LIGHTING PLANS 3:50:42 PM S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\KEYSLT01.DGN kpollard 9/27/2018 NO. SHEET L-1 EXPRESSWAY TURNPI KE 10 PENSACOLA FORT WALTON BEACH PANAMA CITY CHIPLEY TALLAHASSEE 75 10 295 95 JACKSONVILLE ST AUGUSTINE GAINESVILLE OCALA DAYTONA BEACH DELAND 4 NEW PORT RICHEY TAMPA 75 4 LAKELAND MELBOURNE - COCOA ORLANDO BARTOW ST PETERSBURG 275 SARASOTA - BRADENTON 75 95 FT PIERCE FT MYERS WEST PALM BEACH FT LAUDERDALE MIAMI 75 75 NAPLES KEY WEST CITY LAKE FL ORI DA' S BEACH LINE SHEET DESCRIPTION SHEET NO. ENGINEER OF RECORD: LIGHTING PLANS INDEX OF LIGHTING PLANS GOVERNING DESIGN STANDARDS: GOVERNING STANDARD SPECIFICATIONS: following website: http://www.fdot.gov/design/standardplans Standard Plans for Road Construction and associated IRs are available at the Bridge Construction and applicable Interim Revisions (IRs) Florida Department of Transportation, FY2018-19 Standard Plans for Road and http://www.fdot.gov/programmanagement/Implemented/SpecBooks for Road and Bridge Construction at the following website: Florida Department of Transportation, July 2018 Standard Specifications CONTRACT PLANS DEPARTMENT OF TRANSPORTATION PUBLIC WORKS ADMINISTRATION COUNTY COMMISSIONERS LEE COUNTY BOARD OF PLANS OF PROPOSED LITTLETON / KISMET REALIGNMENT COUNTY PROJECT NO. CN160459DLK VINCENT J. MILLER, P.E. LEE COUNTY PROJECT MANAGER: LOCATION OF PROJECT https://goo.gl/maps/tz7mkKWKJV42 IN PROGRESS 60% PLANS CERTIFICATE OF AUTHORIZATION No.: 5564 VENDOR No.: 25-1613591 CONTRACT No.: C-9E24 TAMPA, FL 33634-6323 9119 CORPORATE LAKE DRIVE, SUITE 150 GANNETT FLEMING P.E. No.: 63835 PHUC H. DUONG, P.E. KEY SHEET TABULATION OF QUANTITIES GENERAL NOTES POLE DATA AND LEGEND LIGHTING PLAN L-1 L-2 L-3 L-4 L-5 - L-7 L-8 L-9 POLE DETAIL SERVICE POINT/LOAD CENTER DETAIL THE OFFICIAL RECORD OF THIS SHEET IS THE ELECTRONIC FILE DIGITALLY SIGNED AND SEALED UNDER RULE 61G15-23.004, F.A.C.

Upload: others

Post on 19-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

LIGHTING PLANS

3:50:42 PM S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\KEYSLT01.DGNkpollard 9/27/2018

NO.

SHEET

L-1

EXPRESSWAY

TU

RNPIK

E

10

PENSACOLA FORT WALTON

BEACH

PANAMACITY

CHIPLEY

TALLAHASSEE

75

10

295

95

JACKSONVILLE

ST AUGUSTINE

GAINESVILLE

OCALA DAYTONA BEACH

DELAND4

NEW PORT RICHEY

TAMPA

754

LAKELAND

MELBOURNE -COCOA

ORLANDO

BARTOWST PETERSBURG

275

SARASOTA -

BRADENTON

75

95

FT PIERCE

FT MYERS

WEST PALM

BEACH

FT LAUDERDALE

MIAMI

75

75

NAPLES

KEY WEST

CITY

LAKE

FLO

RID

A'S

BEACH LINE

SHEET DESCRIPTIONSHEET NO.

ENGINEER OF RECORD:

LIGHTING PLANS

INDEX OF LIGHTING PLANS

GOVERNING DESIGN STANDARDS:

GOVERNING STANDARD SPECIFICATIONS:

following website: http://www.fdot.gov/design/standardplans

Standard Plans for Road Construction and associated IRs are available at the

Bridge Construction and applicable Interim Revisions (IRs)

Florida Department of Transportation, FY2018-19 Standard Plans for Road and

http://www.fdot.gov/programmanagement/Implemented/SpecBooks

for Road and Bridge Construction at the following website:

Florida Department of Transportation, July 2018 Standard Specifications

CONTRACT PLANS

DEPARTMENT OF TRANSPORTATION

PUBLIC WORKS ADMINISTRATION

COUNTY COMMISSIONERS

LEE COUNTY BOARD OF

PLANS OF PROPOSED

LITTLETON / KISMET REALIGNMENT

COUNTY PROJECT NO. CN160459DLK

VINCENT J. MILLER, P.E.

LEE COUNTY PROJECT MANAGER:

LOCATION OF PROJECT

https://goo.gl/maps/tz7mkKWKJV42

IN PROGRESS

60% PLANS

CERTIFICATE OF AUTHORIZATION No.: 5564

VENDOR No.: 25-1613591

CONTRACT No.: C-9E24

TAMPA, FL 33634-6323

9119 CORPORATE LAKE DRIVE, SUITE 150

GANNETT FLEMING

P.E. No.: 63835

PHUC H. DUONG, P.E.

KEY SHEET

TABULATION OF QUANTITIES

GENERAL NOTES

POLE DATA AND LEGEND

LIGHTING PLAN

L-1

L-2

L-3

L-4

L-5 - L-7

L-8

L-9 POLE DETAIL

SERVICE POINT/LOAD CENTER DETAIL

TH

E

OF

FI

CI

AL

RE

CO

RD

OF

THI

S

SH

EE

T I

S

TH

E

EL

EC

TR

ONI

C

FI

LE

DI

GI

TA

LL

Y

SI

GN

ED

AN

D

SE

AL

ED

UN

DE

R

RU

LE 61

G15-23.004,

F.

A.

C.

Page 2: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\TABQLT01.DGN3:50:46 PM

CN160459DLK LEE NA

ROAD NO. FINANCIAL PROJECT IDCOUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

TABULATION OF QUANTITIES

NO.

ITEM

PAY

DESCRIPTION UNIT

SHEET NUMBERS

SHEET

THIS

TOTAL

TOTAL

GRAND

L-5 L-6 L-7

PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL

630-2-11 CONDUIT, FURNISH & INSTALL, OPEN TRENCH LF

630-2-12 CONDUIT, FURNISH & INSTALL, DIRECTIONAL BORE LF

635-2-11 PULL & SPLICE BOX, F&I, 13" x 24" COVER SIZE EA

715-1-12 LIGHTING CONDUCTORS, F&I, INSULATED, NO.8 - 6 LF

715-1-13 LIGHTING CONDUCTORS, F&I, INSULATED, NO 4 - 2 LF

715-4-12 LIGHT POLE COMPLETE, FURNISH & INSTALL STANDARD POLE STANDARD FOUNDATION, 35' MOUNTING HEIGHT EA

715-5-31 LUMINAIRE & BRACKET ARM- ALUMINUM, FURNISH & INSTALL NEW LUMINAIRE AND ARM ON NEW/EXISTING POLE EA

715-7-11 LOAD CENTER, F&I, SECONDARY VOLTAGE EA

715-500-1 POLE CABLE DISTRIBUTION SYSTEM, CONVENTIONAL EA

TABULATION OF QUANTITIES

L-2

Page 3: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\GNNTLT01.DGN3:50:48 PM

CN160459DLK LEE NA

ROAD NO. FINANCIAL PROJECT IDCOUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

GENERAL NOTES

AND ASK FOR THE SIGNAL INSPECTION DEPARTMENT.

CONTRACTOR IS HEREBY DIRECTED TO CALL LEE COUNTY SIGNALS AT 239-533-9500

PLAN SET GENERAL NOTES. SHOULD THE INFORMATION BE MISSING, THE

7) TWENTY-FOUR (24) HOUR NOTICE IS REQUIRED TO THE INSPECTOR SHOWN IN THE

5650 ENTERPRISE PARKWAY, FORT MYERS, FL 33905.

WITHHOLD PAYMENT REQUESTS UNTIL LEE COUNTY PROPERTY IS DELIVERED TO

IS IN COMPLIANCE WITH THIS REQUIREMENT. LEE COUNTY SIGNALS WILL

PARAGRAPH WILL RESULT IN NO INSPECTION AT COMPLETION UNTIL CONTRACTOR

REGULAR BUSINESS DAY AND HOURS. FAILURE TO PERFORM AS OUTLINED IN THIS

THE DELIVERY OF THE EQUIPMENT SO THAT DELIVERY TAKES PLACE DURING A

NOTIFY LEE COUNTY OF THE DISCONNECTION 24 HOURS IN ADVANCE TO SCHEDULE

NO LATER THAN 72 HOURS AFTER DISCONNECTION. THE CONTRACTOR SHALL

IN A TIMELY MANNER. TIMELY MANNER FOR EXISTING EQUIPMENT IS DEFINED AS

MAINTENANCE TRANSFER AT 5650 ENTERPRISE PARKWAY, FORT MYERS, FL 33905

GOOD OPERATING CONDITION AND IN THE SAME CONDITION AS ON THE DAY OF THE

6) EXISTING EQUIPMENT: SHALL BE RETURNED TO LEE COUNTY DOT/TRAFFIC IN

REPAIRS ARE MADE BY LEE COUNTY OR A THIRD PARTY.

CONTRACTOR WILL BE RESPONSIBLE FOR ALL REPAIR COSTS INCURRED, WHETHER

QUALIFIED FIBER OPTIC SPLICING COMPANY WILL BE USED TO MAKE REPAIRS.

SHOULD DAMAGE OCCUR TO FIBER OPTIC LINES, LEE COUNTY WILL DECIDE WHICH

LEE COUNTY FIBER OPTIC LINES, SINCE MANY ENTITIES USE THESE FACILITIES.

ALLOWED. CAUTION SHALL BE EXERCISED DURING EXCAVATION NEAR EXISTING

OF NEW CABLE. SPLICING OF COMMUNICATION LINES WILL NOT BE

LINES SHALL NECESSITATE THE REMOVAL OF ALL DAMAGED LINES AND THE REPULLING

FACILITIES ARE LIKE NEW OR BETTER. ANY DAMAGE TO EXISTING COMMUNICATION

BE REPAIRED BY THE CONTRACTOR. REPAIRS SHALL BE MADE TO ENSURE

5) DAMAGE TO EXISTING FACILITIES: ANY DAMAGE TO LEE COUNTY FACILITIES SHALL

“OUT OF TOWN” CONTRACTOR DOES NOT RELIEVE THIS RESPONSIBILITY.NOTICE TO BE FILED WITH LEE COUNTY CONTRACTS AS WELL AS FDOT. BEING AN

PAYMENT REQUEST AND WILL TRIGGER A “VENDOR/CONTRACTOR COMPLAINT”CONTRACTOR WILL BE BILLED THE ENTIRE COST AS A “DEDUCT” ON THE NEXTDUE TO CONTRACTOR REFUSAL OR INABILITY TO MAKE REPAIRS, THE

CONTRACTOR. SHOULD LEE COUNTY FORCES BE CALLED OUT TO MAKE REPAIRS

DUE TO CONTRACTOR FAILURE TO LOCATE SHALL BE REPAIRED BY THE

SUNSHINE LOCATE REQUESTS WITHIN THE WORK ZONE. ANY DAMAGE INCURRED

LEE COUNTY SIGNALS WILL ADVISE THE CONTRACTOR VIA E-MAIL OR FAX OF

(24) HOURS AFTER NOTIFICATION OR AS REQUIRED BY FLORIDA STATUTE.

LOCATES IS DEFINED AS LOCATE SHALL BE PERFORMED NO LATER THAN TWENTYFOUR

SHALL BE PERFORMED IN A TIMELY MANNER. TIMELY MANNER IN RESPONSE TO

WITHIN THE PROJECT LIMITS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND

AND ABOVE GROUND FACILITIES. AFTER THE COURTESY LOCATE, ALL LOCATES

CONTRACTOR SHALL DOCUMENT THE LOCATION OF THE EXISTING UNDERGROUND

SIGNALS AT THE START OF THE PROJECT AT THE CONTRACTOR’S REQUEST. THE4) LOCATES: ONE (1) COURTESY LOCATE SHALL BE PERFORMED BY LEE COUNTY

TOWN” CONTRACTOR DOES NOT RELIEVE THIS RESPONSIBILITY.ENTIRE COST AS A “DEDUCT” ON THE NEXT PAYMENT REQUEST. BEING AN “OUT OFFORCES ARE CALLED OUT TO RESPOND, THE CONTRACTOR WILL BE BILLED THE

THAN TWO (2) HOURS AFTER NOTIFICATION. IN THE EVENT THAT LEE COUNTY

MAINTENANCE RESPONSIBILITIES IS DEFINED AS RESPONSE TO SITE NO LATER

TO LEE COUNTY CONTRACTS AS WELL AS FDOT. TIMELY MANNER IN RESPONSE TO

A TIMELY MANNER WILL TRIGGER A “VENDOR/CONTRACTOR COMPLAINT” NOTICETIME OF TRANSFER. FAILURE TO RESPOND TO MAINTENANCE RESPONSIBILITIES IN

HOUR CONTACT PERSON(S), TELEPHONE NUMBERS AND E-MAIL ADDRESSES AT THE

3) CONTRACTOR MAINTENANCE RESPONSIBILITIES: CONTRACTOR SHALL PROVIDE 24-

RESPONSIBILITY OF THE CONTRACTOR.

AND ALL DEFICIENCIES FOUND FROM THAT DAY AND TIME SHALL BE THE

ANY DEFICIENCIES HAVE BEEN CORRECTED ON THE DAY OF THE TRANSFER, ANY

TRANSFER SHALL BE REPAIRED BY LEE COUNTY TRAFFIC AT THAT TIME. AFTER

2) ANY DEFICIENCIES THAT MAY BE FOUND ON THE DAY OF THE MAINTENANCE

CONDITION OF THE STREET LIGHTING SYSTEM.

ONSITE TO ACCEPT THE MAINTENANCE TRANSFER AND TO WITNESS THE EXISTING

BEGINS. THE CONTRACTOR IS REQUIRED TO HAVE AN AUTHORIZED REPRESENTATIVE

QUALIFIED ELECTRICAL CONTRACTOR NO LATER THAN THE DAY BEFORE THE PROJECT

THE MAINTENANCE WILL TRANSFER FROM LEE COUNTY DOT/TRAFFIC TO AN FDOT

1) BEFORE ANY PROJECT WORK BEGINS THERE SHALL BE A MAINTENANCE TRANSFER.

GENERAL NOTES

L-3

Page 4: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/28/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\PLDTLT01.DGN12:12:06 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

AND LEGEND

POLE DATA

Distribution point. For requirements see Index No. 17504 of Design Standards.

DESCRIPTIONSYMBOLS

LEGEND

LIGHTING DESIGN CRITERIA

CONVENTIONAL

for ___ volt operation. Pole mounting height __ ft. Use curve ____ or equal.

Single arm conventional LED luminaire. Designed for Type distribution. Luminaire wired

inside conduit with other conductors.

size as shown on plan sheets). Run one (1) 6 AWG copper bond conductor (TW green insulation)

Schedule 40 PVC conduit with THW or THWN conductors inside (conduit and conductor

size as shown on plan sheets).

Galvanized metal conduit with THW or THWN conductors inside (conduit and conductor

Bridge Construction.

Pull box. For specifications see Section 635 of Standard Specifications For Road And

NO.POLE

CIRCUIT STATIONOR ARM

DIST.WATTAGE

LUMINAIREHEIGHT

MOUNTINGPOLE SETBACK PAY ITEM OPTION

1 149 30'9+81.58 NEW

10+40.70

10+66.17

NEW1 22+01.53

22+77.69

4-EXT

A-1

A-1

A-1

UNK

A-2

A-2

RETRO

for ___ volt operation. Pole mounting height __ ft. Use curve ____ or equal.

Single arm conventional LED luminaire. Designed for Type distribution. Luminaire wired

L-4

4:1 Or LessUniformity Ratio Avg./Min.

Max./Min. 10:1 Or Less

170 MPHWind Speed

Average Initial Horizontal Intensity

Average Initial Vertical Intensity

3.0 Foot Candles

2.3 Foot Candles

POLE DATA

2

3

NEW

NEW

NEW

715-4-12

715-5-31

715-4-12

715-4-12

715-4-12

715-4-12

30'

30'

TBD

30'

30'2

3

4

5

6

7

8

9

149

149

149

177

177

A-2 24+20.41 177 30' 715-4-12 NEW

A-2 25+09.56 177 30' 715-4-12 NEW

A-2 24+74.87 177 30' 715-4-12 NEW

A-2 23+19.34 177 30' 715-4-12 NEW

A-2 23+93.48 177 30' 715-4-12 NEW

A-2 23+00.34 177 30' 715-4-12 NEW

A-2 22+17.28 177 30' 715-4-12 NEW

NANA

4' FROM EOP

17' FROM EOP

10' FROM EOP

16' FROM EOP

18' FROM EOP

24' FROM EOP

24' FROM EOP

18' FROM EOP

18' FROM EOP

10' FROM EOP

20' FROM EOP

19' FROM EOP

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

8.0'

Page 5: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\PLANLT01.DGN3:51:48 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

WATER

WATER

WATER

SAN

SAN

SAN

POT STA. 100+00.00100

101

102

103

104

PC STA. 11+55.30

POT STA. 200+00.00

200 201 202 203

R/W LINE

R/W LINE

R/W LINE

R/W LINE

KISMET PKWY E

OLD LITTLETON RD

LITTLETON RD

NE 24T

H

AV

E

NE 24T

H

AV

E

R/W LINE

R/W LINE

R/W LINE

R/W LINE

CKT A-1-1STA. 9+81.58

CKT A-1-2STA. 10+40.70

CKT A-1-4STA. 10+66.17

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

CONCRETE LIGHT POLERETROFIT EXISTING

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

MA

TC

H LIN

E

A,

SE

E S

HE

ET ?

L-5

LIGHTING PLAN

50

Feet

0 10

N

Page 6: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\PLANLT02.DGN3:51:56 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

PI STA. 13+65.00

PI STA. 18+84.91

204 205 206 207 208 209 210

OLD LITTLETON RD

LITTLETON RD

R/W LINE

R/W LINE

R/W LINE

R/W LINE

R/W LINE

R/W LINE

LOAD CENTERSTA. 205+22.78

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

POINT

SERIVCE

EXISTING

50

Feet

0 10

N

MA

TC

H LIN

E B,

SE

E S

HE

ET ?

MA

TC

H LIN

E

A,

SE

E S

HE

ET ?

LIGHTING PLAN

L-6

Page 7: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\PLANLT03.DGN3:51:57 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

PI STA. 23+52.03

PT S

TA.

27

+31.5

0

PI S

TA.

26

+18.9

9

PRC STA. 21+91.94

PRC STA. 24+99.77

303

PT

STA. 3

03+91.17

PI STA.

302+

36.67

304

POT STA. 304+80.00

211 212 PO

T S

TA.

212

+79.4

6

OLD LITTLETON RD

LITTLETON RD

CO

RB

ET

T

RD

LITTLETON RD

R/W LINE

R/W LINE

R/W LINE

R/W LINE

R/W LINE

R/W LINE

R/W LINE

CKT A-2-1STA. 22+01.53

CKT A-2-9STA. 22+17.28

CKT A-2-2STA. 22+77.69

CKT A-2-8STA. 23+00.34

CKT A-2-6STA. 23+19.34

CKT A-2-3STA. 24+20.41

CKT A-2-5STA. 24+74.87

CKT A-2-4STA. 25+09.56

IN 2" CONDUIT

2 #4 & 1 #6 GRDIN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

CKT A-2-7STA. 23+93.48

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

IN 2" CONDUIT

2 #4 & 1 #6 GRD

MA

TC

H LIN

E B,

SE

E S

HE

ET ?

50

Feet

0 10

N

LIGHTING PLAN

L-7

Page 8: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\SRPTLT01.DGN3:52:00 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

#6 AWG INSULATED COPPER GROUND WIRE

(FOR NUMBER OF BRANCH CKT'S REFER TO PLAN)

STONE FOR DRAINAGE.

8'-0"

F.P.L. TRANSFORMER

F.P.L. POLE

SERVICE POINT DETAIL

6'-0"

EXOTHERMICAL THERMOWELD CONNECTION

2#2

IN 3 4" RIGID GALVANIZED STEEL CONDUIT./

F.P.L.

IN 2" PVC CONDUIT.

CABLE & PVC U-GUARD

AND BOOT BY F.P.L.

PULL BOX (27-1/2" X 18" X 12")

COVER MARKED "ELECTRIC"

CONCRETE

DPX CONNECTION

BY F.P.L.

N H

CIR

CUIT #1

CIR

CUIT #2

SERVICE

480V TO GROUND

PULL BOX (MARKED STREET LIGHTING)

N.T.S

WIRING DIAGRAM

LIGHTNING PROTECTOR

PULL BOX (27-1/2" X 18" X 12") COVER

MARKED "STREET LIGHTING"

BRANCH CKT'S IN 2" RIGID GALVANIZED STEEL COND.

BRANCH CKT'S AND 1#6 GRD.

IN 2" PVC CONDUIT TO LIGHT POLE

/ 5 8" DIA. X 20' GRD. ROD

CONDUIT CLAMP (TYP.)

LIGHTNING PROTECTOR

6" MIN. COND. STUPUP

DISTRIBUTION LINE

CONCRETE POLE PRESTRESS

TRANSITION FITTING FROM RIGID STEEL

TO PVC AFTER 90 RIGID STEEL ELBOW

CONCRETE

TERMINATE RIGID STEEL CONDUIT

AT PULL BOX

2#2 IN 2" RIGID GALVANIZED STEEL COND.

NOTES:

4. ALL SERVICE EQUIPMENT SHALL BE U.L. APPROVED.

1. THE ENCLOSURE SHALL BE NEMA 4X (STAINLESS STEEL), POLE MOUNTED, RIGIDLY ATTACHED TO THE POLE FACE.

100 AMPS,480V 3 POLE AND S/N

HEAVY DUTY SAFETY SWITCH

SERVICE LOAD CENTER

SERVICE ENTRANCE PANEL

5 8" DIA. X 20' GRD. ROD/

3. A 600V LIGHTNING PROTECTOR SHALL BE WIRED INSIDE THE ENCLOSURE. NO SPLICING IN ENCLOSURE.

5. CONTRACTOR SHALL COORDINATE WITH F.P.L. ENGINEERS FOR THE INSTALLATION OF THE F.P.L. RISER

6. ALL GROUND ROD SHALL BE INTERCONNECTED (USING #6 GROUND WIRE).

7. PROVIDE SUPPLEMENTARY GROUND ELECTRODE SPACE AT LEAST 6FT.

THIS LAYOUT HAVE BEEN APPROVED BY THE MAINTENANCE AGENCY (MIAMI-DADE COUNTY).

NOTE TO DESIGNER: TO BE USED FOR 2 CIRCUITS ONLY.*

COPPER GROUND BUS

(SEE NOTE 8 TYP.)

N.T.S

30" MIN.

TYPE P-II, 16'-0" LONG (SEE NOTE 9)

COPPER NEUTRAL BUS

EXIST. BARE WIRE #6 INHERENT TO THE POLE

BE CONNECTED TO THE GROUND ROD

AT BOTTOM THE GRD. (PIG TAIL) TO

AT TOP OF POLE THE GROUNDING PIG TAIL MUST BE DETACHED

6'-0"

RATED FOR SERVICE ENTRANCE

WITH CONTACTOR AND PHOTOCELL NIGHT

MASTER AS MANUFACTURED BY SQUARE D.

H O A KEY

OPERATED SWITCH

TERMINATE CONDUIT WITH INSULATED GROUNDING

BUSHING WITH SOLDERLESS LUGS

IN NEMA 4X ENCLOSURE W/40 AMP FUSE

PHOTOCELL RATED FOR 480V

LIGHTING CONTACTOR

AND INSTALLED BY THE MANUFACTURER

PHOTOCELL SHALL BE PROVIDED, WIRED

100 AMP, 480V 3 POLE S/N

COMBINATION LIGHTING CONTACTOR AND DISCONNECT

SWITCH RATED FOR SERVICE ENTRANCE IN NEMA

480V, 1 PHASE 2W

4 POLES RATED

FOR 480V AND 100 AMPS

1#6 GRD. IN 3/4" PVC CONDUIT

MANUFACTURED BY

4X ENCLOSURE, LABEL MUST BE FACTORY INSTALL

PHOTOCELL RATED FOR 480V

OR SIEMENS INDUSTRY INC. OR APPROVED EQUAL

SQUARE-D (SHORT VERSION)

SP

AR

E

1'' BED OF CRUSHED

OR SIEMENS INDUSTRY INC. OR APPROVED

EQUAL.

40 AMPS FUSE (TYPE RK5)

THIS LAYOUT HAVE BEEN APPROVED BY THE MAINTENANCE AGENCY (MIAMI-DADE COUNTY AND F.D.O.T. DISTRICT SIX)

11. LIGHTNING PROTECTOR TO BE WIRED ON LOAD SIDE OF DISCONNECT SWITCH.

2. THE ENCLOSURE DOOR SHALL BE SECURED BY LOCKABLE LATCH.

3" WARNING TAPE

12"

8. ALL CONDUCTOR SHALL BE TYPE THWN-2. (OTHER TYPE OF CONDUCTOR IS NOT ALLOWED. EXCEPT

GROUND WIRE WHICH SHALL BE TYPE THWN.)

WHICH INCLUDES A CONNECTION FEE OF $148.00. (THIS FEE SHALL BE INCLUDED IN BID ITEM 715-7-11)

WHICH INCLUDES A CONNECTION FEE OF 148.00 DOLLARS. (THIS FEE SHALL BE INCLUDED IN BID ITEM 715-7-11)

L-8 LOAD CENTER DETAIL

SERVICE POINT/

9. CONTRACTOR SHALL SUBMIT STRUCTURAL CALCULATIONS OF THE POLE, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER.

10. CONTRACTOR SHALL COORDINATE WITH F.P.L. ENGINEERS FOR THE INSTALLATION OF THE F.P.L. RISER

Page 9: LIGHTING PLANS - Lee County Southwest Florida file... · lighting plans kpollard 9/27/2018 3:50:42 pm s:\cf_tops\06xxxx - aim-leeco littleton-kismet\project working\plans\lighting\keyslt01.dgn

9/27/2018kpollard S:\CF_TOPS\06xxxx - AIM-LeeCo Littleton-Kismet\Project Working\Plans\lighting\CNPLLT01.DGN3:52:12 PM

CN160459DLK LEE NA

ROAD NO. COUNTY

DATE DESCRIPTION

REVISIONS

DATE DESCRIPTIONNO.

SHEETSTATE OF FLORIDA

DEPARTMENT OF TRANSPORTATION

COUNTY PROJECT NO

CERTIFICATE OF AUTHORIZATION No. 5564

TAMPA, FLORIDA 33634

9119 CORPORATE LAKE DR., SUITE 150

GANNETT FLEMING

P.E. NO.: 63835

PHUC H. DUONG, P.E.

LUMINAIRE DETAIL

L-9

CLAMPS

EXTRUDED ARM

ALUMINUM POLE

TAPERED

BE NO MORE THAN 5 FEET)

TRUSS ARM (RISE ARM SHALL

BASE

TRANSFORMER

OR OPPOSITE DOOR WALL

INTERNAL GROUND LUG

IN 2" COND.

POWER CABLE

AND WASHERS

BOLTS WITH NUTS

GALV. STEEL ANCHOR

IN 1/2" CONDUIT

1-#6 GRD. WIRE

P.V.C. COUPLER

MOLDED PLUG AND CONNECTOR (RED)

THERMOWELD (EXOTHERMIC CONNECTION)

27 1/2" x 18" x 12" PULL BOX

5/8" DIA. 10" LONG GRD. ROD

SURGE ARRESTOR

WITH 10 AMP. FNQ TYPE FUSE

DISTRIBUTION BLOCK (RED)

CONCRETE SIDEWALK

CONNECTOR (ORANGE)

MOLDED PLUG AND

POWER CABLE

14/3 CONDUCTOR

CABLE SOWA

LUMINAIRE

GROUND LUG

INTERNAL

CABLE STRAIN RELIEF

GROUND WIRE

STONE FOR DRAINAGE

12" BED OF PEAROCK OR CRUSHED

DANGER

HIGH VOLTAGEDO NOT TAMPER

DANGER

HIGH VOLTAGEDO NOT TAMPER

MIN.

6"

POLE DETAIL

SEE INDEX 17500

FOR ADDITIONAL DETAILS

N.T.S.

8' BRACKET ARM

30'

OR 35'