lab lighting controls upgrade 07.01.09 cltc uci

10
2009 CAMPUS LIGHTING RETROFIT FORUM Lab Lighting Controls Upgrade Chris Abbamonto, UC Irvine

Upload: cabbamonto

Post on 22-May-2015

516 views

Category:

Documents


2 download

DESCRIPTION

Laboratory Lighting Controls Retrofit using simplified daylight sensing and occupancy sensing

TRANSCRIPT

Page 1: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Lab Lighting Controls Upgrade

Chris Abbamonto, UC Irvine

Page 2: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Laboratory Lighting Controls Upgrade

• New Laboratory Building Biological Sciences 3

• Beat Title 24 Energy Standard by 20%+

• Challenge to reduce annual energy consumption from lighting by ~50%

• Extremely low Lighting Power Density (LPD)

LPD = Lighting Watts / Square Foot

• Lab Environment with ~50 Foot-candle Requirement

• Reducing true LPD not a probable option

Page 3: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

BE

FO

RE Lab Area LPD = 1.1

Lab Prep LPD = 0.9

Corridor LPD = 0.6

Prep Room LPD = 2.0

Page 4: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Manual Switch to Occupancy Sensor

50% Auto On - Manual to 100% - Auto Off

A-B CIRCUITING

Page 5: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Auto on to 50% Light Level

Page 6: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Lower Blinds to Allow for Daylighting

Page 7: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Photocell to Control Window Fixture

BUTTON PHOTOCELLS

Page 8: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Fixture Closest to the Window is OFF

Page 9: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

AF

TE

RLab Area SAVE +50%

Lab Prep SAVE 40%

Corridor SAVE +50%

Prep Room SAVE +50%

Page 10: Lab Lighting Controls Upgrade 07.01.09 CLTC UCI

2009 CAMPUS LIGHTING RETROFIT FORUM

Summary

• Project Is Scalable (floors, buildings, campuses)

• Simple Payback Period in the 2.3 to 3.4 year range

• Savings Based on Controls not LPD!

• Consider under cabinet task lighting at the work surface to augment overhead lighting

• Consider perforated blinds to increase light and reduce glare through “views” portion of fenestration

Chris Abbamonto, UC Irvine, [email protected], (949) 285-3172