load shedding design for an industrial cogeneration system
TRANSCRIPT
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 1/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
35
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL
COGENERATION S YSTEM
Mukesh Kumar Kirar1
, Renuka Kamdar2
, Manoj Kumar3
, Ganga Agihotri4
1Department of Electrical Engineering, MANIT, Bhopal, India
[email protected], [email protected],
[email protected], [email protected]
A BSTRACT
This paper presents transient stability analysis and enhancement of Industrial Cogeneration Plant (ICP)
using Artificial Neural Network (ANN) based adaptive load shedding. By selecting the total in-plant
generation, spinning reserve, total plant load and rate of change of frequency as the input neurons of the
ANN, the minimum amount of load shedding is determined to maintain in-plant load-generation
equilibrium and to ensure continuity of power supply to critical loads of the plant. The comparison of under
frequency relay based load shedding and ANN based adaptive load shedding is also preformed to evaluate
effectiveness of the ANN based Load Shedding. The system frequency response for deferent generation-load scenarios is also determined. The industrial cogeneration is simulated on ETAP software and transient
stability is analyzed by considering various contingencies and load-generation scenarios. ANN has been
implemented on MATLAB.
K EYWORDS
Artificial Neural Network, Islanded System, Load Shedding, Electrical Transient Analyser Program
(ETAP), Frequency Stability
1. INTRODUCTION
Power supply to critical process loads is extremely important for an industrial cogeneration power
plant not only for continuous production but also important for overall plant safety during severedisturbances. A sudden interruption in production may result in significant economic loss and
raise safety concern. Most of the industrial customers with requirement of uninterrupted input of energy in the form of electric power and steam have installed cogeneration units. The
cogeneration systems are broadly defined as the coincident or simultaneous generation of the
combined heat and power (CHP) [1]. By installing cogeneration units industrial customer canachieve better efficiency of energy usage and enhance the reliability of electricity power supply
[2]. The cogeneration has to be tied together with the Public Power Company (PPC) to cover themismatch of load demand and power output by the cogeneration units in the plant and for the
consideration of power quality. The several techno-economic studies [3-5] are requiredperiodically throughout the operating life of the plant to ensure that a cogeneration plant will
operate safely, reliably, and economically.
To prevent total blackout and to stabilize the system under any abnormal condition, appropriateIslanding and Load Shedding (LS) strategies must be developed for industrial cogeneration
system. The load shedding technique primarily can be classified as conventional load sheddingtechnique and Adaptive or Intelligent load shedding technique. Conventional load shedding
schemes, breaker interlock load shedding [11], under-frequency relay (81) load Shedding [6, 7,
10, 11], programmable logic controller-based load shedding are most common and easy way toisolate the excess amount of load during generation deficit in the islanded power system. The
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 2/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
36
conventional schemes are designed to work on worst system operating conditions. These schemes
are not include, real-time system configuration, type and duration of the disturbances, as well asother important information and total loss of the system is an assumed possibility [14].
Conventional methods of system load shedding are too slow and do not effectively calculate the
correct amount of load to be shed.
Several schemes are reported in the literature [12-17] to overcome the shortcomings of theconventional load shedding schemes, by making it adaptive through complete understanding of
power system dynamics. In this paper ANN based load shedding method in comparison to under
frequency relay based load shedding is described. In order to illustrate the effectiveness of theproposed ANN based load shedding approach for the islanded ICP system, a large Oil Storage
Terminal and refinery distribution system is investigated as a case study. Section 2 introducessystem description and configuration of the ICP system. In Section 3, power studies are
conducted, the frequency response of the system is analyzed. Section 4 illustrates ANN basedload shedding, the 81-relay based and ANN based load shedding methods are compared in section
5 and concluded in section 6.
2. SYSTEM DESCRIPTION
In order to determine transient performance of a power system, the sub-transient model of thegenerators, IEEE standard model of exciter and governor control systems of the cogeneration unit
and static and dynamic model of loads have considered. The single line diagram (SLD) of ICPpower distribution system is shown in figure 1. The industrial cogeneration is simulated on ETAP
software.
Figure.1 Single line diagram for the OTS
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 3/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
37
To provide continuous power supply for critical loads and enhance overall efficiency of the plant,
ICP has installed two 10MW steam based cogeneration units STG-1 and STG-2. Both generatingunits in study are represented by detailed model with transient and subtransient circuits on both
the direct and quadrate axes. The power is generated at 11kV and step-down to 6.6kV by
generator transformers GT-301 and GT-302 and connected to Switchgear SG-301B. The block of the IEEE type 1 excitation model used for the both generators is as shown in figure 2. To achieve
the quick response of the cogeneration unit output to the external disturbance, the single reheatsteam governor-turbine system model as shown in figure 3 is used.
1
1 RsT + 1
A
A
K
sT +
1
E E K sT +
1
F
F
sK
sT +
( ) E fd S f E =
t V fd E +
+
ref V
maxVR
minVR
∑∑
Figure 2. Excitation system for SGT-1 and SGT-2
+
+
ref W
W 1 sr
K
sT +
P
1
1 chsT +
1
1 csT +
maxP
minP
mP1
1
hp
rh
F
sT
−
+
hpF
+
+
∑ ∑
∑
P Pe= I sochref P
Figure 3. Governor system for STG-1 AND STG-2
To improve system reliability and power quality, the ICP has Grid connectivity with public powercompany (PPC) at two points. PPC power is available at 66 kV voltage level through utility ties
UTG-1 and UTG-2. Two on load tap changer grid transformers TR-301 and TR-302 step downthe voltage from the 66 kV to the 6.6 kV level and connected to Switchgear SG-301A through
cable. The Switchgear SG-401A, SG-401B, Motor Control Center MCC-401, Power and MotorControl Center PMCC-402 are supplied through transformers TR-401, TR-402, TR-403 and TR-
404 of 6.6/0.44 kV respectively. The motors above 160kW rating are connected to switchgearSG-401A and SG-401B at 6.6kV voltage level. During islanded condition, due to a utility service
outage, in-plant generators will supply power to the plant load. The rated capacity of each
generator is 10 MW and the total load connected is approximate 28.5 MW.
3. SYSTEM FREQUENCY RESPONSE ANALYSIS
The dynamic performance of the system with respect to change in total generation and load canbe represented by swing equation [17]. The relationship that define variation of frequency withtotal generation and load mismatch can be obtain from swing equation,
ଶ
ଶ= (1)
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 4/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
38
Where,
G: nominal MVA of generatorH: inertia constant
δ: generator rotor angle
f 0: nominal frequencyPa : net accelerated or decelerated power (mismatch between generation and load)
Consider the generator speed variation due to a disturbance which is given by,
= + = 2
Where is the synchronous speed in rad/sec
Differentiating above equation with respect to time,
=ଶ
ଶ= 2 (2)
Substituting equation (2) in equation (1), we get
=
2(3)
Equation (3) defines the rate of change of frequency in Hz with, total power mismatch Pa, system
nominal frequency f 0, and inertia constant H. The equation (3) can be used for an individualgenerator as well as for an equivalent generation in the system. For equivalent case, the inertia
constant (H) can be derived from the following,
= ଵ ଵ+
ଶ ଶ+ ⋯ +
ଵ + ଶ + ⋯ +
Where n is the number of generators in a power system
The average rate of change of system frequency can be calculated by equation (4)
2 1
2
2
2
1
( )
1
f f df pL
dt H f
f
−=
−
(4)
Where
p = average power factor; H= inertia constant
L= total lost generation/ total available generationf 1 = nominal frequency; f 2 = minimum allowable frequency
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 5/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
39
To find the proper relay setting for tie line tripping during fault in utility system and load
shedding design to enhance system performance of an ICP power system during load generationmismatch, detail power system studies are required [20]. The computer simulations of load flow
analysis, short circuit analysis and stability analysis for all possible load-generation scenarios and
network configurations has been executed on ETAP software. The network configuration duringnormal operation is shown in figure 1. The load flow result for rated operating condition is shown
in Table 1.
Bus No. Bus
in kV
Voltage Magnitude
in %age
Voltage
Angle
Gene
(kW)
Gene
(kVAr)
Load
(kW)
Load
(kVAr)
SG-301A 6.6 98.53 -1.71 9868 3882 11066 4661
SG-301B 6.6 98.53 -1.71 18000 9432 10220 4241
SG-401A 0.415 101.1 -4.04 0 0 1243 732
SG-401B 0.415 101.1 -4.04 0 0 1290 892
MCC-401 0.415 98.4 -5.25 0 0 284 215
PMCC-
0.415 99.5 -5.32 0 0 3521 1778
Table 1. Load flow report
The system frequency response without load shedding, for different generation-load scenarios andcontingencies, as given in Table 2 is shown in figure 4. The contingencies considered for study
includes, three phase fault in utility system, loss of utility supply and loss of generators STG-1.
Bus frequency which starts falling after the tie CBs trip continuously along as the generator loaddeficit exists.
Scenarios Total Generation(MW)
Total Load(MW)
Mismatch(MW)
Average
Scenario-1 19 20.786 1.786 -0.39
Scenario-2 17 20.486 3.486 -0.76
Scenario-3 15 24.206 9.206 -2.01Scenario-4 12 24.626 12.626 -2.75
Table 2. Generation and load mismatch at the time of tie-line trip
Figure 4. System frequency response for different load generation scenarios
0 5 10 1550
60
70
80
90
100
110
Time(sec)
F r q u e n c y ( i n % a g e )
Scenario 1
Scenario 2Scenario 3
Scenario 4
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 6/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
40
4. ANN BASED ADAPTIVE LOAD SHEDDING
An artificial neural network (ANN) is a flexible mathematical model consists of aninterconnected group of artificial neurons which is used for modelling complex nonlinear
relationships between input and output data sets [19]. Commonly neural networks are trained, so
that a particular input leads to a specific target output. Once the ANN has been trained it can beused to classify unknown patterns.
Figure 5 depicts three layer feedforward neural each layer has a weight matrix W , a bias vector b,and an output vector a. Where the input signal p with R variables is expressed as [p1, p2, p3,
……pR]T
. Input-output data sets which are used to training, testing and validation of ANN are
{(p1, q1), (p2, q2), (p3, q3), ……(pR, qR)}. Where q is desired output with R variables is calculatedby system analysis.
1,11,1iw
1,1,S Riw
21b
22
S b
22b
33
S b
32b
31b
11n
2
2n
22
S n1
1
S n
1
2n
31n
21n
33
S n
32n
11a
3
3
S a
3
2a
22
S a
2
2a
31a
21a
11
S a
1
2a
2,11,1lw
2 1
2,1
,S S lw
3,21,1lw
3 2
3,2
,S S lw
( )11 1,1 1
IW p b f a = + ( )22 2,1 1 2 LW a b f a = + ( )33 3,2 2 3 LW a b f a = +
1 f
2 f
3 f
1
1
S b
12b
11b
1 f
1 f
2 f
2 f
3 f
3 f
1 p
1 R
p
3 p
2 p
( )( )( )3 3 3,2 2 2.1 1 1,1 1 2 3a f LW f LW f IW p b b b= + + +
Figure 5. Multi-Layer Feed Forward Neural Network
The Levenberg–Marquardt Back-Propagation (LMBP) algorithm is used for training of the ANN
model because of the low error and least epochs. To prepare the training data sets for ANN, thetransient stability analysis has been performed to solve the minimum load shedding for various
operating scenarios with the help of ETAP software.
The data is transmitted from the input layer, multiplied by their respective weights, to the hiddenlayers before reaching the final output layer. The error signals between the target and actual
output at the output layer neurons are then propagated back to the hidden and input layers. Thesum of square error is then minimized by adjusting the synaptic weights and bias in any layers
during the training process of ANN model. For a multi-layer network, the net input nk+1
(i) andoutput a
k+1(i) of neuron i in the k+1 layer can be expressed as:
1 1 1
1
( ) ( , ) ( ) ( )sk
k k k k
j
n i w i j y j b i+ + +
=
= +∑ (5)
1 1 1( ) ( ( ))k k k a i f n i+ + +
= (6)
By representing the sum of the output square error as the performance index for the ANN, theerror function is given by
1 1
1 1( ) ( ) ( )
2 2
R Rk k T T
r r r r r r r r
E e eq qa a= =
= − − =∑ ∑ (7)
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 7/12
Electrical and Electronics Engi
Wherek
r r r e q a= − is the outp
Marquardt algorithm is used to
The Simulation diagram of ANconstant block x1 which is the
process input block the removeThe remove constantrows procesConstant values do not providproblems for some algorithms.
Figure 6. Simu
Figure 7. Regressi
The mapminmax processes inp
range [-1 1]. The processed inpby the scalar weight w {1,1}, to
b {1} that is simply being added
The bias is much like a weight,TANSIG symmetric sigmoid t
layer's net input into its net outp
neering: An International Journal (ELELIJ) Vol 2, No 2,
t error andk
r a is the final output of the rth
input. Th
inimize the mean square error function in Eq. (7)
N in MATLAB is shown in figure 6. The inputprocessed and normalized by process input bloc
constantrows and mapminmax processes are beinses input and target data by removing rows with coe a network with any information and can cau
link block diagram of ANN load shedding scheme
on plot for 20 & 10 neurons in 1st & 2nd hidden layer
t and target data by mapping it from its original
t is transmitted through a connection that multipli
form the product wp, again a scalar. The neuron hato the product if input and weight (wp) at the sum
xcept that it has a constant input of 1. The sum is tansfer function. Transfer functions convert a ne
ut. The output of this first hidden layer is then treat
ay 2013
41
e Levenberg–
is fed to thek. Inside this
g performed.nstant values.se numerical
range to the
s its strength
a scalar biasing junction.
en fed to theural network
d as input to
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 8/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
42
the second hidden layer where the same repeats with the same TANSIG transfer function. The
output of the second hidden layer acts as the input to the output layer and is multiplied by weightw {3,2} added by bias b{3} and fed to purelin transfer function to get the output. This output is
then processed again to convert it back to the original form using mapminmax_reverse and
remove constantrows_reverse process. The output can be viewed in the scope y1.
PG (kW) PL (kW) PS (kW) df/dt PDLS (kW) PANN (kW) % Error
19000 27763 1000 -1.91 8097 8050 -0.16
18000 26822 2000 -2.14 6550 6588 0.13
18000 23378 2000 -1.3 2770 2862 0.32
18000 21016 2000 -0.73 710 722 0.04
17000 25455 3000 -1.84 6261 6228 -0.11
17000 23180 3000 -1.35 3532 3622 0.31
17000 19468 3000 -0.54 0 134 0.47
16000 26806 4000 -2.94 6660 6669 0.03
16000 22364 4000 -1.73 2320 2292 -0.09
16000 19096 4000 -0.84 0 8 0.0315000 25410 5000 -3.02 6620 6375 -0.86
15000 23322 5000 -2.42 4660 4620 -0.14
15000 19878 5000 -1.42 900 906 0.02
14000 21938 6000 -2.47 4150 4182 0.11
14000 20960 6000 -2.17 3170 3206 0.12
14000 17964 6000 -1.23 160 204 0.15
13000 21420 7000 -2.82 4620 4643 0.082
13000 18550 7000 -1.86 1600 1588 -0.04
13000 16584 7000 -1.2 0 25 0.08
12000 20012 8000 -2.91 4220 4212 -0.02
12000 19482 8000 -2.71 3600 3577 -0.08
12000 16926 8000 -1.79 960 865 -0.33
11000 18312 9000 -2.9 3510 3516 0.02
11000 16604 9000 -2.22 1640 1628 -0.04
11000 15772 9000 -1.89 770 803 0.11
10000 14936 10000 -2.15 960 925 -0.12
10000 14440 10000 -1.94 400 433 0.11
10000 13820 10000 -1.67 0 -120 -0.42
9000 14768 11000 -2.79 1915 1928 0.05
9000 14240 11000 -2.54 1290 1295 0.01
9000 12472 11000 -1.68 0 -20 -0.07
Table 3. ANN-based load shedding results
The number of neurons in input layer is equal to the number of inputs i.e. 4 while the output layer
has one neuron. The selection of number of neurons for the two hidden layer is made on hit andtrial method basis, comparing the regression plot of each and choosing the best among them. The
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 9/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
43
best performance is obtained with 20 neurons in 1st
hidden layer and 10 neurons in 2nd
hidden
layer. The regression plot is shown in figure 7.By selecting the total in-plant generation, total load, spinning reserve of generators and rate of
change of frequency as the input neurons of the ANN, the minimum amount of load shedding is
determined. The input signal p with four variables is expressed as [ , , ௦ , ⁄ ]் and one
output q as PDLS
.
The transient stability analysis for 121 load-generation scenarios have been carried out, with the
values of inputs PG, PS, PL, and df/dt varied between 9000–18000KW, 2000-10000KW, 19468-27868KW, and 0.54-3.02Hz/s respectively and ANN targets PDLS are determined. The 80% of the
total cases is selected for the ANN training, 10% for testing and 10% for validation. Thecorresponding load shedding amount as calculated by ANN with LMBP algorithm (PANN) for 31
load-generation scenarios and fault in utility system with tie-line trip is shown in Table 3.
4. COMPARISON OF LOAD SHEDDING METHODS
To demonstrate the effectiveness of the proposed methodology, system under study has beenmade to undergo a fault contingency and load shedding is performed by underfrequency relay and
ANN based adaptive load shedding method. The underfrequency relays settings for the first-stepload shedding will be activated simultaneously upon loss of the tie line. Underfrequency load
shedding design, number of steps, step frequency, and percentage load shedding amount for 81Lrelay is shown in Table 4.
Steps Threshold frequency %age LS Time Delay (sec)
Step-1 49.5 40 0.1
Step-2 48.5 30 0.1
Step-3 48 30 0.1
Table 4. Underfrequency relay setting for load shedding
Figure 8 depicts frequency response of islanded system with 15000KW generation and 25410KW
load, with underfrequency relay based load shedding and ANN based load shedding methods. Inthe case of underfrequency load shedding, at t=0.5 sec three phase fault is created in utility grid
which is cleared by opening tie-line Circuit Breaker (CB-1 and CB-2) at 0.6 sec. As the system
frequency reaches below 49.5 Hz at 1 sec, underfrequency relay is activated and first stage loadshedding is implemented at 1.1 sec.
Figure 8. System frequency with different load shedding methods
0 5 10 1 5 20 25 3097.5
98
98.5
99
99.5
100
100.5
101
101.5
Time(sec)
F r e q
u e n c y ( i n % a g e )
Relay Based UFLS
ANN Based UFLS
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 10/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
44
The system frequency still not recovered and it crosses 49 Hz (second step load shedding
threshold) and second step load shedding is implemented at 1.46 sec. After 2-step load sheddingsystem frequency is improved upto 49.5 Hz in 3.65 sec. It was found that the total amount of loadshed using underfrequency relay method is 11500 KW. For the same contingency in case of ANN
based adaptive load shedding, after the opening of tie-line Circuit Breaker (CB-1 and CB-2) at 0.6
sec the entire load shedding is performed at 0.74 sec with the calculation delay of 0.02 sec
included. The amount of load shedding is 6620 KW of load which is 4880 KW less than theconventional scheme. The system electrical power and mechanical power variations for both the
methods of load shedding is as shown in figure 9 and figure 10 respectively.
Figure 9. System electrical power with different load shedding methods
Figure 10. System mechanical power with different load shedding methods
5. CONCLUSION
In this paper an approach for improvement of frequency stability using ANN based adaptive
minimum load-shedding scheme is developed for industrial cogeneration system. By executing
the transient stability analysis for various operation scenarios of the ICP system, the training dataset of ANN model, which includes, total system power generation, spinning reserve, total load,
0 5 10 15 20 25 300
2
4
6
8
10
12
14
Time(sec)
E l e c t r i c a l P o w e r ( M W )
ANN Based UFLS
Relay Based UFLS
0 5 10 157
7.5
8
8.5
9
9.5
10
Time(sec)
M e c h a n i c a l P o w e r ( M W
)
ANN Based UFLS
Relay Based UFLS
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 11/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
45
and frequency decay rate as input, and the minimum amount of load shedding required as output,
has been prepared. To verify the effectiveness of the proposed ANN based load shedding ascompare to the present underfrequency relay based load-shedding, schemes are applied in the
simulation on ETAP software to investigate the dynamic response of system frequency. It is
concluded that the proposed ANN based methodology with two hidden layers and LMBPalgorithm can achieve more effective load shedding to maintain system stability as compare to
underfrequency based relay.
REFERENCES
[1] E. Joh McConnell, "Industrial Cogeneration - Insights and Observations," Industry Applications,
IEEE Transactions on , vol.IA-19, no.4, pp.614-618, July 1983
[2] A. Sheikhi, B. Mozafari, A.M.Ranjbar, “CHP Optimized Selection Methodology for a Multi-
Carrier Energy System” IEEE Trondheim PowerTech 2011
[3] Benny McHugh, Sreto Boljevic, F Michael, Conlon, “Feasibility Studies on Technical and
Economic Impact of Combined Heat and Power (CHP)” UPEC 2011 · 46th International
Universities' Power Engineering Conference · 5-8th September 2011 · Soest Germany
[4] Philip A Nobile "Power System Studies for Cogeneration: What's Really Needed?," Industry
Applications, IEEE Transactions on , vol.IA-23, no.5, pp.777-785, Sept. 1987
[5] Edward E Hogwood, David E Rice, "The Electrical Aspects of Cogeneration System Design,"
Industry Applications, IEEE Transactions on , vol.IA-23, no.4, pp.712-722, July 1987
[6] C. T Hsu, C. S. Chen, "Design of protective scheme for tie line tripping of an industrial power
system," Industry Applications Conference, 1999. Thirty-Fourth IAS Annual Meeting. Conference
Record of the 1999 IEEE , vol.3, no., pp.2058-2064 vol.3, 1999
[7] Chao-Shun Chen; Yu-Lung Ke; Cheng-Ting Hsu; , "Protective relay setting of the tie line tripping
and load shedding for the industrial power system," Industry Applications, IEEE Transactions on ,
vol.36, no.5, pp.1226-1234, Sep/Oct 2000
[8] Cheng-Ting Hsu; , "Cogeneration system design for a high-tech science-based industrial park,"
Industry Applications, IEEE Transactions on , vol.39, no.5, pp. 1486- 1492, Sept.-Oct. 2003
[9] C. S. Chen, Y D Lee, "Design of Under voltage Relay Setting for an Industrial Plant With
Cogeneration Units to Enhance Power Quality of Critical Loads," Industry Applications, IEEE
Transactions on , vol.44, no.4, pp.1295-1302, July-aug. 2008
[10] J. C. Das, “Transient stability of small plant generators connected to a weak utility system-a case
study”, Industry Applications, IEEE Transactions on , vol.41, no.1, pp. 155- 162, Jan.-Feb. 2005[11] Charles F. Dalziel, Edward W. Steinback, “Underfrequency Protection of Power Systems for
System Relief Load Shedding-System Splitting”, Power Apparatus and Systems, Part III.
Transactions of the American Institute of Electrical Engineers , vol.78, no.4, pp.1227-1237, Dec.
1959
[12] Chen Chao-Shun, Hsu Cheng-Ting, Lee Yih-Der, “Protective Relay Settings of Tie Line Tripping
and Load Shedding for an Integrated Steelmaking Cogeneration System”, Industry Applications,
IEEE Transactions on , vol.46, no.1, pp.38-45, Jan.-feb. 2010
[13] U.K. Jethwa, R.K Bansal, N. Date, R. Vaishnav, "Comprehensive Load-Shedding System,"
Industry Applications, IEEE Transactions on , vol.46, no.2, pp.740-749, March-april 2010
[14] F. Shokooh, J.J Dai, S Shokooh, J. Tastet, H. Castro, T. Khandelwal, G. Donner, "Intelligent Load
Shedding," Industry Applications Magazine, IEEE , vol.17, no.2, pp.44-53, March-April 2011
[15] W.-J Lee, J.-C. Gu, “A microcomputer-based intelligent load shedding relay”, Power Delivery,
IEEE Transactions on , vol.4, no.4, pp.2018-2024, Oct 1989
[16] Cheng-Ting Hsu, Hui-Jen Chuang,Chao-Shun Chen, “Adaptive load shedding for an industrialpetroleum cogeneration system” ScienceDirect Expert Systems with Applications 38 (2011)
13967–13974.
[17] IEEE Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE
Brown Book), IEEE Std 399-1997.
[18] M. S Pasand, H. Seyedi, New centralised adaptive load-shedding algorithms to mitigate power
system blackouts," IET Gener. Transm. Distrib., 2009, Vol. 3, No. 1, pp. 99–114.
7/28/2019 LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
http://slidepdf.com/reader/full/load-shedding-design-for-an-industrial-cogeneration-system 12/12
Electrical and Electronics Engineering: An International Journal (ELELIJ) Vol 2, No 2, May 2013
46
[19] Kuo-lin Hsu, Hoshin Vijai Gupta, Soroosh Sorooshian, “Artificial neural network modeling of the
rainfall-runoff process” Water Resources Research - WATER RESOUR RES , vol. 31, no. 10, pp.
2517-2530, 1995.
Authors
Mukesh Kumar Kirar was born in Narsinghpur, India, in 06 Feb 1983. He received the
B.E. (Electrical) degree from Government Engg. College, Ujjain, India in 2006 and
M.Tech. (Power System) in 2008 and pursuing Ph.D from MANIT Bhopal, India. He is
currently working as an assistant professor in the Department of Electrical Engineering,
MANIT, Bhopal, India. His field of interests are power system stability and control,
transformers and machines.
Renuka Kamdar was born in Bhopal, India in 1987. She has received BE degree (2009)
in Electrical and Electronics Engineering from Oriental Institute of Science and
Technology Bhopal and pursuing her M. Tech degree in Power System from MANIT
Bhopal.
Ganga Agnihotri was born in Sagar, India, in 27 May 1949. She received the B.E.
(Electrical) degree from MACT, Bhopal, India. She received the M.E. (Advance
Electrical Machine) and PhD (Power System Planning Operation and Control) from
University Of Roorkee, Roorkee in 1974 and 1989 respectively. She is currently
working as a professor in the Department of Electrical Engineering, MANIT, Bhopal,
India. She has 12 research papers in International journals, 20 research papers inNational journals, 22 research papers in International Conferences and 70 research
papers in National Conferences. Her fields of interest are Power System Planning,
Power Transmission Pricing, Power System Analysis and Deregulation. Dr. Agnihotri has a membership of
Fellow IE(I) and LISTE.