ler 84-007-00:on 840529,loop 1 shutdown occurred when

6
U.3, BeUCLEA2 AGOULATORY -:- -- meC p, Joe * Arr*OVE3 Oue eso 21e0-410e S,4% * ' ' ' ' * " ' ' ' ' " " LICENSEE EVENT REPORT (LER) P*at a ooc ET uimen . ,ACiur? =Ame ni Fort St. Vrain, Unit No. 1 0 151010Io1216 17 1 |OF| O |3 TITLE tel Loss Of 480V Bus 1 - Loop 1 Shutdown EVENT DATE 104 LER gegnagga gg) agpO8tT DATE475 UTleGA F AClWTIES IsrVOLVSD W) YEAR I '',Q ,{ '44* nsOsgTM OAY YEAR P4CiuTY eseeses DOCKET 8evassen. * MONTM DAY YEAR i , , N/A 0 | 510 | 0 t o ! ; I O |5 2 |9 8' 4 8|4 - 0 | 0 |7 0|0 0|6 2|8 8|4 lo is to to 1 0, ! | ~ TMIS REPORT IS SugestTTED PunguANT TO Tese neousseneSNTE Op 14 CPR h tomass ans or an.se of me .' J till CPORAtlesO x .m.,a. m ia.: =<=8* N .m. m, _ _ m in H. == n , .m.H., n= gg _ _ _ _ g.yp,,g 0, 0,2 . in ,. _ _ m. .m. n., _ a ni., . n .H. = = A. -A, g _ _ _ 30 eS.sH1Hhi go.?sene.tsi .J3em6. malWI 30.a.tett1Hv6 es33enH3Hus) .J3emH3Hal UCS8IBGE CoeffACT POR THIS LSA 4tB TELEPHOpet NUMGER NJ,ns t ^ " * ^ * * Frank Novachek, Technical Services Engineering Supervisor 31013 71815 |- 12121214 ConsPLETE Oest LBleE POR EACM Composegar? PA:ang 0sE28880 IN 79tas AGPOst? (13 "I[ ^[g'I ' ,g - hAUSE fv879md C0esposseNT **^T,," "$ ,LE Uhjf. O ' CAUSE SYSTEM COMPONENT 79 ma, <. s s s I i 1 i i ! I J i , I i I I i ' ' ~ " 4 $; @ | I I I I I I b"~' 1 I I I I I I ' e SUPPLEMENTAL REPOft? FXPECTED f1e MONTM DAY YEAR YEE (99 v.n. comeneen EXPECTtQ SvenetstION D.TE] seo | | | Asst =ACTro,-c ,me - u ,v, aa - - ,n On May 29, 1984, at approximately 1135 hours, with the reactor operating at less than 2% power, a Loop I shutdown occurred when the rapid rise relay (RRR-1) on the 4160/480 volt transformer (N-9274) actuated. This actuation resulted in a trip of the 4160/480 volt transformer, supplying the 480V A.C. Esstntial Bus IA, and a Loop I shutdown, due to the trip of both helium ci'rculators (C-2101, C-2102) and the associated auxiliaries in that loop, when a loss of circulator bearing water 1 was detected by the helium circulator's bearing water pressure differential ! indicating switches. No apparent malfunction in the rapid rise relay was detected when inspected by plant electrical personnel. The transformer was thoroughly checked and samples of the transformer oil and nitrogen blanket were taken and tested. The transformer (N-9274) was pre warmed and returned to service at 1100 hours on May 30, 1984. At 2205 hours on May 30, 1984, Loop I was returned to service. 1 The automatic actuation of the Plant Protective System (PPS) circuitry for a loop ; ' shutdown is being reported per 10 CFR 50.73(a)(2)(iv). F) I 8407090250 840628 PDR ADOCK 05000267 S PDR ! 77d"'" *" - . .. . _ _ - - - . - .- - .- - - - - _ . ,

Upload: others

Post on 14-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

U.3, BeUCLEA2 AGOULATORY -:- --

meC p, Joe* Arr*OVE3 Oue eso 21e0-410eS,4%*

' ' ' ' * " ' ' ' ' " "LICENSEE EVENT REPORT (LER)

P*at aooc ET uimen .,ACiur? =Ame ni

Fort St. Vrain, Unit No. 1 0 151010Io1216 17 1 |OF| O |3TITLE tel

Loss Of 480V Bus 1 - Loop 1 ShutdownEVENT DATE 104 LER gegnagga gg) agpO8tT DATE475 UTleGA F AClWTIES IsrVOLVSD W)

YEAR - I '',Q ,{ '44* nsOsgTM OAY YEAR P4CiuTY eseeses DOCKET 8evassen.*MONTM DAY YEAR i , ,

N/A 0 | 510 | 0 t o ! ; I

O |5 2 |9 8' 4 8|4-

0 | 0 |7 0|0 0|6 2|8 8|4 lo is to to 1 0, ! |~

TMIS REPORT IS SugestTTED PunguANT TO Tese neousseneSNTE Op 14 CPR h tomass ans or an.se of me .' J tillCPORAtlesO

x .m.,a. m ia.:=<=8* N .m. m,_

_

m in H. == n , .m.H., n=gg __ _ _ g.yp,,g0, 0,2 . in ,._ _

m. .m.n., _

a ni., . n .H. = = A. -A,

g _ _ _

30 eS.sH1Hhi go.?sene.tsi .J3em6. malWI

30.a.tett1Hv6 es33enH3Hus) .J3emH3Hal

UCS8IBGE CoeffACT POR THIS LSA 4tBTELEPHOpet NUMGERNJ,ns t

^ " * ^ * *Frank Novachek, Technical Services Engineering Supervisor31013 71815 |- 12121214

ConsPLETE Oest LBleE POR EACM Composegar? PA:ang 0sE28880 IN 79tas AGPOst? (13

"I[ ^[g'I ',g - hAUSE fv879md C0esposseNT **^T,," "$ ,LE Uhjf.O '

CAUSE SYSTEM COMPONENT 79ma, <.

ss s

I i 1 i i ! I J i , I i I I i ' '~

"4 $; @| I I I I I I b"~' 1 I I I I I I'

e

SUPPLEMENTAL REPOft? FXPECTED f1e MONTM DAY YEAR

YEE (99 v.n. comeneen EXPECTtQ SvenetstION D.TE] seo | | |

Asst =ACTro,-c ,me - u ,v, aa - - ,n

On May 29, 1984, at approximately 1135 hours, with the reactor operating at lessthan 2% power, a Loop I shutdown occurred when the rapid rise relay (RRR-1) on the4160/480 volt transformer (N-9274) actuated. This actuation resulted in a trip ofthe 4160/480 volt transformer, supplying the 480V A.C. Esstntial Bus IA, and aLoop I shutdown, due to the trip of both helium ci'rculators (C-2101, C-2102) andthe associated auxiliaries in that loop, when a loss of circulator bearing water 1

was detected by the helium circulator's bearing water pressure differential !

indicating switches.

No apparent malfunction in the rapid rise relay was detected when inspected byplant electrical personnel. The transformer was thoroughly checked and samples ofthe transformer oil and nitrogen blanket were taken and tested. The transformer(N-9274) was pre warmed and returned to service at 1100 hours on May 30, 1984. At2205 hours on May 30, 1984, Loop I was returned to service.

1

The automatic actuation of the Plant Protective System (PPS) circuitry for a loop;' shutdown is being reported per 10 CFR 50.73(a)(2)(iv).

F)I 8407090250 840628

PDR ADOCK 05000267S PDR

! 77d"'" *"- . .. . _ _ - - - . - .- - .- - - - - _ .

,

Page 2: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

meC Perne 30sA U S. NUCLEA2 KEIULf.TCav C0eaMess604* * ' '' ~

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION uPaovEo ous =o mo-oio.-

E x PIR ES. 4/31185

PACsLITV Naast its DOCKET Nue8SER 12) Lgm NunsetA (64 PAGE435

" R ',|,' P.' ' 9"?vi*.72*saa

Fort St. Vrain, Unit No. 1010 012 oF 0 |50 |0 |7o|510lo o|216|7 8|4 --

TUT t# mese ammes a measut, ese amatunt 44C Fusuo M*ss if7)

EVENT DESCRIPTION:

The Fort St. Vrain helium primary coolant system is equipped with four identicalhelium circulators, two in each loop. The helium circulators are supplied withhigh pressure water sources for bearing lubrication from the bearing water systemwhich consists of two separate and independent recirculating bearing water loopswith three bearing water pumps in each loop piped for operation in series. Thebearing water supply system is monitored by three pressure differential indicatingswitches (PDIS) per helium circulator which monitor the pressure differentialbetween the bearing water supply cavity and the main drain system.

The Loop I shutdown was initiated when a loss of circulator bearing water wasdetected by instrumentation in the Plant Protective System (PPS).

The sequence of events leading to the Loop 1 shutdown on May 29, 1984 were asfollows:

(

1. The rapid rise relay (RRR-1) on the auxiliary transformer 4160/480V A.C.(N-9274) tripped.

2. The fire water (System 45) deluge at the auxiliary transformers wasactivated.

3. The lock out relay in the 480V A.C. Essential Bus 1A cabinet energized,causing the essential Bus IA main breaker and the 4160V feed breaker tothe auxiliary transformer (N-9274) to trip open.

4 The essential 480V A.C. bus tie 2 from Bus IB to 480V A.C. Essential BusIA breaker closed automatically to energize Bus 1.

The momentary loss of electrical motive power to the in-service bearing waterpumps initiated trip inputs to the Plant Protective System when a pressuredifferential of less than 475 PSID was detected by the helium circulators pressuredifferential indicating switches with the resultant Loop I shutdown.

ANALYSIS OF EVENT:

The Plant Protective System (PPS) consists of instrumentation and controlsrequired to automatically initiate safety actions to protect the reactor core andvarious plant components important to maintaining core cooling. The basic logicsystem employs a 2 of 3 redundancy for the sensing channels. The tripped bearingwater pumps were unable to satisfy the trip setting of equal to or greater than475 PS:D. The switches acted to trip the circulators on sensing a pressuredifferential of less than 475 PSID, indicating a loss of bearing water flow andinitiating sufficient PPS inputs to trip the helium circulators C-2101 and C-2102and the shutdown of Loop I.

.

F%M 308e

Page 3: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

jv.s. UCLEAR HnH.AroAY Commessione ,a m

l".*' ' UCENSEE EVENT REPORT (LER) TEXT CONTINUATION Amoveo ous =o sino-oion i'*

jexmss snues

|'ac'urv aa=* m ooc ==T av= Sea m ten muu en i.i ..o i1

:'JJ.;;.... p at!.;;'t- ,

'

Fort St. Vrain, Unit No. 1o In I 7 - n in n I, OF n lea959Olo10 21 Al? 8I6 -

rixr,,- . - - acwamonm

Referring to Figure 1, as the pressure differential between the water supplycavity and the main drain decreases, the pressure differential switches(PDIS) [1] will individually close at their respective setpoints. This applies avoltage to the switch input modules (XDIS) [2] , tripping them. Each tripped XDISmodule transmits a signal to both "A" and "B" logic channels [3] . When either"A" or "B" logic receives inputs from any two of the three XDIS modules, they willtransmit a signal to the "A" or "B" logic OR gate [4] respectively., The OR gatestransmit any input signal to the respective special control relay (XCR) -[5] toenergize auxiliary relays which trip the helium circulator and initiate thefollowing helium circulator protective actions:

1. Isolation of the steam and water turbine supply and return lines.

2. Fire the bearing water accumulator system, which initiates a surge ofbearing water, to allow coastdown of the circulator.

3. Apply the brake when speed has decreased below 700 RPM.

4. Apply the mechanical shutdown seal.

5. Isolate the remaining circulator auxiliaries.

This event had no potential affect on the health and safety of the public.

l

I

l

W "" ~_ _ ..

-- _ _ _

Page 4: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

U.S. NUCLEAR KEEULATORY F -- Cos+ - m Fwe an5A

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION tmovso ous =o. siso-oion** *.

EX7IEES S/3i/BS

F ACILifV maaes (H DOCERT feuedBER (2) LER NUMesa (H PAGE13

vsam- si Yeas : .- esEg

Fort St. Vrain, Unit No. 1 0|0 0|4 OF 0po sto|olo|2|6|7 8| 4 - 0|0|7 -

fat a- me.- e ==w. w mec = ma w nn

' FIGURE 1

''

TYPICAL FOR EACH CIRCULATOR

e

w

chanr.e3 1 Channel 3 Chanael C -

? DIS FDis TD15

$ *O O

6 s t

.

@ D15 2 15 XDIS

___

l !

II

h "A" lagie "2" 143 c12/3 2/3

_

' ~ Tres Other Circulator 4' ,

Trip Paraneters ||I"3" 14gic.A= gg gg 03 Cate |OR.Cate

h XCR XCR

.

, ,.

4

e

9 P

CI'*"3**** CisculanerAuxiliary

II *Sys t em Rafays , " , ,

.

e

D

ne somes senaID436

-- - - -- - - . ._ _ ., . _ _ . _ , _ . _ . . _ _ _ , _ _ , _ _ _ _ _ _ , , _ , _ _ ,

Page 5: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

_ -. _ _ _ _ _ . - _ _ _ .-

U.S. NUCLEA10 KEIULATORY ss eemlONNaC Pen * 3SA

T*** UCENSEE EVENT REPORT (LER) TEXT CONTINUATION AreRovte out mo. mo-oio.*'

EXPSIES 8/3:45

fP ACsLITY Naast (13 DOCKET NutASER Q) LER NJMSSR (6) PAGE 138

,... - s.emy:- . 2:.T:

Fort St. Vrain, Unit No. 1 o |s jo |o jo |2 |6|7 8|4 - 0| 0| 7 010 0|5 OF 0 |5-

var ,,- . - me w am.w nn

CAUSE DESCRIPTION:

The rapid rise relay (RRR-1) on the 4160/480V A.C. transformer (N-9274) wasinspected immediately following this event by plant electrical personnel who couldfind no apparent malfunction in the relay or circuitry.

The cause of this event has been attributed to the spurious actuation of the rapidrise relay (RRR-1) contact circuitry. -

CORRECTIVE ACTION:

The oil in the transformer (N-9274) was sampled and tested. A sample of thegaseous nitrogen blanket was also tested with negative results.

The transformer was thoroughly checked and pre-warmed prior to returning toservice at 1100 hours on May 30, 1984.

,

The Loop I steam generator was returned to service on May 30, 1984, at 2205 hours.

No further corrective action is anticipated or required.

2 U AY ARobert A. Dickerson

Technical Services Senior Technician

bt ,

4.* Wankl. NoV'achek

Technical Services Engineering Supervisor

7'27I k w a d' L. M. McBride

Station Manager

|

Os- %nL- @'?"f/ 7Y), M2,*

Don ' War'embourgManager, Nuclear Production-

)!

soaw see... ._. _ , -

Page 6: LER 84-007-00:on 840529,Loop 1 shutdown occurred when

1

.' .>..., ._-

'

public Service Company Cf O&ndro

V. 16805 WCR 19 1/2, Platteville, Colorado 80651

go 7June 28, 1984,

Fort St. VrainUnit #1P-84190

3 @ 3 0WM %Mr. E. H. Johnson, Chief 1Reactor Project Branch 1Region IV JUl. - 2 WNuclear Regulatory Commission .yl611 Ryan Plaza Drive .

Suite 1000Arlington, TX 76011

REFERENCE: Facility Operating LicenseNo. DPR-34

Docket No. 50-267

Dear Mr. Johnson:

Enclosed please find a copy of Licensee Event ReportNo. 50-267/84-007, Final, submitted per the requirements of

10 CFR 50.73(a)(2)(iv).

Very truly yours,

0anLJuembuvy h y).'& pyeg Ce

Don WarembourgManager, Nuclear Production

DW/djm

Enclosure

cc: Director, MIPC

hDO $i i

. . .-