lm 79: il-tp-6060-36w-hpd-0-10v
DESCRIPTION
Independant LM79 test data for the 36W HPD-Series LED panel IL-TP-6060-36W-HPD-0-10vTRANSCRIPT
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
1 / 19
LM-79-08 Test Report
For
Illumis Lights PTE Ltd
(Brand Name: Illumis Lights)
133 New Bridge Road #09-06, Chinatown Point, Singapore, 059413
2x2 Luminaires for Ambient Lighting of Interior
Commercial Spaces
Model name(s): IL-TP-6060-36W-HPD-0-10v
Representative (Tested) Model: IL-TP-6060-36W-HPD-0-10v-3000KIL-TP-6060-36W-HPD-0-10v-4000KIL-TP-6060-36W-HPD-0-10v-5000K
Model Difference: All construction and rating are the same, except CCT.
Test & Report By: Review By:
Sean Zhuo Engineer: Sean Zhuo Manager: Tommy Liang
Date: Nov.13,2014
Note: This report does not imply product certification, approval, or endorsement by NVLAP, NIST, or
any agency of the Federal Government.
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
2 / 19
U.S. Department of Energy
Lighting FactsTM
Uniform LM-79 Reporting Template
Laboratory Information:
Name of Test Laboratory Standard-Tech Co. Ltd
Date of Test Report Nov.13,2014
Test Report No. GZN140948-A
Laboratory Contact Name Tommy Liang
Product Information:
Organization Name Illumis Lights PTE LtdBrand Name llumis Lights
Model Number IL-TP-6060-36W-HPD-0-10vSKU (if available) N/A
Type of Luminaire
(for integral lamps, list base type and lamp type)
2x2 Luminaires for Ambient Lighting of Interior
Commercial Spaces
Luminaire Aperture (for downlights) -- in.
Luminaire Length -- mm
Luminaires Width -- mm
Number of Units (modular products) N/A
Electrical Measurements:
Integrating Sphere
Output
Goniophotometer
Output
Input Wattage -- 34.42 W
Input Current -- 0.2893 A
Input Voltage (ac) -- 120.1 V
Power Factor -- 0.9906
Off-State Power -- 0 W
Photometric Characteristics
Total Initial Lumen Output -- 3147.4 lm
Initial Lumen Efficacy -- 91.45 lm/w
Correlated color temperature / CCT 2888 -- K
Color rendering index / CRI 81.7 --
R9 Value 12 --
Duv 0.0004 --
Luminous Intensity Distribution
Center beam candlepower (if applicable)
-----
1103 cd
Beam angle (if applicable) 112.1 °
Zonal lumens in the 0°-60° zone 78.4 %
Zonal lumens in the 60°-90° zone 21.5 %
Zonal lumens in the 90°-120° zone 0 %
Zonal lumens in the 120°-180° zone 0 %
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
3 / 19
U.S. Department of Energy
Lighting FactsTM
Uniform LM-79 Reporting Template
Laboratory Information:
Name of Test Laboratory Standard-Tech Co. Ltd
Date of Test Report Nov.13,2014
Test Report No. GZN140948-A
Laboratory Contact Name Tommy Liang
Product Information:
Organization Name Illumis Lights PTE LtdBrand Name llumis LightsModel Number IL-TP-6060-36W-HPD-0-10vSKU (if available) N/A
Type of Luminaire
(for integral lamps, list base type and lamp type)
2x2 Luminaires for Ambient Lighting of Interior
Commercial Spaces
Luminaire Aperture (for downlights) -- in.
Luminaire Length -- mm
Luminaires Width -- mm
Number of Units (modular products) N/A
Electrical Measurements:
Integrating Sphere
Output
Goniophotometer
Output
Input Wattage 34.86 -- W
Input Current 0.2925 -- A
Input Voltage (ac) 120.0 -- V
Power Factor 0.9931 --
Off-State Power 0 -- W
Photometric Characteristics
Total Initial Lumen Output 3599 -- lm
Initial Lumen Efficacy 103.25 -- lm/w
Correlated color temperature / CCT 4021 -- K
Color rendering index / CRI 82.5 --
R9 Value 7 --
Duv 0.0015 --
Luminous Intensity Distribution
Center beam candlepower (if applicable)
-----
-- cd
Beam angle (if applicable) -- °
Zonal lumens in the 0°-60° zone -- %
Zonal lumens in the 60°-90° zone -- %
Zonal lumens in the 90°-120° zone -- %
Zonal lumens in the 120°-180° zone -- %
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
4 / 19
U.S. Department of Energy
Lighting FactsTM
Uniform LM-79 Reporting Template
Laboratory Information:
Name of Test Laboratory Standard-Tech Co. Ltd
Date of Test Report Nov.13,2014
Test Report No. GZN140948-A
Laboratory Contact Name Tommy Liang
Product Information:
Organization Name Illumis Lights PTE LtdBrand Name llumis Lights
Model Number IL-TP-6060-36W-HPD-0-10vSKU (if available) N/A
Type of Luminaire
(for integral lamps, list base type and lamp type)
2x2 Luminaires for Ambient Lighting of Interior
Commercial Spaces
Luminaire Aperture (for downlights) -- in.
Luminaire Length -- mm
Luminaires Width -- mm
Number of Units (modular products) N/A
Electrical Measurements:
Integrating Sphere
Output
Goniophotometer
Output
Input Wattage 33.24 -- W
Input Current 0.2790 -- A
Input Voltage (ac) 120.0 -- V
Power Factor 0.9928 --
Off-State Power 0 -- W
Photometric Characteristics
Total Initial Lumen Output 3675 -- lm
Initial Lumen Efficacy 110.56 -- lm/w
Correlated color temperature / CCT 4820 -- K
Color rendering index / CRI 83.6 --
R9 Value 11 --
Duv 0.0037 --
Luminous Intensity Distribution
Center beam candlepower (if applicable)
-----
-- cd
Beam angle (if applicable) -- °
Zonal lumens in the 0°-60° zone -- %
Zonal lumens in the 60°-90° zone -- %
Zonal lumens in the 90°-120° zone -- %
Zonal lumens in the 120°-180° zone -- %
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
5 / 19
Test Specifications:
Date of Receipt : Nov.11,2014
Date of Test : Nov.12,2014
Test item : Total Luminous Flux, Luminous Distribution Intensity, Luminous Efficacy,
Correlated Color Temperature, Color Rendering Index, Chromaticity
Coordinate, Electrical parameters
Reference Standard IES LM-79-2008 Electrical and Photometric Measurements of Solid-State
Lighting Products
ANSI C78.377-2008 Specifications for the Chromaticity of Solid State
Lighting Products
CIE 13.3-1995 Method of Measuring and Specifying Colour Rendering
Properties of Light Sources
CIE 15-2004 Technical Report Colorimetry
IESNA LM-16-93 Practical Guide to Colorimetry of Light Source
IESNA TM-16-05 Technical Memorandum on Light Emitting Diode (LED)
Sources and Systems
Reference Work
Instruction
QD25
Test Methods
1. Photometric and Electrical measurements – Light Distribution Method:
Photometric parameters were measured using the goniophotometer and software. The ambient
temperature shall be maintained at 25° C ± 1° C, measured at a point not more than 1 m from the
sample and at the same height as the sample. The sample was operated at 120 Volts AC, 60Hz. It was
stabilized before measurement was made. Luminous flux, luminaire efficacy, zonal lumen were
calculated from the software taken at 1° vertical intervals and 22.5° horizontal intervals.
2. Photometric and Electrical Measurements – Integrating Sphere Method:
Photometric parameters were measured using an integrating sphere, a spectroradiometer and software.
The ambient temperature condition inside the sphere was maintained at 25º C ± 1º C. The sample
measurements were made using a spectroradiometer connected by a fiber optic cable and detector
through the detector port of the integrating sphere. The sample was operated at 120 Volts AC, 60Hz. It
was stabilized before measurement was made. Chromaticity coordinates, correlated color temperature
and color rendering index were calculated from the spectral radiant flux measurements taken at least 5
nm intervals over the range of 380 to 780 nm.
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
6 / 19
1. Product Information:
Brand Name llumis Lights
Model Number IL-TP-6060-36W-HPD-0-10vLuminaire Type 2x2 Luminaires for Ambient Lighting of Interior
Commercial Spaces
Rated Voltage / Frequency 100 ~ 277 Vac, 50/60 Hz
Nominal Power 36W
Rated Initial Lamp Lumen --
Declared CCT 3000K, 4000K, 5000K
LED Manufacturer ShenZhen JuFei Optoelectronics Co., Ltd.
LED Model 4014
Sample Receipt Date Nov.12,2014
Sample Number 140948-1(3000K),-2(4000K),-3(5000K)
Photo
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
7 / 19
2.1 Electrical, Photometric and Chromaticity Measurements
(Refer to Work Instruction QD25)
IES LM-79 2008
Test date 2014-11-12 Test Ambient: 25.0 º C
Test Orientation horizontal Stabilization Time (min) 90
Model Number IL-TP-6060-36W-HPD-0-10v-3000K
Electrical Measurement:
Sample No. Voltage (Vac) Frequency (Hz ) Current (A) Power (W) Power Factor THD %
140948-1 120.0 60 0.2893 34.42 0.9906 11.32
277.0 60 0.1372 35.08 0.9229 15.21
Sphere-Spectroradiometer Method:
Parameter Result Special Color Rendering Indices
Test Voltage (V) 120.0 R1 79 R9 12
Frequency (Hz) 60 R2 90 R10 76
Color Rendering Index (CRI) 81.7 R3 97 R11 75
R9 12 R4 78 R12 67
CCT (K) 2888 R5 79 R13 81
Chromaticity (x, y) x=0.4458 y=0.4081 R6 86 R14 99
Chromaticity (u’, v’) u'=0.2546 v'=0.5243 R7 84 R15 74
Duv 0.0004 R8 61 -- --
Goniophotometer Method:
Parameter Result
Test Voltage (V) 120.0
Frequency (Hz) 60
Total Luminous (lm) 3147.4
Luminous Efficacy (lm/W) 91.45
Beam Angle° 112.1
Center Beam Candle Power (cd) 1103
S/MH(C0/180) 1.26
S/MH(C90/270) 1.27
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
8 / 19
Spectral Power Distribution & Chromaticity Diagram
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
9 / 19
Zonal Lumen Tabulation
Zonal Lumen Summary
Zone Lumens % Lamp % Luminaire
0-30 854.1 27.1% 27.1%
0-40 1,397.4 44.4% 44.4%
0-60 2,468.9 78.4% 78.4%
60-90 677.6 21.5% 21.5%
70-100 287.7 9.1% 9.1%
90-120 0.0 0% 0%
0-90 3,146.5 100% 100%
90-180 0.6 0% 0%
0-180 3,147.1 100% 100%
Lumens Per Zone
Zone Lumens % Total Zone Lumens % Total
0-10 104.3 3.3% 90-100 0.0 0%
10-20 298.4 9.5% 100-110 0 0%
20-30 451.4 14.3% 110-120 0.0 0%
30-40 543.3 17.3% 120-130 0.0 0%
40-50 562.9 17.9% 130-140 0.1 0%
50-60 508.6 16.2% 140-150 0.1 0%
60-70 390.0 12.4% 150-160 0.2 0%
70-80 227.7 7.2% 160-170 0.1 0%
80-90 60.0 1.9% 170-180 0.1 0%
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
10 / 19
Photometric Data
Illuminance Plots
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
11 / 19
ISOCANDELA DIAGRAM
ISOLUX DIAGRAM
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
12 / 19
Candela Table - Type C
0 22.5 45 67.5 90 112.5 135 157.5 180 202.5 225 247.5 270 292.5 315 337.5 360
0 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103 1103
1 1102 1102 1102 1102 1103 1103 1103 1103 1103 1102 1103 1102 1102 1102 1102 1101 1102
2 1101 1101 1101 1102 1102 1103 1103 1103 1103 1102 1102 1101 1101 1101 1101 1100 1101
3 1099 1100 1100 1101 1102 1102 1102 1102 1102 1102 1101 1100 1100 1099 1099 1099 1099
4 1097 1098 1098 1099 1101 1101 1102 1101 1101 1101 1100 1099 1098 1097 1097 1097 1097
5 1095 1096 1096 1097 1099 1100 1100 1100 1100 1099 1098 1097 1095 1095 1094 1094 1095
6 1092 1093 1094 1095 1098 1098 1098 1099 1098 1097 1096 1095 1093 1092 1092 1092 1092
7 1089 1090 1091 1092 1095 1096 1097 1096 1096 1095 1093 1092 1090 1089 1089 1089 1089
8 1086 1087 1088 1089 1093 1094 1094 1094 1093 1092 1090 1089 1086 1085 1085 1085 1086
9 1082 1083 1084 1086 1090 1091 1091 1091 1091 1089 1087 1085 1083 1082 1081 1081 1082
10 1078 1079 1081 1082 1086 1087 1088 1088 1087 1086 1084 1082 1079 1077 1077 1076 1078
11 1073 1075 1076 1078 1082 1084 1084 1084 1084 1082 1080 1077 1074 1073 1072 1072 1073
12 1068 1070 1071 1073 1078 1079 1080 1080 1079 1078 1075 1072 1069 1068 1067 1067 1068
13 1063 1065 1066 1068 1074 1075 1076 1076 1075 1073 1070 1067 1063 1062 1061 1061 1063
14 1057 1059 1061 1062 1069 1070 1071 1071 1070 1068 1065 1062 1057 1056 1055 1055 1057
15 1051 1053 1055 1056 1063 1065 1066 1066 1065 1063 1059 1056 1051 1050 1049 1049 1051
16 1045 1047 1049 1050 1057 1059 1060 1060 1059 1057 1053 1049 1045 1043 1043 1043 1045
17 1038 1040 1042 1044 1051 1053 1054 1054 1053 1051 1047 1043 1038 1036 1035 1036 1038
18 1031 1033 1035 1037 1044 1046 1047 1048 1047 1044 1040 1036 1030 1029 1028 1029 1031
19 1023 1026 1028 1030 1037 1040 1041 1041 1040 1037 1033 1028 1023 1021 1020 1021 1023
20 1016 1018 1020 1022 1030 1032 1034 1034 1033 1030 1025 1021 1015 1013 1012 1013 1016
21 1007 1010 1012 1014 1022 1025 1026 1026 1026 1022 1018 1012 1006 1005 1004 1005 1007
22 999 1002 1004 1006 1014 1017 1018 1018 1018 1014 1009 1004 998 996 995 996 999
23 990 993 995 997 1006 1008 1010 1010 1009 1006 1001 995 989 987 986 987 990
24 981 984 986 988 997 999 1001 1001 1000 997 992 986 979 978 977 978 981
25 972 974 977 979 988 990 992 992 992 988 982 976 970 968 967 969 972
26 962 965 967 969 979 981 983 983 982 978 973 967 960 958 957 959 962
27 952 955 957 959 969 972 974 973 973 969 962 956 949 947 946 948 952
28 941 944 946 949 959 961 963 963 963 958 952 946 938 936 936 938 941
29 931 934 936 938 948 951 953 953 952 948 941 935 927 925 925 927 931
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
13 / 19
30 919 923 925 927 938 940 942 943 942 937 930 924 916 914 914 916 919
31 908 911 914 916 927 929 931 931 930 926 919 912 904 902 902 905 908
32 897 900 902 905 915 918 920 920 919 914 907 900 892 890 890 893 897
33 885 888 891 893 904 906 908 908 907 902 895 888 880 878 878 881 885
34 873 876 879 881 892 894 897 897 895 890 883 876 867 866 866 869 873
35 860 864 866 869 880 882 884 884 883 878 871 864 855 853 853 856 860
36 847 851 854 856 867 870 872 872 870 865 858 851 842 840 840 843 847
37 834 838 841 843 854 857 859 859 858 852 845 837 828 827 827 830 834
38 821 825 828 830 841 844 846 846 844 839 831 824 815 813 814 817 821
39 808 812 814 817 828 830 832 832 831 826 818 810 801 800 800 803 808
40 794 798 801 803 815 817 819 819 817 812 804 796 787 786 786 789 794
41 780 784 787 789 801 803 805 805 803 797 790 782 772 772 772 775 780
42 766 770 773 775 787 789 791 791 788 783 775 768 758 757 758 761 766
43 751 756 759 761 772 775 776 776 774 768 760 753 743 742 743 747 751
44 737 741 744 746 758 760 762 761 759 753 745 738 728 727 728 732 737
45 722 726 729 732 743 745 747 746 744 738 730 723 714 713 714 717 722
46 707 712 714 717 728 730 732 731 728 723 715 707 698 697 698 702 707
47 691 696 699 702 713 715 716 716 713 707 699 692 682 682 683 687 691
48 676 681 684 686 697 699 701 700 697 691 683 676 666 666 668 671 676
49 660 665 668 671 681 684 685 684 681 675 667 660 651 650 651 655 660
50 644 649 653 655 665 668 669 668 664 659 651 644 634 634 635 639 644
51 628 633 636 639 649 652 653 651 648 642 635 627 618 618 620 623 628
52 612 617 621 623 633 635 636 635 631 626 618 611 601 601 603 607 612
53 595 601 604 607 617 619 620 618 615 609 601 594 584 585 587 591 595
54 579 584 588 590 601 602 603 601 598 592 584 577 568 568 570 574 579
55 562 568 571 574 584 586 586 584 581 575 567 560 551 551 553 557 562
56 545 551 555 557 567 569 569 567 563 557 550 543 534 534 536 540 545
57 528 534 538 540 550 552 552 549 546 539 532 526 517 517 519 523 528
58 511 517 521 523 534 535 534 532 528 522 515 508 499 499 502 506 511
59 494 500 504 506 516 517 517 514 511 504 497 491 482 482 484 489 494
60 477 482 486 489 499 500 499 497 493 486 479 473 464 464 467 472 477
61 459 465 469 471 481 482 481 479 475 468 461 456 447 447 449 454 459
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
14 / 19
62 442 447 451 454 464 465 464 461 457 450 443 438 429 429 432 437 442
63 425 429 433 437 446 447 445 443 439 432 425 420 411 411 414 419 425
64 407 412 416 419 429 429 427 424 421 414 407 402 394 394 396 401 407
65 389 394 398 401 412 411 409 406 403 396 389 385 376 376 379 384 389
66 372 377 381 384 394 393 392 388 384 377 371 367 358 358 361 366 372
67 354 359 363 366 376 375 373 370 366 360 353 349 340 340 343 348 354
68 336 341 345 348 358 357 355 352 347 341 335 331 322 323 325 330 336
69 319 323 327 331 341 339 337 333 329 323 317 313 304 305 307 313 319
70 301 306 309 312 322 321 319 315 311 304 299 294 286 286 290 295 301
71 283 288 292 295 304 303 301 297 292 287 281 276 268 269 272 277 283
72 265 270 274 277 287 285 283 279 274 268 263 258 249 250 254 260 265
73 248 253 257 259 268 267 265 261 256 250 245 240 231 232 237 242 248
74 231 235 239 242 250 249 247 243 238 232 227 222 213 214 219 225 231
75 213 218 222 224 232 231 229 225 220 215 210 204 195 196 202 207 213
76 196 201 205 206 214 213 212 208 202 197 192 186 178 179 184 190 196
77 179 184 188 189 196 195 194 190 185 180 174 169 161 162 167 174 179
78 162 168 171 171 179 177 176 173 168 163 157 152 144 145 150 157 162
79 145 151 154 154 162 160 159 156 151 146 140 135 127 128 133 140 145
80 129 134 137 137 145 143 142 139 135 130 123 118 111 112 117 124 129
81 113 118 121 121 128 126 125 123 118 113 107 102 95 96 101 108 113
82 97 102 105 105 112 110 108 107 102 97 91 87 80 81 85 91 97
83 81 86 89 89 96 94 92 91 86 81 75 71 65 66 69 76 81
84 66 71 73 74 81 78 77 75 71 66 60 57 50 51 54 60 66
85 52 56 58 59 66 63 62 60 56 50 45 42 36 37 40 46 52
86 37 41 43 45 51 49 47 44 41 35 30 28 23 24 26 32 37
87 24 27 29 31 37 35 32 30 27 21 17 15 11 12 14 18 24
88 11 14 16 18 24 22 19 16 14 9 6 4 1 2 3 7 11
89 2 3 5 6 12 10 8 5 2 1 0 0 0 0 0 0 2
90 0 0 0 0 2 1 1 0 0 0 0 0 0 0 0 0 0
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
15 / 19
Test date 2014-11-12 Test Ambient: 25.0 º C
Test Orientation As Intended Stabilization Time (min) 90
Model Number IL-TP-6060-36W-HPD-0-10v-4000K
Electrical Measurement:
Sample No. Voltage (Vac) Frequency (Hz ) Current (A) Power (W) Power Factor THD %
140948-2 120.0 60 0.2925 34.86 0.9931 10.79
277.0 60 0.1374 35.13 0.9233 15.47
Sphere-Spectroradiometer Method:
Parameter Result Special Color Rendering Indices
Test Voltage (V) 120.0 R1 80 R9 7
Frequency (Hz) 60 R2 90 R10 75
Color Rendering Index (CRI) 82.5 R3 96 R11 78
R9 7 R4 80 R12 61
CCT (K) 4021 R5 80 R13 83
Chromaticity (x, y) x=0.3806 y=0.3802 R6 85 R14 98
Chromaticity (u’, v’) u'=0.2238 v'=0.5031 R7 86 R15 74
Duv 0.0015 R8 64 -- --
Total Luminous (lm) 3599
Luminous Efficacy (lm/W) 103.25
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
16 / 19
Spectral Power Distribution & Chromaticity Diagram
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
17 / 19
Test date 2014-11-12 Test Ambient: 25.0 º C
Test Orientation As Intended Stabilization Time (min) 90
Model Number IL-TP-6060-36W-HPD-0-10v-5000K
Electrical Measurement:
Sample No. Voltage (Vac) Frequency (Hz ) Current (A) Power (W) Power Factor THD %
140948-3 120.0 60 0.2791 33.24 0.9925 11.21
277.0 60 0.1326 33.96 0.9249 16.37
Sphere-Spectroradiometer Method:
Parameter Result Special Color Rendering Indices
Test Voltage (V) 120.0 R1 82 R9 11
Frequency (Hz) 60 R2 93 R10 81
Color Rendering Index (CRI) 83.6 R3 95 R11 78
R9 11 R4 78 R12 56
CCT (K) 4820 R5 81 R13 86
Chromaticity (x, y) x=0.3513 y=0.3640 R6 88 R14 98
Chromaticity (u’, v’) u'=0.2108 v'=0.4915 R7 85 R15 76
Duv 0.0037 R8 66 -- --
Total Luminous (lm) 3675
Luminous Efficacy (lm/W) 110.56
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
18 / 19
Spectral Power Distribution & Chromaticity Diagram
NVLAP LAB CODE 201011-0
Report No.:GZN140948-A
Laboratory: Standard-Tech Co. Ltd Testing Center
NVLAP CODE: 201011-0
Report Format Number STD/QR4909-A/2
Address:8th floor, Block B, No. 11 Caipin Road, Guangzhou Science City, Tianhe, Guangzhou 510663, China
Tel: 8620-3229 0320 Fax: 8620-32290422 http://www.standard-tech.com
19 / 19
3. Test Equipment
Equipment ID Equipment Name Last Calibration Date Next Calibration Date
ST-R-336 2 meter Integrating Sphere 2014-07-01 2015-06-30
ST-R-331 Spectral analysis system HAAS-2000 2014-07-01 2015-06-30
D204 Standard Lamp 2014-07-01 2015-06-30
PF2010 Power Meter for Integrating Sphere 2014-07-01 2015-06-30
EE-09 Goniophotometer system 2014-07-01 2015-06-30
D908S Standard Lamp 2014-07-01 2015-06-30
PF210 Power Meter for Goniophotometer 2014-07-01 2015-06-30
ST-R-181A Temperature Tester 2014-07-01 2015-06-30
****** END OF DATASHEET PACKAGE ******