P/N 01661
Lead/Lag ControllerModel LL357D4
Operational Specifications
• ThermostatRange:45ºFto90ºF(7ºCto32ºC)
• Accuracy:±1ºF(±½ºC)
• ChangeoverTemperatureDifferential(separationbetweentheheatsetpointandthecoolsetpoint):2ºFto9ºF(1.0ºCto4.5ºC)
• FirstStageTemperatureDifferential(numberofdegreesbetweenthesetpointtemperatureandthe“turnon”temperature):1ºFto3ºF(.5ºCto1.5ºC)
• SecondStageTemperatureDifferential(numberofdegreesbetweenwhenstage1turnsonandwhenstage2turnson):1ºFto6ºF(.5ºCto3.0ºC).
• MinimumCoolTemperatureSetPoint:Adjustablefrom45ºFto75ºF(7ºCto24.0ºC).
• MaximumHeatTemperatureSetPoint:Adjustablefrom55ºFto90ºF(13ºCto32.0ºC)
• StagedOFFOutputs:Airconditionerswillturnoffindependently.
Electrical Specifications
• Compatiblewithstandard24-voltAC,2stageheating/coolingsystems.
• 24Voltcontrol(18to30VAC).
• 1ampmaximumperterminal.
• 4ampmaximumtotalload.
Ease of Use
• BacklightingofthelargedisplaymakestheLiquidCrystalDisplay(LCD)easytoread.
• MostfrequentlyusedkeysarelocatedbytheLCDforquick&easyaccesstoinformation.
• Easyinstallation,setupandsystemtestssavestime.
• Setpointsarepermanentlyheldinmemoryandretainedduringpoweroutages-nobatteriesrequired.
• Programmingnotrequired.
• Digitaldisplayshowstemperaturein°For°C.
• RoomTemperatureOffset:Usedtocalibratedisplayedroomtemperaturewithactualroomtemperature
• StatusIndicatorLight:Indicateswhichstageisrunning.Greenlightmeanscooling&redlightmeansheating.
Model LL357D4 Lead/Lag ControllerTheMarvair®LL357D4isacompletecontrolpackage
designedtooperateafullyorpartiallyredundantairconditioningsystem.Itconsistsofatwo-stageheatandcoolelectronicthermostatandasolidstatetimer.ItcanbeusedwitheithertheMarvairComPac®Iverticalpackagedwallmountairconditioner,ouruniqueComPac®IIairconditionerwithbuilt-ineconomizerandmanyoftheMarvairEnvironmentalControlUnits(ECU).TheLL357D4providesenvironmentalcontrolandthesecuritydemandedbythecommunicationshelterindustryforaback-upunit.Thelead/lagcontrollerinsuresequalwearonbothairconditionerswhileallowingthelagunittoassistupondemand.Phasingofairconditionersisnotrequiredforproperoperation.Theenvironmentallysafe,mercury-freeLL357D4isfactorywired,testedandmountedinanenclosureforquickinstallation.TheLL357D4whenusedwiththeheatpumpadapter,ModelLL357H,providescontrolofredundantheatpumpsystems.RefertotheHeatPumpAdapterProductBulletinfordetails.
Specification/Features
LL357D4 PDS 4.2011 rev. 1
LL357D4 PDS, 4.2011 2
Specification/Features (cont'd)Ease of Installation
• Wiringconnectionsinsensitivetothephasingoftheairconditioners.
• Temperaturesensorbuiltintotheunit(optionalremotesensoravailable).
• Easyterminalconnectionsforthermostatwire.
Timing Device
• Solidstatetimerwithboth3.5and7daychangeovercapability.Timingaccuracy±5%.
• Momentarypushbuttonforacceleratedmanualtimeradvance.(7seconds=7days)
• Lightemittingdiodesindicatepoweronandidentifiestheleadunit.
Enclosure
• 16gaugeappliancewhite,pre-paintedaluminum.
• Provideslowprofilethermostatmounting.
• Openingsincoverfor“LED”indicationofpoweronandforleadunit.
• Doublesasjunctionboxforcontrolwiringtoairconditioners.
Low Voltage Wiring1. Allwiringmustcomply
withlocalcodesandordinances.
2. Disconnectpowertopreventelectricalshockorequipmentdamage.
3. Ondualunits,wiretheairconditionersaccordingtothewiringdetail.
4. Providepowertothecontroller.
NOTE:
• Terminals 5 and 7 on the ComPac® I & ComPac® II air conditioner’s terminal board are dry contacts which can be used for remote signalling in the event of equipment cut-off on refrigerant pressure limit.
• For continuous indoor fan operation, install a jumper between terminals 8 and 3 and remove jumper between 1 and 3.
• Also, terminals 8 and 10 can be connected to a normally closed smoke or fire detector to cause equipment shutdown when the circuit is opened. (Remove factory jumper.)
LED Operation• Green (middle light) means
power on to both units.
• Red (left and right lights) indicates the lead unit.
3 LL357D4 PDS, 4.2011
Sub-base Illustration
Important Safety PrecautionsWARNING!:Always turn off power at the main power supply before installing, cleaning, or
removing thermostat.• Thisthermostatisfor24VACapplicationsonly;donotuseonvoltagesover30VAC• Donotshortacrossterminalsofsystemcontroltotestoperation;thiswilldamageyourthermostat
andvoidyourwarranty• Allwiringmustconformtolocalandnationalelectricalandbuildingcodes• Usethisthermostatonlyasdescribedinthismanual
To Install LL357D4 Thermostat/ControllerELECTRICAL SHOCK HAZARD – Turn off power at the main service panel by removing the
fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat.
IMPORTANT:Thermostatinstallationmustconformtolocalandnationalbuildingandelectricalcodesandordinances.
Note:Mountthethermostataboutfivefeetabovethefloor.Donotmountthethermostatonanoutsidewall,indirectsunlight,behindadoor,orinanareaaffectedbyaventorduct.
1. Turnoffpowertotheheatingandcoolingsystembyremovingthefuseorswitchingofftheappropriatecircuitbreaker.
2. Putthermostatbaseagainstthewallwhereyouplantomountit(Besurewireswillfeedthroughthewireopeninginthebaseofthethermostat).
3. Marktheplacementofthemountingholes.
4. Usingadrillbit,drillholesintheplacesyouhavemarkedformounting.
5. Alignthermostatbasewithmountingholesandfeedthecontrolwiresthroughwireopening.
6. Usescrewstomountthermostatbasetowall.
7.Insertstripped,labeledwiresinmatchingwireterminals.SeeWiringDiagrams.CAUTION!:Besureexposedportionofwiresdoesnottouchotherwires.
8.Tightenscrewsonterminalblock.Gentlytugwiretobesureofproperconnection.Doublecheckthateachwireisconnectedtotheproperterminal.
LL357D4 PDS, 4.2011 4
9.Sealholeforwiresbehindthermostatwithnon-flammableinsulationorputty.
10.Replacecoveronthermostat.
11.Turnonpowertothesystematthemainservicepanel.
12.Testthermostatoperationasdescribedin“TestingtheThermostat”(Page6).
Remote Sensor Installation (optional)1. Removecoverfromremotesensorhousing.
2. Selectanappropriatelocationformountingtheremotesensor.
3. Mountremotesensorunitusinghardwareprovided.
4. Installtwowiresbetweenremotesensorandthermostat(useshieldedcablethatisadequatelygrounded).
• Wire1shouldrunbetweentheS1terminalonthethermostatandtheS1terminalontheremotesensor
• Wire2shouldrunbetweentheS2terminalonthethermostatandtheS2terminalontheremotesensor
5. Disablethemainsensor(R12)onthethermostatbycuttingitfromthecircuitboard.
Configuration ModeTheconfigurationmodeisusedtosettheLL357D4thermostattomatchyourheating/coolingsystem.
TheLL357D4functionswithairconditionerswithelectricheatsystems.
ToconfiguretheLL357D4,performthefollowingsteps:
1. VerifythattheLL357D4isintheOFFmode.PresstheSYS(left)buttonuntilmodedisplays.
2. Removethecoverofthethermostatbygentlypullingnearoneofthecornersatthetopofthethermostat.
3. PresstheCONFIGbuttonforonesecondwhilethethermostatisintheOFFmode.
UsetheUpandDownbuttonstochangesettingswithineachscreen.
PresstheRightbuttontoadvancetothenextscreen.
PresstheLeftbuttontoreturntopreviousscreen.
4. ToexitConfigurationMode,presstheCONFIGswitchfor1second.
Configuration Mode Settings
ThesetupscreensfortheConfigurationModefollow:
1. TemperatureScale(°For°C)ChooseFahrenheitorCelsius.
PresstheUporDownbuttontoselectscale.
PresstheRightbuttontoadvancetothenextscreen.
2. 1st Stage Temperature Differential(1°Fto5°F)(0.5°Cto2.5°C)Setthenumberofdegreesbetweenyour“setpoint”temperatureandyour“turnon”temperature.Marvairrecommends2ºF.
PresstheUporDownbuttontosetdifferentialvalue.
PresstheRightbuttontoadvancetothenextscreen.
5 LL357D4 PDS, 4.2011
3. 2nd Stage Temperature Differential(1°Fto5°F)(0.5°Cto2.5°C)Setthenumberofdegreesbetweenwhenstage1turnsonandwhenstage2turnson.Marvairrecommends2ºF.
PresstheUporDownbuttontoselectdifferential.
PresstheRightbuttontoadvancetothenextscreen.
4. Staged Off OutputsSelectwhethertheoutputsforheatingandcoolingarestagedoffindependentlyoraresatisfiedsimultaneously.Select“1”,outputsstagedindependently.
1=outputsstagedoffindependently
0=outputsoffsimultaneously
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
5. Minimum Deadband(1°Fto9°F)(1°Cto5°C)SettheminimumseparationbetweenheatsetpointandcoolsetpointinAutoChangeoverMode.Marvairrecommends3ºF.
PresstheUporDownbuttontosetdeadbandvalue.
PresstheRightbuttontoadvancetothenextscreen.
6. System–Setforheatpump,non-HeatPump(airconditioner),reversingvalveoperationandnumberofcompressorsinyoursystem.Setupfor“Non-HeatPump”andTypeofHeat“Electric”.
PresstheUporDownbuttontoselectscale.
PresstheRightbuttontoadvancetothenextscreen.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
7. Auxiliary Delay ON–(0-30minutes)Setthedelaytimeinminutesforauxiliaryheattobelockedoutafteracallforsecondstage.Thisextrasavingsfeatureisusedtotemporarilylockoutauxiliaryheatdevices,allowingjustheatpumptotrytosatisfyheatcall.Setto0minutes.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
8. Lockout(0-8°,COOL-HEAT)Selectthenumberofdegreessettemperaturecanbechangedduringkeypadlockout.COOL-HEATlockoutallowsadjustmentofthesettemperaturestothemaximumheatsettemperatureselectedinStep9andminimumcoolsettemperatureselectedinStep10.
Note:Themodecannotbechangedwhenthethermostatislocked.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
Choose System Reversing Valve Active
Number of Compressorsor Compressor Stages
Type ofHeat
HeatPump
HP O 1
HP b 1
HP O 2
HP b 2
Non-HeatPump
Heat Gas
Heat Electric
LL357D4 PDS, 4.2011 6
Configuration Mode Settings (cont'd)
9. Maximum Heat Setpoint(45°Fto90°F)(7°Cto32°C) Adjusttocontrolthemaximumheatsettemperatureallowed.Marvairrecommendsamax.heat setpointof78ºF(25.6ºC)
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
10. Minimum Cool Setpoint(45°Fto90°F)(7°Cto32°C) Adjusttocontroltheminimumcoolsettemperatureallowed.Marvairrecommendsaminimum coolsetpointof68ºF(20ºC).
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
11. Room Temperature Offset(+9°Fto-9°F)(+4.5°Cto-4.5°C) Adjusttocalibratedisplayedroomtemperaturetomatchactualroomtemperature.Note:When notsetto0,ºwilldisplay.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
12. Temperature Sensor (1-3)
1.Onlyon-boardsensordeterminesroomtemperature.
2.Onlyremotesensordeterminesroomtemperature.
3.Averagetemperatureofon-boardandremotesensor.
Note:Ifthereisnoremotesensor,option1mustbeselected.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
13. Cooling Fan Delay Off Time(0,30,60,90seconds) Selectthefanpurgetimeforcooling.Marvairrecommends0seconds.
PresstheUporDownbuttontoselect.
PresstheRightbuttontoadvancetothenextscreen.
14. Status Indicator Light (Led0,1,2) Marvairrecommends1.
0=Statusindicatorneveron
1=Statusindicatoronwithfirststage
2=Statusindicatoronwithsecondstage
PresstheUporDownbuttontoselect.
PresstheCONFIGbuttonfor2secondstoexitconfiguration.
7 LL357D4 PDS, 4.2011
Testing the ThermostatNote: The LL357D4 does not require the units to be in phase.
Procedure: (A/C Testing with LL357D4 Lead/Lag Control for Two Units)
UP-Usedtoincreasethetime,settemperaturesandtoadjustconfigurationsettings.
DOWN-Usedtodecreasethetime,settemperaturesandtoadjustconfigurationsettings.
SYS(left)-UsedtochangefromOFF,HEAT,COOLandAUTOchangeovermodes.
RIGHT-Usedtoturnonandofftheindoorfan.
UP, SYS and RIGHT-Heldinsimultaneouslyfor10secondstolockandunlockthethermostat.
DOWN and SYS-Pressedsimultaneouslytodisplayoutdoortemperatureifoutdoorremotesensorisconnected.
1. Setthecoolingtemperatureonthewallthermostattoapointhigherthantheambienttemperature.Settheheatingtemperaturetoatemperaturethatislowerthantheambienttemperature.Turntheselectorswitchtothe“off”position.
2. SetthetimedelayonunitNo.1to“3”minutes,andNo.2to“5”minutes.
3. Setthechangeoversettingoftheenthalpycontroltothe“d”setting(ComPac®IIA/Conly).
4. ProvidepowertoA/Cunitsandturndisconnectson.
5. Checkincomingpowertoeachunit.Forunitsdesignedforoperationon208/230v,60hzpowersupply,thetransformerisfactorywiredfora230powersupply.Fora208powersupplyremovetheorangeleadfromthetransformerandconnecttheredlead.Insulatetheorangelead.
6. Cooling.UsetheSYSswitchtosetthethermostatto“AUTO”.Slowlylowerthecoolingtemperatureuntiltheswitchcloses.Theindoorfanshouldoperateontheleadunit.Oncetheindoorfanturnson,allowapproximately3to5minutesforthecompressortostart.Notethattheoutdoorfanmaynotcomeonimmediatelybecauseitiscycledbyrefrigerantpressures.Next,lowerthetemperatureuntiltheswitchcloses.Followtheaboveproceduresforthelagunit.
Thegreenlightontheleadlagcontrolshouldbeon.Oneamberlightwillbeontoidentifytheleadunit.Theotherlightshouldbeoff.Ifthelagunitcomesonwiththeleadunitthelightforthelagunitwillnotcomeon.Youshouldneverhaveall3lightsonatonetime.
Allowtheunitstorunfor2to3minutesthencheckthetemperaturedifferentialbetweenthereturnairandthesupplyairwithdigitalthermometer.Thetemperaturedifferentialshouldbebetween12and20degreesdependingonambienttemperature.
Next,slowlyraisethecoolingtemperatureuntiltheswitchopens.Thecompressorandoutdoorfanshouldturnoff.Theindoorfanwillcontinuetorunfor“90”secondsuntilthefanpurgetimesout.Raisethetemperatureuntiltheswitchopens.Theleadunitwillshutdownaccordinglytothesameproceduresasoutlinesabove.
Note:(ComPac®IIA/Conly)Tocheckthesystemoperationunderdifferentambientconditions,theairtemperatureandenthalpysensorsmustbe“tricked”.Whenoutdoorambientconditionsarehigherthanthecontrolsetting,acomponentcooleraerosolmaybesprayeddirectlyintotheenthalpysensortostimulatelowenthalpyconditions,causingtheeconomizerdampertoopen.
Alternately,whenoutdoorconditionsarelowerthanthesetpoint,asourceofheatsuchasahairdryercanbedirectedontheenthalpysensortosimulatewarmconditions,whichwillbringonmechanicalcoolingandstartthecompressor.
7.Heating.Slowlyraisetheheatingtemperatureuntiltheswitchcloses.Thefanandelectricalheatshouldimmediatelycycleon.Theunitshouldstartblowingwarmairin2to3minutes.Next,raisethetemperatureuntiltheswitchcloses.Followtheaboveproceduresforlagunit.
Holdthemanualadvancebuttoninforninesecondstheleadlaglightsshouldswitch.Next,slowlylowerthetemperatureuntiltheswitchesopen.Thelagunitshouldshutdownimmediately.Next,slowlylowerthetemperatureuntiltheswitchopens,theleadunitshouldshutdownimmediately.
8.Replacethermostatcoverandpanelsontheunit.
LL357D4 PDS, 4.2011 8
Mode of OperationForanunmannedsite,AutoMUSTbeselectedastheOperatingMode.Sincethecontrolmodulein
theLL357D4doesnothavea"G"input,thefanselectorswitchonthethermostatisnotfunctional.Innormaloperation,thefanandthecompressoroperatesimultaneously.Forcontinuousfanondualunitinstallations,installajumperwirebetweenterminals8and3andremovethejumperwirebetween1and3.Theseterminalsareonthelowvoltageterminalboardintheairconditionercontrolbox.
TherearefourpossibleoperatingmodesfortheLL357D4,Off,Cool,Heat,andCool&Heat(auto-changeover).ModesareaccessedbypressingtheSYS(left)button.
OFF Mode
•Inthismode,thethermostatwillnotheatorcool.
Heat Mode
•Inthismode,thethermostatcontrolstheheatingsystem.Whentheheatison,theflameiconappearsonthedisplay.
Cool Mode
•Inthismode,thethermostatcontrolsthecoolingsystem.Whenthetheunitiscooling,thesnowflakeiconappearsonthedisplay.
Cool and Heat Mode (AutoChangeover)
•Inthismode,thethermostatcontrolsthecoolingandheatingsystems,automaticallychangingoverfromonetotheotherasneeded.
•Thetimingdisplayalternateswiththesettemperatureevery10secondsinthecoolandheatmode.
Lockout Feature
Thethermostathasabuttonlockoutfeaturesothemodecannotbechangedandthetemperatureadjustmentislimited.SelecttheappropriatelockoutfromConfigurationModeSettings.
ToactivatetheLOCKfeature:
1.SimultaneouslypresstheSYS,RIGHTandUPbuttonsfor10seconds.
2.Thelockouticonwilldisplayandthelockoutfunctionwillbeenabled.
TodeactivatetheLOCKfeature,repeatsteps1and2above.
LL357D4 PDS, 4.2011 9
Troubleshooting
Symptom Remedy
Nodisplay Checkfor24VACatthermostat;displayisblankwhen24VACisnotpresent.
Indoorblowerdoesnotturnon Verifywiringiscorrect.ChecksettingsinConfigMode,No.6,“Settings”.
Allthermostatbuttonsareinoperative. Verify24VACispresent;unitlocksoutwhen24VACnotpresent.
Noresponsewhenfirstbuttonispressed. Firstbuttonpressedonlyactivatesbacklight.
AirconditionersturnsOnandOfftoofrequently(shortcycles)
Increasetemperaturedifferential.SeeConfigMode,steps2&3.
StatusindicatorlightdoesnotcomeonduringcallforCoolingorHeating.
Turnstatusindicatorlightfunctionon.SeeConfigMode,Step14.
Roomtemperatureisnotcorrect. Calibratethermostat.SeeConfigMode,step11.
Lockiconisdisplayedwhenanybuttonispressed.
Thermostathasthelockoutfunctionactivated.SeeLockoutFeatureandConfigMode,step8.
ErondisplayinsteadofSEntemperature CheckforabadconnectionatS1andS2terminals.SeeConfigMode,step12
Airconditionerisnotcoolingorheating. Verifywiringiscorrect.Gentlypulloneachwiretoverifythereisagoodconnectionattheterminalbloc.
Problemnotlistedabove PressResetonce.Timeanddayarereset;configurationssettingsarenotchanged.
LL357D4 PDS, 4.2011 10
Configuration ModeToenterConfigurationmode:
1. VerifythatthethermostatisintheOFFmode.
2. PresstheSYS(left)buttonuntiltheoffmodedisplays.
3. Removethethermostatscoverbygentlypullingononecorneratthetopofthethermostat.
4. PresstheCONFIGbuttonfor1second.
5. Presstheupordownbuttontochangethesettingswithineachscreen.
6. PresstheRIGHTbuttontoadvancetothenextscreen.Presstheleftbuttontoreturntoprevious
Screen Number Description
Marvair Recommended Selection Default
1 TemperatureScale°For°C Asdesired F
2 1stStageTemperatureDifferential1°Fto3°F(0.5°Cto1.5°C) 2°F 1°
3 2ndStageTemperatureDifferential1°Fto6°F(0.5°Cto3.0°C) 2°F 2°
4 StagedOffOutputs1=outputsstagedoffindependently2=outputsstagedoffsimultaneously
Select11 1
5 MinimumDeadband2°Fto9°F(1.0°Cto4.5°C)
3°F 5°
6 SystemChoosefromheatpump,non-heatpump(airconditioner),reversingvalveandnumberofcompressors.
Select“non-heatpump”and“Electric”1
GAS
7 AuxiliaryDelayOnSetthetimedelay(inminutes)foraux.heattobelockedoutafteracallforsecondstage
Setto0minutes.1 0:00
8 LockoutSelectthenumberofdegreesthatthesettemperaturecanbechangedduringkeypadlockout.
Asdesired 00
9 MaximumHeatingSetpoint55°Fto90°F(13°Cto232.0°C)
Nohigherthan78°F(25.6°C) 90°
10 MinimumCoolingSetpoint45°Fto75°F(7.0°Cto24.0°C)
Nolowerthan68°F(20°C) 45°
11 RoomTemperatureOffset+9°Fto-9°F(+4.5°Cto-4.5°C)
Asdesired 0°
12 TemperatureSensor1=Onboardtemperaturesensor2=Onlyremotesensor3=Avg.temperatureofon-boardsensorandremotesensor
Asdesired 1
13 CoolingfanDelayOffTime0,30,60,90seconds
0seconds 0
14 Statusindicatorlight0=statusindicatorneveron1=statusindicatoronwithfirststage2=statusindicatoronwithsecondstage
Select1 1
ToexittheConfigurationMode,presstheCONFIGswitchfor1second.Note:Theredlightindicatestheunit(s)isintheheatingcycleandthegreenlightindicatethattheunit(s)isinthecoolingcycle.1Settingsandselectionsinitalicsarerequiredsettings/selections.
LL357D4 PDS, 4.2011 11
Notes
LL357D4 PDS, 4.2011 12
P.O.Box400•Cordele,GA31010156SeedlingDrive•Cordele,GA31015Ph:229-273-3636•Fax:229-273-5154Email:[email protected]• Internet:www.marvair.com
Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website or by contacting Marvair at 229-273-3636. As part of the Marvair continuous improvement program, specifications are subject to change without notice.