LIGHTING CONSTRUCTION MANUAL
CONSTRUCTION PRACTICES
Go to SECTION INDEX Back to MAIN INDEX
1-3-1-1
1 3 1-1 0E
LIGHTING
10500-A4-1-3-1-1
1-3-2-1
DESCRIPTIONTYPE PAGE TYPE DESCRIPTION PAGE
CONSTRUCTION PRACTICES INDEX
Construction Type Guide Service Cable
Luminaire Glare Shield Minor Road Decorative
Luminaire Glare Shield Major & Minor Road
Luminaire Stone Guard Minor Road
Attach Site ID Label to Steel or Concrete Pole (Maj/Min Rd)
Attach Site ID Label to Estate Pole (Minor Rd)
Attach Rate 3 Site ID Label to Pole
Stabilised Backfill
Termination of 16mm2
& 4mm2
N/S cable Install Instructions
Pedestrian Crossing Floodlight Aiming Details
Pedestrian Crossing Floodlight Aiming Details
Typical Physical Arrangement of Supply Pit to Pole
Access for Const & Maint Vehicles on Roundabout
Energex Pole Labelling
Energex Pole Labelling
Energex Pole Labelling
High Mast Pole Headframe Details 1 & 2 Way Outreach
High Mast Pole Headframe Details 3 & 4 Way Outreach
Clearance between Lighting Structure & Overhead Line
Dynamic Clearance of SBM Pole From and Overhead Line
Major Road Mid Hinged BPM Pole Installation Details
Major Road Mid Hinged BPM Pole Operation Details
Major & Minor Roads Typical Cross Section Conduits
1-3-3-1
1-3-4-1
1-3-5-1
1-3-6-1
1-3-6-2
1-3-6-3
1-3-7-1
1-3-8-1
1-3-9-1
1-3-9-2
1-3-10-1
1-3-11-1
1-3-11-2
1-3-12-1
1-3-12-2
1-3-12-3
1-3-13-1
1-3-13-2
1-3-14-1
1-3-14-2
1-3-15-1
1-3-15-2
1-3-16-1
1-3-17-1
B 07.12.12
1-3-2-2Construction Type Guide Rate 3 Public Lighting
1-3-18-1Steel Pole Attachments
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
1-11-10
C 22.03.16
1-3-17-2
1-3-17-3
1-3-17-4
Pit installation - sloping ground
Conduit entry to pits - general arrangement
Pit installation - concrete surround
1-3-7-2
1-3-7-3
1-3-7-4
BIG Pole - typical installation details
BIG Pole - Major Rd footing / erection details
BIG Pole - Minor Rd footing / erection details
Pit installation - general arrangement
D 06.03.17
Access for Const & Maint Vehicles on Roundabout
1-3-2-3Construction Type Guide Service Cable
1-3-19-1
1-3-19-2
1-3-19-3
Pit Installation - Type B Level Ground
Pit Installation - Type B Sloping Ground
Conduit Entry to Pits - Type B General Arrangement
03.04.18E
Dynamic Clearance of SBM Pole From and Overhead Line 1-3-14-3
B225
CABLE CODE CABLE DESCRIPTION I.I. NUMBER USE
1420045 O/H Service Major & Minor
O/H Service Major & Minor
EXAMPLE:-
2
2
SERVICE CABLE OVERHEAD - CONSTRUCTION CODE
OVERHEAD MANUAL CODE
CABLE CODE CABLE DESCRIPTION USE
SERVICE CABLE UNDERGROUND - CONSTRUCTION CODE
UNDERGROUND MANUAL CODE
EXAMPLE:- 2
These cable codes are included in the Overhead Construction Manual
These cable codes are included in the Underground Construction Manual
= 4 x 25mm ABC/XLPE
= 2 x 25mm ABC/XLPE
U/G Service Major
I.I. NUMBER
REFERENCE No.
CABLE CODE
= 16mm† Cu NS 1672
LVI-16CUNS/1672
LVI-16CUNS/1672 2406943
LVI-4CUNS/1671 = 4mm† Cu NS 1671 2400260
LVI-16CUNS/1672 = LVI 16mm† Cu Neutral Screen Cable, Code reference No. 1672
1-3-2-1
1 3 2-1 0B
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
CONSTRUCTION CODE GUIDE
SERVICE CABLE
NIL
5 87 8054 1
NILB 08.01.13
B225
B425 1420051
B225 = Cable 2 x 25mm ABC/XLPE
U/G Service Major & Minor
LV-6CUCI/1673 1673 1542919= 6mm† Cu 1 Core PVC (Green/Yellow) Earth Cable
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
24/04/13
24/04/13
04/04/13
14/10/10
EXAMPLE:-
1-3-2-2
1 3 2-2 0B
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
CONSTRUCTION CODE GUIDE
RATE 3 PUBLIC LIGHTING
NIL
NIL
NIL
STREETLIGHT LUMINAIRE RATE 3 - CONSTRUCTION CODE
PUBLIC LIGHTING MANUAL CODE
STREETLIGHT LAMP TYPE PRODUCT CODE
SL = Streetlight LED = Light-Emitting Diode 0009 = ADV Lighting Tech Ledway 20 2D350
SL LED 0027
SL LED 0027 = Streetlight, Light-Emitting Diode, Sylvania Lighting Street LED 25W
0010 = ADV Lighting Tech Ledway 20 D700
0011 = ADV Lighting Tech Ledway 40 D350
0012 = ADV Lighting Tech Ledway 80 D525
0013 = ADV Lighting Tech Ledway 120 D700
0015 = ADV Lighting Tech Ledway 40 D350R
0016 = ADV Lighting Tech Ledway 80 D525R
0019 = ADV Lighting Tech Ledway 30 C350
0020 = ADV Lighting Tech Ledway 60 C350
0021 = ADV Lighting Tech Canopy 60 C350
0027 = Sylvania Lighting Street LED 25W
0014 = ADV Lighting Tech Ledway 20 D350R
0017 = ADV Lighting Tech Ledway 120 D525R
0018 = ADV Lighting Tech Ledway 120 D700R
0022 = Pecan Lighting 96M 86W
0023 = Pecan Lighting 96M 200W
0024 = Pecan Lighting 48S 44W
0025 = Pecan Lighting 48S 55W
0026 = Orange Tek Terraled 48
0028 = GE Lighting R250 158W
0029 = GE Lighting R250 237W
0030 = GE Lighting R250 30W
0031 = Toshiba Inter Corp. Urban Light 32W
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
08/01/13
B 21.11.16
0039 = Aldridge ALS 216/298 298W
SERVICE CABLE OVERHEAD - CONSTRUCTION CODE
SERVICE CABLE UNDERGROUND - CONSTRUCTION CODE
UNDERGROUND MANUAL CODE
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
22/11/16
1-3-2-3
1 3 2-3 0A
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
CONSTRUCTION CODE GUIDE
SERVICE CABLE
NIL
NIL
NIL
EXAMPLE:-
CABLE CODE CABLE DESCRIPTION USEI.I. NUMBER
4B25
4B25 O/H Service Major & Minor= 4 x 25mm† ABC / XLPE
These cable codes are included in the Overhead Construction Manual
OVERHEAD MANUAL CODE
16578
4B25 = Cable 4 x 25mm† ABC / XLPE
EXAMPLE:-
CABLE CODE CABLE DESCRIPTION USEI.I. NUMBER
U/G Service Major & Minor07127LVC24 PVPV
O/H Service Major & Minor08727
07231
These cable codes are included in the Underground Construction Manual
LVC216 PVPV
LVC416 PVPV
= LV 4mm† Cu 2 core PVC / PVC
= LV 16mm† Cu 2 core PVC / PVC
= LV 16mm† Cu 4 core XLPE / PVC Loop In Between Pits
LVC216 PVPV = LV 16mm† Cu 2 core PVC / PVC
LVC24
F
Nostalgia type 2:
Suits Luminaires:
Nostalgia type 1:
F
F
F
FSetscrew M4 x 20,
button phillips head
Locking Nut
Star Washer
Wing Nut
Aluminium
Glare Shield
Refer to Instruction Sheet supplied with shield
for installation details.
NOTE: Also suitable for Sylvania Minor Road
B2224 series luminaires (Flower Pot type).
GLARE SHIELD FOR DECORATIVE LUMINAIRES
M50 Normal
M80 Normal
S70 Normal
M50 Normal
M80 Normal
S70 Normal
ALUMINIUM GLARE SHIELD: SC - 11609 / 2407078
1-3-3-1
1 3 3-1 0A
LIGHTINGCONSTRUCTION PRACTICES
LUMINAIRE GLARE SHIELD
MINOR ROAD DECORATIVE
NIL
5 87 8064 1
4927-84-2.24
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
F
Suits Luminaires:
(Suits Sylvania B2222, Maxi or Urban luminaires)Suits Luminaires:
Remove existing diffuser
and fit replacement
containing glare shield.
(Suits Sylvania Roadster Luminaires up to 250W)
(Suits Sylvania Roadster Luminaires 400W only)
GLARE SHIELD FOR MAJOR ROAD LUMINAIRES
GLARE SHIELD FOR MINOR ROAD LUMINAIRES
F
Remove existing diffuser
and fit replacement
containing glare shields.
NOTE: Not suitable for M125D as maximum
allowable power is 80 watts.
Suits Luminaire:
REPLACEMENT DIFFUSER: SC - 18050 / 2407077
REPLACEMENT DIFFUSER: SC - 18051 / 0104389
REPLACEMENT DIFFUSER: SC - 18051 / 0104390
S100 Normal SC - 21576 / 2403262
S150 Normal SC - 21577 / 1150251
S250 Normal SC - 21578 / 1150283
M50 Normal SC - 21520 / 1150075
M80 Normal SC - 21521 / 1150078
S70 Normal SC - 21540 / 2403257
S400 Normal SC - 21579 / 1150285
1-3-4-1
1 3 4-1 0A
LIGHTINGCONSTRUCTION PRACTICES
LUMINAIRE GLARE SHIELD
MAJOR & MINOR ROAD
10500-A4-1-3-4-1
5 87 8065 1
NIL
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
F
STONE GUARD FOR MINOR ROAD LUMINAIRES
Suits Luminaires:
Stone Guard
F
Luminaire
B 06.03.13
H70 Normal SC - 22765 / 2438257
H35 Normal SC - 22789 / 2438232
CF32 Normal SC - 21224 / 2438174
S70 Normal SC - 21540 / 2403257
M80 Normal SC - 21521 / 1150078
M50 Normal SC - 21520 / 1150075
Suits Sylvania Suburban Luminaires
SC - 23171 / 2443539
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
14/10/10
C 07.09.16
Suits Sylvania B2222 Maxi or Urban Luminaires
SC - 19462 / 2407079
1-3-5-1
1 3 5-1 0D
LIGHTINGCONSTRUCTION PRACTICES
LUMINAIRE STONE GUARD
MINOR ROAD
10500-A4-1-3-5-1
5 87 8066 1
NIL
D 23.03.18
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
4321
567
MINOR ROADMAJOR ROAD
F
F
F
F
7 DIGIT ASSET
IDENTIFICATION NUMBER
Used on undiscovered poles only
Location
Requirement:
Ensure that existing information is not covered.
Surface should be wiped clean to ensure no dust or grease
is left which could impair the effectiveness of the adhesive.
If the pole is serviceable, position the site label on the side
of the pole nearest the road, with the bottom edge of the
label a minimum of 2.4metres above ground level.
If the pole is Unserviceable, position the site label on the
side of the pole nearest the road, at whatever height may
be reached without exerting a force on the pole,
e.g. without leaning a ladder against the pole.
Galvanised steel / concrete light poles
Identifier Type:
Asset Type:
7 digit, vertical, bare aluminium number plate with embossed numbers.
Use on all undiscovered steel and concrete major / minor road light poles.
Identifier Application:
NOTE:- Number automatically
generated in Small World.
123456789A
123456789A
123456789A
Assy Selection
830-5 or
873-0 to 9 and
873-A to E and
874-6
Glue: Sikaflex 11FC, Refer assy 874-6, or Dow Corning 1080 RTV Black
Silicone Adhesive with caulking gun.
Apply using manufacturers’ instructions.
8-10 DIGIT / LETTER
ASSET IDENTIFIER
Attach to all new poles
8-10 digit / letter vertical bare aluminium tray with black embossed
numbers / letters on yellow background. Use on all galvanised
steel and concrete major / minor road light poles.
2400
1-3-6-1
1 3 6-1 0A
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
ATTACHING SITE IDENTIFICATION LABEL TO
STEEL OR CONCRETE POLE (MAJOR / MINOR)
10500-A4-1-3-6-1
5 87 8068 1
NIL
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10F
F
2400
NOSTALGIA S/L COLUMNF
4321
5
6 DIGIT ASSET
IDENTIFICATION NUMBER
Used on undiscovered poles only
Location
Requirement:
Ensure that existing information is not covered.
Surface should be wiped clean to ensure no dust or grease
is left which could impair the effectiveness of the adhesive.
If the pole is serviceable, position the site label on the side
of the pole nearest the road, with the bottom edge of the
label a minimum of 2.4metres above ground level.
If the pole is Unserviceable, position the site label on the
side of the pole nearest the road, at whatever height may
be reached without exerting a force on the pole,
e.g. without leaning a ladder against the pole.
Identifier Type:
Asset Type:
Identifier Application:
Assy Selection
830-1 or
873-0 to 9 and
873-A to E and
874-4
NOTE:- Number automatically
generated in Small World.
123456789A
123456789A
Powder coated nostalgia poles
Glue: Loctite 454 instant adhesive gel. Refer assy 874-4.
Apply using manufacturers’ instructions.
6
8-10 DIGIT / LETTER
ASSET IDENTIFIER
Attach to all new poles
6 digit, vertical, yellow and black numbers.
Use on all undiscovered nostalgia poles.
8-10 digit / letter vertical bare aluminium tray with black embossed
numbers / letters on yellow background. Use on all nostalgia poles.
1-3-6-2
1 3 6-2 0A
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
ASSET IDENTIFICATION LABEL TO
ESTATE POLE (MINOR ROAD)
10500-A4-1-3-6-2
5 87 8069 1
NIL
Pole Type
Requirement
Location
F
F
FWOOD / CONCRETE / METAL POLE
Concrete Pole
Metal Pole
Wood Pole
APPLICATION:
Screw backing plate to pole.
backing plate.
Apply self adhesive label to clean, dry aluminium
Curve aluminium backing plate to suit pole if necessary.
Apply using manufacturers’ instructions.
1080 RTV Black Silicone Adhesive with chalking gun.
Glue plate to pole with Sikaflex 11FC or Dow Corning
of the adhesive.
grease is left which could impair the effectiveness
Clean surface of pole to ensure no dust or
backing plate.
Apply self adhesive label to clean, dry aluminium
plate.
Clean and dry front and rear of aluminium backing
Curve backing plate to suit pole if necessary.
Avoid longitudinal seam weld.
Apply self adhesive label direct to clean, dry pole.
adhesive.
left which could impair the effectiveness of the
Clean surface of pole to ensure no dust or grease is
label a minimum of 2.4metres above ground level.
nearest the road, with the bottom edge of the
Position the site label on the side of the pole
is not covered.
Ensure that any existing information on the pole
Min
2400
Wood/Concrete/Metal PolesMetal pole, Assy 835-3
Concrete pole, Assy 835-2
Wood pole, Assy 835-1
Non-Energex/Ergon Lighting Identification,
3
B 08.09.16
1-3-6-3
1 3 6-3 0B
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
ATTACHING RATE 3 SITE IDENTIFICATION LABEL
TO POLE
10500-A4-1-3-6-3
5 87 8080 1
NIL
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
14/10/10
Min.
100NOTES:
1.
2.
3.
BURIED IN GROUND
PRECAST
1-3-7-1
1 3 7-1 0B
LIGHTINGCONSTRUCTION PRACTICES
STABILISIED BACKFILL
10500-A4-1-3-7-1
5 87 8055 1
NILB 24.10.14
Stabilised backfill
Refer note 2
100 min.
Stabilised backfill
Refer note 2
100 min.
100 min.
to reduce dust problems is acceptable.
concrete should be added dry. The use of a fine water spray
premix concrete supplied in bags is accepted. The premix
(e) For one off or a small number of foundations the use of
compact thoroughly.
(d) Place backfill in 200mm thick layers and mechanically
thoroughly mixed in a rotary mixer.
1 part cement to 8 parts fill (by volume) and shall be
(c) Backfill shall be stabilised with cement in the ratio of
requirements then imported material shall be used.
(b) If the excavated material does not conform to the above
Mechanically compact bottom of foundation.
Remove all loose material from bottom of hole.
After excavation:-
smaller than 25mm in size.
Silts and clays have all clods broken down to be
Gravels and sand have a maximum particle size of 25mm.
suitable for compacting.
The material consists of gravel sand or loam
(a) Excavated material may be used as backfill provided:-
Backfill:-
clearance of 100mm between the precast foundation and the edge of the hole.
Centrally position the precast foundation within the excavated hole, with a minimum
Precast Foundation Positioning:-
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
14/10/10
600
G.L.
IN GROUND POSITION
NOTES:
Pavement Side Street Side
PanelChamberTerminal
200 Nominal
Inside PolePanel StrapsTerminal
Earth Backfill
Line (white)Ground Level
Concrete Collar
Earth BackfillCompacted
Concrete Dry Mix
Panting D
epth
75 Minor Rd140 Major Rd
SleeveArea ProctectiveResistant CoatedCorrosion
1-3-7-2
1 3 7-2 0A
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
BURIED IN GROUND POLE
TYPICAL INSTALLATION DETAILS
10500-A4-1-3-7-2
NIL
4927-A4-2.3
be 75mm/140mm greater than the planting depth.3) Depth of hole to suit size of pole, actual depth to and dimensions.2) Refer to 1-3-7-3 & 1-3-7-4 for Footing Details corrosion protection. Protective sleeve is to provide mechanical and is undamaged and positioned as shown. 1) Before erecting pole check that protective sleeve
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
NOTES:
300
450
600
’B’
’A’
300
76
200
150
HEIGHT (M)LUMINAIRENOMINAL
9.0
(M)’A’
LENGTH
DEPTH ’B’ (M)PLANTINGMINIMUM
10.5
12.0
15.0
7.0
8.5
10.0
13.0
1.5
1.75
1.9
2.2
(steel poles)
Terminal Chamber
(note 4)
on all installations (note 6)
Concrete collar to be used
backfill (note 6)Compacted earth
openingsCable entry
all poles (note 6)drymix to be used on1:2:4 bagged concrete
(refer note 5)Hole Diameter
min140
min
460 min(note 7)
7. Actual depth shall be 140mm greater than planting depth ’B’. all backfill to be rammed down hard.6. Concrete drymix to be wet at time of installation, 100mm ramming space around base of pole.5. Standard 460mm auger size or greater to ensure (min. 200mm above G.L) by supplier.4. Steel poles coated with a corrosion resistant coating pole is erected.3. Terminal chamber normally faces building line when fitted will be at right angles to kerb line.2. Align pole during erection so that outreach where types of fabricated steel poles.1. Footings and dimensions shown are applicable to all
1-3-7-3
1 3 7-3 0A
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
BURIED IN GROUND POLE - MAJOR ROAD
FOOTING / ERECTION DETAILS
10500-A4-1-3-7-3
NIL
4927-A4-2.6
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
460 MIN
75
300
450
600
’B’
’A’
300
50
6.5
7.5
6.5
500
’A’
2200
150
NOTES:
HEIGHT (METRES)NOMINAL LUMINAIRE
’A’ (METRES)LENGTH
(METRES)DEPTH ’B’PLANTINGMINIMUM
OUTREACHWITHPOLE
POLEPIECESINGLE
4.5
5.5
6.5 1.2
1.5
1.2
POLE
SINGLE PIECE
Outreach
Single Integral
SPIGOTOUTREACHPOLE WITH
Name Plate
Chamber
Terminal
Note 4
Backfill (note 6)Compacted Earth
OpeningCable Entry
on all installations (note 6)Concrete Collar to be used
all poles. (note 6)Drymix to be used on
1:2:4 Bagged Concrete
Refer Note 5Hole Diameter
Nom
Min
1-3-7-4
1 3 7-4 0A
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
BURIED IN GROUND POLE - MINOR ROAD
FOOTING ERECTION DETAILS
10500-A4-1-3-7-4
NIL
4927-A4-2.4
Note 7
greater than planting depth ’B’.
7. Actual depth shall be 75mm
rammed down hard.
of installation, all backfill to be
6. Concrete drymix to be wet at time
space around base of pole.
greater to ensure 100mm ramming
5. Standard 460mm auger size or
above G.L.) by supplier.
resistant sleeve (Min. 200mm
4. Steel poles coated with a corrosion
building line when pole is erected.
3. Terminal chamber normally faces
angles to kerb line.
outreach where fitted will be at right
2. Align pole during erection so that
poles.
applicable to all types of fabricated
1. Footings and dimensions shown are
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
INSTALLATION INSTRUCTIONS
Termination 16mm† & 4mm† N/S cable
STEP 1:
STEP 2: Apply red mastic to crutch area starting at
the outer sheath cut off.
Finishing 10mm up each core
STEP 3:
STEP 4:
STEP 5:
10
F
F 20
Nylon jacket
Outer PVC
sheath
Inner PVC
sheath
F
FF
Red mastic
F
Strip cable to required length leaving 20mm
of nylon jacket exposed (Black) & 10mm
of the inner PVC jacket exposed.
Abrade 20mm of the outer sheath
F
Red mastic
F
Heatshrink tubing
F F
Heatshrink glove
Install & shrink glove into position
Install a red mastic block on the screen core
10mm short of where the tubing will
end when installed.
Position the tubing over each core slipping
over the glove finger.
Shrink in position.
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
1-3-8-1
1 3 8-1 0A
LIGHTINGCONSTRUCTION PRACTICES - ERGON ENERGY ONLY
TERMINATION 16mm† & 4mm† N/S CABLE
INSTALLATION INSTRUCTIONS
10500-A4-1-3-8-1
5 87 8098 1
NIL
’X’ ’Y’
Crossing
Width
Beam axis
Floodlight
KerbF
F
F
Traffic
Flow
Place Aiming Device on floodlight as shown.
Hold flat plate against glass front of floodlight.
Sight through tube to Aim Point on carriageway.
F
F
F
F
F
Half
Carriagew
ay
width
F
F
F
F
F
INSTALLATION REQUIREMENTS:
AIMING DEVICE
Aim point on carriageway.
Designer to nominate
dimensions ’X’ & ’Y’.
Refer Construction plan.
Set-out
point Flat plate
Sighting tube
F
F
To provide the required vertical illuminance and at
the same time control glare to oncoming motorists
on the opposite side of the road, accurate location
and aiming of the floodlights is essential.
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
1-3-9-1
1 3 9-1 0A
LIGHTINGCONSTRUCTION PRACTICES
PEDESTRIAN CROSSING FLOODLIGHT
AIMING DETAILS
10500-A4-1-3-9-1
5 87 8070 1
NIL
1.5
A7 A4 A1
A8
A5
A2
A9 A6 A3
B1B4B7
B2B5B8
B3B6B9
90%%d
2.5%%d to 5%%d
DIMENSIONS SHOWN IN MILLIMETRES
400
20
120
150
X
AIMING DEVICE
To Aiming Point
’Normal to the Glass’
MATERIAL :0.6mm Zincalum or 1.6mm Aluminium
NOTES :
These 3 edges to sit flat on
glass front so that sight line
is 90° to glass in both axies
25 x 10 notch to
clear front frame
Aiming Point
Normal to
the glass
Maximum
Intensity
Direction of traffic
Kerb
Normal to
the glass
Maximum In
tensity
Louvre
Lamp
CRITICAL MEASURING POINTS
ON PEDESTRIAN CROSSING
ANGULAR DISPLACEMENT OF MAXIMUM
INTENSITY TO FLOODLIGHT HOUSING
1-3-9-2
1 3 9-2 0A
LIGHTINGCONSTRUCTION PRACTICES
PEDESTRIAN CROSSING FLOODLIGHT
AIMING DETAILS
10500-A4-1-3-9-2
NIL
4927-A4-1.4
Philips
floodlight luminaire
1. Aiming points nominated in Mains Project Department
recommendations are for ’Normal to Glass’ aiming.
2. Aiming device to be held at centre of floodlight when aiming.
3. Sight along top end of aiming device and adjust floodlight
position until the nominated roadway aiming point is targeted.
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
1000
Footing Conduit
3000 max
Road lighting luminaire
Traffic Flow
Edge of carriagewayVerge
Carriageway
Supply cable conduit
(500 min)
Road surface
Electrical conduit system
Kerb
location
Preferred
Pit
Refer detail A
pole and outreach arm
Road lighting
drainage paths
be located in
Pits should not
Detail A
General Arrangements
1.
2.
Access to pit to be clear of obstructions eg. guard rails3.
4.
5.
6.
rear face of kerb
Pit may butt against
acceptable. For preferred location refer plan view.
located within these boundaries as indicated is
closer than 0.5m to road lighting poles. The pit
Pit to be located no further than 3.0m from and no
however pit may butt against rear face of kerb.
When kerb is present pit to be clear of obstructions,
all conduits except those shown on footing drawings.
more cables which may be drawn in. This is generally
constructs and which is designed to recieve one of
between footings or foundations or other engineering
conduit which creates a closed underground passage
Underground electrical duct system is the ducting or
F
F
F
F
F
F
F
F
F
F
F
F
F
Notes:
600 min
cable conduit for preferred location see plan view
Pit to be located along longitudinal alignment of supply
7.
the pole within the 3m radius
pole, an additional pit is to be supplied at the base of
Where supply conduit alignment is >3m radius from the
F
F
1-3-10-1
1 3 10-1 0D
LIGHTINGCONSTRUCTION PRACTICES
TYPICAL PHYSICAL ARRANGEMENT OF
SUPPLY PIT RELATIVE TO POLE
10500-A4-1-3-10-1
NIL
NILB 08.01.13
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
14/10/10
11.09.13C
system clear through the footing of foundation.
cables to be drawn from the undergound ducting
duct system. The footing ducting allows one or more
engineering constructs to the underground electrical
used to connect footings, foundations or other civil
which is shown on the footing drawings and which is
Footing / Foundation ducting is the ducting or conduit
30.07.14D
8.
junction box is not required.
supplied from the previous pit if a
streetlight in a circuit may be
For BPM or BIG installation the last
1000 min
F
F
Note:
No plants within a 1 meter
radus of streetlight
F
Alternate access to
suit approach road
Concrete access
strips for vehical
F
F
Edge of
roundabout
F
F
F
A
A
ROUNDABOUTS 9 METERS OR LARGER
1000
F
F2000 F
F
2000 F
F
1100
Streetlight PoleF
Access area
around pole
F
Concrete base 150mm
depth & FB2 mesh
F
F
SECTION A-A
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
1-3-11-1
1 3 11-1 0A
LIGHTINGCONSTRUCTION PRACTICES
ACCESS REQUIREMENTS FOR CONSTRUCTION &
MAINTENANCE - VEHICLES ON ROUNDABOUTS
10500-A4-1-3-11-1
NIL
4927-A4-2.41
Alternate location
F
EPV access to roundabout
drive on - drive off
(Reversing into traffic from
the roundabout is prohibited)
Notes:
1. No other service to pass under vehical tracks.
2. No taps, drains ect. or other obstructions
within 1m of vehical tracks
3. Vehical tracks to be angled to align with
traffic flow (as in intersection diagram)
4. Central street lighting in large roundabouts not to
be used - perimeter lighting should be used.
5.
6. If vehical access to the roundabout can not be
gained - Road / lane closure may be required
resulting in additional charges by Energex.
Where vehical access at roundabout is difficult
or unsuitable, an alternative mid hinged pole
may be suitable.
Refer to Lighting Design for options / costs.
1-3-11-2
1 3 11-2 0A
LIGHTINGCONSTRUCTION PRACTICES
ACCESS REQUIREMENTS FOR CONSTRUCTION &
MAINTENANCE - VEHICLES ON ROUNDABOUTS
10500-A4-1-3-11-2
NIL
4927-A4-2.41
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
ROAD SIDENOTES:
1. This practice used for the attachment of :-
- Pole numbers.- Transformer numbers.
- Streetlight numbers.- A.B.S. numbers.
2. Do not overlap numbers.
3. Pole numbers to be mounted a minimum
of 2.7m above ground or above pole
test/identification point (wood pole).
4. Pole numbers to be mounted facing road,
towards oncoming traffic.
HEAD
BUTT
TYPICAL POLE INSTALLATION
PROPERTY SIDE
Pole
Length
See
Note 3
Sinking
Depth
2.7m
600Terminal Chamber
(concrete only)
Pole Test Point
(wood only)
Pole Numbers (wood/
concrete poles)
Pole steps
fitted from 7m
above ground
VOLUME FOLDER ISSUEPAGE
A
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
Ergon Energy Corporation Limited
ABN 50 087 646 062
C COPYRIGHT 2002 ERGON ENERGY
ENERGEX Corporation Limited
ABN 40 078 849 055This document must not be
reproduced in part or whole
without written permission from
ENERGEX or Ergon Energy
EE DRWG NO:
EGX DRWG NO:
J. Brooks
R. English
D. Taylor / B. Oyegoke
L. Burton / T. Borg
14/10/10
14/10/10
14/10/10
14/10/10
1-3-12-1
1 3 12-1 0A
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
ENERGEX POLE LABELLING
10500-A4-1-3-12-1
NIL
4927-A4-2.39, 2.40
SIDE VIEW
TOP VIEW TOP VIEW
SIDE VIEW
headframe cap
Removeable
F
Assy 851-1
F
SL1 SL1 SL2
809-8 or 9
Assy SelectionF
Assy 851-1
F
F
headframe cap
Removeable
809-8 or 9
Assy SelectionF
1 Way Construction
1 Way Construction
2 Way Construction
2 Way Construction
1-3-13-1
1 3 13-1 0B
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
HIGH MAST POLE HEADFRAME DETAILS
1 & 2 WAY OUTREACH
10500-A4-1-3-13-1
NIL
NIL
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
A. Bletchly / P. Relf
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
14/10/10
B 23.03.18
for high mast constructions.
1-5-13-1 or 1-5-14-1
1-5-10-1,
Refer drawings
TOP VIEW
3 Way Construction
TOP VIEW
3 Way Construction
TOP VIEW
4 Way Construction
TOP VIEW
4 Way Construction
SL1SL2
SL3
SL1
SL2
SL3
SL4
headframe cap
Removeable Assy 852-1
809-8 or 9
Assy SelectionF
F809-8 or 9
Assy Selection
F
F
Assy 852-2
headframe cap
Removeable F
F
1-3-13-1
1 3 13-2 0C
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
HIGH MAST POLE HEADFRAME DETAILS
3 & 4 WAY OUTREACH
10500-A4-1-3-13-2
NIL
NIL
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
14/10/10
B 06.12.12
23.03.18C
for high mast constructions.
1-5-13-1 or 1-5-14-1
1-5-10-1,
Refer drawings
FHC
F
VC
HCF
1-3-14-1
1 3 14-1 0C
LIGHTINGCONSTRUCTION PRACTICES
CLEARANCE BETWEEN LIGHTING STRUCTURE &
OVERHEAD LINE
10500-A4-1-3-14-1
5 84 8038 2
NILB 30.07.14
structure and the overhead line.
Clearance is the distance between the lighting
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
A. Bletchly / P. Relf
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
14/10/10
C 23.03.18
CABLEOTHER COMMS ADSS, PILOT OR
(NOT CCT)CABLEINSULATED
OR CCTBARE = 33kV
FROM:CLEARANCE
MINIMUM DISTANCE
"VC"VERTICAL
"HC"HORIZONTAL
1.5m
0.6m
0.05m
1.5m
0.3m
0.05m
(minimum sag condition)
c) conductor temperature of 0° in still air
(maximum horizontal swing condition)
wind pressure on the conductor
b) conductor temperature of 35° with 500pa
in still air (maximum sag condition)
a) maximum conductor design temperature
Clearances shall be maintained under:
NOTE:
F
F
F
F
F
F
1.2H
F
F1.2
H
F
F0.6
H
F
F0.6
H
F
F0.6
H
F
F
1.2H F
F
1.2H
prevents the pole being mounted at 1.2H
minimum of 0.6H, only if conflicts with existing infrastructure (eg driveways)
In this situation only, the horizontal clearance may be reduced to an absolute
F
H is the mounting height of the Luminaire.
The distances shown are to the nearest conductor.
E
E E E
E
E
1-3-14-2
1 3 14-2 0B
LIGHTINGCONSTRUCTION PRACTICES
DYNAMIC CLEARANCE OF SLIP BASE POLE
FROM AN OVERHEAD LINE
10500-A4-1-3-14-2
NIL
4927-A4-2.42
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
A. Bletchly / P. Relf
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
14/10/10
B 23.03.18
intersection or when an overhead line crosses the carriageway.
flow the clearance for slip base pole should be increased to 1.2H. This situation occurs at an
where H is the mounting height of the luminaire. If the overhead line transverses the direction of traffic
The recommended minimum horizontal clearance of a slip base pole from an overhead line is 0.6H,
NOTE:
1-3-14-3
1 3 14-3 0A
LIGHTINGCONSTRUCTION PRACTICES
DYNAMIC CLEARANCE OF SLIP BASE POLE
FROM AN OVERHEAD LINE
10500-A4-1-3-14-3
NIL
4927-A4-2.42
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
A. Bletchly / P. Relf
L. Burton / T. Borg
01/05/18
01/05/18
01/05/18
23/03/18
H1.2H
F
F
Clearance Zone
Overhead Electrical
F
maintained. Refer to drawing 1-3-14-1.
Statutory electrical clearances to be
F
NOTES :
luminaires are amended.
pole - ajustments will be necessary if the number of
Do not alter the mass fitted to the headframe of this
headframe configuration.
counter balances - balance weights varies to suit
of designed and specified headframe loads and apron
Do not raise or lower pole without full complement
Do not raise or lower pole in windy conditions.
3.
2.
1.
W A R N I N G
Latch
Latch Bar
Luminaires
F
1, 2, 3 or 4 way
Variable headframe
F
Hinge point
F
F
F
Balance weights
F
Apron
F
of pole
apron to base
Nut securing
F
decent of pole
Hand line controlling
F
Terminal chamber
F
4.
3.
2.
1.
1-3-15-1
1 3 15-1 0B
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
MAJOR ROAD MID HINGED BPM POLE
INSTALLATION DETAILS
10500-A4-1-3-15-1
NIL
4927-A4-2.42B 06.12.12
is difficult. (Rate 2 only)
Only to be used on roundabouts where access
Refer sheet 2 for operating notes
when pole is erected with baseplate square
Terminal chamber normally faces building line
For foundation details refer to construction drawing
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
24/04/13
24/04/13
04/04/13
14/10/10
OPERATING NOTES - Lowering Headframe
Provide two lengths of rope - minimum length 15m (Not Supplied)
1.
2.
3.
4.
5.
opposite side to the apron.
Remove access door panel at base of apron located on the
pole from the apron and secure the apron to the base of the pole
Remove padlock from internal lug which protrudes through the
This rope is the ’raise and lowering’ rope.
handle which is located at the base of the apron section.
Securely attach the end of one of the ropes (rope ’A’) to the
F
F
rope ’B’
Saftey backup
Use suitable lengths of nylon rope to suit height of pole
RAISE AND LOWER METHOD
6.
the pole where the headframe will be lowered.
standing either directly behind the apron or in the area in front of
Before removing apron fixing screw, ensure that personnel are not
7.
8.
of the first rope.
maintain a slight tension in the backup rope ’B’ in case of failure
rope ’A’, avoiding jerky movements. A second person should
One person should slowly lower the pole using the raise and lower
9.
the headframe.
at any stage when the mass or luminaires have been removed from
tied to the base of the pole. The headframe should NOT be released
in the folded down position, the top of the pole must be securely
During maintenance of the headframe equipment, while the pole is
RAISING HEADFRAME
10.
snuggly against the pole.
controls the rate of descent and slowly allows the apron to close
encourages the lowering of the apron to continue. Rope ’A’ now
downwards until rope ’B’ assumes the transfer of the weight and
To return headframe to its upright position, rope ’A’ is drawn
11.
12.
securely refitting the access door panel.
It is suggested that the ropes be stored in the pole base before
screw and locks the internal security padlock.
rope while the other person immideately replaces the apron fixing
on rope ’B’ should maintain a slight tension on the saftey backup
Once the pole is returned to its upright position, the second person
F
F
Pole length + 15%
F
F
width x 3
Headframe
Hazard area
F
1-3-15-2
1 3 15-2 0B
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
MAJOR ROAD MID HINGED BPM POLE
OPERATION DETAILS
10500-A4-1-3-15-2
drawing no
4927-A4-2.42
approx. 15kg load
Raise & lower rope ’A’
B 06.12.12
at the base of the pole. This rope is the ’safety back-up’ rope.
same handle and thread the rope through the lifting lug located
Securely attach the end of the second rope (rope ’B’) to the
decend under its own weight.
using the handle and lowering rope ’a’ until top of pole starts to
pulls the saftey backup rope ’B’ tight. Pull apron away from pole
Before removing apron fixing screw, ensure that a second person
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
24/04/13
24/04/13
04/04/13
14/10/10
312 06837 AR
311 15528 ARUnderground Pit JC4
275 06514 AR
242 13538 ARConduit, 50mm ID Flexible, ORANGE
276 17030 ARBend,Conduit UPVC,40mm x 600mm R
226 12471 ARConduit,40mm Rigid UPVC,HD, Orange
Tape,U/G Marking,Orange, 150mm W AR14318
QTYDESCRIPTIONPART
216
S.C.
Underground Pit JC4 Cover
Bend,Conduit UPVC,40mm x 300mm R
272
274
Conduit, 80mm Rigid UPVC, Orange
Bend,Conduit UPVC,80mm x 450mm R 15271
06643 AR
AR
S.C.
279
PART DESCRIPTION QTY
06640 ARConduit, 40mm RIGID, ORANGE
Adaptor, 40mm RIGID/40mm Flexible AR287
Conduit 40mm Flexible, ORANGE AR288 17121
17122
NOTES:
Slip Base Adaptor
SurfaceFinished
275 276 227or or
242 287 288or &
ARRANGEMENTSLIP BASE POLE
279
610
760
750 Min
1200 M
IN
50
600 Min
Refer to note 3
311& 312
760 1
00
300
281
600
Min
or
Road
î
requiredConduits as
pegsurvey propertyReal
90� conduit be40mm, 600mm RAD,
276
plug the conduitsproperty survey peg and ENERGEX and Telstra conduits 1000mm from the realprior to the formation of the road pavement terminate At the initial installation of the road crossing conduits
conduitExtent of
279
Min
Finished Surface Level
800
Note 1
PavementRoad 800
750 Min
1200 Min
DM
R Arterial
Major
Road
Kerb
’E’ Marker ’E’ Marker
Kerb
90� conduit be40mm, 600mm RAD,
276
TapeMarkerWarning
216
90� conduit be40mm, 300mm RAD,
275
600
Min
100
300
î
pegsurvey propertyReal
90� conduit80mm, 450mm RAD.
274
property survey pegscrossing conduit on a line between real1 x 80mm dia minimum nominal size of road
272
90� conduit80mm, 450mm RAD.
274
300 NOTE 1 300
90� conduit be40mm, 300mm RAD,OR(wall thckness approx 6mm)Flexible conduit-orange
242
275
287 288OR
B 06.12.12
1-3-16-1
1 3 16-1 0B
LIGHTINGCONSTRUCTION PRACTICES - ENERGEX ONLY
MAJOR & MINOR ROADS - TYPICAL CROSS SECTION
ACROSS ROAD & STREET LIGHT SERVICES
10500-A4-1-3-16-1
NIL
4927-A4-10.9
Manual for conduit footpath and roadway.4. Refer to Underground Construction pit installation details.3. Refer to section 1.3.17 for underground to installing pole or streetlight services.2. Check existing services in road prior footpath width or 800mm nominal. 300mm setback to suit road and 1. As per local governement requirements
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
24/04/13
24/04/13
04/04/13
01/10/10
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
11/09/14
F
F
INT EDGE AT TOP 656 – 4
F
F
INT EDGE 351 – 3
F
F
OPENING 280
F
F
550
F
F
704
50
F
F
-+50
0
F
F 100F
F-+25
0100-+25
0
in any direction.about the centre line3° Max. tilt off vertical
F
F
F
flush with pit lid
Finished Surface LevelF
(refer note 4)
Compacted sand / clean fill
400 F
F
50
F
F
-+50
0
240 F
F
400 F
F
F
F100-
+25
0F
F100-
+25
0
F
F
in any direction.about the centre line3° Max. tilt off vertical
F
F
NOTES:
1.
2.
3.
White plastic / fibre pits are not acceptable
Only pits constructed of black HDPE are to be used.
4.F
F
Compacted bedding sand
B 29.03.16
PLAN
ELEVATION END ELEVATION
Bedding sand to be used around electrical conduits.
surround shall be installed. Refer 1-3-17-4 for details.
pit a minimum 150mm wide x 150mm deep concrete
In location where soil or other material is likely to cover
falling back into the pit or obscuring the lid.
Area around pit to be kept clear of soil to prevent soil
deep concrete surround.
be rigidly supported by a minimum 150mm wide x 150mm
If soil around pit is not compacted, area around lid must
1-3-17-1
1 3 17-1 0B
LIGHTINGCONSTRUCTION PRACTICES
PIT INSTALLATION
LEVEL GROUND
10500-A4-1-3-17-1
NIL
NILF
F
560 (Type 2)830 (Type 4)
F
F
553 (Type 2) 586 (Type 4) OPENING AT TOP
F
F
INT EDGE AT TOP 656 – 4
F
F
INT EDGE 351 – 3
F
F
OPENING 280
F
F
550
F
F
704
50
F
F
-+50
0
F
F
in any direction.about the centre line3° Max. tilt off vertical
F
F
F
flush with pit lid
Finished Surface LevelF
(refer note 4)
Compacted sand / clean fill
400 F
F
50
F
F
-+50
0
240 F
F
400 F
F
F
F
100-+25
0
F
F
NOTES:
1-3-17-2
1 3 17-2 0A
LIGHTINGCONSTRUCTION PRACTICES
PIT INSTALLATION
SLOPING GROUND
10500-A4-1-3-17-2
NIL
NIL
F
F
200mm Min.
F100-+25
0
F200mm Min.
F
F
is the allowable vertical tolerance.the centre line in any direction3° Max. tilt off vertical about
F
F
F100-+25
0
F200mm Min.
F
F100-+25
0
200mm Min.
F
F
F
F
Compacted bedding sand
1.
2.
3.
White plastic / fibre pits are not acceptable
Only pits constructed of black HDPE are to be used.
4.
PLAN
ELEVATION END ELEVATION
surround shall be installed. Refer 1-3-17-4 for details.
pit a minimum 150mm wide x 150mm deep concrete
In location where soil or other material is likely to cover
falling back into the pit or obscuring the lid.
Area around pit to be kept clear of soil to prevent soil
deep concrete surround.
be rigidly supported by a minimum 150mm wide x 150mm
If soil around pit is not compacted, area around lid must
Bedding sand to be used around electrical conduits.
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
F
F
560 (Type 2)830 (Type 4)
F
F
553 (Type 2) 586 (Type 4) OPENING AT TOP
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
50F
F
-+5
0
1.
2.
3.
4.
1-3-17-3
1 3 17-3 0A
LIGHTINGCONSTRUCTION PRACTICES
CONDUIT ENTRY TO PITS
GENERAL ARRANGEMENT
10500-A4-1-3-17-3
NIL
NIL
25mm Min.
F
FF
F
F
F
F
F
F
F
300mm Rad.40 dia. 90°
Conduit bend
Conduit 40 Dia. Conduit 40 Dia.
LightTo Public
Conduit bushConduit bush
Conduit 40 Dia.Conduit 40 Dia.
STREETLIGHT CIRCUIT
STREETLIGHT CIRCUIT
of dirt, stones and moisture.
ends shall be adequately sealed to prevent the entrance
Where cables have been installed in conduit, the conduit
NOTES:
the entry of foreign material
All conduit entries into a pit shall be capped to prevent
minimum 25mm.
the pit, the conduit must be separated at the pit by a
Where more than one conduit enters the same end of
5. -+5
0
preference is for conduits to enter / exit on the short side.
All conduit entries and exits must enter the pit at 90°
from bottom.
Ramp conduits at pit to inable entry 50 mm
NOTES:
1.
2.
1-3-17-4
1 3 17-4 0A
LIGHTINGCONSTRUCTION PRACTICES
PIT INSTALLATION
CONCRETE SURROUND
10500-A4-1-3-17-4
NIL
NIL
F
F
A
A
F
Refer note 1
N12 bar lappedPLAN
150
F
F
150
F
F
SECTION A-A
150
F
F
F
N12 bar lappedF
N25 concrete surround
Install bar centrally in concrete surround.
concrete surround and footpath or larger concrete surround.
surround an abelflex sealant joint is to be included between the
If concrete surround is to be part of footpath or larger concrete
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
01/04/16
01/04/16
01/04/16
23/03/16
Cutting C
ompound
STEP 1
STEP 2
Cold G
alvanisin
g paint
and cutting compound
Required holes to be center punched and drilled using step drill
Clean excess drilling compound
Paint exposed metal
cutting compound until required hole dia. is achieved
Stop and set drill to slow speed and proceed drilling using
Set drill to high speed and drill till penetration of the pole.
Pilot hole approx. 6mm is optional
Assy 903-5
903-10
Assy selection
Assy 903-1
1-3-18-1
1 3 18-1 0A
LIGHTINGCONSTRUCTION PRACTICES
STEEL POLE ATTACHMENTS
FLOODLIGHT CABLE ENTRY
10500-A4-1-3-18-1
NIL
NIL
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
24/04/13
24/04/13
04/04/13
19/03/13
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
02/11/16
F
flush with pit lid
Finished Surface LevelF
(refer note 3)
Compacted sand / clean fill
NOTES:
1.
2.
3.
White plastic / fibre pits are not acceptable
Only pits constructed of black HDPE are to be used.
F
Compacted bedding sand
PLAN
Bedding sand to be used around electrical conduits.
1-3-19-1
1 3 19-1 0A
LIGHTINGCONSTRUCTION PRACTICES
PIT INSTALLATION - TYPE B
LEVEL GROUND
10500-A4-1-3-19-1
NIL
NIL
F
F
700
ELEVATION
-+10
075
F
F
F
F
1000 – 10
F
F100-+25
0 F
F100-+25
0
in any direction.about the centre line3° Max. tilt off vertical
F
F
falling back into the pit or obscuring the lid.
Area around pit to be kept clear of soil to prevent soil
F
F
652 – 1 dia
F
F
630 – 2 dia
NOTES:
1.
2.
3.
White plastic / fibre pits are not acceptable
Only pits constructed of black HDPE are to be used.
PLAN
ELEVATION
Bedding sand to be used around electrical conduits.
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
09/11/16
F
F
652 – 1 dia
F
F
630 – 2 dia
F
flush with pit lid
Finished Surface LevelF
(refer note 3)
Compacted sand / clean fill
F
Compacted bedding sand
F
F
700
-+10
075
F
F
F
F
1000 – 10
F
F100-+25
0F
F100-+25
0
in any direction.about the centre line3° Max. tilt off vertical
F
F
200mm Min.F
F F200mm Min.F
falling back into the pit or obscuring the lid.
Area around pit to be kept clear of soil to prevent soil
1-3-19-2
1 3 19-2 0A
LIGHTINGCONSTRUCTION PRACTICES
PIT INSTALLATION - TYPE B
SLOPING GROUND
10500-A4-1-3-19-2
NIL
NIL
VOLUME FOLDER ISSUEPAGE
Approved Ergon
Approved Energex
Checked
Drawn
Date
Date
Date
Date
A ORIGINAL ISSUE
HARD COPY UNCONTROLLED
C COPYRIGHT 2002 ENERGEX
ABN 50 087 646 062
Ergon Energy Corporation Limited
C COPYRIGHT 2002 ERGON ENERGY
ABN 40 078 849 055
ENERGEX Corporation Limited
ENERGEX or Ergon Energy
without written permission from
reproduced in part or whole
This document must not be
REFERENCE DRAWING ENERGEX
REFERENCE DRAWING ERGON
EE DRWG NO:
EGX DRWG NO:
C. Noel
F. Zaini
P. Relf / A. Bletchly
L. Burton / T. Borg
19/04/17
19/04/17
01/04/17
09/11/16
1.
2.
3.
4.
25mm Min.
F
F
F
F
F
F
F
F
F
F
300mm Rad.40 dia. 90°
Conduit bend
Conduit 40 Dia. Conduit 40 Dia.
LightTo Public
Conduit bushConduit bush
Conduit 40 Dia.Conduit 40 Dia.
STREETLIGHT CIRCUIT
STREETLIGHT CIRCUIT
of dirt, stones and moisture.
ends shall be adequately sealed to prevent the entrance
Where cables have been installed in conduit, the conduit
NOTES:
the entry of foreign material
All conduit entries into a pit shall be capped to prevent
minimum 25mm.
the pit, the conduit must be separated at the pit by a
Where more than one conduit enters the same side of
5. -+5
0
from bottom.
Ramp conduits at pit to inable entry 100 mm
1-3-19-3
1 3 19-3 0A
LIGHTINGCONSTRUCTION PRACTICES
CONDUIT ENTRY TO PITS - TYPE B
GENERAL ARRANGEMENT
10500-A4-1-3-19-3
NIL
NIL
ELEVATION
F
F
100 min
All conduit entries and exits must enter the pit at 90°.
6.Conduits shall not enter from the base of the pit.