Locating buried pipes and cables. Radiodetection. ABC to XYZ of locating buried pipes and cables - For the beginner to the specialist. Radiodetection Corp. 154 Portland Rd Bridgton ME, 04009 877 247 3797. Cable locators do not find cables. ?. ...they find magnetic fields. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/1.jpg)
COMPANY CONFIDENTIAL
GLOBAL INFRASTRUCTURE X PROCESS EQUIPMENT X DIAGNOSTIC TOOLS
Locating buried pipes and cables
April 19, 2023 1
![Page 2: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/2.jpg)
COMPANY CONFIDENTIAL
Radiodetection
ABC to XYZ of locating buried pipes and cables - For the beginner to the specialist
Radiodetection Corp.154 Portland RdBridgtonME, 04009877 247 3797
![Page 3: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/3.jpg)
COMPANY CONFIDENTIAL
![Page 4: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/4.jpg)
COMPANY CONFIDENTIAL
Cable locators do not find cables.....
?
![Page 5: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/5.jpg)
COMPANY CONFIDENTIAL
...they find magnetic fields
![Page 6: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/6.jpg)
COMPANY CONFIDENTIAL
Because fields do things that pipes and cables don’t do
Why does it matter?
![Page 7: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/7.jpg)
COMPANY CONFIDENTIAL
Buried conductors don’t move, but the fields we’re tracing are subject to…
![Page 8: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/8.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application2. Grounding3. Peak or Null4. Congestion5. Frequency applied
...Distortion
![Page 9: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/9.jpg)
COMPANY CONFIDENTIAL
What is a Magnetic Field ?
A magnetic field is radiated by a current carrying conductor
![Page 10: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/10.jpg)
COMPANY CONFIDENTIAL
…Which can be detected by a receiving coil which is excited by the expansion and contraction of the field.
Aerial
Volts
![Page 11: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/11.jpg)
COMPANY CONFIDENTIAL
What is Electromagnetic Induction?
If a bar magnet is inserted into a coil of wire, a voltmeter will show a deflection but only while the magnet is moving. When the magnet stops, the meter reads Zero. When the movement of the magnet is reversed, the meter deflection is reversed.
S
N
+ volts0
![Page 12: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/12.jpg)
COMPANY CONFIDENTIAL
one a.c. cycle
Alternating current creates a moving and reversing magnetic field
What is an Alternating Magnetic Field?
![Page 13: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/13.jpg)
COMPANY CONFIDENTIAL
What is Electromagnetic Induction ?
Direct current does not produce an electro - magnetic field detectable with a locator. DC Current builds to its voltage and produces a constant level of magnetism. There is no change in this voltage to excite an adjacent receiving coil.
Bulb will not light
![Page 14: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/14.jpg)
COMPANY CONFIDENTIAL
Passive
Active
There are two methods of signal detection
![Page 15: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/15.jpg)
COMPANY CONFIDENTIAL
Passive signals are a by-product of the 20th century. The proliferation of power and radio technology in this century has caused almost every underground metallic pipe or cable to emit detectable magnetic fields.
Passive
![Page 16: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/16.jpg)
COMPANY CONFIDENTIAL
Detectable Radio signals come from high power, low frequency international communication and navigation systems.
Such signals are present nearly everywhere on earth.
Passive
![Page 17: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/17.jpg)
COMPANY CONFIDENTIAL
FastEasyDoes not identify
Passive
![Page 18: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/18.jpg)
COMPANY CONFIDENTIAL
However tracking lines to their source can also aid identification
Passive
![Page 19: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/19.jpg)
COMPANY CONFIDENTIAL
Passive
Ensure a full grid search is done to detect conductors laid in different directions.
![Page 20: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/20.jpg)
COMPANY CONFIDENTIAL
Passive
Active
There are two methods of signal detection
![Page 21: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/21.jpg)
COMPANY CONFIDENTIAL
Increases Locator VersatilityDepth MeasurementPositive Identification
Active
![Page 22: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/22.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application
…Distortion
![Page 23: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/23.jpg)
COMPANY CONFIDENTIAL
There are three main methods of Active Signal Application
Induction "Spill"
Connection "Clip"
Signal Clamp "Clamp"
Applying a signal
![Page 24: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/24.jpg)
COMPANY CONFIDENTIAL
Connection
A successful connection to the metallic pipe or cable will be indicated by a change in the transmitter audio or visual indicator. Always make the best possible connection for reliable signal.
mA
mA
![Page 25: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/25.jpg)
COMPANY CONFIDENTIAL
Requires three components:
1. A transmitter or signal source
2. A metallic conductor
3. A return path. Ideally, the earth.
Direct Connection Locating
![Page 26: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/26.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application
2. Grounding
…Distortion
![Page 27: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/27.jpg)
COMPANY CONFIDENTIAL
Connection
The ground return point is the "back door" that the outgoing signal returns to. What you ground to and where you place the ground can significantly affect your results.
Remember: Every milliamp of signal that is going out the metal to metal connection on the red lead has to come back in through a metal to dirt connection on the ground lead.
![Page 28: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/28.jpg)
COMPANY CONFIDENTIAL
Ground stake too close to target conductor: Less range, some signal transfer.
Connection
![Page 29: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/29.jpg)
COMPANY CONFIDENTIAL
Badly positioned remote ground causes more signal transfer
Where possible, place ground rod away from known adjacent utilities which may act as return paths.
Connection
![Page 30: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/30.jpg)
COMPANY CONFIDENTIAL
Remote ground = better range, less signal transfer.
As a general rule, try to position the ground point at right angles to and 5-10' from the connection point and direction of conductor.
Connection
![Page 31: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/31.jpg)
COMPANY CONFIDENTIAL
Grounding to a structure which is also grounded can produce multiple signals.
The signal returns on every conductor that shares the same ground
Connection
![Page 32: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/32.jpg)
COMPANY CONFIDENTIAL
Connection
Positioning the ground stake in the direction you wish to locate will often encourage the signal to flow in that direction
![Page 33: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/33.jpg)
COMPANY CONFIDENTIAL
Connection
When locating Tees, position ground stake in the direction you wish to locate.
![Page 34: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/34.jpg)
COMPANY CONFIDENTIAL
Connection
For greater signal travel, an extension cable can be used to place the ground stake further away.
![Page 35: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/35.jpg)
COMPANY CONFIDENTIAL
The Cable Reel
![Page 36: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/36.jpg)
COMPANY CONFIDENTIAL
A double-ended connection does not use ground as part of the circuit and is more dependable. This is particularly true when trying to locate metallic pipes buried close together.
Connection
![Page 37: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/37.jpg)
COMPANY CONFIDENTIAL
Metal fences may seem a convenient ground point, but might produce interfering signals.
Always use an independent ground such as a ground stake, large screwdriver or other isolated metallic object buried in the ground.
Connection
![Page 38: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/38.jpg)
COMPANY CONFIDENTIAL
After making a connection, sweep a complete circle around a signal source; measure and mark all occurrences of signal. Repeat to assure accuracy.
Connection
![Page 39: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/39.jpg)
COMPANY CONFIDENTIAL
At older buildings where the services are all metallic and may share a common ground, connecting close to multiple service bondings may produce multiple signals.
Connection
![Page 40: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/40.jpg)
COMPANY CONFIDENTIAL
Energizing in the street and tracing toward the bonding point can be more reliable
Connection
![Page 41: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/41.jpg)
COMPANY CONFIDENTIAL
The Signal clamp is a current transformer which induces or spills a locate signal onto a target line
Clamp
![Page 42: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/42.jpg)
COMPANY CONFIDENTIAL
A clamp safely applies a signal to a live cable without interrupting the supply
Transmitter Clamps
![Page 43: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/43.jpg)
COMPANY CONFIDENTIAL
The Signal Clamp is a means of applying a transmitter signal to an insulated pipe or cable, without physical connection. It's most useful for live electric cables.
Signal Clamp must be completely around line with jaws closed.
Clamp
![Page 44: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/44.jpg)
COMPANY CONFIDENTIAL
When using a clamp, the applied signal moves away from the nearest ground to a distant ground. For this reason, it's a useful way to put a locate signal on a specific line.
Clamp
![Page 45: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/45.jpg)
COMPANY CONFIDENTIAL
At higher frequencies - or with longer lines - capacitive leakage completes the circuit.
Clamp
![Page 46: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/46.jpg)
COMPANY CONFIDENTIAL
Direct connection does not give reliable identification on multiple bonded lines
As an exception, connection to the bonding ribbon in a manhole will send tone in one direction, allowing the conduit run to be located.
Connection
6 12 14 6
![Page 47: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/47.jpg)
COMPANY CONFIDENTIAL
Generally, clamping produces more reliable signal identification.
Excellent on headers. Especially with using current measurement and direction.
Clamp
6 22 10 6
![Page 48: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/48.jpg)
COMPANY CONFIDENTIAL
Place the clamp below the earth bond when locating cables. Do not place above the earth bond.
If there is no bonding strap, the clamp may not transmit a signal.
Clamp
![Page 49: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/49.jpg)
COMPANY CONFIDENTIAL
If using the clamp around a metallic pipe, any insulating flange must be bridged.
Clamp
![Page 50: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/50.jpg)
COMPANY CONFIDENTIAL
Induction
Induction allows the user to quickly and easily apply a locate signal, by placing the transmitter in the vicinity of a known conductor or conductors
![Page 51: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/51.jpg)
COMPANY CONFIDENTIAL
min. 10 paces
A minimum distance of 10 paces between receiver and transmitter is necessary to avoid the receiver detecting the signal directly from the transmitter. This is known as "Air coupling".
Induction
![Page 52: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/52.jpg)
COMPANY CONFIDENTIAL
Often induction will energize every metallic conductor close to the transmitter. This is useful for checking an area for buried conductors, but not useful for finding specific conductors in congested areas.
Induction
![Page 53: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/53.jpg)
COMPANY CONFIDENTIAL
The induced transmitter signal is usually strongest on the line directly below and in line with the transmitter
Induction
![Page 54: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/54.jpg)
COMPANY CONFIDENTIAL
Aerial
The orientation of the aerial is important as seen with an AM radio
![Page 55: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/55.jpg)
COMPANY CONFIDENTIAL
When the aerial is not in line with the magnetic field, no signal is detected. This is known as "Nulling".
Aerial
![Page 56: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/56.jpg)
COMPANY CONFIDENTIAL
When the transmitter is turned onto its side so the coil axis is vertical, the induction signal is spread over a wider area; but this results in zero signal directly below the transmitter. Which can be useful...
Induction
![Page 57: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/57.jpg)
COMPANY CONFIDENTIAL
Min. 10 paces
Using transmitter on its side to 'Null out''When the transmitter is over the target cable, minimum signal will be found by the receiver and the adjacent conductors will be energized strongly.
Induction
![Page 58: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/58.jpg)
COMPANY CONFIDENTIAL
100 20 5.8 2.7
Induction
Estimated induction signal ratios
![Page 59: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/59.jpg)
COMPANY CONFIDENTIAL
50 30 19 140
Estimated induction signal ratios
Induction
![Page 60: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/60.jpg)
COMPANY CONFIDENTIAL
Induction Search (two person).Maintain minimum Rx/Tx separation.
Sweep 3 times ! +/- 30-40 degrees
Induction
![Page 61: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/61.jpg)
COMPANY CONFIDENTIAL
Induction search, radial.
Maintain constant Rx/Tx separation
- Lazy Susan idea
Induction
![Page 62: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/62.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application
2. Grounding
3. Peak or null
...Distortion
![Page 63: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/63.jpg)
COMPANY CONFIDENTIAL
Aerial Responses
Different aerial orientations can be used for different responses
1 2 3
Signalresponse
1 2 3
Signalresponse
![Page 64: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/64.jpg)
COMPANY CONFIDENTIAL
In Null, minimum signal is encountered exactly over the center of the buried conductor field
A maximum signal response will be detected on each side of the minimum. If both of the "shoulders" are symmetrical, the Null point is accurate.
Receiver Response
![Page 65: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/65.jpg)
COMPANY CONFIDENTIAL
Null antenna gives a sharp response which gives the impression of good accuracy, but can be less accurate than Peak.
100%
5%
Receiver Response
![Page 66: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/66.jpg)
COMPANY CONFIDENTIAL
Peak coil response is less sharp, but actually more accurate.
100%95%
Receiver Response
![Page 67: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/67.jpg)
COMPANY CONFIDENTIAL
This is a typical peak signal response over a buried conductor. Peak response provides position and direction.
Note that the maximum signal response occurs directly over the center of the underground conductor
Receiver Response
![Page 68: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/68.jpg)
COMPANY CONFIDENTIAL
Peak response is more reliable. It enables you to measure depth.
Peak response is more accurate in congested areas
Peak
Receiver Response
![Page 69: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/69.jpg)
COMPANY CONFIDENTIAL
Null is useful for deep lines and rapid line tracing , but...
Null
d
Receiver Response
![Page 70: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/70.jpg)
COMPANY CONFIDENTIAL
Null response in an area with congested plant is often useless and misleading
Null
Receiver Response
![Page 71: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/71.jpg)
COMPANY CONFIDENTIAL
Peak and Null coils produce opposite types of error when tracing bends
PeakNull
Receiver Response
![Page 72: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/72.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application
2. Grounding
3. Peak or Null
4. Congestion
...Distortion
![Page 73: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/73.jpg)
COMPANY CONFIDENTIAL
Distortion
Current on one line may induce 'stray' signals onto nearby conductors
![Page 74: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/74.jpg)
COMPANY CONFIDENTIAL
When the conductors are close together, the magnetic fields can interfere with each other, causing a distorted field which is no longer cylindrical. This can lead to poor locate results and inaccurate measurements.
Distortion
![Page 75: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/75.jpg)
COMPANY CONFIDENTIAL
d
PeakNull
d
Distortion and Depth
When there is a discrepancy between the aerial responses the following must be observed.1. The Peak response will always be more accurate.2. Push button depth estimation should not be used until the two responses agree
Peak Null
![Page 76: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/76.jpg)
COMPANY CONFIDENTIAL
Peak
Null
13
This distortion varies depending upon the direction and magnitude of the current flow, causing a discrepancy between the peak and null aerial responses.
Distortion
![Page 77: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/77.jpg)
COMPANY CONFIDENTIAL
dd d
Because we know the field is likely distorted,it's not a good idea to rely on depth readings taken near a change of direction...
Depth
![Page 78: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/78.jpg)
COMPANY CONFIDENTIAL
dd
d
or near a tee
Depth
![Page 79: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/79.jpg)
COMPANY CONFIDENTIAL
dd
or near another line
Depth
![Page 80: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/80.jpg)
COMPANY CONFIDENTIAL
dd d
or near a depth change
Depth
![Page 81: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/81.jpg)
COMPANY CONFIDENTIAL
d dmin. 30 paces
or near an inducing transmitter
Depth
![Page 82: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/82.jpg)
COMPANY CONFIDENTIAL
100%70%
d
d
Depth Triangulation Peak Aerials
Depth estimation can be verified using a triangulation technique. Move the receiver from 100% to 70% signal strength, on each side of conductor and measure the distance. This distance will be approximately equal to the depth.
![Page 83: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/83.jpg)
COMPANY CONFIDENTIAL
Affected by:
1. Method of signal application
2. Grounding
3. Peak or null
4. Congestion
5. Frequency applied
...Distortion
![Page 84: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/84.jpg)
COMPANY CONFIDENTIAL
Which frequency should I use ?
Very LowLess than 1 kHzVery Long RangeNo InductionLittle "Spillage"Better IDent
Low1-10 kHzLong RangePoor InductionLess "Spillage"
High10-50 kHz.Easy InductionShorter RangeMore "Spillage"
Very High50kHz+Short RangeExcellent InductionSevere "Spillage"
Characteristics of different frequencies.
All of these characteristics get better or worse linearly with frequency. There is no signal that is magically better for one than another.
![Page 85: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/85.jpg)
COMPANY CONFIDENTIAL
High frequency signal quickly escapes from target line and may return on an adjacent line Lines in close proximity will readily accept signal. This can lead to field distortion and poor locate information.
Which Frequency ?
![Page 86: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/86.jpg)
COMPANY CONFIDENTIAL
Higher frequency = shorter range (greater capacitive signal loss to ground) This frequency is better for induction onto small or short length conductors, such as telephone drops, CATV cables or street light cables.
Which Frequency ?
![Page 87: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/87.jpg)
COMPANY CONFIDENTIAL
Low frequency = long range (minimum capacitance signal loss to ground)
This frequency is better for connection and locating longer metal pipes or cables
Which Frequency?
![Page 88: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/88.jpg)
COMPANY CONFIDENTIAL
High frequency may locate service drops which are not grounded at the termination point but range on main line is reduced and may induce onto crossing services
Which Frequency?
![Page 89: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/89.jpg)
COMPANY CONFIDENTIAL
Low frequency tends to keep to main line, does not induce onto crossing lines and bypasses service drops which are not grounded.
Which Frequency ?
![Page 90: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/90.jpg)
COMPANY CONFIDENTIAL
High frequency can use a capacitive ground connection through a metal plate
This provides a ground in areas where direct earth ground cannot be achieved
Which Frequency ?
![Page 91: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/91.jpg)
COMPANY CONFIDENTIAL
General Locating
When pinpointing the signal, keep the bottom of the receiver blade close to and parallel to the ground.
![Page 92: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/92.jpg)
COMPANY CONFIDENTIAL
Always pivot receiver to ensure maximum signal is received
This is particularly true prior to taking a depth reading
General Locating
![Page 93: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/93.jpg)
COMPANY CONFIDENTIAL
General Locating
Searching for laterals
Use Peak and search 2 paces away from and parallel to the main line
![Page 94: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/94.jpg)
COMPANY CONFIDENTIAL
Problems
If multiple signals are received at uniform distances apart, you are probably trying to locate through reinforcing bars.
Raise the receiver up to chest height. This should allow the main signal to be detected.
![Page 95: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/95.jpg)
COMPANY CONFIDENTIAL
Problems
Lost signal must be either: End of line
![Page 96: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/96.jpg)
COMPANY CONFIDENTIAL
Problems
OR: a T lateral
![Page 97: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/97.jpg)
COMPANY CONFIDENTIAL
Problems
OR: a bend
![Page 98: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/98.jpg)
COMPANY CONFIDENTIAL
Problems
OR: a depth increase
The field has simply become weaker at the coils because of the change of depth
![Page 99: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/99.jpg)
COMPANY CONFIDENTIAL
Small Waterproof self contained transmitters enabling non metallic ducts, drains or sewers to be located and traced with a Receiver.
Transmitting Sondes
![Page 100: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/100.jpg)
COMPANY CONFIDENTIAL
Ghost Ghost
Receiver response to a Sonde signal. Small ghost signals may be detected either side of main signal
Note: Receiver is held in line with Sonde
Sondes
![Page 101: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/101.jpg)
COMPANY CONFIDENTIAL
Sondes
Location procedure for pinpointing Sondes
![Page 102: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/102.jpg)
COMPANY CONFIDENTIAL
Sondes
Location procedure for pinpointing Sondes
![Page 103: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/103.jpg)
COMPANY CONFIDENTIAL
Using a Sonde to find a collapsed sewer
Sondes
![Page 104: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/104.jpg)
COMPANY CONFIDENTIAL
Tracking an inspection camera with a Sonde
Sondes
![Page 105: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/105.jpg)
COMPANY CONFIDENTIAL
Tracking a boring tool with built-in Sonde
Sondes
![Page 106: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/106.jpg)
COMPANY CONFIDENTIAL
Sondes
A sonde in a vertical position gives a very precise "null" signal
![Page 107: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/107.jpg)
COMPANY CONFIDENTIAL
Sondes
This can be used for very accurate positioning through a wall prior to drilling etc
![Page 108: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/108.jpg)
COMPANY CONFIDENTIAL
Locating a leak in a non metallic water pipe using a Sonde inside a "Pig“
Need VLF for metal pipes
Sondes
![Page 109: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/109.jpg)
COMPANY CONFIDENTIAL
A B
d=0.7AB
d
Triangulation depth method for verifying "push button" depth or estimating depth which is beyond the receiver's depth range
Sondes
![Page 110: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/110.jpg)
COMPANY CONFIDENTIAL
Levels of Confirmation
![Page 111: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/111.jpg)
COMPANY CONFIDENTIAL
Automatic Gain Control - AGC
![Page 112: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/112.jpg)
COMPANY CONFIDENTIAL
m
%
mA
m
%
mA
Signal strength
Current reading
Depth
Signal strength
Current reading
Depth
Change of depth effects signal strength but not current reading
RD400 Digital Series
![Page 113: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/113.jpg)
COMPANY CONFIDENTIAL
mA mA mA
Current losses returning to signal source
RD7/8000 Digital Series
![Page 114: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/114.jpg)
COMPANY CONFIDENTIAL
mA mA
Current loss due to poor insulation
There is very specialized equipment for this
RD7/8000 Digital Series
![Page 115: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/115.jpg)
COMPANY CONFIDENTIAL
mA
mA
mA
Current loss due to a Tee connection
RD7/8000 Digital Series
![Page 116: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/116.jpg)
COMPANY CONFIDENTIAL
Expected current direction indications and return signal path
For locators equipped with current direction indication only
Target line always
identifiable by current direction
RD7/8000 Digital Series
![Page 117: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/117.jpg)
COMPANY CONFIDENTIAL
Possible current direction indication on conductors.
RD7/8000 CD Series
![Page 118: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/118.jpg)
COMPANY CONFIDENTIAL
100%
60%40%
Modern equipment has many “Levels of Confirmation”
RD7/8000 Digital Series
![Page 119: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/119.jpg)
COMPANY CONFIDENTIAL
Current flow through an earth fault
FaultFind
![Page 120: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/120.jpg)
COMPANY CONFIDENTIAL
Meter readings before, at and after the fault.
FaultFind
![Page 121: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/121.jpg)
COMPANY CONFIDENTIAL
Distant fault – no indication
Line fault
ahead
Line fault
behind
FaultFind
Meter readings along a faulted cable
![Page 122: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/122.jpg)
COMPANY CONFIDENTIAL
FaultFind
FaultPositionLocate
Faultline
Locate line
It is possible to detect a fault a reasonable distance away, and to the side of the cable
FaultFind
![Page 123: Locating buried pipes and cables](https://reader038.vdocuments.site/reader038/viewer/2022102416/56812a8b550346895d8e2fb8/html5/thumbnails/123.jpg)
COMPANY CONFIDENTIAL
Pinpointing a fault under a roadway with two or more bearings (triangulation)
Fault line 1
Fault line 2
Faultposition
FaultFind