liebert
DESCRIPTION
LIEBERT ITTTRANSCRIPT
-
Precision Cooling For Business-Critical Continuity
Liebert XDFlexible, Energy-Saving Cooling Solutions For High Heat Density Applications
-
22
High Heat Density. High Temperatures.
Todays data center technologies compound conventional coolingproblems. Blade servers, communications switches and other electronicsare being packed into tighter and tighter spaces. Computing capacity thatonce filled an entire room is now contained in a single rack creatingextreme power and heat densities.
Conventional Solutions Just Cant Keep Up
While the cornerstone of an effective cooling strategy, you cant rely solely
on conventional mission-critical cooling systems to resolve such high
heat densities. Hot spots or zones require targeted cooling solutions.
And, for extremely high heat loads, conventional approaches may
simply take up too much floor space to be practical.
Business continuity professionals will rely on an integrated solution one
that solves both room-level and rack-level cooling challenges.
Higher Watt, Higher Heat Densities
This increased capacity is fueled by rapid growth in processing capacity. But,
more compact capacity means higher heat densities. What was a 1 kW rack
now may exceed 10 kW. This requires a shift in focus from a room-based
view of cooling to a rack-based view. More literally, business continuity
professionals must consider both Watt per square foot and kW per rack
when evaluating cooling solutions.
Today, more than ever, environmental and economic
issues are pushing business continuity professionals to
lobby for energy efficient, environmentally friendly
solutions in their data centers. The Liebert XD solution is
the answer on both fronts. With a hybrid approach that
requires 15% - 50% less chiller plant capacity, as well as
less diesel generator and switchgear capacity required,
the potential energy consumption for your centers is
reduced up to 40%. The significant energy savings
achieved by the Liebert XD solution are attributed to
these factors:
Locating cooling units closer to the load reducesthe energy required to move the air and resultsin less mixing of hot and cold air.
Micro channel coils provide minimal air pressuredrop losses and improved thermal heat transfer.
No need to over-chill data centers to eliminatehot spots.
However, flexibility is also an important attributeof your cooling systems. The Liebert XD solution a combination of floormount mission-criticalcooling units and supplemental cooling allowsyour facility to adapt as heat loads increase. And byadding/reconfiguring solutions to react to changesin your environment, the flexible configuration ofthe Liebert XD system modules also allowsscalability for future growth.
-
10,000
6,000 60,000
2,000
1,000
600
400 4,000
200
100
601992 1996
Year of Product Announcement
2000 2004 2008 20121994 1998 2002 2006 2010 2014
4,000
8,000
800
100,000
20,000
10,000
6,000
2,000
800Hea
t load
per equipmen
t foot
print (w
att/eq
uipmen
t sq
.ft.)
Hea
t load
per equipmen
t foot
print (w
atts/equipmen
t sq
.m.)
Commun
ication - Ex
treme Den
sity
Communication - Extreme Density
Computer S
ervers
Comput S
er
Storage Serv
ers
Storage ServersComputer Servers - 2U
and GreaterCommunication - High Density
Computer Servers - 1U, Blade and Custom
Workstations (
standalone)
Workstations (standalone)
Tape Storage
Tape Storage
Densit
Tap
3
No Relief In Sight: Heat Loads Rising
Hotter FacilitiesAs processor capabilities increase, so do computer roompower densitiesfrom 50 Watt per square foot (540W/m2)to over 300 Watt per square foot (320W/m2). Your wholedata center just keeps getting hotter.
Hot SpotsCompounding the problem, this higher heat load is notevenly distributed throughout the room. Sometimes, powerdensities can grow into hundreds of Watt per square foot,creating localized hot spots of extreme heat.
And, They Attack Your Facility in Two Ways
50W TO 300W 600+W
ASHRAE, Datacom Equipment Power Trends andCooling Applications, 2005. American Societyof Heating, Refrigerating and Air-ConditioningEngineers, Inc.., www.ashrae.org
-
4Heat Load = 3 kW Per Rack Without Hot Aisle /Cold Aisle Layout
Heat Load = 6 kW Per Rack With Hot Aisle /Cold Aisle Layout
F C
100 / 38
90 / 32
80 / 27
70 / 21
60 / 16
F C
98 / 37
88 / 31
79 / 26
69 / 21
60 / 16
Heat Load = 10 kW Per Rack With Hot Aisle /Cold Aisle Layout
F C
115 / 46
101 / 38
87 / 31
73 / 23
60 / 16
RA
CK
Heat Load = 3 kW Per Rack With Hot Aisle /Cold Aisle Layout
F C
87 / 31
80 / 27
73 / 23
66 / 19
60 / 16
RA
CK
RA
CK
RA
CK
COLD
AIS
LE
RA
CK
COLD
AIS
LE
RA
CK
RA
CK
RA
CK
COLD
AIS
LE
COLD
AIS
LE
RA
CK
COLD
AIS
LE
RA
CK
RA
CK
RA
CK
COLD
AIS
LE
COLD
AIS
LE
RA
CK
COLD
AIS
LE
RA
CK
RA
CK
RA
CK
COLD
AIS
LE
HO
T A
ISLE
HO
T A
ISLE
HO
T A
ISLE
HO
T A
ISLE
HO
T A
ISLE
HO
T A
ISLE
A common way to improve performance of
existing raised floor cooling applications has
been the hot aisle/cold aisle approach. In
this configuration, rows of equipment racks
are arranged in alternating "hot" and "cold"
aisles. Only the cold aisles have perforated
floor tiles that allow cool air to come up
from under the raised floor.
The Cold Aisle Is Feeling A Bit Hot
See also white paper Adaptive Cooling In The Data Center: The Roadmap For Growth at www.liebert.com
Unfortunately, even when using a hot aisle/cold aisle configuration, the limits of standard underfloor coolingare soon reached as rack heat loads increase.
Hot Aisle /Cold Aisle Approach
Side views of Computational Fluid Dynamics (CFD) by Fluent showing
limitations of hot aisle/cold aisle approach as heat load increases.
-
5Business continuity professionals are demanding
an integrated high heat density cooling solution
one that considers both room-level and
rack-level needs.
Effective solutions need to be flexible.
Liebert XD: The Flexible Solution
Flexibility
Floor-mount, rack-mount and ceiling-mount modules, plus a choice of cooling capacities, coverany application requirements.
Plug and play for initial installation and future growth.
Can cool more than 30 kW per rack.
Higher Availability
The Liebert XD solution assures continuous operation of critical IT systems under extreme heat conditions.
Designed to work with the hot aisle/cold aisledesign of raised floor applications by efficientlydrawing hot air out of equipment racks and moving cool air into the cold aisle.
The Liebert XD solution for high heat density cooling applications is a hybrid approach using a combination of floormount mission-critical cooling units and supplemental cooling from the Liebert XD Series.
Added as heat loads increase, supplemental
Liebert XD cooling capacity allows your facility
to adapt as heat loads rise allowing cooling
solutions to be added and reconfigured to react
to the changes in your environment.
Benefits of the Liebert XD approach include:
Lowest Total Cost of Ownership
The Liebert XD targeted cooling solution is morecost-effective than increasing the overall room airconditioning capacity using floor-mounted coolingunits only.
Total energy savings potential of up to 40% can beachieved with the Liebert XD solution.
Minimal floor space requirements allow moreroom for IT equipment.
-
6Open and Closed ArchitectureSystems as defined by ASHRAE
The open architecture systems utilize cooling coils near the heat load eitherinside or outside the open server rack andutilize the room air volume as a thermalstorage to ride through short power outages.
The closed architecture fully encloses the rack with the cooling coils inside. Other provisions are required for power loss ride through.
Liebert XD Pumped Refrigerant-BasedSystemsPumped refrigerant is ideal for use in data center environments. By eliminating the use of cooling water, it removes the chance of electrical hazards. It operates atlow pressure and becomes a gas at room temperatures,making it ideal for use around electronic equipment.
It utilizes micro-channel coil efficiency and low pressuredrop for lower operating costs. Use of pumped refrigerantalso saves space with smaller piping requirements and theability to utilize more compact heat exchangers.Pumped refrigerant is designed for medium to largecomputer rooms and data centers.
Liebert XD Water-Cooled SystemsLiebert XD water-cooled systems offer a cost-efficientcooling alternative where electrical hazards are minimal.They are also designed to work in any size space from asmall computer room to a large data center.
A Choice Of Cooling Methods
Flexible Approaches For High Heat Density Cooling
Adding targeted cooling is more cost-efficient than trying to lower the temperature of localizedhot spots by increasing the overall room air conditioning capacity. Liebert X-treme Densitymission-critical cooling systems are specificallydesigned to address the higher heat loads generated by tightly packed electronic rack enclosures. Individual systems can improve interior air flow, cool hot air ejected from theenclosure or cool hot spots near the racks.
No one offers you more ways to meet the challenges of cooling high heat density installations
than Liebert. We offer open and closed architectures, a choice of pumped refrigerant and
water-based cooling, and the widest range of equipment configurations to meet every need
from small communications equipment closets to the largest data centers.
-
7WATERBASED
PUMPEDREFRIGERANT
BASED
OPEN ARCHITECTURECLOSED ARCHITECTURE
DIRECT EXPANSION REFRIGERANT BASED
CHILLED WATER BASED
A Cooling Solution For Every High Heat Density Application
XDK-WHigh HeatDensity RackEnclosure
Liebert XDPPumping Unit
Liebert XDCRefrigerant
Chiller
XDK High Heat Density Rack Enclosure(Coming Soon)
Liebert XDOOverhead
Cooling Module
Liebert XDV Top Mounted
Cooling Module
Liebert XDHHorizontal
Row Cooler
Liebert XDCoolFrame
Module
Liebert XDP-W CoolantDistribution Unit
Liebert XDR-WRackCooler
The Liebert XD Piping system makes it easy to planand expand your Liebert XD Cooling system inresponse to a growing heat load. The key is to putthe necessary piping in place in advance and thenadd cooling units, chillers or pumping units as theneed arises for more cooling capability. The flexible connection piping allows the coolingmodules to be added or repositioned withoutinterruption in operation as needs change.
Liebert XDF High HeatDensity Rack Enclosure (Air Cooled orWater Cooled)
Liebert XDFN High HeatDensity RackEnclosure (AirCooled or WaterCooled)
Liebert XDFNHigh Heat DensityRack Enclosure(Chilled Water)
-
Liebert XD Cooling Solutions
8
LiebertXDP
LiebertXDC
LiebertXDO
The Overhead Cooling Solution
The ceiling-mounted Liebert XDO OverheadCooling Module mountsdirectly above the cold aisle.It draws in hot air from thehot aisle and then dischargescool air into the cold aislewhere the equipment airinlets are located. This energy-efficient unit takes up no floor space.
Pumping Unit Designed For Indirect ConfigurationApplications
When a building chilled water system is available, the Liebert XDPPumping Unit serves as an isolatinginterface between the buildingchilled water system and the pumpedrefrigerant circuit. It circulates refrigerant to the XD CoolingModules at a temperature alwaysabove the actual dew point to prevent condensation.
Liebert XD zone and spot cooling units are available in several configurations using
open or closed architecture and pumped refrigerant. Heat removal is provided
by either the Liebert XDC Refrigerant Chiller or a Liebert XDP Pumping Unit used in
conjunction with an existing building chilled water circuit.
The XD Solution StartsWith An InnovativePumped RefrigerantApplication
This unique application of anoff-the-shelf product makesthe Liebert XD solution veryenergy efficient. Pumpingrefrigerant as a liquid andallowing it to expand to a gasas it absorbs heat is overseven times as efficient as asingle phase fluid (water).The pumped refrigerantoperates at low pressure andbecomes a gas at roomtemperatures, making it idealfor use around electronicequipment.
Pumped Refrigerant-Based Approach
A Chiller DesignedFor Direct SystemConfigurations
The Liebert XDC Chiller is a speciallydesigned indoor unit that connectsdirectly to the Liebert XD CoolingModules and provides chilledpumped refrigerant circulation and control. It ensures that therefrigerant is constantly above the actual dew point in the room,eliminating concern about condensation. Available with several heat rejection options.
Open Architecture
LiebertHeat
Rejection
LiebertXDC
Refrigerant Chiller
LiebertXDC
Refrigerant Chiller
BuildingChilledWater
LiebertXDP
Pumping Unit
LiebertXDP
Pumping Unit
Pumped Refrigerant
Pumped Refrigerant
Pumped Refrigerant
Pumped Refrigerant
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
Indirect system configurationDirect system configuration
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
LiebertHeat
Rejection
LiebertXDC
Refrigerant Chiller
LiebertXDC
Refrigerant Chiller
BuildingChilledWater
LiebertXDP
Pumping Unit
LiebertXDP
Pumping Unit
Pumped Refrigerant
Pumped Refrigerant
Pumped Refrigerant
Pumped Refrigerant
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
Indirect system configurationDirect system configuration
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
-
9Space-SavingSolution That CoolsFrom The Top
The Liebert XDV CoolingModule mounts verticallyabove or on the IT rack enclosure, drawing hot air from inside the cabinetor from the hot aisle. Itthen cools the air and discharges it down to the cold aisle. This space-saving solution requireszero floor space.
In-Row Cooling Thats Right In Line With Your Needs
The modular Liebert XDH HorizontalRow Cooler is placed directly in linewith rack enclosures. Air from the hotaisle is drawn in through the rear ofthe unit, cooled, and then dischargedthrough the front of the unit into thecold aisle. The modular and adaptivedesign of the Liebert XDH allows it tobe easily added as the demand forcooling increases.
LiebertXDH
Liebert XDCoolFrame
A Specialized Rack Cooling Solution
Liebert XD CoolFrame module is specially designed to attach directlyto the rear of the Egenera BladeFrameEX system. The Liebert XD CoolFrameallows these racks to be placed in a data center environment around other heat-generating equipment without adding to the heat load in the room. Use of the Liebert XDCoolFrame solution can promote efficient expansion of data center capacity with a minimal impact on your critical infrastructure.
LiebertXDV
Temperature F C
95 / 35
86 / 30
77 / 25
68 / 20
60 / 16
The XDO and XDV fill the cold aisle with air atthe temperature required for proper operationof the electronic equipment.
Temperature Profile of XDO System Temperature Profile of XDV System
The Liebert XD Units Enhance The Hot Aisle/Cold Aisle Approach
Liebert XDK
These high heat density server racksutilize Liebert XD pumped refrigerantand closed architecture. The server heatload is dissipated into the cooling systemthrough a heat exchanger in the bottomof the rack. Redundant high-performance fans drive closed loop aircirculation in the racks interior, whileservers are supplied with cold air at thefront of the rack. This keeps thedissipated heat from being expelled asan additional load on the IT room as isusually the case
XDK(Coming Soon)
Closed ArchitectureH
OT
AIS
LE
COLD
AIS
LE
COLD
AIS
LE
HO
T A
ISLE
HO
T A
ISLE
Liebert XDV
HO
T A
ISLE
COLD
AIS
LE
HO
T A
ISLE
COLD
AIS
LE
HO
T A
ISLE
Liebert XDO
Side views of Computational Fluid Dynamics (CFD) by Fluent.
-
10
Liebert XDV System With8 kW Heat Load Per Rack
XDV ModuleAbove Rack
Lieb
ert D
S or
Del
uxe
Syst
em/3
Racks
Ceiling-MountedXDO Modules
Liebert XDV System With14 kW Heat Load Per Rack
Liebert XDV & XD0 System With 24 kW Heat Load Per Rack
XDP/XDC
XDP/XDC Units
XDP/XDC Units
PerforatedRaised
Floor Tile
XDV ModulesAbove Rack
XDV ModulesAbove Rack
Liebert XD Piping: The Key To Adaptability
The Liebert XD Piping system makes it easy to plan and expandyour Liebert XD Cooling system in response to a growing heat load.
The key is to put the necessary piping in place in advance and then add cooling units and pump unts /chillers as the need arisesfor more cooling capability.
This unique system allows the room cooling capacity to increase tomore than 500 Watt per square foot (5400W/m2) with no additionaldisruptive piping installation. The flexible connection piping alsoallows the cooling modules to be re-positioned without interruptionin operation.
Invest Now, Save In The Future Liebert XD Piping provides for future expansion and simplifies both the installation of additional units and the reconfiguration of components as needs change.
These computer room layouts illustrate howgrowth can be accommodated within thesame space by installing additional LiebertXD Cooling capacity.
Liebert XD Piping is pre-fabricated distribution piping that is installed inanticipation of a growing system, thenLiebert XD Cooling modules areadded, disconnected, or repositionedas required and are quickly made operational with flexible connectionpiping with quick-connect fittings.
Lieb
ert D
S or
Del
uxe
Syst
em/3
Lieb
ert D
S or
Del
uxe
Syst
em/3
Lieb
ert D
S or
Del
uxe
Syst
em/3
Lieb
ert D
S or
Del
uxe
Syst
em/3
Lieb
ert D
S or
Del
uxe
Syst
em/3
-
11
Open ArchitectureThe Heart of the Water-based SystemThe Liebert XDP-W Coolant PumpingUnit is the key to the performance, efficiency and space saving of the LiebertXDR-W RackCooler and Liebert XDK-Wwater- cooled rack enclosure. The unithouses the isolating heat exchangerbetween the Liebert XDR-W/XDK-W circuitfluid and building chilled water, the controlvalve, the dual redundant pumps and thesystem controls. It controls the fluidtemperature above the actual roomdewpoint. The Liebert XDP-W can be usedwith other brands of rack coolingequipment.
Liebert XDK-WUtilizing closed air circulation, theracks are completely sealed from room air. The server heat load is dissipated into the process chilledwater system through an air-to-waterheat exchanger in the bottom of therack. Redundant high-performancefans drive closed loop air circulation in the racks interior, while servers are supplied with cold air at the frontof the rack.
LiebertXDP-W
LiebertXDR-W
Liebert XD Cooling Solutions
Closed Architecture
XDK-W
Water-Cooled Based Approach
BuildingChilledWater
LiebertXDP-W
Liebert XDR-W or XDK-W
Liebert XDR-W or XDK-W
Liebert XDR-W or XDK-W
Liebert XDR-W or XDK-W
Water
WaterLiebertXDP-W
Indirect system configuration
Up to 12 Liebert XDR-Wunits can be piped to eachcoolant distribution unit.
Liebert XDR-W modulesare connected via quick-connect ports to a Liebert XDP-W thatcontrols coolant flow and acts as an interfacewith your buildingschilled water systemthrough a heat exchanger.
BUILDINGCHILLED WATERLOOP
HEATEXCHANGER
2-WAY VALVE CONTROLSSECONDARY FLUID ABOVE ROOM DEWPOINT
DUALPUMPS
Hydraulic Schematic
Liebert RackCoolerThe Liebert XDR-W Rack Cooler utilizes a cooling unit that is attached tothe back door of the enclosure. Fans in the module move air from the equipmentin the rack, through a cooling coil andexpel it from the back of the unit, chilledto the point where the impact on theroom is close to neutral. This makes the Liebert XDR-W an ideal solution inapplications where the hot aisle/cold aisle arrangement is not practical. The Liebert XDR-W can be configured to eliminate hot spots or uneven heat loads within the room.
-
12
Liebert XD Cooling Solutions
Direct Expansion Refrigerant Based Approach
Cooling For High Heat Density Racks In 60hZ Applications
The Liebert XDF includes integrated high capacity cooling that providesthe benefits of big room support in a cost-effective package to create anintegrated, mission-critical protection system for sensitive electronics. Advantages include:
Digital scroll compressor for continual and precise adjustments in cooling, resulting in lower energy costs.Optimized horizontal air circulation cools protected equipment, both in standard mode and in the unique backup ventilation mode. Automatic back-up ventilation feature ensures room air circulationthrough the rack in case of a failure.Control and monitoring provided through a cabinet-mounted Liebert iCOM control system, providing local and remote access tomonitoring of conditions within the enclosure.The air-cooled Liebert XDF is a fully self-contained plug-and-play rack-enclosure system that requires only an AC power connection to protect up to 36U of equipment.Water or glycol-cooled units use remote heat rejection to support the in-rack cooling system and protect up to 42U of equipment.Business-critical power protection provided through optional Liebert GXT rack-mounted UPS. Liebert MP Advanced Power Strips available to provide power control at the receptacle level.
Closed Loop Cooling For High Heat Density RacksIn 50hZ Applications
The Liebert XDFN is an integrated equipment cabinet with built in cooling, power distribution, monitoring and fire extinguishing systemoffering full redundancy and back-up ventilation. The Liebert XDFNfeatures a 42U rack that provides these advantages:
Self-contained cooling module is a modular direct expansion unitwith remote air cooled condenser or water cooled condenser.Digital scroll compressor for continual and precise adjustments incooling, resulting in lower energy costs.The modular design of Liebert XDFN allows for racks and cooling modules to be combined, in order to provide cooling to multiple racks.Back-up ventilation system ensures circulation through the rack of the air coming from the room in case of cooling module or power failureN+1 redundancy configuration utilizes one redundant coolingmodule ready to be activated in case of failure or maintenance ofone of the running units. Control and monitoring provided through a cabinet-mounted Liebert iCOM control system, providing local and remote access to monitoring of conditions within the enclosure.Business-critical power protection provided through optional Liebert GXT rack-mounted UPS. Liebert MP Advanced Power Strips available to provide power control at the receptacle level.
Liebert XDF High Heat Density
Rack Enclosure (Air Cooled or Water Cooled)
Liebert XDFN High Heat Density
Rack Enclosure (Air Cooled, Water Cooled
or Chilled Water)
Extreme density electronic equipment is turning up in many non-conventional spaces spaces without the benefit
of computer room air conditioning to provide cooling for the generated heat loads. This rack-based equipment
must be protected with the same level of air, power and physical security support as a conventional computer
room, but with the economies of scale and price in mind.
-
13
Pumped Refrigerant
Based vs.
Water-Based System
Comparisons
Pumped Refrigerant Based System
Advantagesn No water in data center No risk if a leak occurs n Higher energy efficiency n Smaller piping requirements
Other Considerationsn Possible compatibility issues with small rooms n Higher fluid costn Piping must be overhead
Water-Based System
Advantagesn Lower fluid cost n No limitation to room size
Other Considerationsn May require fluid treatment to prevent fouling
Open Architecture System
Advantagesn Ride-through/redundancy on room leveln Lower first cost and lower operating costn No limits on rack selectionn Plug and Play modules allow easy
capacity increases if needed later
Other Considerationsn Mainly a room or zone solution
Closed Architecture System
Advantagesn Low audible noisen Deployable as a single rackn Does not require Data Center to be in a hot
aisle/cold aisle configuration
Other Considerationsn Shorter ride-through time on cooling system loss n Fixed capacity, can not increase capacity later
Only Liebert Offers A Real Choice In Protection Solutions
The wide variety of system architecture and cooling methods offered by the Liebert XD Series means you can find
a perfect fit for any high heat density application within your data center, computer room or network closet.
Open vs. Closed
Cooling Architecture
System Comparisons
-
Tota
l Dat
a C
ente
r C
ost
(les
s la
nd
)($
000)
Cooling System
Data Center Cost (New Construction)
Liebert XD - Supplemental Cooling Requires less Chiller Capacity
Liebert XD - Supplemental Cooling with Lower Operating Costs
$30,000
$25,000
$20,000
$15,000
$10,000
$5,000
$0
Building Cost Less Cooling
50 W/sq.ft(500 W/m )
150 W/sq.ft(1500 W/m )
Fixed Load of 4,000 kW
400 W/sq.ft(4000 W/m )
Building Size
2 2 2
Power Usage
0.00
0.10
0.20
0.30
0.40
0.50
0.60
CW CRAC at 100% Capacity
CW CRACat 50%
Capacity
Liebert XD at 100% Capacity
Liebert XD at 50%
Capacity
kW p
ower
to c
oo
l 1 k
W o
f sen
sib
le h
eat
FanPump (XD)Pump (CW)Chiller
Chiller Capacity
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
CW CRAC Liebert XD
kW C
hill
er C
apac
ity
per
kW
O
f Sen
sib
le H
eat
Load
Latent LoadFan LoadSensible Load
15% Lower
27% Lower
32% Lower
80,000 sq.ft.8,000 m2
27,000 sq.ft.2,700 m2
10,000 sq.ft.1,000 m2
Tota
l Dat
a C
ente
r C
ost
(les
s la
nd
)($
000)
Cooling System
Data Center Cost (New Construction)
Liebert XD - Supplemental Cooling Requires less Chiller Capacity
Liebert XD - Supplemental Cooling with Lower Operating Costs
$30,000
$25,000
$20,000
$15,000
$10,000
$5,000
$0
Building Cost Less Cooling
50 W/sq.ft(500 W/m )
150 W/sq.ft(1500 W/m )
Fixed Load of 4,000 kW
400 W/sq.ft(4000 W/m )
Building Size
2 2 2
Power Usage
0.50
0.60
sen
sib
le h
eat
FanPump (XD)Pump (CW)Chill
Chiller Capacity
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
CW CRAC Liebert XD
kW C
hill
er C
apac
ity
per
kW
O
f Sen
sib
le H
eat
Load
Latent LoadFan LoadSensible Load
15% Lower
80,000 sq.ft.8,000 m2
27,000 sq.ft.2,700 m2
10,000 sq.ft.1,000 m2
14
Liebert XD Solutions Cut Capital Costs...
The capital costs of a data center are significantly reduced as higherdensities of IT equipment are housed in smaller sized areas.
Study Data Center Cost (New Construction) 400 racks with an averageheat load of 10 kW each. Cost for building, power, cooling, lighting, fire protection, security, etc. included. Cost of land not included.
Building 1: 80,000 sq.ft. (8000m2), 18" (450mm) Raised Floor, Designed for 50 W/sq.ft (500W/m2), Raised-floor Precision Air Conditioning units for cooling.
Building 2: 27,000 sq.ft. (2700m2), 36" (900mm) Raised Floor. Designed for 150 W/sq.ft (1500W/m2), Raised-floor Precision Air Conditioning units for cooling.
Building 3: 10,000 sq.ft. (1000m2), 18" (450mm) Raised Floor. Designed for 400 W/sq.ft (4000W/m2), Raised-floor Precision Air Conditioning units (for basic cooling and humidity control) and Liebert XD.
Investing in a facility that utilizes a higher rack density design along with a cooling system designed especially
for this type of installation offers a significant cost savings advantage in terms of building size and energy usage.
The flexible configuration of the Liebert XD system modules also allows scalability for future growth, as well as
the ability to efficiently add redundant units for maximum reliability in the most mission-critical applications.
The Liebert XD approach significantly improves floor space utilization compared to an installation using only
floor-mounted cooling units. Because of the variety of cooling module sizes and placement, installing more XD
capacity uses little or no additional floor area.
The smaller chiller plant and lower fan load result in significant energysavings as well. A 27% energy savings is very conservative.
Tota
l Dat
a C
ente
r C
ost
(les
s la
nd
)($
000)
Cooling System
Data Center Cost (New Construction)
Liebert XD - Supplemental Cooling Requires less Chiller Capacity
Liebert XD - Supplemental Cooling with Lower Operating Costs
$30,000
$25,000
$20,000
$15,000
$10,000
$5,000
$0
Building Cost Less Cooling
50 W/sq.ft(500 W/m )
150 W/sq.ft(1500 W/m )
Fixed Load of 4,000 kW
400 W/sq.ft(4000 W/m )
Building Size
2 2 2
Power Usage
0.00
0.10
0.20
0.30
0.40
0.50
0.60
CW CRAC at 100% Capacity
CW CRACat 50%
Capacity
Liebert XD at 100% Capacity
Liebert XD at 50%
Capacity
kW p
ower
to c
oo
l 1 k
W o
f sen
sib
le h
eat
FanPump (XD)Pump (CW)Chiller
Chiller Capacity
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
CW CRAC Liebert XD
kW C
hill
er C
apac
ity
per
kW
O
f Sen
sib
le H
eat
Load
Latent LoadFan LoadSensible Load
15% Lower
27% Lower
32% Lower
80,000 sq.ft.8,000 m2
27,000 sq.ft.2,700 m2
10,000 sq.ft.1,000 m2
One of the major areas of savings identified with the use of Liebert XD equipmentis the fact that the chiller plant size can be reduced. This is because the chillertypically is sized for the total gross capacity of the raised-floor cooling units.The 65% lower fan load of the Liebert XD System modules and the fact theyare 100% sensible easily results in a capital chiller size savings of 15% or more.
-
15
And Save Significant Energy Dollars
The Liebert XD CoolingSolution Saves Floor Space
Heres a typical example of how implementation
of the Liebert XD solution can impact life cycle
costs. The example compares two data center
layouts housing a total of 40 server racks with a
capacity of 16 kW each.
Raised-Floor Cooling OnlyEight 30-Ton (105 kW) Precision Air Conditioners N+2 redundancy284 Tons (998 kW) chiller plant3000 sq. ft. (300m2)
Raised-Floor And Liebert XD CoolingTwo 20-Ton (70 kW) Precision Air Conditioners and 60 zero-footprint high heat density coolingmodules 33% redundancy182 Tons (640 kW)Chiller Plant1500 sq. ft.(150m2)
Here are two solution possibilities to be considered:The raised-floor only approach of System 1 requires eight 30 Ton (105 kW) floor-mountunits (6 primary, two redundant), 3000 sq. ft. (300 m2) of raised floor space due to theneed for 6 foot (1.8m) cold aisles to handle the air flow requirements and a 284 Ton (998 kW) chiller plant.
With the raised-floor and Liebert XD cooling solution of System 2, the facility requiresonly two 20-Ton (70 kW) floor-mount units (one primary, one redundant) in half the floor space. Even with more redundancy, the chiller plant size is cut by 30% and energyconsumption reduced by 40% per year. Here are the specifics on these numbers:
The significant energy savings achievedby the Liebert XD solution are, in greatpart, due to several factors. n The cooling units are located closer to
the load, which results in less mixing ofhot and cold air.
n The fans can be optimized for a verylow total system static pressure thanksto the micro channel coils and no pressure drop losses in ducts.
Capital Cost Comparison
The sensible load is based on 40 racks times 16 kW each. But the chiller plant is sized tohandle the gross total capacity of the raised-floor units. Only six raised-floor units areused for this calculation, but the cooling units at the rating conditions of 72 (22 C)/50%humidity have a relatively high latent capacity requirement and the fan load needs to beadded back to the chiller load. The Liebert XD System hybrid approach requires 1/3 lesschiller plant capacity, also less diesel generator and switchgear capacity required. Aconservative estimate is a savings of over $60,000 in capital costs.
Capital SavingsChiller at $400 / Ton = $40,000Diesel Generator / Switchgear capacity reduction 360 kW / 450 KVA =$20,000Total Savings =$60,000
Customers are also finding they do notneed to over chill their data centers to eliminate the hot spots as they have had to do with the raised-floor coolingonly approach. They no longer need the cold aisle to be 62F (17C) in someplaces to maintain the desired 70F (21C)in other areas experiencing the hotbypass air.
Energy System 1 System 2 kW ea Qty / kW Qty / kW Savings
Chiller per Ton 0.9 284 / 256 184 / 16630 Ton CRAC 7.5 8 / 60 2 / 415 Ton CRAC 2.2 8 / 60 2 / 4Liebert XDO 0.37 20 / 7Liebert XDV 0.2 40 / 8Liebert XDP 1.7 4 / 7Total kW 316 192 124Cost / year @ $0.10 /kWhr $276,816 $168,192 $108,624Operational CostsMaintenance $6,400 $1,600 $4,800 Humidifier $5,400 $1,350 $4,050 Total Annual Savings $117,474
Total First Year Savings $184,624 10 month payback
System 1 System 2 SavingsNet Sensible Load 2,184,320 2,184,320Total Gross Load 3,405,600 2,208,500Chiller Tons Required 284 184 100 (351 kW)
XDP
-
Emerson Network Power.The global leader in enabling Business-Critical Continuity.
EmersonNetworkPower.com
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Racks & Integrated Cabinets
Services
Precision Cooling Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2005 Emerson Electric Co.
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2005 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-11265 (R06/07) Printed in USA
Ensuring The High Availability OfMission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity,
ensures network resiliency and adaptability through a family of technologies
including Liebert power and cooling technologies that protect and support
business-critical systems. Liebert solutions employ an adaptive architecture that
responds to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility, and reduced capital
equipment and operating costs.
-
Key Features n Increases air flow through rack
enclosures that have obstructed
air patternn Redundant fans and dual power
feeds for continuous availability.n Gives maximum uptime by
providing redundancy and
continuous availability through
dual power feeds (A and B).n Two available mounts per rack,
inside or outn Compatible with most rack
enclosuresn Perfect in combination with
Liebert Deluxe unitsn Complete kit includes:
n XDA assembly (fans, dual
power cords & main switch).n Assembly positioning tooln Cable grommetn Excess door perforation
covering
Easily-Installed Fan Unit Increases Enclosure Air FlowLiebert XDA Air Flow Enhancer
Liebert XDA Air Flow Enhancer increases
the air flow through densely populated
enclosures, past congested cabling,
removing hot spots within the enclosure
that can threaten the uptime of your
critical systems.
Server fans often produce
insufficient flow to push air through
the masses of data communication
wiring at the rear of the enclosure.
But with a Liebert XDA placed on the
exhaust side of the enclosure, the
five high-static fans ensure positive
air flow, moving heat out of the
enclosure and into the room where
it can be removed by the room air
conditioning system.
Each unit is rated for 1000 CFM
(@60Hz). The unit mounts on the
rear (inside or outside) of any
standard rack (minimum 60" height).
Two XDA units mounted side by
side on the rear of a rack enclosure
(2000 CFM capacity) move a nominal
14 KW heat load.
Liebert XDA features dual power
cords for continuous availability.
They are easy to install and
compatible with most rack
enclosures.
Precision Coolingfor Business-Critical Continuity
-
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumesno responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
2005 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-16605 (R11/05) Printed in USA
Emerson Network Power.The global leader in enabling business-critical continuity.
AC Power SystemsConnectivityDC Power SystemsEmbedded PowerInbound PowerIntegrated Cabinet SolutionsOutside PlantPrecision CoolingSite Monitoring and Services
Emerson Network Power and the EmersonNetwork Power logo are trademarks andservice marks of Emerson Electric Co. 2005 Emerson Electric Co.
Technical Data
Nominal Capacity 1000 CFMInput Voltage 120 V, 1 , 60 Hz
230 V, 1 ,50/60 HzFull load amps 1.5 A @ 120 VHeight 56"Width 8"Depth 2.25"Weight, unit only 27 lbs
-
Precision Cooling For Business-Critical Continuity
Specifically Designed To Support The Modules In The Liebert XD SystemLiebert XDC Refrigerant Chiller
The Liebert XDC Refrigerant Chiller is a part of Lieberts highlyenergy-efficient high heat density cooling system Liebert XD.
The system can cool more than 30kW per rack and
uses pumped refrigerant, which is ideal for use around
electronic equipment.
Liebert XDC is specifically designed to support the
Liebert XDO, XDV, XDH and CoolFrame modules. The
XDC is an indoor unit that connects directly to the XD
cooling modules and it provides refrigerant circulation
and control while maintaining the refrigerant at a
temperature always above the actual dewpoint.
The packaged unit includes Enclosure, Pumps, Heat
Exchanger, Scroll Compressors, Receiver Tank, Controls,
Valves and Piping. The XDC is available in an air cooled
configuration with remote condenser.
Key Features n Energy Efficientn Floor Space Efficientn Scalablen Easy to Install
-
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
Technical Data
Nominal Capacity, 60 Hz 160 kW / 46 TonNominal Capacity, 50 Hz 130 kW / 37 TonInput Voltage 460 V, 3 ph, 60 Hz
380/415 V, 3 ph, 50 HzFull load amps 79 AHeight 78 (1981 mm)Width 74 (1879 mm)Depth 34 5/8 (879mm)Weight, empty 1800 lbs (817 kg)
The indoor Liebert Refrigerant Chiller is specifically designed to
support the Liebert XD cooling modules. The XDC connects
directly to the modules through the pumped refrigerant.
When a building chilled water system is available, the Liebert XDP
Pumping Unit is utilized as an interface between the pumped
refrigerant circuit and the chilled water system. Both the XDC
and the XDP units circulate the refrigerant to the XD modules,
while maintaining the refrigerant at a temperature always above
the actual dewpoint.
Liebert XD Hydraulic System Schematic
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-16670 (R12/07) Printed in USA
Business-Critical Continuity, Emerson NetworkPower and the Emerson Network Power logoare trademarks and service marks of EmersonElectric Co. 2007 Emerson Electric Co.
LiebertHeat
Rejection
LiebertXDC
Refrigerant Chiller
LiebertXDC
Refrigerant Chiller
PumpedRefrigerant
PumpedRefrigerant
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
Direct system configuration
BuildingChilledWater
LiebertXDP
LiebertXDP
PumpedRefrigerant
PumpedRefrigerant
Indirect system configuration
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
-
Precision Cooling For Business-Critical Continuity
Liebert XDFRack Enclosure With Integrated High Density Cooling
Extreme density electronic equipment is turning up in many non-traditional spaces
spaces without the benefit of computer room air conditioning to provide cooling
for the generated heat loads. This rack-based equipment must be protected with the
same level of air, power and security support as a conventional computer room, but
with the economies of scale and price in mind.
Key Features n Integrated high density cooling
with horizontal air flown Automatic back-up ventilation n 2 Configurations:
n Air Cooled, Self Contained with
integrated condensern Water Cooled
n Digital scroll compressor
for precise and energy-
efficient operationn Quickly deployablen Liebert iCOM intelligent
controlsn Remote monitoringn Compatible with Liebert
rackmount UPS and power strips
Ideal Applicationsn High density equipment
requiring individualized
cooling and protection:n Warehousesn Small computer roomsn Closets and sheltersn Data centers
n RFIDn VolPn Disaster recovery operations
Liebert XDF is high density
cooling integrated into a secured
rack enclosure, providing the
benefits of big room support in a
cost-effective package. Optimized
horizontal air circulation cools the
protected equipment, both in
standard mode and in backup
ventilation mode. Control and
monitoring are accomplished
with the cabinet-mounted Liebert
iCOM control system. In addition,
optional Liebert UPS, advanced
power strips and remote
monitoring systems are available
to customize the level of support
to individual equipment needs.
Air Cooled, Self Contained version, Front Water Cooled
Air Cooled, Self Contained version,With Open Side Panel
-
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2006 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-17005 (R10/06) Printed in USA
Emerson Network Power and the EmersonNetwork Power logo are trademarks andservice marks of Emerson Electric Co. 2006 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
Condenser Fan
EvaporatorFans
Digital ScrollCompressor
Power CordConnections
EvaporatorCoil
Air InletDamper
Air ExitDamper
GraphicControlDisplay
Technical Data
Liebert XDF Air Cooled, Water CooledSelf Contained
Overall Unit Height, With Casters 82.5" (2095mm) 82.5" (2095mm)
Overall Unit Width 35" (890mm) 35" (890mm)
Overall Unit Depth, Footprint 48" (1219mm) 48" (1219mm)
Rack Width 19" (483mm) EIA 19" (483mm) EIA
Rack Height 36U 42U
Adjustable Rack Depth, Max 32.1" (815mm) 32.1" (815mm)
Adjustable Rack Depth, Min 24.4" (620mm) 24.4" (620mm)
Weight, empty 800 lbs (360 kg) 750 lbs (338 kg)
Max Weight Filled 2000 lbs (907kg) 2000 lbs (907kg)
Sound Power Level 86 dBA 79 dBA
Nominal Cooling Capacity*** 14.4 kW (4.1Ton) 14.4 kW (4.1Ton)
Nominal Air Flow 2100 CFM (3500 m3/h) 2100 CFM (3500 m3/h)
Input Voltage 120V, 1ph, 60Hz* and 208V, 3ph, 60Hz**
Full Load Amps 7.7A* and 15.7A** 5.0A* and 15.7A**respectively, 60Hz respectively, 60Hz
Local and Remote Monitoring Capabilities
iCOM allows for local or remote monitoring of the
conditions in the Liebert XDF to protect critical rack compo-
nents. Options are available for connecting to
Liebert remote monitoring devices or for BMS (Building
Management System) interface via MODbus or SNMP.
The menu driven display is organized into three main sec-
tions: User Menus, Service Menus and Advanced Menus.
iCOM Control Display
Standard Mode (SelfContained Unit Shown)
Back-Up Ventilation Mode(Self Contained Unit Shown)
Front Rear
* For controls and evaporator and condenser fans power supply.** For compressor power supply
*** At rating 95F amb, 77F supply air to load
-
Precision Cooling For Business-Critical Continuity
The modular, Liebert XDH Horizontal Row
Cooler provides efficient and economical
cooling for high heat density equipment.
The Liebert XDH is placed in line with rack
enclosures and air from the hot aisle is
drawn in through the rear of the unit,
cooled, and discharged into the cold aisle
where the electronic equipment air inlets
are located. The Liebert XDH draws
directly from the hot aisle, allowing the
unit to take advantage of higher heat
transfer efficiency.
The Liebert XDH is a part of our highheat-density cooling product familythat utilizes pumped refrigeranttechnology.The pumped refrigerantoperates at low pressure in the systemand becomes a gas at roomconditions, making it ideal for usearound electronic equipment.
Since the Liebert XD system alwaysprovides 100% sensible capacity, theneed for humidification is significantlyreduced, further reducing energy usage and maintenance.
The modular and adaptive design of the Liebert XDH unit also allows it to be easily added as the demand forcooling increases.
The Liebert XDH Offers Many Benefits:
Reliability:Can cool more than 30 kW
per rack.
Dual (A and B) detachable power
cords for increased uptime.
Uses pumped refrigerant
which is ideal for use around
electronic equipment.
Two pumped refrigerant circuits.
Flexibility:Complements Liebert precision
cooling units.
Optional pre-charged flexible
piping with threaded quick
connect fittings allows adaptive
and scalable expansion without
interruption of cooling operations.
Flexible installation.
Complete packaged unit includes
enclosure, coils, controls, fans
and piping.
Low Total Cost Of Ownership:Superior cost for cooling per high
heat density rack.
Highly energy efficient.
Liebert XDH Horizontal Row CoolerCooling For High Heat Density Equipment
-
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2006 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-17200 (R10/06) Printed in USA
Business-Critical Continuity, Emerson NetworkPower and the Emerson Network Power logoare trademarks and service marks of EmersonElectric Co. 2006 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
Liebert XDH SpecificationsModel Size XDH20 XDH32Nominal Capacity, 60 Hz1 22 kW /6.3 Ton 30 kW / 8.5 TonNominal Capacity, 50 Hz 2 19 kW /5.4 Ton 27 kW / 7.7 TonNominal Airflow, 60 Hz 2500 CFM (4200 m3/h) 4000 CFM (6800 m3/h) Nominal Airflow, 50 Hz 2100 CFM (3500 m3/h) 3300 CFM (5600 m3/h)Input Voltage 120 V, 1 ph, 60 Hz
230 V, 1 ph, 50 HzPower Draw 500 W 1200 WFull load amps 4.2 A @ 120V 10.5 A @ 120VNumber of Fans 6Sound Power Level 81 dBA 86 dBAHeight (unit only) 78 (1982 mm)Width 12 (300 mm)Depth 42 (1066 mm)Weight 246 lbs (112 kg)Options Quick Connect Couplings (for Flexible Piping)
Condensate Detection (dry contacts)Diffuser for front air discharge to both sides or to one side.
1 Nominal Capacity Rating @ 55F (13C) Entering Fluid Temperature and 98F (37C) Entering Air Temperature. Max Capacity @ 55F (13C) EFT and 105F (40C) EAT is 25.5 kW and 34.5 kW, respectively.
2 Nominal Capacity Rating @ 55F (13C) Entering Fluid Temperature and 98F (37C) Entering Air Temperature. Max Capacity @ 55F (13C) EFT and 116F (47C) EAT is 25.5 kW for XDH20 and 34.5 kW @ 108F (42C) EAT for XDH32.
Building Chilled Water Liebert
XDPPumped Refrigerant
Liebert XD ModulesLiebert
XDP
Liebert Heat
Rejection
Pumped Refrigerant
Liebert XDC
Liebert XD Modules
Direct System
Indirect System
The indoor Liebert XDC RefrigerantChiller is specifically designed tosupport Liebert XD cooling modules.The Liebert XDC connects directly to the XD Modules.
When a building chilled watersystem is available, the Liebert XDPPumping Unit is utilized as aninterface between the pumpedrefrigerant circuit and the chilledwater system.
Both the Liebert XDC and the XDPunits circulate the refrigerant toLiebert XD units, while maintainingthe refrigerant at a temperaturealways above the actual dewpoint.
-
Precision Cooling For Business-Critical Continuity
Liebert XDO Overhead Cooling ModuleSensible Spot And Zone Cooling For High Heat Density Equipment
Flexibility: n Can cool more than
500 W/sq.ft. (5400 W/m2).n No floor space required.n Complements the cooling of
Liebert precision cooling units.n Excellent for spot and
zone cooling.n Scalable.n Flexible installation with
several connection possibilities.n Optional pre-charged flexible
piping with threaded quick-
connect fittings allows adaptive
and scalable expansion without
interruption of cooling operations.n Possible to be fully installed
from an existing cold aisle
without the need for reaching
over existing racks.
Higher Availability:n Uses pumped refrigerant,
which is ideal for use around
electronic equipment.n Complete packaged unit includes
enclosure, coils, fan and piping.
Lowest Total CostOf Ownership:n Superior cost for cooling per high
heat density rack.n Highly Energy Efficient.
The ceiling mounted Liebert XDO
overhead cooling module provides
sensible spot and zone cooling for
high heat density equipment.
The Liebert XDO draws in hot air through two
opposite inlets and discharges cool air down into the
cold aisle where the electronic equipment air inlets are
located. This flexible, scalable and space saving product
mounts to the ceiling requiring zero floor space.
The Liebert XDO is a part of our high heat-density
cooling product family that utilizes pumped refrigerant
technology. The pumped refrigerant operates at low
pressure in the system and becomes a gas at room
conditions, making it ideal for use around electronic
equipment. Since the Liebert XDO always provides
100% sensible capacity, the need for humidification
is significantly reduced, further reducing energy
usage and maintenance.
-
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-16665 (R05/07) Printed in USA
Business-Critical Continuity, Emerson NetworkPower and the Emerson Network Power logo aretrademarks and service marks of EmersonElectric Co. 2007 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
Technical DataXDO16 XDO20
Nominal Capacity, 60 Hz1 17.2 kW / 5 Ton 20 kW / 5.7 Ton Nominal Capacity, 50 Hz1 17.1 kW / 4.9 Ton 17.7 kW / 5 TonNominal Airflow, 60Hz 2700 CFM (4590 m3/h)Nominal Airflow, 50Hz 2250 CFM (3820 m3/h)Input Voltage 120 V, 1 ph, 60 Hz
220-240 V, 1 ph, 50/60 HzFull load amps 2.7A @ 120V, 1ph, 60 Hz
1.5A @ 230V, 1ph, 50 HzAudible Noise, 60 Hz / 50 Hz 85 dBa / 83 dBa Sound PowerHeight, module only 22.5 (572 mm)Width 72.0 (1829 mm)Depth 24 (610 mm)Weight, empty 150 lbs (68 kg)Options Condensate Detection (dry contacts)
Quick Connect Couplings (for Flexible Piping)
HO
T A
ISLE
COLD
AIS
LE
HO
T A
ISLE
COLD
AIS
LE
HO
T A
ISLE
The Liebert XDO systems work extremely well with the "hot aisle-cold aisle" approach.
BuildingChilledWater Pumped
Refrigerant
LiebertXDO
Pumped Refrigerant
LiebertXDO
LiebertXDO
Liebert XDP
Liebert XDP
The indoor Liebert XDC refrigerant chiller isspecifically designed to support Liebert XDcooling modules. The Liebert XDC connectsdirectly to the XD modules.
When a building chilled water system isavailable, the Liebert XDP pumping unit is utilized as an interface between thepumped refrigerant circuit and the chilledwater system.
Both the Liebert XDC and the XDP unitscirculate the refrigerant to Liebert XD units, while maintaining the refrigerant at a temperature always above the actual dewpoint.
Liebert Heat
Rejection
Pumped Refrigerant Liebert XDO
Liebert XDCRefrigerant
Chiller
Liebert XDO
Direct System
Indirect System
Liebert XD Hydraulic System Schematic
1Nominal Capacity Rating is @ 55F (13C) Entering Fluid Temperature and 92F (33C) Entering Air Temperature.Max capacity 60Hz: XDO16 - 17.2kW @ 90 F (32 C), XDO20 - 23kW @ 100 F (38 C)Max capacity 50Hz: XDO16 - 17.2kW @ 93 F (34 C), XDO20 - 23kW @ 103 F (39 C)
-
Precision Cooling For Business-Critical Continuity
The Liebert XDP Pumping Unit is part of the the highly energy-efficient, high heat density Liebert XD cooling system.
The system can cool more than 30 kW per rack and
utilizes pumped refrigerant, which is ideal for use
around electronic equipment. Liebert XDP is specifically
designed to support the Liebert XDO, XDV, XDH and
CoolFrame modules. The XDP is an interface between
the pumped refrigerant circuit and the building chilled
water system. The XDP circulates the refrigerant to the
Liebert XDV modules while maintaining the refrigerant
at a temperature always above the actual dewpoint.
The packaged unit includes Enclosure, Pumps, Heat
Exchanger, Receiver Tank, Controls, Valves and Piping.
Key Features n Energy Efficientn Redundant Pumpsn Floor Space Efficientn Scalablen Easy to Install
Specifically Designed To Support The Modules In The Liebert XD SystemLiebert XDP Pumping Unit
-
Technical Data
Nominal Capacity, 60 Hz 160 kW / 46 TonNominal Capacity, 50 Hz, 140 kW / 40 TonInput Voltage 208 V, 3 ph, 60 Hz
460 V, 3 ph, 60 Hz380/415 V, 3 ph, 50 Hz
Full load amps 2.1 A @ 460 V, 3 ph, 60 Hz2.3 A @ 380/420 V, 3 ph, 50 Hz
Height 78 (1981mm)Width 38 (965mm)Depth 34 (864mm)Weight, empty 821 lbs (372 kg)
The indoor Liebert XDC Refrigerant Chiller is specifically designed to
support the Liebert XD cooling modules. The XDC connects directly to
the modules through the pumped refrigerant circuit.
When a building chilled water system is available, the Liebert XDP
Pumping Unit is utilized as an interface between the pumped refrigerant
circuit and the chilled water system. Both the XDC and the XDP units
circulate the refrigerant to the XD modules, while maintaining the
refrigerant at a temperature always above the actual dewpoint.
Liebert XD Hydraulic System Schematic
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.
SL-16640 (R12/07) Printed in USA
Business-Critical Continuity, Emerson NetworkPower and the Emerson Network Power logoare trademarks and service marks of EmersonElectric Co. 2007 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
LiebertHeat
Rejection
LiebertXDC
Refrigerant Chiller
LiebertXDC
Refrigerant Chiller
PumpedRefrigerant
PumpedRefrigerant
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
Direct system configuration
BuildingChilledWater
LiebertXDP
LiebertXDP
PumpedRefrigerant
PumpedRefrigerant
Indirect system configuration
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
XD Cooling Module/Rack
-
Precision Cooling For Business-Critical Continuity
Liebert XDV Vertical Top Cooling ModuleSensible Spot And Zone Cooling For High Heat Density Equipment
Flexibility:n Can cool more than 10 kW per rack.n No floor space required.n Complements Liebert precision cooling units.n Optional pre-charged flexible piping with threaded
quick connect fitting allows adaptive and scalableexpansion without interruption of cooling operations.
n Flexible installation mounts on top of the cabinet or suspended from the ceiling.
n Excellent for spot and zone cooling.
Higher Availability:n Uses pumped refrigerant, which is ideal for use around
electronic equipment.n Dual (A and B) detachable power cords for
increased uptime.n Complete packaged unit includes enclosure, coil,
controls, fans and piping.
Lowest Total Cost Of Ownership: n Highly Energy Efficient.n Superior cost for cooling per high heat density rack.
The Liebert XDV top-mounted cooling module provides sensiblespot and zone cooling for high heat density equipment.
This flexible, scalable and space saving product mounts
on top of the cabinet or suspended from the ceiling,
requiring zero floor space. The modular and adaptive
design of the Liebert XDV unit also allows it to be easily
added as the demand for cooling increases.
It can either draw in hot air directly from inside the
cabinet or from the hot aisle, and discharge cool air
down into the cold aisle where the electronic
equipment air inlets are located
The Liebert XDV is a part of our high heat-density
cooling product family that utilizes pumped refrigerant
technology. The pumped refrigerant operates at low
pressure in the system and becomes a gas at room
conditions, making it ideal for use around electronic
equipment. Since the Liebert XD system always
provides 100% sensible capacity, the need for
humidification is significantly reduced, further
reducing energy usage and maintenance.
-
BuildingChilledWater Pumped
Refrigerant
LiebertXDV
Pumped Refrigerant
LiebertXDV
LiebertXDV
Liebert XDP
Liebert XDP
Technical DataXDV8 XDV10
Nominal Capacity, 60 Hz1 8.8 kW / 2.5 Ton 10 kW / 2.8 TonNominal Capacity, 50 Hz1 8 kW / 2.3 Ton 8 kW / 2.3 TonNominal Airflow, 60 Hz 1000 CFM (1700 m3/h)Nominal Airflow, 50 Hz 830 CFM (1410 m3/h)Input Voltage 120 V, 1 ph, 60 Hz
230 V, 1 ph, 50/60 HzFull load amps 2A @ 120V, 1ph, 60 Hz
1A @ 230V, 1ph, 50 HzAudible Noise, 60 Hz / 50 Hz 78 dBa / 73 dBa Sound PowerHeight, module only 14 (355 mm)Width 23 (581 mm)Depth 29.5-39.5 (749-1003 mm)Weight, empty 77 lbs (35 kg)Options Quick Connect Couplings (for Flexible Piping)
Condensate Detection (dry contacts)1 Nominal Capacity Rating is @ 55F (13C) Entering Fluid Temperature and 98F (37C) Entering Air Temperature.
Max capacity 60Hz: XDV8 - 8.8kW @ 95 F (35 C), XDV10 - 11.8kW @ 106 F (41 C)Max capacity 50Hz: XDV8 - 8.8kW @ 103 F (39 C), XDV10 - 11.8kW @ 116 F (47 C)
The indoor Liebert XDC refrigerant chiller isspecifically designed to support the LiebertXD cooling modules. The Liebert XDCconnects directly to the XD modules.
When a building chilled water system isavailable, the Liebert XDP pumping unit is utilized as an interface between thepumped refrigerant circuit and the chilledwater system.
Both the Liebert XDC and the XDP unitscirculate the refrigerant to Liebert XD units, while maintaining the refrigerant at a temperature always above the actualdewpoint.
Liebert Heat
Rejection
Pumped Refrigerant Liebert XDV
Liebert XDC Refrigerant
Chiller
Liebert XDV
Direct System
Indirect System
Liebert XD Hydraulic System Schematic
HO
T A
ISLE
COLD
AIS
LE
COLD
AIS
LE
HO
T A
ISLE
The Liebert XDV works extremely well with the hot aisle-cold aisle approach.
HO
T A
ISLE
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes noresponsibility, and disclaims all liability for damages resultingfrom use of this information or for any errors or omissions.
2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarksof their respective owners.
Liebert is a registered trademark of the Liebert Corporation.
SL-16625 (R12/07) Printed in USA
Business-Critical Continuity, Emerson NetworkPower and the Emerson Network Power logo aretrademarks and service marks of EmersonElectric Co. 2007 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.The global leader in enablingBusiness-Critical Continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, Ohio 43229800 877 9222 Phone (U.S. & Canada Only)614 888 0246 Phone (Outside U.S.)614 841 6022 FAX
Via Leonardo Da Vinci 8Zona Industriale Tognana 35028 Piove Di Sacco (PD)Italy39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific7/F., Dah Sing Financial Centre108 Gloucester Rd, WanchaiHong Kong852 25722201 Phone 852 28029250 FAX
liebert.com
24 x 7 Tech Support800 222 5877 Phone614 841 6755 (outside U.S.)
-
Precision Cooling For Business-Critical Continuity
Liebert ChallengerUnmatched Environmental Control To Match Many Applications
-
2When It Comes To Precision Air Conditioning,Liebert Doesnt Accept Almost
Although sensitive equipment can leave the computerroom, it cant leave the environmental protection behind.Electronics are susceptible to heat, humidity, and airbornedust and contaminants. These systems require precision air conditioning to prevent downtime due to:
Equipment shutdown or mechanical failure.Temperature fluctuations can cause equipment toexhibit random errors and premature mechanical failure.Low humidity static discharge can alter data and maydestroy electronic components.High humidity can accelerate the deterioration ofmagnetic media, cause paper to swell and jam in printers,and leads to deterioration from condensation.
The choice is simple: provide precision air conditioning or risk significant levels of downtime.
But configuration of air conditioning is not so simple.
Sensitive computer-based electronics are no longer restricted
to computer room glass house environments. Todays
computers manage complex telecommunications networks,
optimize industrial systems, process sophisticated medical
and laboratory information, and control LANs and WANs.
-
3Liebert Challenger includes all environmental functionscooling, reheat, dehumidification,
humidification, and filtrationand an intelligent control system to make sure every
function works in harmony with the other. Installation is fast, and maintenance is easy.
All systems are factory tested.
Designed to run 24 hours a day, 365 days a year. The inherently efficient scroll compressor
has an EER of 11.3. Liebert Microprocessor-based controls intelligently determine
operational requirements and minimize wasteful operating patterns such as short cycling.
Optional GLYCOOL free-cooling system permits compressorless operation in cold climates.
The Liebert Challenger is a self-contained system.The status and control panel is on the
front, and all control functions are menu-driven. You have complete control of your
environment at all times.
Footprint is a mere 7.3 square feet, with front access to all interior components for
maintenance and service. Theres no need to keep the back or sides clear, so the Liebert
Challenger can fit into a corner or squeeze between existing installed equipment.
Liebert Challenger is the most versatile system available. It can be placed inside the
room, or remotely. Conditioned air can move up into ducts or down into a raised
floor plenum. Self-contained or split systems. Air, water, glycol, GLYCOOL, and chilled
water configurations.
I need a cooling source I can controlthat is totally independent of thebuilding HVAC system.
My equipment will be running continuously, so the air conditioner needs to be energy efficient.
That room is jammed to the rafters; I need a cooling system that takes very little space.
I want everything in one cabinetfrom one supplier.
There are a dozen sites here, all unique. I want to simplify my selection process without compromising my site needs.
The Complete Solution
-
4Medical and Laboratory Applications Need:
Large Load VariationsHigh Air Filtration RequirementsMinimal Floorspace
Labs and Medical suites such as MRI and CATscan sitesneed to handle cooling loads precisely and quietly. The Liebert Challenger offers such precision features asIntelligent, microprocessor based control systems, SCR controlled reheats for infinite levels of response, an A-Frame coil that reduces air turbulence and a quiet,dependable scroll compressor. All in a compact packagethat fits easily into any setting.
Years of experience in the design and manufacture of precision environmental control systems and staying abreast of new
technological developments and requirements has helped us produce the Liebert Liebert Challenger. We know that all critical
electronic systems demand a high quality environment...but we also know that not all applications are created equal. Thats
why Liebert Challenger is configurable to meet the needs of a wide variety of site requirements.
Network Closet And TelecomApplications Need:
Unattended SitesMinimal FloorspaceContinuous Operation
In Telecommunications sites, space is at a premium. And you need a system dependable to operate yearround in unattended sites. The Liebert Challenger features a reliable scroll compressor, remote communications capability, and a microprocessor that controls the system without supervision. And it provides all this protection while consuming only 7.3 square feet.
Regardless Of The Application, Liebert ChallengerWill Meet Your Critical Requirements.
-
5Industrial Process AutomationApplications Need:
Potentially Corrosive EnvironmentsHigh Static Pressure AirDischarge RequirementsHigh Air Filtration Requirements
On the factory floor, you need a cooling system thatsdependable and tough. Tough enough to withstand the corrosive environments, and tough enough to supply continuous air flow in ducted applications. The Liebert Challenger answers all this with a MIG welded steelframe surrounded by insulated heavy gauge steel panels.
Computer Room Applications Need:
24 Hour Per Day/365 Days Per Year OperationUnderfloor Air DischargeHigh Sensible Heat Ratio1800-3000 C.F.M. Air DischargeHigh Energy Efficiency Requirements
On a square foot basis, computer rooms generate up to five times the heat of normal office space. And theyrequire higher than normal air handling requirements to reduce hot spots. The Liebert Challenger is designedto handle this load efficiently with a high sensible heatratio and an air delivery system capable of 1800-3000C.F.M. Because most computer rooms use a raised floorfor air circulation and cable management, the LiebertChallenger can be specified with underfloor air discharge. This reduces the turbulence created by competing warm and cold air streams.
-
6Front Access For EasyMaintenanceAll interior components are frontaccessible to simplify maintenanceand reduce the floorspace that mustbe kept open.
Stable and QuietA MIG welded steel frame provides a solid platform for the internal components. Units incorporate avibration-isolated fan deck whichreduces noise and vibration transmission to any connected ductwork. The heavy gaugepanels/heavy duty gaskets option provides upgraded protection, popular in industrial and/or high static applications.
Corrosion ResistantThe frame and exterior panels are powder coated and baked, a solvent-free process that is not onlyenvironmentally safe, but produces an attractive, durable finish.
Precise Humidity ControlThe Infrared Humidifier has been a feature on Liebert environmentalcontrol systems for over 25 years. Its rapid response and cleanliness has made it an industry standard in applications that demand precise, particle-free humidity control.
More Benefits And Higher Quality...Trademarks Of A Liebert System
An Autoflush System reduces thebuildup of mineral solids and reducesmaintenance time. If your applicationcalls for a Steam-GeneratingHumidifier, Liebert can respond. The disposable canister makes maintenance quick and easy.
High Performance Coolingand Heating ComponentsAn A-Frame Evaporator Coil exposes more coil surface to the airthat passes through it. This not onlyprovides a more rapid and preciseresponse to changing room conditions, but it reduces the horsepower requirements of the fan motor, saving energy.
The 304/304 Stainless Steel, FinnedTube Reheat, like the evaporator coil,is designed to maximize surface area.This allows lower sheath temperatures,reducing the likelihood of ionizationthat could trip fire detection equipment,and more precisely controlling room temperature during dehumidification.The reheat coils are constructed ofstainless steel for corrosion resistanceand long life.
An optional SCR-Controlled Reheat is available that provides infinite response levels to changingroom temperatures.
Year-Round DependabilityAnd Energy EfficiencyA rugged and quiet ScrollCompressor is at the heart of therefrigeration system. It operates atone of the highest EERs in the industry, 11.3.
Air cooled systems with outdoorcondenser can operate between -30 and +120F (-34 and 49C).Water and glycol cooled systems feature a coaxial condenser and regulating valves that can be adjusted to meet the capabilities of the site.
All Components From OneManufacturerLiebert is the only manufacturer in thecomputer support industry that buildsits own condensers and drycoolers.They feature aluminum cabinets andcopper-tube, aluminum-fin coils, andare built to precisely match the heatrejection requirements of the LiebertChallenger .
NRTL-C Certified Standard 60Hz products are NRTL-C listed/certified. NRTL-C meets bothU.S. and Canadian government safety standards, providing fast, hassle-free inspection and buildingcode approval.
-
7The GLYCOOL system is a patentedLiebert process that allows colder
outdoor temperatures to reduce or
eliminate compressor operation.
This not only reduces operating
costs,it increases reliability.
How it works:When outdoor temperatures are
above room temperature, the
GLYCOOL Liebert Challenger
functions as a normally-cooled
system. But when outdoor
temperatures fall below room
temperatures, the glycol that
circulates between the condenser
and drycooler becomes cold
enough to provide some or all
of the rooms cooling needs.
The cold glycol is redirected to a
supplemental cooling coil by means
of a microprocessor controlled valve.
During outdoor temperatures
below 45F (7.2C), the circulating
glycol can provide the same
cooling capacity as the mechanical
refrigeration system.
For Ultimate EnergyEfficiency: GLYCOOL
InfraredHumidifierFor PreciseHumidityControl
A-FrameEvaporator Coil
Stainless SteelFinned-TubeReheat
Corrosion-ResistantSteel Frame
ScrollCompressor
Front Access ForEasy Maintenance
Vibration-IsolatedFan Deck
Liebert Commitment to Quality All Liebert products available in the marketplace are the results of exhaustive testing. Our state-of-the-arttesting laboratory is the most complete in the industry. Products are tested under both indoor and strenuousoutdoor conditions to insure year round reliability. All electronic components are subjected to rigorous life-cycle testing far in excess of normal operating stresses. In short, you can be sure that a Liebert productnot only will help you solve your unique environmental control problems...it will help you solve them right.
-
8Communicating With Your Precision Environmental System
Liebert Advanced Microprocessor Control
This control system automatically selects the most
precise and efficient action based on the environmental
trends of your site. The Liebert Advanced Microprocessor
Control uses an LCD display and a five-key pad to program
setpoints and alarms. The menu-driven system monitors a
wealth of data digital and analog to keep you constantly
informed of system operation. Features include:
Backlit display panel that shows room conditions and
operational status in normal mode.
Event logging that shows alarm history and run time log.
Choice of four custom alarms with inputs allowing external
20mA analog signals for water and similar external alarms.
Proportional control system.
Programmable temperature and humidity setpoints
and alarm conditions.
Auto restart.
Local alarm.
Compatibility with Liebert remote monitoring and
control devices.
In the alarm mode, the control panel candisplay any of up to 21 alarms.
Liebert Advanced Microprocessor
Control With Graphics
The Liebert Advanced Microprocessor Control with Graphics
offers the same features and control schemes as the Advanced
system. However, this model adds a 240x128 pixel backlit dot
matrix display that provides data at-a-glance screens for quick
review. Additional features include expanded alarm capabilities
and in-depth system operating information. The system offers
graphic representations of:
Temperature, humidity and analog inputs.
Component operating status by hour.
System operating status.
The standard operations screen shows temperatureand humidity in large, easy-to-read type.
Whether you use its local or remote monitoring and control capabilities, the Liebert Challenger is designed to provide the
widest range of monitoring options.
Local Monitoring And ControlAside from streamlining your operation for peak performance, microprocessor-based controls help the LiebertChallenger achieve precise temperature and humidity for your sensitive electronics. Two levels of Liebert microprocessor control systems are available, providing precise control and monitoring of the critical space. The Liebert Advanced Microprocessor is standard, while the Liebert Advanced Microprocessor with Graphics isoptional. These controls provide unit control, monitoring, diagnostics, alarms and event logging.
-
9Network MonitoringSystemsThe Liebert OpenComms family of productsleverages one-to-one unit connections andyour existing network for a comprehensivemonitoring solution for distributed equipment.
Liebert OpenComms NformCentralized monitoring of all Liebert SNMPenabled devices.Event and alarm management.Adaptable and configurable graphical user interface.Integration of third-party SNMP enableddevices through custom Liebert services.Windows NT, 2000 and XP compatible.
Liebert OpenComms NICMonitoring option available for Liebert precision air conditioning units. Web interface for viewing and control.Modbus interface for building management systems.Liebert SNMP interface for network management systems.
Stand-Alone MonitoringAnd Leak DetectionSolutions Autonomous Liebert microprocessor controlled modules are available to provide supervision,control and remote notification of Liebert equipment. These stand-alone devices include:
Contact Closure Alarm PanelsContinuously monitor critical support equipment and instantly notify on alarm condition.
Liebert Control PanelsSequence the operation of multiple environmental units.
Liebert Leak Detection ModulesProvide quick detection and location of hazardous fluid leaks.
Discrete Output Interface CardStraightforward way to tie environmental units to a building management system or alarm panel.
Enterprise Monitoring SystemsLiebert SiteScan Web is a comprehensive critical systems monitoring solution dedicatedto ensur