2
Liquid Resistance Starter Complementing CSE-Uniserve’s complete liquid resistance starter product offering, the Unistarter SSE provides a cost effective starting solution for fixed speed and low power applications. Key Benefits Optimum control of motor current, torque and acceleration Smooth motor starting High reliability Low maintenance Stainless steel construction The CSE-Uniserve Advantage CSE-Uniserve proudly offers a range of services to ensure the successful application, installation, commissioning and maintenance of the Unistarter SSE to provide optimal performance and long term operation. Application Scope The Unistarter SSE is suitable for high torque starting applications that are found in a wide variety of industries such as metallurgy, mining, coal, cement plants, quarries, water treatment, and associated general industry. The Unistarter SSE is designed to provide controlled, smooth soft starting of heavy-load applications that use 3 phase slip ring motors with rated voltage up to & including 11kV, rated motor powers from 200kW up to 10,000kW. Reference Projects Omya Australia - NSW Ball mill application: Rating 600 kW Fixed speed Test and commissioning RASP Mine Project - NSW Ball mill application: Rating 900 kW Fixed speed Test and commissioning Testing & Commissioning Maintenance & Technical Support Customer Training

Upload: others

Post on 12-Oct-2019

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Liquid Resistance Starter - CSE-Uniserve · Liquid Resistance Starter Complementing CSE-Uniserve’s complete liquid resistance starter product offering, the Unistarter SSE provides

Liquid Resistance Starter

Complementing CSE-Uniserve’s complete liquid

resistance starter product offering, the Unistarter

SSE provides a cost effective starting solution for

fixed speed and low power applications.

Key Benefits

■■ Optimum control of motor current, torque and acceleration

■■ Smooth motor starting■■ High reliability■■ Low maintenance■■ Stainless steel construction

The CSE-Uniserve Advantage

CSE-Uniserve proudly offers a range of services to ensure the successful application, installation, commissioning and maintenance of the Unistarter SSE to provide optimal performance and long term operation.

Application Scope

The Unistarter SSE is suitable for high torque starting applications that are found in a wide variety of industries such as metallurgy, mining, coal, cement plants, quarries, water treatment, and associated general industry.

The Unistarter SSE is designed to provide controlled, smooth soft starting of heavy-load applications that use 3 phase slip ring motors with rated voltage up to & including 11kV, rated motor powers from 200kW up to 10,000kW.

Reference Projects

Omya Australia - NSW

Ball mill application:

■■ Rating 600 kW■■ Fixed speed■■ Test and commissioning

RASP Mine Project - NSW

Ball mill application:

■■ Rating 900 kW■■ Fixed speed■■ Test and commissioning

Testing &Commissioning

Maintenance &Technical Support

CustomerTraining

Page 2: Liquid Resistance Starter - CSE-Uniserve · Liquid Resistance Starter Complementing CSE-Uniserve’s complete liquid resistance starter product offering, the Unistarter SSE provides

UNISTARTER SSE - DIMENSIONS

UNISTARTER SSE - STANDARD SPECIFICATIONS

Initial starting current Ist = 1.3In

Starting time: (preset, or adjustable on site to suit load inertia or power supply restrictions)

10 to 60 seconds

Starting duty1 to 6 times per hour (Ambient temperature dependent)

Starter cubicle IP54 construction

Low voltage switch panels and controllersIEC60947-1:1999; IEC60694:1996IEC439-1:1992; IEC298:1990

Automatic liquid resistor starting, speed regulation and compensating controller

Q/FZR1-2003

Ambient temperature 0 to 40°C (others on request)

Relative air humidity < 90% (at temperature of 25°C)

Altitude above sea level < 2000m

Inclination of base < 5°

Width Depth

Hei

ght

Hei

ght

ModelMotor Power

Max.kW

External dimensions(mm) Weight (kg)

Height Width Depth Without Liquid With Liquid

ZYQ2 - 500 500 2000 1100 700 450 1017

ZYQ2 - 1000 1000 2000 1100 800 450 1017

ZYQ2 - 1500 1500 2100 1100 800 450 1017

ZYQ2 - 2000 2000 2300 1200 900 680 1443

ZYQ2 - 2500 2500 2300 1200 900 680 1443

ZYQ2 - 3000 3000 2450 1400 1100 850 2379

ZYQ2 - 3500 3500 2450 1400 1100 850 2379

ZYQ2 - 4000 4000 2800 1500 1200 940 2747

ZYQ2 - 5000 5000 2800 1500 1200 940 2747