1/2
LineTroll
3100D/TFault Passage Indicator for Overhead lines (6-132kV)
NORTROLL AS Postboks 133N-7601 Levanger - Norway
Phone: (+47) 7408 5500Fax: (+47) 7408 5501
Email: [email protected]:www.nortroll.com
DSL
T
3100July2004
LineTroll3100 Fault Indicator indicates earth- and
shortcircuit-faults by detection of changes in the mag-
netic field set up by the fault current. The indicator
can detect and independently indicate both permanent
and transient faults. A cluster of red LEDs for per-
manent fault and one green LED for transient fault.
An orange LED will give indication on low battery
status. High visibility,
Features LineTroll3100
Programmable operating parameters High visibility ( > 10 lumens)
Usable on all Medium Voltage distribution/
sub transmissionnetworks 6-132kV.
Two models, model LT 3100D for distribu-
tion 6-66kV and model LT 3100T for sub-
transmission 66-132kV.
Dual indications (permanent and transient
faults)
Display unity can rotate for maximum visi-
bility.
Built in log and fault counter.
Resistant to tough weather conditions Communication modules available.
Resistant to tough weather conditions
Battery capacity monitoring.
Functional Description
LineTroll3100 continuously monitors the line voltage and current, the sources of information it needs tooperate. The unit is fully self-contained, no external transformers or connections is required.
During normal line conditions, LineTroll3100 remains extinguished.
The indicator is looking for a specific sequence of line conditions to happen before it starts flashing. The
general sequence is as follows:
A. The line should be energised (voltage present) for a minimum of 5 seconds.
B. Di/Dt: The line current should increase rapidly by the amount of a user set value (the step level).
C. The line should be de-energised, (Circuit-breaker trip, voltage not present).
The user may program the criteria for operation to suit his local requirement by manipulating a bank of mi-
cro-switches inside the indicator.
LineTroll3100 can be equipped with a relay card, short-range radio or GSM communication module for
remote indication. Hardware relay interface or software protocol converter (IEC-870 or RP-570) availablefor integration to a SCADA system.
-
8/12/2019 Linetroll3100 Datasheet En
2/2
LineTroll
3100D/TFault Passage Indicator for Overhead lines (6-132kV)
NORTROLL AS Postboks 133N-7601 Levanger - Norway
Phone: (+47) 7408 5500Fax: (+47) 7408 5501
Email: [email protected]:www.nortroll.com
DSL
T
3100July2004
Technical Specifications
Ordering Information
About Nortroll AS Your Representative
Application: Short circuit and Earth fault indication for overhead lines.
System Voltage: MV voltage network (6-132kV)
Grounding system: Isolated, resistor and solidly grounded
Fault-detection: Sensitivity Di/Dt: 6, 12, 25, or 60*
Duration: >25ms*
Innrush-blocking: 5 sec
Reset: Automatic: Renergized line (Voltage), delay 30 sec
Timer: 2, 6, 12, or 32 hours
Manual: By internal magnet/Mounting-reset tool
Note *: All trip-levels, timers etc. are selectable and programmable by microswitches.
Indication: 1 Green LED for transient fault
4 Red LEDs for permanent fault
1 Orange Led for low battery indication
Intensity: > 10 lumens
Log, fault counter Built in log and fault counter with time tagging
Power supply: 1 Lithium Cell (D size 16,5 Ah)
External DC 10-24VDC (with relay card)
Battery change: Every 1200 hous flashing, normally every 7-8 years
Mounting: 3-5 meters below the conductorTemp: -40 to +70 deg
Housing: Polycarbonate, UV stablized
Dimension: 100 x 380x200mm
Weight: 1200g (including box and battery)
Degree of protection: IP54, IK09 & V-0 UL
Product nr: 3110 LineTroll3100D Product nr: 3115 LineTroll3100T
Product nr: 3120 LineTroll3100D w. relay card Product nr: 3125 LineTroll3100T w. relay card
Product nr: 3130 LineTroll3100D w. QLM Product nr: 3135 LineTroll3100T w. QLM
Product nr: 3140 LineTroll3100D w. GLM Product nr: 3145 LineTroll3100T w. GLMProduct nr: 3150 Relay card (for upgrade)
Since the foundation in 1976, Nortroll AS has de-
voted its activities to the development of equip-
ment aiming to reduce electric utilities outage
times. We offers a wide range of products for
fault detection and remote operation in the MV
Distribution Network.