Small Generator 25 kW Inverter Process Page 45
Level 1Application Form Interconnecting a Certified Inverter-Based Small Generating Facility No Larger
than Ten (10) kW for Residential or Twenty-five (25) kW for Commercial
Interconnection Customer Information
Name: Contact Person:
Account Number:____________________________________________________________
Address:
City: State: Zip:
Phone Number: ______________________ E-Mail: _________
Equipment Installation Contractor/Electrical Contractor (If different from above) Contact Name:
Company Name:
Contact Phone Number:__________________ E-Mail Address:
Additional Ownership of the generation facility:
Small Generating Facility Information Location (if different from above): Inverter Manufacturer: Model _
System AC Rating: ___ (kW) _____ (Amps) __ (AC Volts)
System DC Rating:______(kW)_______ (Amps)
Adjustable Power Factor: Power Factor Setting:_____
Single Phase Three Phase
Projected Annual Energy Production: (kWh)
Estimated Installation Date:_______________Estimated In-Service Date:
Please include the following documents: One Line Diagram (Including Production Meter Location)
Site Plan
Site Control Documentation
Personal Liability Insurance Documentation ($300,000 minimum)
Specification Sheets for the Modules and Inverter(s)
$100 Application Processing Fee
Application ID (IREA use only):________
Small Generator 25 kW Inverter Process Page 46
This Application shall be deemed complete when the Interconnection Customer provides all applicable and correct information required below, as well as any additional information required by the Association to evaluate the Request. The terms of this Application are governed by the provisions applicable to the Level 1 Process under Association’s Small Generation Interconnection Procedures, as the same may be amended, modified or restated from time to time.
Interconnection Customer Signature I hereby certify that, to the best of my knowledge, the information provided in this Application is true. I agree to abide by the Terms and Conditions for Interconnecting an Inverter-Based Small Generating Facility No Larger than ten (10) kW for residential or twenty-five (25) kW for commercial nor larger than 120% of the twelve (12) month historical usage at the meter location and return the Certificate of Completion when the Small Generating Facility has been installed. I further agree that IREA shall be entitled to any renewable energy credits or other similar attributes associated with the production of electricity by the equipment referred to in this application upon interconnection of that equipment, until such time as IREA is notified in writing of the transfer or assignment of such credits or attributes to a third party.
I UNDERSTAND THAT THE ASSOCIATION HAS THE RIGHT TO CHANGE ITS RATES AT ANY TIME AND THAT FUTURE REVISIONS MAY INCLUDE A REDUCTION IN THE ENERGY CREDIT RATE, THE ADDITION OF A DEMAND CHARGE, AN INCREASED SERVICE CHARGE, A MODIFICATION TO THE COMPENSATION PAID FOR ANNUAL EXCESS GENERATION, OR OTHER CHANGES THAT WOULD ALLOW IREA TO RECOVER COSTS OF PROVIDING SERVICE TO NET METERING AND OTHER CUSTOMERS.
I UNDERSTAND THAT SUCH REVISIONS, IF ADOPTED, MAY AFFECT THE RELATIVE COSTS AND ECONOMIC BENEFITS OF MY GENERATION EQUIPMENT AND I ACKNOWLEDGE THAT IN AGREEING TO INTERCONNECT MY GENERATION EQUIPMENT, IREA RESERVES ITS RIGHT TO ESTABLISH RATES DESIGNED TO FULLY RECOVER ITS COSTS AND MAKES NO COMMITMENT TO ME THAT IT WILL CONTINUE ITS CURRENT RATES OR RATE STRUCTURE FOR ANY PERIOD OF TIME.
Signed: _______
Title: ________________________________ Date:
Contingent Approval to Interconnect the Small Generating Facility (For Association use only)
Interconnection of the Small Generating Facility is approved contingent upon the Terms and Conditions for Interconnecting an Inverter-Based Small Generating Facility No Larger than ten (10) kW for residential or twenty-five (25) kW for commercial and return of the Certificate of Completion.
Association Signature: __________________________________________________
Title: ______________________________ Date: _______________
Application ID (IREA use only):________
N Site Plan
SYSTEM LEGEND
Solar Installation,
Inc.
HOMEOWNER RESIDENCE
1200 Main St.Sedalia, CO, 80135
UTILITY ACCOUNT #: 11235813
SITE PLANSCALE: 1/8" = 1'-0"
M
P
1200 Main St.FRONT OF HOUSE.
#2) 15 MODULES
PV STRING(S):
#1) 15 MODULES
ROOF SECTION(S):1 SLOPE - 26.6AZIMUTH - 269.8MATERIAL -COMPOSITION SHINGLE2 SLOPE - 26.6AZIMUTH - 89.8MATERIAL -COMPOSITION SHINGLE3 SLOPE - 26.4AZIMUTH - 179.8MATERIAL -COMPOSITION SHINGLE
720.456.1414
1
2
3
FIRE CODE OFFSET
RIDGE: 36"| SIDE: 36"| VALLEY: 18"
AC
EXISTING EXTERIOR MAIN SERVICE PANEL TIED M TO UTILITY METER
I
NEW PV SYSTEM AC DISCONNECT. LOCATEDWITHIN 5' OF MSP.
PNEW SREC PRODUCTION METER. LOCATED WITHIN5' OF MSP.
│ 7.5 kW ACPV SYSTEM SIZE:NEW 9 kW DC
30 NEW SOLAR PV-XYZ 300 MODULES.
1 NEW PV SYSTEM INVERTER: Inverter King IK7500H-
NEW JUNCTION BOX. (MOUNTED TO PV MODULE)
NEW PV CONDUIT RUN.*SEE EE1.0 CONDUIT SCHEDULE= EXTERIOR RUN = ATTIC RUN
ACIFence
Tag # Description Wire Gauge # of Conductors/Color Conduit Type Conduit Size
1 PV Wire 12 AWG 2(V+, V-) N/A-Free Air N/A-Free Air
1 Bare Copper Ground - EGC 6 AWG 1 BARE N/A-Free Air N/A-Free Air
2 THWN-2 12 AWG 4(2V+, 2V-) B/R EMT 1/2"
2 THWN-2 EGC 12 AWG 1(GRN) EMT 1/2"
3 THWN-2 8 AWG 3(1L1 1L2 1N) B/R/W EMT 3/4"
3 THWN-2 EGC 10 AWG 1(GRN) EMT 3/4"
4 THWN-2 6 AWG 3(1L1 1L2 1N) B/R/W EMT 3/4"
4 THWN-2 GEC 8 AWG 1(GRN) EMT 3/4"
Photovoltaic System
DC System Size (Watts)
AC System Size (Watts)
Total Module Count
90007500
30
SHEET
NUMBER:
1-Line
INST
ALL
ER: S
olar
Inst
alla
tion,
Inc.
IN
STA
LLER
NU
MB
ER: 7
20.4
56.1
414
CO
LIC
ENSE
: 123
45
SHEET
NAME:
Cre
ated
: 9/1
5/1
9
Conduit Conductor Schedule (ALL CONDUCTORS MUST BE COPPER)
John
Hom
eow
ner
120
0 M
ain
St.
Seda
lia, C
O 8
01
35
ALL STICKERSSMALLER THAN 3/8" WHITE ARIAL FONT TEXT, AND HAVE A RED BACKGROUND, UNLESS OTHERWISE DEPICTED OR DESCRIBED.ALL PLACARDS SHALL BE WEATHER
311
10
1
STC
STRING 1: 15 PVMODULES
STRING 2: 15 PVMODULES
2
3
1
NEMA 4 Junction Box
Visible/Lockable 'Knife' AC Disconnect
3
Existing 240V/100AService Panel, Single
Phase, with 200A MainDisconnect
Square D D222NRB, 240V/60A, Fused, NEMA3,
or equivalent
Visible/Lockable 'Knife' ACDisconnect
Minimum GEC size 6 AWG copper
40A
Point of Interconnection, Supply Side 705.12(A)
200A
4
Inverter King
SE7500H-US
SREC/ANSI Meter Socket
Inverter King - Single Phase Inverters for North America IK-3000 / IK-3800 /
IK-5000 / IK-6800 / IK-7500
IK-3000 IK-3800 IK-5000 IK-6000 IK-7500OUTPUT RatedACPowerOutput 3000 3800 5000 6000 7500 VAMax.ACPowerOutput 3000 3800 5000 6000 7500 VAACOutputVoltageMin.-Nom.-Max.(183-208-229) - - 3 - - VacACOutputVoltageMin.-Nom.-Max.(211-240-264) 3 3 3 3 3 VacACFrequency(Nominal) 59.3-60-60.5(1) HzMaximumContinuousOutputCurrent208V - - 24 - - AMaximumContinuousOutputCurrent240V 12.5 16 21 25 32 AGFDIThreshold 1 AUtilityMonitoring,IslandingProtection, CountryConfigurableThresholds Yes
INPUT MaximumDCPower 4650 5900 7750 9300 11800 WTransformer-less,Ungrounded YesMaximumInputVoltage 480 VdcNominalDCInputVoltage 380 400 Vdc MaximumInputCurrent208V - - 15.5 - - AdcMaximumInputCurrent240V 8.5 10.5 13.5 16.5 20 AdcMax.InputShortCircuitCurrent 45 AdcReverse-PolarityProtection YesGround-FaultIsolationDetection 600k SensitivityMaximumInverterEfficiency 99 99.2 %CECWeightedEfficiency 99 %NighttimePowerConsumption <2.5 WSELF-SUSTAINING POWER OUTLET (OPTIONAL)NominalOutputVoltage 120 VMaximumOutputPower 1500(2) WExternalOutletwithGFDI YesADDITIONAL FEATURESSupportedCommunicationInterfaces RS485,Ethernet,ZigBee(optional),Cellular(optional)RevenueGradeData,ANSIC12.20 Optional(3)
RapidShutdown-NEC2014690.12 AutomaticRapidShutdownuponACGridDisconnectSTANDARD COMPLIANCESafety UL1741,UL1699B,CSAC22.2,CanadianAFCIaccordingtoT.I.L.M-07GridConnectionStandards IEEE1547,Rule21,Rule14(HI)Emissions FCCPart15ClassBINSTALLATION SPECIFICATIONS ACOutputConduitSize/AWGRange 0.75-1”Conduit/14-6AWGDCInputConduitSize/#ofStrings/AWGRange 0.75-1”Conduit/1-2strings/14-6AWGDimensionswithSafetySwitch(HxWxD) 17.7x14.6x6.8/450x370x174 in/mmWeightwithSafetySwitch 25.3/11.5 lb/kgNoise <25 dBACooling NaturalConvectionOperatingTemperatureRange -13to+140/-25to+60(4)(-40˚F/-40˚Coption)(5) ˚F/˚CProtectionRating NEMA3R(InverterwithSafetySwitch)
(1)ForotherregionalsettingspleasecontactSolarEdgesupport (2)DependsonPVavailability(3)RevenuegradeinverterP/N:SExxxxH-US000NNC2(4)Powerde-ratingfrom50˚C(5)-40versionP/N:SExxxxH-US000NNU4
UL 1703; VDE Quality Tested; CE-compliant; IEC 61215:2016; IEC 61730:201, application class A
At least 98 % of nominal power during first year. Thereafter max. 0.54 % degradation per year.At least 93.1 % of nominal power up to 10 years.At least 85 % of nominal power up to 25 years.
All data within measurement tolerances.Full warranties in accordance with the warranty terms of the sales organization of your respective country.
Typical module performance under low irradiance conditions in comparison to STC conditions (25 °C, 1000 W/m2).
PV XYZ - MECHANICAL SPECIFICATION
PERFORMANCE WARRANTY PERFORMANCE AT LOW IRRADIANCE
IRRADIANCE [W/m²]
RELA
TIVE
EFF
ICIE
NCY
[%
]
200 400 600 800 1000
110
100
90
80
Irradiance [W/m²]
Rela
tive
effic
ienc
y [%
]
Format 66.3 in × 39.4 in × 1.26 in (including frame)(1685 mm × 1000 mm × 32 mm)
Weight 41.2 lbs (18.7 kg)
Front Cover 0.13 in (3.2 mm) thermally pre-stressed glass with anti-reflection technology
Back Cover Composite film
Frame Black anodized aluminum
Cell 6 × 20 monocrystalline solar half-cells
Junction box 2.76-3.35 in × 1.97-2.76 in × 0.51-0.83 in(70-85 mm × 50-70 mm × 13-21 mm), decentralized, IP67
Cable 4 mm² Solar cable; (+) ≥ 43.3 in (1100 mm), (−) ≥ 43.3 in (1100 mm)
Connector Multi-Contact MC4, IP68
PROPERTIES FOR SYSTEM DESIGNMaximum System Voltage VSYS [V] 1000 (IEC) / 1000 (UL) Safety Class II
Maximum Series Fuse Rating [A DC] 20 Fire Rating C (IEC) / TYPE 1 (UL)
Max. Design Load, push2 [lbs/ft2] 75 (3600 Pa) / 55 (2667 Pa) Permitted module temperatureon continuous duty
− 40 °F up to +185 °F(− 40 °C up to +85 °C)
Max. Test Load, Push / Pull2 [lbs/ft2] 113 (5400 Pa) / 84 (4000 Pa) 2 see installation manual
NOTE: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and use of this product.
EN
RELA
TIVE
EFF
ICIE
NCY
COM
PARE
D TO
NOM
INAL
POW
ER [
%] 100
95
90
85
80
75
155 25200 10
YEARS
98CELLS
Industry standard for tiered warranties*
Industry standard for linear warranties*
*Standard terms of guarantee for the 10 PV companieswith the highest production capacity in 2014 (as at: September 2014)
NA
DETAIL A 0.630" (16mm)
0.335" (8.5mm)0.965" (24.5mm)
38.58" (980mm)
66.3" (1685mm)
4 × Mounting slots (DETAIL A)
Frame
39.4" (1000mm)
37.44" (951mm)
1.26" (32mm)
8 × Drainage holes
13.9“ (352.5mm)
4 × Grounding points ø 0.177" (4,5mm)≥ 43.3“ (≥ 1100 mm)
≥ 43.3“ (≥ 1100 mm)
ELECTRICAL CHARACTERISTICSPOWER CLASS 300 320 325 330
MINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC1 (POWER TOLERANCE +5 W / −0 W)
Min
imum
Power at MPP1 PMPP [W] 300 320 325 330
Short Circuit Current1 ISC [A] 10.04 10.09 10.14 10.20
Open Circuit Voltage1 VOC [V] 39.87 40.13 40.40 40.66
Current at MPP1 IMPP [A] 9.55 9.60 9.66 9.71
Voltage at MPP VMPP [V] 32.98 33.32 33.65 33.98
Efficiency1 η [%] ≥ 18.7 ≥ 19.0 ≥ 19.3 ≥ 19.6
MINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NMOT2
Min
imum
Power at MPP PMPP [W] 235.3 239.0 242.8 246.5
Short Circuit Current ISC [A] 8.09 8.13 8.17 8.22
Open Circuit Voltage VOC [V] 37.52 37.77 38.02 38.27
Current at MPP IMPP [A] 7.52 7.56 7.60 7.64
Voltage at MPP VMPP [V] 31.30 31.62 31.94 32.251Measurement tolerances PMPP ± 3 %; ISC; VOC ± 5 % at STC: 1000 W/m2, 25 ± 2 °C, AM 1.5 G according to IEC 60904-3 ∙ 2800 W/m², NMOT, spectrum AM 1.5 G
CertifiedUL 1703(254141)
TEMPERATURE COEFFICIENTS
Temperature Coefficient of ISC α [% / K] + 0.04 Temperature Coefficient of VOC β [% / K] − 0.28
Temperature Coefficient of PMPP γ [% / K] − 0.37 Normal Module Operating Temperature NMOT [°F] 109 ± 5.4 (43 ± 3 °C)
QUALIFICATIONS AND CERTIFICATES PACKAGING INFORMATIONNumber of Modules per Pallet 32
Number of Pallets per 53' Trailer 30
Number of Pallets per 40' High Cube Container 26
Pallet Dimensions (L × W × H) 69.3 in × 45.3 in × 46.9 in(1760 mm × 1150 mm × 1190 mm)
Pallet Weight 1415 lbs (642 kg)