (2.5 VA + power to 24 Vac auxiliary supply and triac outputs)

IQL consumption<= 13 VA (3 VA + power

to 24 Vac auxiliary supply and triac outputs)

continued over page

Maximum 64 nodes per LONWORKS segmentMaximum 40 IQLs (and LONCs) per virtual Lan

Recommend terminate at LINC or Router.e.g. use IQLRouter integral terminators

A switch or circuit breaker must be included in the supply to the unit and be in close proximity to it, and must be clearly marked as the disconnecting device for the unit.

This unit is protected to safety class 2. The earth on this unit is NOT a

protective earth, but it is essential that anearthisfittedforfunctionalreasons.

Page 4: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

4 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

SupplyFan

InletDamper Extract

Fan

1 2 3

6 7 8 9 10 11 12 13 14

Connect Inputs and Outputs7If non standard strategy, follow special installation instructions and jump to step 13

Non-standard Strategy Installation Instructions

6

3 Installation - Mounting (continued)

Connect LONWORKS (continued)

If used with LPT-10 (powered bus), cable lengths differ - see “Link Power Transceiver User’s Guide (078-0105-01C)”.

LINC LINC

IQ System Outstations IQ System

Outstation

L M

Device

ON ARK

IQL

L WON ORKS bus

Normal IQ System current loop Lan cable is not recommendedDo not use screened cable

Terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)

Cable Max bus length Max node to nodeBelden 85102 500 m (545 yds) 500 m (545 yds)TrendTP/1/0/16/HF/200 (Belden 8471)

500 m (545 yds) 400 m (430 yds)

UL Level IV, 22 AWG 500 m (545 yds) 400 m (430 yds)

JY(St) Y2 x 2 x 0.8 500 m (545 yds) 320 m (350 yds)

TIA5268A Cat. 5, 24 AWG 450 m (430 yds) 250 m (270 yds)

Connect Inputs8� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

Connect Relay Outputs9

Trip -e.g. Filter Dirty

FrostThermostat

LocalSpace

TemperatureSensor

Local SetpointAdjust

Potentiometer

DuctTemperature

Sensor

COM

21 22 23 24 25 26 27 28

COM

1 2 3 4 5

C

12 3

TB/TS /K

COM

21 22 23 24 25 26 27 28

COM

1 2 3 4 5

C

Sensors TB/TS, TB/TS/K recommended; wire as shown below.

alarm trip

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

WARNING: The wires may be connected to hazardous voltages. Disconnect power before attempting any wiring.

For IQL16/24VAC, UL rating applies up to 30 Vterminal size 0.5 to 2.5 mm2 (14 to 20 AWG) - Cu only

Arc Suppression TG200208

t e r m i n a l size 0.5 to 2.5 mm2 (14 to 20 AWG) - Cu only

Note t ha t t e rm ina l

types COM, � �� �

and C should not be connected together.

5A maximum at 240 V resistive or inductive (cos Ø>=0.4)5A at 30 Vdc (resistive), 2A at 24 Vdc (inductive, T<=30 mS)

Note that to meet safety requirements, for the 3 relays (OUT1 to OUT3), those being used must all be switching either low voltage or mains and not a mixture of voltages. If switching mains, they must all switch the same phase and polarity.

Page 5: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 5

Installation Instructions IQL16/xxx, /AHU

14 Close Enclosure

15 Cleaning & Maintenance

There are no serviceable parts inside the unit. Cleaning of the unit

should be carried out in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning. Clean surfaces with a cloth moistened with water.

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

Load

24 Vac

4 5

Ra

ise

Recirc/FAMixing

Damper

Co

mm

on

Lo

we

r

~24V 10V 0V 10V

AO

54 6 7

15 16 17 18 19 20

3 Installation - Mounting (continued)

Close Hinged Cover13

LAN

NID

Strategy

::

::

:

O/S

Serial No

1 1 +

L

a

b

LAN

NID

Strategy

::

::

:

O/S

Serial No

1 1 +

L

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

Connect Heat/Cool Outputs10

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

He

at

Va

lve

Co

ol V

alv

e

~24V 10V 0V 10V

AO

54 6 7

15 16 17 18 19 20

0 to 10 Vdc, 10 mA max.; shares 280 mA with mixing damper output and auxiliary supply

Above 40 °C (104 °F) the maximum current available is 180 mA

Note that terminal types

COM, � �� �

and C should not be connected together.

Connect Mixing Damper Output11

24 Vac, 280 mA max. shared with heat/cool output and auxiliary supply

Above 40 °C (104 °F) the maximum current available is 180 mA

Connect 24 Vac Auxiliary Supply12

24 Vac, 280 mA max. shared with heat/cool and mixing damper outputs

Above 40 °C (104 °F) the maximum current available is 180 mA

terminal size 0.5 to 2.5 mm2 (14 to 20 AWG) - Cu only

terminal size 0.5 to 2.5 mm2 (14 to 20 AWG) - Cu only

terminal size 0.5 to 2.5 mm2 (14 to 20 AWG) - Cu only

Note that terminal types

COM, � �� �

and C should not be connected together.

1 3+

LLAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

21 22 23 24 25 26 27 281 2 3

COM

1 2 3 54 6 7

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5

~24V

LON

29 30 31 32

LONOK

SRVPIN

C24 Vac

Page 6: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

6 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

4 Installation - Configuration

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

LINC LINC

IQ System Outstations IQ System

Outstation

L M

Device

ON ARK

IQL

L WON ORKS bus

(Check LONWORKS, LINCs)

LON OK (green)

Flashes every 24 s, ON after 1½ mins

Switch On2

Check IQL/LINC on LONWORKS Bus3

Flashes every 1 s (Deaf IQL. Check LONWORKS)

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

See LONWORKS network management tool manual. See IQ System LONWORKS Produc ts Eng ineer ing Manua l (TE200292). LONWORKS System Integrator must have LONWORKS engineering expertise.

a). When installing IQL in LONWORKS tool, press service button when requested.

b). The IQL network image can be obtained from www.lonmark.org, or from www.pnet.trend-controls.com.

c). Set up bindings if required (bind network variables between IQL and LONMARK devices).

IQL16 Data Sheet TA200451 for LONWORKS network variables (NVs)

Install using LONWORKS Network Managment Tool4 If a binding IQLs to LONMARK devicesor b LINCs version <3.23 straddle routeror c otherdeviceshaveaddressconflictswithIQSystemdevicesor d IQLROUTERs used on installed system

SRV PINservice button

LINC

L W

network

ON ORKS

IQL

LONMARK

device

If one IQ System LONWORKS device is installed, all must be installed.

Tear off Label Strip1

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

� � � � �� � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �� � � � � � � � � � � � � � � � � � �

� � � � � � � � � � �� �

� � �

� � � �� � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � � � � � � �

� � � � � � � � � � � � � � � �

� � � �� �

� � � � �

XTEND -4000070963Xtream

LAN

MAC Addr 00.10.70.00.UD.BB

O/S

S/No:

IP Addr Location

MAC Addr 00.10.70.00.UD.BB

S/No:Q3B____X73010003

IP Addr

� � �

� � � � � � � � �� � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � � � � � � � � �� � �� � �

‘locate’

Page 7: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 7

Installation Instructions IQL16/xxx, /AHU

4 Installation - Configuration (continued)

Note that a PIN may be required to make changes. If the PIN has been forgotten the users should contact their supplier (installers contact Technical Support)

quoting the generator number and neuron id (both from Address module) whereupon a default PIN will be supplied. This will only work for three attempts at entering the PIN. After the default PIN is entered a new PIN should be set up and remembered.

1 1 +

L

LAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

15 16 17 18 191 2 3

24 Vac

LON

20 21 22 23

1 32 4 5

4 5 6 7 8 9 10 11 12 13 14

1 2 3

~24V

LONOK

SRVPIN

C

L WON ORKS

network

LCI

IQL

Connect software tool for text commissioning5if required

Exercise I/O6If IqlTool2 available

IqlTool2 Manual TE200185

Use IqlTool2 to monitor inputs and exercise outputs

Test input/output functionality7

Non-standard Strategy Installation Instructions

If non standard strategy follow special installation instructions and jump to step 12.

IqlTool2 ManualTE200185

LCI Installation Instructions TG200429SET Manual TE200147

IqlTool2 (SET)IqlTool2 runs within SETV5 (or later)

RS232 cable supplied with LCI

1 1 +

L

LAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

15 16 17 18 191 2 3

24 Vac

LON

20 21 22 23

1 32 4 5

4 5 6 7 8 9 10 11 12 13 14

1 2 3

~24V

LONOK

SRVPIN

C

L WON ORKS

network

LCI

IQL

IqlTool2(SET)

Note that IqlTool2 may also be used for mapping the LONWORKS segment, resolving duplicate addresses on LONWORKS network, identification via service button, associating with SDU-LON (for other uses see later)

LONWORKS adapter cable supplied with LCI

Page 8: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

8 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

S

S

Check Strategy, Sensors/Dampers/Fans/Heat, Cool Valves

IN1

OUT1 � � � � � �� � � �

� � � � �� � � �

� � � � � �� � � �

� � � � �� � � �

Free cooling if outside air temperature (K7) < S1

�� � �

�� � �

S

S

IN3

inlet OUT2inlet extract

spaceduct

OUT3

OUT4,5coolOUT7

heatOUT6

During occupation (default)

8

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

9

OUT1� � � � � �� � � �

� � � � �� � � �

�� � ��� � �

inlet OUT2inlet extract

OUT3

OUT4,5coolOUT7

heatOUT6

Check Frost Thermostat if fitted

�IN5

fan off fan off

if W3=0, Frost Stat enabled (default)

Note that if Frost Thermostat is not fitted, it must be disabled for fans to run (W3=1).

4 Installation - Configuration (continued)

Page 9: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 9

Installation Instructions IQL16/xxx, /AHU

Check Operation - Local SP Adjust10

IN2

OUT1 � � � � � �� � � �

� � � � �� � � �

�� � ��� � �

inlet OUT2inlet extract

OUT3

OUT4,5coolOUT7

heatOUT6

Wait 6 secs at each end to calibrate potentiometer

� �

�� � �

� � �

� � � � � � � �

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� � �

� � � � � � � � �

During occupation (default)

4 Installation - Configuration (continued)

Set up Strategy Parameters 11if required

Use IqlTool2 (see step 5) and text communications

For standard strategies use table below, else refer to non-standard strategy installation instructions

Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=O), recommended], to commit changes to flash memory.Note that D4 full scale drive time should not be greater than 262s.

Parameter Label Function DefaultK1(V) Remote Setpoint Base setpoint can be adjusted remotely 20 °CK2(V) RemoteSpace Temp Used if bound to LONWORKS sensor, or if space sensor disconnected 20 °CK3(V) OCC Deadbnd Deadband around setpoint during Occ 1 °C

K5(V) NOCC Deadbnd Deadband around setpoint during Nocc 12 °CK6(V) Remote Occ Sets state 0=Occ, 1=Nocc 0=OccupiedK7(V) Remote OAT. Outside Air Temp for free cooling 10 °CK8(V) Remote SP Offset SP offset used if bound to a LONWORKS sensor or SP adjust has error 0 °C

K9(V) Rem Supply Temp Used if bound to LONWORKS sensor, or if duct sensor disconnected 20 °CK10(V) Duct Frost Pro If duct temp falls below this, frost protection is required 5 °C

K14(V) Min Nocc Run Min inlet damper open on time during Nocc 1200 secsK15(V) Offset range DefinesrangeofLocalSPadjustpot. 2 °C

W2(S) Free Clg Enable Enables free cooling if Remote OAT < Space Temp 0=disable free coolW3(S) Frst St Disable Disablesfrostactionifsetto1(e.g.thermostatnotfitted) 0=enable frost action

W8(S) Remote Shutdown Shuts off fans, closes inlet damper, closes valves, mixing damper goes to full recirculation 0=no shutdown

L1(G) Heat Loop Gain 20L1(I) Heat Loop Integral 0 mins

L2(G) Cool Loop Gain -20

L2(I) Cool Loop Integral 0 mins

Page 10: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

10 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

4 Installation - Configuration (continued)

Note 1: IqlTool2 facilitates setting of these parameters across the LONWORKS segmentNote 2: Changing any of these parameters results in a controller reset (clears down time and and sensor logs)Note 3: Any changes to these parameters should immediately be followed by a write to the address module, [text comms command, R(z=O), recommended], to commit changes to flash memory.Note 4: IqlTool2 facilitates setting to timekeeper (sets up timemaster Lan and changes own address to 11)Note 5: Message code can only be changed by text comms if ‘lonworks managed’ (read only) is set to No.Note 6: If PIN is forgotten see note in step 5

Using IqlTool2 (see step 5) and text communications

Set up System Core Firmware Module Parametersif required - see conditions

12

Parameter Setting Function Condition NoteR(..address L - own address device address of IQL if required to rearrange

Lans, address1, 2, 4

N - own LaN Lan number of IQL if required to rearrange Lans, address

1, 2

D-identifier identifierattributeofIQL For alarm ident, text comms, IC comms

1

F - attribute 2 text comms attributes For text comms, IC comms 1G - attribute 3 1A - own Lan alarm address

address and Lan of own Lan alarm target

to report Lan alarms to a supervisor

1

R - Own Lan alarm Lan 1E - Internetwork alarm address

address and Lan of Internetwork alarm target

to report internetwork alarms to a supervisor (only for lowest addressed IQ System device on Lan)

1

T - Internetwork alarm Lan 1

r - LONWORKS retry time See IQ System LONWORKS Products Engineering Manual for details

2i - LONWORKS interpacket delay

2

a - LONWORKS service class

2

b - router Buffer size buffer size (bytes) Default = 146

specifiessmallestrouterbuffer on system

If routers separate IQLs/LINCs/LONCs and have buffer size smaller that 146 bytes - set to smallest buffer size. (minimum = 66)

2

m - LONWORKS Message code

code number. Default = 64

Code used by IQLs/LINCs/LONCs, all LINCs/LONCs must use same code

If message code being used by other users - must be exclusive to IQ System

2, 5

g - generator number TofindPINiflost (read only)e - Neuron Chip id unique

identifierforNeuron®

TofindPINiflost;toidentify LONWORKS node

(read only)

T(..Time H - Hours Current time To synchronise time for alarms and loggingN - Minutes

D - Day of month Current date To synchronise date for alarms and logging

3M - Month 3Y - Year 3l - Lan of system timemaster

IQL timekeeper gets time sync from IQ at address 11 on this Lan

IQL will be timekeeper If this ‘l’ parameter is non-zero and own address = 11

3, 4

U1(..User P - PIN PIN number in IQ To protect from unauthorised changes

3, 6

l -level authority level of PIN No protection if zero 3

Page 11: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011 11

Installation Instructions IQL16/xxx, /AHU

4 Installation - Configuration (continued)

Set up Lan System 13 LINCInstallation Instructions TG103062

L WON ORKSnetwork

IQL1 1 +

L

LAN

NID

Strategy

: : : : :

O/S

Serial No

230 Vac

~24V COM

15 16 17 18 191 2 3

24 Vac

LON

20 21 22 23

1 32 4 5

4 5 6 7 8 9 10 11 12 13 14

1 2 3

~24V

LONOK

SRVPIN

C

LINC

IQ

Check Lan

if required

IQ System LONWORKS Products Engineering Manual TE200292

Use SET and terse text communications

SET

IQL

IC Comms

LINC

IQ

L W networkON ORKS

Nx

K1

W1

S1

K2

K8

W7

W8

I1

I8

S8

Nx

LCI

IC Comms Module Nx(.. - (x=1 to y; y=4 for standard strategies)

Set up IC Comms from IQL if required

14

Parameter Function

A - Remote device address

If zero, ‘global to’ comms. Ifnon-zerospecifiestarget device address for ‘data to’ comms

B - Attribute

For ‘global to’ comms only, attribute of target IQ, references attribute in address module (0 ‘no attribute’, - all IQs onLan,1‘identifier’,2‘attribute 2’, 3 ‘attribute 3’)

N - Remote LanTarget IQ Lan number; if Lan zero, address zero, specifiesglobalglobal

I - Interval Interval between sending (minutes)

S-Significantchange

Amount analogue must change before sending

M - Source item string

Item and parameter being sent (e.g. S1(V))

E - Destination module number

No. of destination module receiving IC comms

T - Destination typeType of destn module receiving comms (e.g. W,K)

Use IqlTool2 (see step 5) and text communications

Page 12: LONMARK Terminal Unit Controllers - Honeywellproducts.ecc.emea.honeywell.com/europe-historic... · Note that this product may involve L ONWORKS ® system integration as referred to

12 IQL16/xxx, /AHU Installation Instructions TG200453 Issue 5, 21-Nov-2011

IQL16/xxx, /AHU Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems LimitedAlberyHouse,SpringfieldRoad,Horsham,WestSussex,RH122PQ,UK.Tel:+44(0)1403211888Fax:+44(0)1403241608www.trendcontrols.comTrend Control System USA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

WEEE Directive :At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.

IQL

IC Comms

LINC

IQ

L W networkON ORKS

Nx

K1

W1

S1

K2

K8

W7

W8

I1

I8

S8

Nx

IC Comms ‘direction’ in IQ must be: Global To, Min, Max, Sum, or Average (directions 2 to 6)

see IQConfigurationManual 90-1533

Set up IC Comms from IQif required

15

LINC

IQ

Terse Text Comms

K1

W1

S1

K2

K8

W7

W8

I1

I8

S8

L W networkON ORKS

IQL

Set up Communications from Supervisor

if required

16

Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.

4 Installation - Configuration (continued)

e.g. 963 (drag and drop values)

Note that standard strategy pages are available for 963 from Partnernet

Use SET and terse text communications

5 Disposal