lecture protection
TRANSCRIPT
-
8/12/2019 Lecture protection
1/58
Advanced Power System Protection
Lecture No.1
Dr. Muhammad Kamran
-
8/12/2019 Lecture protection
2/58
Text Book
Elsevier Practical Power System Protection
By
L.G Hewitson, Mark Brown and Ramesh Balakrishanan Any other reference book or Website
13-Feb-14 2 Muhammad Kamran
-
8/12/2019 Lecture protection
3/58
Contents
Need for protective system Basic requirements
Basic components Summary
13-Feb-14 3 Muhammad Kamran
-
8/12/2019 Lecture protection
4/58
Need for protection
A power system is not only capable to meet thepresent load but also has the flexibility to meetthe future demands
A power system is designed to generate electricpower in sufficient quantity, to meet the presentand estimated future demands of the users in a
particular area, to transmit it to the areas whereit will be used and then distribute it within thatarea, on a continuous basis.
13-Feb-14 4 Muhammad Kamran
-
8/12/2019 Lecture protection
5/58
To ensure the maximum return on the largeinvestment in the equipment, which goes tomake up the power system and to keep theusers satisfied with reliable service, the wholesystem must be kept in operationcontinuously without major breakdowns
13-Feb-14 5 Muhammad Kamran
-
8/12/2019 Lecture protection
6/58
The first way is to implement a systemadopting components, which should not failand requires the least or nil maintenance tomaintain the continuity of service
By common sense, implementing such asystem is neither economical nor feasible,except for small systems.
13-Feb-14 6 Muhammad Kamran
-
8/12/2019 Lecture protection
7/58
The second option is to foresee any possibleeffects or failures that may cause long-termshutdown of a system, which in turn may take
longer time to bring back the system to itsnormal course The main idea is to restrict the disturbances
during such failures to a limited area andcontinue power distribution in the balanceareas
13-Feb-14 7 Muhammad Kamran
-
8/12/2019 Lecture protection
8/58
Special equipment is normally installed todetect such kind of failures (also calledfaults) that can possibly happen in varioussections of a system, and to isolate faultysections so that the interruption is limited to alocalized area in the total system covering
various area
13-Feb-14 8 Muhammad Kamran
-
8/12/2019 Lecture protection
9/58
The special equipment adopted to detect suchpossible faults is referred to as protective equipment or protective relay and the systemthat uses such equipment is termed as protectionsystem
A protective relay is the device, which givesinstruction to disconnect a faulty part of thesystem
This action ensures that the remaining system isstill fed with power, and protects the system fromfurther damage due to the fault
13-Feb-14 9 Muhammad Kamran
-
8/12/2019 Lecture protection
10/58
Hence, use of protective apparatus is verynecessary in the electrical systems, which areexpected to generate, transmit and distribute
power with least interruptions and restorationtime It can be well recognized that use of
protective equipment are very vital tominimize the effects of faults, which otherwisecan kill the whole system.
13-Feb-14 10 Muhammad Kamran
-
8/12/2019 Lecture protection
11/58
The special equipment adopted to detect suchpossible faults is referred to as protective equipment or protective relay and the systemthat uses such equipment is termed asprotection system
A protective relay is the device, which givesinstruction to disconnect a faulty part of thesystem
This action ensures that the remaining system isstill fed with power, and protects the system fromfurther damage due to the fault
13-Feb-14 11 Muhammad Kamran
-
8/12/2019 Lecture protection
12/58
-
8/12/2019 Lecture protection
13/58
Basic Requirements for Protection
A protection apparatus has three mainfunctions/duties:
1. Safeguard the entire system to maintaincontinuity of supply
2. Minimize damage and repair costs where itsenses fault
3. Ensure safety of personnel.
13-Feb-14 13 Muhammad Kamran
-
8/12/2019 Lecture protection
14/58
These requirements are necessary, firstly for early detection andlocalization of faults, and secondly for prompt removal of faultyequipment from service
In order to carry out the above duties, protection must have thefollowing qualities:
Selectivity: To detect and isolate the faulty item only. Stability: To leave all healthy circuits intact to ensure continuity orsupply. Sensitivity: To detect even the smallest fault, current or systemabnormalities and operate correctly at its setting before the fault
causes irreparable damage. Speed: To operate speedily when it is called upon to do so, therebyminimizing damage to the surroundings and ensuring safety topersonnel.
13-Feb-14 14 Muhammad Kamran
-
8/12/2019 Lecture protection
15/58
Basic components of protection Protection of any distribution system is a function of
many elements and this manual gives a brief outline ofvarious components that go in protecting a system
Following are the main components of protection; Fuse is the self-destructing one, which carries the
currents in a power circuit continuously and sacrificesitself by blowing under abnormal conditions
These are normally independent or stand-alone protective components in an electrical system unlike acircuit breaker, which necessarily requires the supportof external components
13-Feb-14 15 Muhammad Kamran
-
8/12/2019 Lecture protection
16/58
Accurate protection cannot be achieved withoutproperly measuring the normal and abnormalconditions of a system
In electrical systems, voltage and currentmeasurements give feedback on whether asystem is healthy or not
Voltage transformers and current transformersmeasure these basic parameters and are capableof providing accurate measurement during faultconditions without failure
13-Feb-14 16 Muhammad Kamran
-
8/12/2019 Lecture protection
17/58
The measured values are converted into analog and/ordigital signals and are made to operate the relays,which in turn isolate the circuits by opening the faultycircuits. In most of the cases, the relays provide two
functions viz., alarm and trip, once the abnormality isnoticed The relays in old days had very limited functions and
were quite bulky However, with advancement in digital technology and
use of microprocessors, relays monitor variousparameters, which give complete history of a systemduring both pre-fault and post-fault conditions
13-Feb-14 17 Muhammad Kamran
-
8/12/2019 Lecture protection
18/58
The opening of faulty circuits requires some time,which may be in milliseconds, which for acommon day life could be insignificant
However, the circuit breakers, which are used toisolate the faulty circuits, are capable of carryingthese fault currents until the fault currents aretotally cleared
The circuit breakers are the main isolating devicesin a distribution system, which can be said todirectly protect the system
13-Feb-14 18 Muhammad Kamran
-
8/12/2019 Lecture protection
19/58
The operation of relays and breakers requirepower sources, which shall not be affected byfaults in the main distribution
Hence, the other component, which is vital inprotective system, is batteries that are used toensure uninterrupted power to relays andbreaker coils
13-Feb-14 19 Muhammad Kamran
-
8/12/2019 Lecture protection
20/58
Faults, types and effects
When a consumer requests electrical powerfrom a supply authority, ideally all that isrequired is a cable and a transformer, shownphysically as in Figure 2.1
While Radial Distribution system is shown infigure 2.2
13-Feb-14 20 Muhammad Kamran
-
8/12/2019 Lecture protection
21/58
13-Feb-14 21 Muhammad Kamran
-
8/12/2019 Lecture protection
22/58
13-Feb-14 22 Muhammad Kamran
-
8/12/2019 Lecture protection
23/58
Advantages and disadvantages ofRadial system
If a fault occurs at T2 then only the protectionon one leg connecting T2 is called intooperation to isolate this leg
The other consumers are not affected If the conductor to T2 fails, then supply to this
particular consumer is lost completely andcannot be restored until the conductor isreplaced/repaired.
13-Feb-14 23 Muhammad Kamran
-
8/12/2019 Lecture protection
24/58
This disadvantage can be overcome byintroducing additional/parallel feeders asshown in figure, connecting each of theconsumers radially as shown in next slide
However, this requires more cabling and is notalways economical
The fault current also tends to increase due touse of two cables
13-Feb-14 24 Muhammad Kamran
-
8/12/2019 Lecture protection
25/58
Radial Distribution system with parallelfeeders
13-Feb-14 25 Muhammad Kamran
-
8/12/2019 Lecture protection
26/58
-
8/12/2019 Lecture protection
27/58
Ring Main Distribution system
13-Feb-14 27 Muhammad Kamran
-
8/12/2019 Lecture protection
28/58
Essentially, meets the requirements of twoalternative feeds to give 100% continuity ofsupply, whilst saving in cabling/copper comparedto parallel feeders
For faults at T1 fault current is fed into fault viatwo parallel paths effectively reducing theimpedance from the source to the fault location,and hence the fault current is much higher
compared to a radial path The fault currents in particular could vary
depending on the exact location of the fault
13-Feb-14 28 Muhammad Kamran
-
8/12/2019 Lecture protection
29/58
Protection must therefore be fast anddiscriminate correctly, so that other consumersare not interrupted
The above case basically covers feeder failure,since cable tend to be the most vulnerablecomponent in the network
Not only are they likely to be hit by a pick oralternatively dug-up, or crushed by heavymachinery, but their joints are notoriously weak,being susceptible to moisture, ingress, etc.,amongst other things
13-Feb-14 29 Muhammad Kamran
-
8/12/2019 Lecture protection
30/58
Transformer faults are not so frequent,however they do occur as windings are oftenstrained when carrying through-fault current
Also, their insulation lifespan is very oftenreduced due to temporary or extendedoverloading leading to eventual failure
Hence interruption or restriction in the powerbeing distributed cannot be avoided in case oftransformer failures
13-Feb-14 30 Muhammad Kamran
-
8/12/2019 Lecture protection
31/58
-
8/12/2019 Lecture protection
32/58
The loss of a busbar in a network can in factbe a catastrophic situation, and it isrecommended that this component be givencareful consideration from a protectionviewpoint when designing network,particularly for continuous process plants such
as mineral processing
13-Feb-14 32 Muhammad Kamran
-
8/12/2019 Lecture protection
33/58
Fault types and their effects
It is not practical to design and build electricalequipment or networks to eliminate thepossibility of failure in service
It is therefore an everyday fact that differenttypes of faults occur on electrical systems,however infrequently, and at random locations
Faults can be broadly classified into two mainareas, which have been designated active andpassive
13-Feb-14 33 Muhammad Kamran
-
8/12/2019 Lecture protection
34/58
Active faults
The active fault is when actual current flowsfrom one phase conductor to another (phase-to-phase), or alternatively from one phaseconductor to earth (phase-to-earth)
This type of fault can also be further classifiedinto two areas, namely the solid fault and the
incipient(Beginning) fault
13-Feb-14 34 Muhammad Kamran
-
8/12/2019 Lecture protection
35/58
The solid fault occurs as a result of an immediatecomplete breakdown of insulation as wouldhappen if, say, a pick struck an underground
cable, bridging conductors, etc. or the cable wasdug up by a bulldozer
In mining, a rockfall could crush a cable, as would
a shuttle car In these circumstances the fault current would be
very high resulting in an electrical explosion
13-Feb-14 35 Muhammad Kamran
-
8/12/2019 Lecture protection
36/58
This type of fault must be cleared as quickly aspossible, otherwise there will be:
Increased damage at fault location
Fault energy = I2
Rf t , where t is time in seconds. Danger to operating personnel (flashes due to high
fault energy sustaining for a long time). Danger of igniting combustible gas in hazardous areas,
such as methane in coal mines which could causehorrendous disaster. Increased probability of earth faults spreading to
healthy phases
13-Feb-14 36 Muhammad Kamran
-
8/12/2019 Lecture protection
37/58
Higher mechanical and thermal stressing of allitems of plant carrying the fault current,particularly transformers whose windings sufferprogressive and cumulative deteriorationbecause of the enormous electromechanicalforces caused by multi-phase faults proportionalto the square of the fault current
Sustained voltage dips resulting in motor (and
generator) instability leading to extensiveshutdown at the plant concerned and possiblyother nearby plants connected to the system
13-Feb-14 37 Muhammad Kamran
-
8/12/2019 Lecture protection
38/58
The incipient fault, on the other hand, is afault that starts as a small thing and getsdeveloped into catastrophic failure
Like for example some partial discharge(excessive discharge activity often referred toas Corona) in a void in the insulation over anextended period can burn away adjacentinsulation, eventually spreading further anddeveloping into a solid fault
13-Feb-14 38 Muhammad Kamran
-
8/12/2019 Lecture protection
39/58
Other causes can typically be a high-resistance joint or contact, alternatively pollution ofinsulators causing tracking across their surface
Once tracking occurs, any surrounding air willionize which then behaves like a solidconductor consequently creating a solid fault
13-Feb-14 39 Muhammad Kamran
-
8/12/2019 Lecture protection
40/58
Passive Faults Passive faults are not real faults in the true sense of the
word, but are rather conditions that are stressing thesystem beyond its design capacity, so that ultimately activefaults will occur
Typical examples are: Overloading leading to over heating of insulation
(deteriorating quality, reduced life and ultimate failure). Overvoltage: Stressing the insulation beyond its withstand
capacities.
Under frequency: Causing plant to behave incorrectly. Power swings: Generators going out-of-step or out-of-
synchronism with each other
13-Feb-14 40 Muhammad Kamran
-
8/12/2019 Lecture protection
41/58
Largely, the power distribution is globally athree-phase distribution especially frompower sources
The types of faults that can occur on a three-phase AC system are shown in Figure;
13-Feb-14 41 Muhammad Kamran
-
8/12/2019 Lecture protection
42/58
-
8/12/2019 Lecture protection
43/58
Types of faults on a three-phase system: (A)Phase-to-earth fault; (B) Phase-to-phase fault;(C) Phase-to phase- to-earth fault; (D) Three-phase fault; (E) Three-phase-to-earth fault; (F)Phase-to-pilot fault*; (G) Pilot-to-earth fault
13-Feb-14 43 Muhammad Kamran
-
8/12/2019 Lecture protection
44/58
Voltage situation at Relay positionunder various faults
Voltage of phase which encounters the faultdecays
13-Feb-14 Muhammad Kamran 44
-
8/12/2019 Lecture protection
45/58
It will be noted that for a phase-to-phase fault, thecurrents will be high, because the fault current is onlylimited by the inherent (natural) series impedance ofthe power system up to the point of fault (Ohms law)
By design, this inherent series impedance in a powersystem is purposely chosen to be as low as possible inorder to get maximum power transfer to the consumerso that unnecessary losses in the network are limitedthereby increasing the distribution efficiency
Hence, the fault current cannot be decreased without acompromise on the distribution efficiency, and furtherreduction cannot be substantial
13-Feb-14 45 Muhammad Kamran
-
8/12/2019 Lecture protection
46/58
On the other hand, the magnitude of earthfault currents will be determined by themanner in which the system neutral is earthed
It is worth noting at this juncture that it ispossible to control the level of earth faultcurrent that can flow by the judicious choice
of earthing arrangements for the neutral
13-Feb-14 46 Muhammad Kamran
-
8/12/2019 Lecture protection
47/58
Solid neutral earthing means high earth fault currents,being limited by the inherent earth fault (zerosequence) impedance of the system, whereasadditional impedance introduced between neutral and
earth can result in comparatively lower earth faultcurrents
In other words, by the use of resistance or impedancein the neutral of the system, earth fault currents can be
engineered to be at whatever level desired and aretherefore controllable This cannot be achieved for phase faults
13-Feb-14 47 Muhammad Kamran
-
8/12/2019 Lecture protection
48/58
Transient and permanent faults Transient faults are faults, which do not damage the insulation
permanently and allow the circuit to be safely re-energizedafter a short period.
A typical example would be an insulator flashover following alightning strike, which would be successfully cleared onopening of the circuit breaker, which could then beautomatically closed. Transient faults occur mainly on outdoorequipment where air is the main insulating medium
Permanent faults, as the name implies, are the result ofpermanent damage to the insulation
In this case, the equipment has to be repaired and rechargingmust not be entertained before repair/restoration
13-Feb-14 48 Muhammad Kamran
-
8/12/2019 Lecture protection
49/58
Symmetrical and asymmetrical faults
A symmetrical fault is a balanced fault withthe sinusoidal waves being equal about theiraxes, and represents a steady-state condition
An asymmetrical fault displays a DC offset,transient in nature and decaying to the steadystate of the symmetrical fault after a period of
time, as shown in Figure
13-Feb-14 49 Muhammad Kamran
-
8/12/2019 Lecture protection
50/58
13-Feb-14 50 Muhammad Kamran
-
8/12/2019 Lecture protection
51/58
-
8/12/2019 Lecture protection
52/58
-
8/12/2019 Lecture protection
53/58
Example of power station
13-Feb-14 53 Muhammad Kamran
-
8/12/2019 Lecture protection
54/58
Effect of fault on Transmission lines
13-Feb-14 54 Muhammad Kamran
-
8/12/2019 Lecture protection
55/58
Protection equipment The definitions that follow are generally used in
relation to power system protection: a. Protection System: a complete arrangement of
protection equipment and other devices required toachieve a specified function based on a protectionprincipal (IEC 60255-20)
b. Protection Equipment: a collection of protectiondevices (relays, fuses, etc.). Excluded are devices such asCTs, CBs, Contactors, etc.
c. Protection Scheme: a collection of protectionequipment providing a defined function and including allequipment required to make the scheme work (i.e. relays,CTs, CBs, batteries, etc.)
13-Feb-14 Muhammad Kamran 55
-
8/12/2019 Lecture protection
56/58
General Relaying Requirement In order to fulfil the requirements of protection with the
optimum speed for the many different configurations,operating conditions and construction features of powersystems, it has been necessary to develop many types ofrelay that respond to various functions of the power systemquantities
For example, observation simply of the magnitude of thefault current suffices in some cases but measurement ofpower or impedance may be necessary in others
Relays frequently measure complex functions of the systemquantities, which are only readily expressible bymathematical or graphical means
13-Feb-14 Muhammad Kamran 56
-
8/12/2019 Lecture protection
57/58
Relays may be classified according to thetechnology used:
a. electromechanical b. static c. digital
d. numerical
13-Feb-14 Muhammad Kamran 57
-
8/12/2019 Lecture protection
58/58
Next Lecture
Calculations and Zones of Protection