Product Lis ngs Micro‐Inverter— Integrated Ba ery; Pure Sinewave AC Output….…………………..4 Constant Power—Integrated Ba ery; Broad Range DC Output…………………...…..6 Constant Power – Integrated Ba ery; Op onal Bluetooth…………...….……………...8 Constant Power – Integrated Ba ery..…….……………………..…………….………………..10 Constant Power with Replaceable Ba ery Pack.….…….……………...…………………..12 Constant Current with Replaceable Ba ery Pack…….….…...……….…………...……...14 Dual‐Mode Normal + Emergency Programmable “Driverless”………………...……..16
Addi onal Resources
Limited Warranty ...………...………………………………………………….……….………………..19
Table of Contents
The Micro‐Inverter is designed for emergency opera on of LED, incandescent, and fluorescent fixtures up to 120W (~30% of rated luminaire power) using circuit design which enables shar‐ing of power. The Micro‐Inverter can also be used as a stand‐alone 36W inverter when used with ligh ng loads less than or equal to 36W. Features: Pure sinusoidal AC output Output voltage auto se ng equal to input
voltage Total dimmable power up to 120W Slim Aluminum housing Factory or field installa on Suitable for use in dry or damp loca ons
Auto Test Standard: Safety compliance to UL 924 and CAN/CSA‐
C22.2 No. 141 for 90 minute egress Compliance to CEC Title 20 FCC part 15, ICES‐005 Over voltage, over current, Inrush current
limi ng, over temperature, short circuit, open circuit protec on with auto‐reset
Opera ng temperature: 32°F/0°C to 131F/55°C
Test switch / charging indicator light Emergency reac on me ≤ 2 sec
Micro‐Inverter
— Integrated Ba ery; Pure Sinewave AC Output
4
Wiring Diagrams: LEM‐INV‐036‐U‐V1
NO
N-D
IMM
AB
LE
EM
ER
GE
NC
Y
LIG
HT
ING
SY
ST
EM
Micro‐Inverter
— Integrated Ba ery; Pure Sinewave AC Output
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
0-10
V D
IMM
AB
LE
EM
ER
GE
NC
Y
LIG
HT
ING
SY
ST
EM
5
Type LEM-INV-036-U-V1
Lamp type For emergency operation of LED and fluorescent fixtures up to 36W
Rated voltage 120-277VAC 50/60Hz
Rated current 0.06A (Max.)
Rated power 7W
Output voltage 120-277VAC 50/60Hz
Output power Ta: 10-55℃ 36W (Max.), Ta: 0-10℃ 27W (Max.) Battery Li-ion
Charging time 24 Hours
Discharge time 90 Minutes
Charging current 0.335A (Max)
Life time of Module 5 Years
Abnormal Protection Over load, Inrush current limiting, over temperature, open circuit, short-circuit protection with auto-reset
EMC/FCC/IC standard EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3; FCC part 15, ICES-005
Safety standard EN 61347-1, EN 61347-2-7, UL924,CSA C.22.2 No. 141
Meas. mm [inch] L346 [13.62]xW82 [3.23]xH30 [1.18] Mounting center: 338 [13.31]
McWong’s broad range DC output LEM series is a UL Listed and CEC compliant constant power LED emergency driver family. This series is de‐signed for both AC LED tube/bulb and DC LED load. The driver offers best‐in‐class low profile form factor, with op ons for terminal block, flex conduit or IP66 waterproof case. Features: Constant emergency power output, wide
range of output voltage from 5 up to 300Vdc, output current auto adjusts
Ultra‐Slim aluminum housing Factory or field installa on Drivers with terminal block or conduit exit
are suitable for use in dry or damp Loca‐
ons; IP66 waterproof series is suitable for use in outdoor or wet loca ons
Auto Test Standard: Safety compliance to UL 924 for 90 minute
egress Compliance to CEC Title 20 FCC part 15, ICES‐005 Over load, Inrush current limi ng, over tem‐
perature, open circuit, short circuit protec‐on with auto‐reset
Opera ng temperature: 32°F/0°C to 131F/55°C
Test switch / charging indicator light Emergency reac on me ≤ 2 sec
6
Constant Power
—Integrated Ba ery; Broad Range DC Output
Wiring Diagrams: LEM‐Pww‐vvv‐A‐U‐Hx
Constant Power
—Integrated Ba ery; Broad Range DC Output Type LEM-P04-200-A-U-Hx LEM-P09-300-A-U-Hx LEM-P13-300-A-U-Hx LEM-P18-300-A-U-Hx Rated voltage 120-277VAC 50/60Hz
Rated current 0.025A 0.04A 0.06A 0.08A Rated power 2.7W 3.5W 4.5W 6.0W Emergency output power 4.5W 9W 13.5W 18W Output voltage 5-200VDC 10-300VDC 15-300VDC 20-300VDC Battery Li-ion Charging time 24 Hours Discharge time >90Minutes Life time 5 years Operation temperature 0-55℃ (32°F-131°F) Abnormal protection Over load, Inrush current limiting, over temperature, open circuit, short-circuit protection with auto-reset EMC/FCC/IC standard EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3; FCC part 15, ICES-005 Safety standard EN 61347-1, EN 61347-2-7, UL924,CSA C.22.2 No. 141
LEM-Pww-vvv-A-U-HT (Terminal Block)
LEM-P04-200-A-U-HT: L200 [7.87] x W30 [1.18] x H22 [0.87] LEM-P09-300-A-U-HT: L260 [10.24] x W30 [1.18] x H22 [0.87] LEM-P13-300-A-U-HT: L345 [13.58] x W30 [1.18] x H22 [0.87] LEM-P18-300-A-U-HT: L410 [16.14] x W30 [1.18] x H22 [0.87]
LEM-Pww-vvv-A-U-HAC (Flexible Metal conduits)
LEM-P04-200-A-U-HAC: L258 [10.16] x W30 [1.18] x H22 [0.87] LEM-P09-300-A-U-HAC: L318 [12.52] x W30 [1.18] x H22 [0.87] LEM-P13-300-A-U-HAC: L403 [15.87] x W30 [1.18] x H22 [0.87] LEM-P18-300-A-U-HAC: L468 [18.43] x W30 [1.18] x H22 [0.87]
LEM-Pww-vvv-A-U-HE (IP66 Waterproof mounting)
LEM-P04-200-A-U-HE: L526 [20.71] x W56 [2.20] x H44 [1.73] LEM-P09-300-A-U-HE: L586 [23.07] x W56 [2.20] x H44 [1.73] LEM-P13-300-A-U-HE: L671 [26.42] x W56 [2.20] x H44 [1.73] LEM-P18-300-A-U-HE: L736 [28.98] x W56 [2.20] x H44 [1.73]
FO
R A
C L
ED
TU
BE
/B
UL
B/L
UM
INA
IRE
F
OR
DC
LE
D L
OA
D
7
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
The LEM‐P12‐060‐A‐U‐ML is a UL Listed, con‐stant power, ultra‐slim LED emergency driver designed to provide emergency backup power for LED ligh ng in indoor or damp loca on lumi‐naires. Features: Constant emergency power output, output
current auto adjusts Op onal Bluetooth Factory or field installa on Ultra‐Slim aluminum housing Suitable for use in dry or damp loca ons
Standard Features: Safety compliance to UL 924; CAN/CSA‐
C22.2 No. 141‐10 and NFPA requirements for 90 minute egress
Compliance to CEC Title 20 Over load, Inrush current limi ng, over tem‐
perature, open circuit, short circuit protec‐on with auto‐reset
Opera ng temperature: 32°F/0°C to 131F/55°C
Test switch / charging indicator light LiFePO4 19.2V/ C1500mAh ba er pack Emergency reac on me ≤ 2 sec
8
Constant Power
—Integrated Ba ery; Op onal Bluetooth
9
Driver Model No. Input
Voltage (VAC)
Output Power
(W)
Output Current
(mA)
Output Voltage (VDC)
Battery Pack Case Dimension
LEM-P12-060-A-U-ML 120-277VAC 12 200-660 18-60V BCP-LiFePO4 -19.2-1.5-L L24.1” x W1.2” x H1.1”
Wiring Diagrams: LEM‐P12‐060‐A‐U‐ML
Co
nfi
gura
on
#3
: S
ep
arat
e E
me
rge
ncy
/ A
C L
oad
s C
on
figu
rao
n #
2:
Par
al L
oad
C
on
figu
rao
n #
1:
Sh
are
d L
oad
Constant Power
– Integrated Ba ery; Op onal Bluetooth
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
Constant Power—Integrated Ba ery
McWong’s Class 2 UL Listed LEM series offers CEC compliant constant power LED emergency drivers, ranging from 5W to 25W. Exit wire op‐
ons include flying leads or flex conduit. Features: Constant emergency power output, output
auto adjusts Class 2 output voltage Slim aluminum housing Factory or field installa on Suitable for use in dry or damp loca ons Auto Test
Standard: Safety compliance to UL 924 for 90 mi‐
nute egress Compliance to CEC Title 20 Compliance to Class 2 FCC part 15, ICES‐005 Over load, Inrush current limi ng, over
temperature, open circuit, short circuit protec on with auto‐reset
Opera ng temperature: 32°F/0°C to 122°F/ 50°C
Test switch / charging indicator light Emergency reac on me ≤ 2 sec
10
11
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
Type LEM-P05-060-A-U-Px LEM-P09-060-A-U-Px LEM-P15-060-A-U-Px LEM-P25-060-A-U-Px
Rated voltage 120-277VAC 50/60Hz
Rated current 0.05A 0.06A 0.08A 0.15A
Rated power 2W 3W 4.5W 5.5W Emergency output power 5W 9W 15W 25W Output voltage 10-60VDC 11-60VDC 15-60VDC 25-60VDC Battery Ni-MH
Charging time 24 Hours Discharge time >90Minutes Charging current 0.08A 0.11A 0.19A 0.23A Life time 5 years
Operation temperature 0-50℃ (32°F-122°F)
Abnormal protection Over load, Inrush current limiting, over temperature, open circuit, short-circuit protection with auto-reset
EMC/FCC/IC standard EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3; FCC part 15, ICES-005
Safety standard EN 61347-1, EN 61347-2-7, UL924,CSA C.22.2 No. 141
LEM-Pww-060-A-U-PW (External wire, Integrated Battery)
LEM-P05-060-A-U-PW: L10.24” x W2.56” x H0.87” LEM-P09-060-A-U-PW: L12.09” x W2.56” x H0.87” LEM-P15-060-A-U-PW: L14.65” x W2.56” x H0.87” LEM-P25-060-A-U-PW: L14.09” x W3.23” x H1.18”
LEM-Pww-060-A-U-PC (Lead-wires with Flexible Metal conduits, Integrated Battery)
LEM-P05-060-A-U-PC: L10.24” x W2.56” x H0.87” LEM-P09-060-A-U-PC: L12.09” x W2.56” x H0.87” LEM-P15-060-A-U-PC: L14.65” x W2.56” x H0.87” LEM-P25-060-A-U-PC: L14.09” x W3.23” x H1.18”
Constant Power – Integrated Ba ery
Wiring Diagrams:
LE
M-P
ww
-060
-A-U
-PW
L
EM
-Pw
w-0
60-A
-U-P
C
12
Constant Power with Replaceable Ba ery Pack
McWong’s Class 2 UL Recognized LEM series offers CEC compliant constant power LED emer‐gency drivers, ranging from 5W to 25W. A single driver model can pair with different ba ery packs to provide flexibility in fixture design. Features: Constant emergency power output, output
auto adjusts Class 2 output voltage Factory installa on Field‐replaceable ba ery pack with quick
connect Slim aluminum housing Suitable for use in dry or damp loca ons Auto Test
Standard: Safety compliance to UL 924 for 90 minute
egress Compliance to CEC Title 20 Compliance to Class 2 FCC part 15, ICES‐005 Over load, Inrush current limi ng, over tem‐
perature, open circuit, short circuit protec‐on with auto‐reset
Opera ng temperature: 32°F/0°C to 122°F/ 50°C
Test switch / charging indicator light Emergency reac on me ≤ 2 sec
12
13
Constant Power with Replaceable Ba ery Pack
Battery Type BCP-NiMH-9.6-1.5 BCP-NiMH-10.8-2.1 BCP-NiMH-10.8-3.8 BCP-NiMH-14.4-4.5
Nominal Voltage (V) 9.6 10.8 10.8 14.4
Pack Capacity (mAh) 1500 2100 3800 4500
Output Wattage (W) 5 9 15 25
Chemistry NiMH
Charging time 24 Hours
Discharge time >90Minutes
Charging current (A) 0.08 0.11 0.19 0.23
Dimension mm[inch] L100[3.94] xW57[2.24] xH14 [0.55] Mounting
Center:115 [4.53]
L150[5.91] xW51 [2.01] xH17[0.67] Mounting
Center: 165 [6.50]
L213[8.39]xW56.4[2.22]xH18.8 [0.74] Mounting
Center: 230 [9.06]
L196[7.72]xW76.5[3.01]xH26 [1.02] Mounting
Center: 211 [8.31]
Wiring Diagrams:
L
EM
-Pw
w-0
60-A
-U-P
T
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
Module Type LEM-P05-060-A-U-PT LEM‐P09‐060‐A‐U‐PT LEM-P15-060-A-U-PT LEM-P25-060-A-U-PT Rated voltage 120‐277VAC 50/60Hz Rated current 0.04A 0.05A 0.07A 0.1A Rated power 2W 3W 4.5W 5.5W Emergency output power 5W@1500mAh Battery 9W@2100mAh Battery 15W@3800mAh Battery 25W@4500mAh Battery
Output voltage 10-60VDC 11-60VDC 15-60VDC 25-60VDC Operation temperature 0-50℃ (32°F-122°F)
Abnormal protection Over Load, inrush current limiting, over temperature, open circuit, short-circuit protection with auto-reset
Life time 5 years
Dimension mm[inch] L125 [4.92] x W65 [2.56] x H22 [0.87] Mounting Center: 117 [4.61]
McWong’s LEM series of UL Recognized con‐stant current LED emergency drivers are de‐signed to provide emergency backup power for 90 minutes egress. This product replaces emer‐gency fluorescent ballasts when fixtures are converted from fluorescent to LED light sources. Features: Constant emergency current output Field‐replaceable ba ery pack with quick
connect Factory installa on Powder coat steel, stainless or galvan‐
nealed case Suitable for use in dry or damp loca ons
Standard: Safety compliance to UL 924; CAN/CSA‐
C22.2 No. 141‐10 and NFPA requirements for 90 minute egress
Over load, Inrush current limi ng, over temperature, open circuit, short circuit protec on with auto‐rest
Opera ng temperature: 32°F/0°C to 122F/50°C
Test switch / charging indicator light Emergency reac on me ≤ 2 sec
14
Constant Current with Replaceable Ba ery Pack
15
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
Model No. Output Power (W) Output Voltage (VAC)
Output Current
(mA) Battery Battery Pak Case
Dimension
LEM-020-056-0350-U ~20 (max @ 56Vf) 12—56 350 NiCd (2 x 9.6V, 2.5Ah packs) 17.3” x 1” x 1.1” 14” x 1.2” x 1”
LEM-018-026-0700-U 18 (max @ 26Vf) 18 – 26 700 NiCd (2 x 8.4V, 2.5Ah packs) 15.3” x 1” x 1.1” 14” x 1.2” x 1”
LEM-010-028-0350-U ~10 (max @ 28Vf) 12—28 350 NiCd (2 x 9.6V, 1.2Ah packs)
12.6” x 0.8” x 0.9” 14” x 1.2” x 1”
Constant Current Linear
Model No. Output Power (W)
Output Voltage (VAC)
Output Current
(mA) Battery Battery Pak Case Dimension
LEM-C14-036-0400-U ~14 (max @ 36Vf) 12—36 400 NiMH (7.2V, 4.0Ah pack) 5.9” x 2” x 1” 6.3” x 1.6” x 1.1”
LEM-C07-036-0200-U ~7 (max @ 36Vf) 12 – 36 200 NiMH (7.2V, 2.1Ah pack) 5.9” x 1.4” x 0.8” 6.3” x 1.6” x 1.1”
Constant Current Compact
Model No. Output Power (W) Output Voltage (VAC)
Output Current
(mA) Battery Battery Pak Case
Dimension
LEM-M20-056-0350-U ~20 (max @ 56Vf) 12—56 350 NiCd (2 x 9.6V, 2.5Ah packs) 9.5” x 2.2” x 1.1” 7.8” x 2.1” x 1.3”
LEM-M10-028-0350-U ~10 (max @ 28Vf) 12—28 350 NiCd (2 x 9.6V, 1.2Ah packs) 5.2” x 1.8” x 0.9” 7.8” x 1.8” x 1.3”
Constant Current Rectangular
*Each LED emergency driver model is assigned a default set of ba ery packs, which are automa cally included with your order. Other ba ery pack op ons are available, but must be special ordered. This product series is op mized for use with McWong’s LED modules. For ques ons regarding compa bility with light sources from other manufacturers please contact technical support.
16
Dual‐Mode Normal + Emergency Programmable “Driverless”
McWong’s LEM series of UL Recognized con‐stant current Dual‐Mode Normal + Emergency Programmable “Driverless” is a combina on of LED driver and LED Emergency Driver. Emergen‐cy mode current se ngs: 150mA, 300mA, 450mA, or 600mA; Normal mode current se ngs for the two models range from 150mA to 300mA and 600mA to 1000mA, respec vely. Features: For normal opera on and emergency opera‐
on of LEDs, no need of an extra LED driver Normal mode LED so start, emergency
mode conversion within 1 second Field‐replaceable NiCd ba ery pack with
quick connect
Slim aluminum housing 1‐10V dimmable, DALI dimmable Suitable for use in dry or damp loca ons Standard: Safety compliance to UL 924 for 90 minute
egress Over load, Inrush current limi ng, over tem‐
perature, open circuit, short circuit protec‐on with auto‐reset
Opera ng temperature: 32°F/0°C to 122°F/50°C
Test switch / charging indicator light RoHS Compliant
Model No. LEM-D25-042P0600-U LEM-D42-042P1000-U
Rated voltage 120-277VAC 50/60Hz 120-277VAC 50/60Hz
Rated input current 0.3A (Max) 0.5A (Max)
Rated output power 25W (Max) 42W (Max)
Emergency output power ≤16.8W (Max @ 38V load) ≤16.8W (Max @ 42V load)
Output voltage 3~38VDC 3~42VDC
Operation frequency 320kHz≥f≥50kHz 320kHz≥f≥50kHz
Power Factor ≥0.9 ≥0.9
Battery 1.0, 2.0, 4.0Ah; 9.6V NiCd 1.0, 2.0, 4.0Ah; 9.6V NiCd
Charging time 36 Hours 36 Hours
Discharge time >90 Minutes >90 Minutes
Charging current 0.18A (Max) 0.18A (Max)
Life time 5 years 5 years
Operation temperature 0-50°C (32°F-122°F) 0-50°C (32°F-122°F)
Normal Operation Output current
150mA, 250mA, 300mA, 350mA, 400mA, 450mA, 500mA, 600mA ±3%
600mA, 700mA, 750mA, 800mA, 850mA, 900mA, 950mA, 1000mA ±3%
Abnormal protection Over load, Inrush current limiting, over temperature, open circuit, short-circuit
Protection with auto-reset
Over load, Inrush current limiting, over temperature, open circuit, short-circuit
Protection with auto-reset
Case Dimensions L6.9” x W2.6” x H0.9” L7.7” x W2.6” x H0.9”
EMC& EMF standard EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3; EN 62493
Safety standard EN 61347-1,EN 61347-2-13 ,EN 61347-2-7, UL924
Battery Pack Ni-Cd 1.0Ah 9.6V (AA): L7.7” x W1.3” x H0.6” —> Max 4W Ni-Cd 2.0Ah 9.6V (SC): L6.8” x W1.9” x H0.9” —> Max 8W Ni-Cd 4.0Ah 9.6V (D): L9.3” x W2.8” x H1.4” —> Max 17W
Dual‐Mode Normal + Emergency Programmable “Driverless”
17
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
18
Dual‐Mode Normal + Emergency Programmable “Driverless”
Wiring Diagrams: LEM‐D25‐042P0600‐U and LEM‐D42‐042P1000‐U
Dri
verl
ess
LED
Em
erg
en
cy
*Output current se ngs must be limited such that the product of the Emergency LED Array Voltage mes the Emergency Output Current does not exceed Ba ery Max Emergency Power ra ng.
Dipswitch Se ngs:
LEM‐D25‐042P0600‐U LEM‐D42‐042P1000‐U
4 5 �emergency Req’d Ba ery Typical Ra ng
0 0 150mA 1.0Ah 2W @ 12V
1.0Ah 4W @ 24V
2.0Ah 6W @ 36V
1 0 300mA 1.0Ah 4W @ 12V
2.0Ah 7W @ 24V
4.0Ah 11W @ 36V
0 1 450mA 2.0Ah 6W @ 12V
4.0Ah 11W @ 24V
4.0Ah 16W @ 36V
1 1 600mA 2.0Ah 7W @ 12V
4.0Ah 14W @ 24V
Dipswitches 4 and 5 set various emergency current values.
LEM‐Dxx‐042Pxxxx‐U Ba ery Op ons at Typical Voltages
Dipswitches 1‐3 determine the normal mode output current.
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 | Email: [email protected] | Web: www.mcwonginc.com
1 2 3 Current
150mA
250mA
300mA
350mA
400mA
450mA
500mA
600mA
1 2 3 Current
600mA
700mA
750mA
800mA
850mA
900mA
950mA
1000mA
19
Limited Warranty — LED Emergency Drivers
McWong Interna onal, Inc. (herea er referred to as
“MCWONG”), corporate headquarters located at 1921
Arena Blvd., Sacramento, CA 95834, warrants its
products to be free from defects in materials and
workmanship from the date of manufacture for the
following me periods:
MCWONG cannot assume any obliga ons or liabili es
for consequen al or incidental damages arising from,
or in connec on with, the use or performance of its
products or other indirect damages with respect to loss
of property, revenue or profit, or cost of removal,
installa on or reinstalla on.
This limited warranty is not applicable to any product
subjected to abnormal stress, such as improper
storage, installa on, use and/or maintenance. This
warranty is invalid for any product not installed and
operated in accordance with all relevant federal, state,
and local government regula ons, established industry
safety standards, published electrical and temperature
ra ngs, and any specific instruc ons provided by
MCWONG for the installa on of the product (s).
This limited warranty is extended by MCWONG only to
the original or first end‐user purchaser.
The standards and condi ons of any tests performed
on any MCWONG product(s) by the original purchaser,
or by any third party ac ng on behalf of the original
purchaser, shall be mutually agreed upon in wri ng
and MCWONG shall be no fied of, and may be
represented at any such tests.
Should defects occur a er installa on, and within the
warranty period, they should be specifically described
to a MCWONG representa ve. MCWONG shall correct
any defects, at MCWONG’s op on, by furnishing
materials to repair or replace any product (s) that may
prove defec ve in materials or workmanship within
the warranty period, or by extending a credit in the
amount of the purchase price. This does not apply to:
(1) damage caused by accident, abuse, mishandling, or
dropping; (2) materials which have been subject to
unauthorized repair; (3) materials not used in
accordance with instruc ons; (4) ordinary wear and
tear. MCWONG will be limited to the furnishing of new
parts, free of charge, or extending credit for in the
amount of the purchase price, in exchange for parts
proven to be defec ve and does not include any other
costs of removal or installa on.
This limited warranty cons tutes the sole and
exclusive remedy of the purchase and the exclusive
liability of MCWONG, and is in lieu of any and all other
warran es, expressed, implied, or statutory as to
merchantability, fitness for purpose sold, descrip on,
quality produc veness, or any other ma er. NO
IMPLIED STATUTORY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE SHALL APPLY BEYOND THE
AFOREMENTIONED WARRANTY PERIOD.
Warranty claims can be submi ed by calling our toll
free technical support hotline (888) 600‐9188 or by
visi ng our website www.McWonginc.com and filling
out a Warranty Replacement Form (Click on Support >>
Warranty Statements). Completed forms should be
faxed to (916) 371‐6666 or emailed to
Product Series Warranty
LED Emergency Drivers (all types) 60 months
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834 Tel: 916‐371‐8080 Fax: 916‐371‐6666 Email: [email protected] Web: www.mcwonginc.com
Copyright© 2020 McWong Interna onal, Inc. Specifica ons subject to change without no ce V5.01