© 2011 UTC Fire & Security. All rights reserved. 1 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11 KAL455 Manual Call Point Installation Sheet EN DE ES IT NL PL PT RU 1 2 EN: Installation Sheet Description This document includes installation information for UTC Fire & Security KAL455 manual call points. These manual call points are designed for use in UTC Fire & Security Kilsen analogue addressable fire alarm systems and include models for indoor and outdoor use. Installation Caution: This product must be installed by qualified personnel adhering to the CEN/TS 54-14 standard and any other applicable local authority laws. Electrical connections Connect to the KAL455 connection block (Figure 2) as follows: 1. Line in (positive) 2. Line out (positive) 3. Line in (negative) 4. Line out (negative) Addressing Use the DIP switch (Figure 1) to allocate a device address from 128 to 252 (see page 9). Maintenance Basic maintenance consists of a yearly inspection. Do not modify internal wiring or circuitry. Specifications Voltage 22 to 35 VDC Current Standby Alarm max. 250 ųA max. 2.5 mA Cable size Minimum Maximum 0.8 mm 2 2.5 mm 2 IP rating KAL455, KAL455-18 KAL455E, KAL455E-18 IP24D IP67 Operating environment Operating temperature Storage temperature Relative humidity 10°C to +70°C 20°C to +70°C 10% to 95% noncondensing Dimensions (W × H × D) KAL455, KAL455-18 KAL455E, KAL455E-18 89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1] Weight 187 g [1] Excluding surface mount.

Upload: 123vb123

Post on 06-Dec-2015

258 views

Category:

Documents


7 download

DESCRIPTION

MCP

TRANSCRIPT

Page 1: KAL455 Manual Call Point Installation R4.0 (Multilingual)

© 2011 UTC Fire & Security. All rights reserved. 1 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

KAL455 Manual Call Point Installation Sheet

EN DE ES IT NL PL PT RU

1

2

EN: Installation Sheet

Description

This document includes installation information for UTC Fire & Security KAL455 manual call points. These manual call points are designed for use in UTC Fire & Security Kilsen analogue addressable fire alarm systems and include models for indoor and outdoor use.

Installation

Caution: This product must be installed by qualified personnel adhering to the CEN/TS 54-14 standard and any other applicable local authority laws.

Electrical connections

Connect to the KAL455 connection block (Figure 2) as follows:

1. Line in (positive) 2. Line out (positive) 3. Line in (negative) 4. Line out (negative)

Addressing

Use the DIP switch (Figure 1) to allocate a device address from 128 to 252 (see page 9).

Maintenance

Basic maintenance consists of a yearly inspection. Do not modify internal wiring or circuitry.

Specifications

Voltage 22 to 35 VDC

Current Standby Alarm

max. 250 ųA max. 2.5 mA

Cable size Minimum Maximum

0.8 mm2 2.5 mm2

IP rating KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Operating environment Operating temperature Storage temperature Relative humidity

−10°C to +70°C −20°C to +70°C 10% to 95% noncondensing

Dimensions (W × H × D) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Weight 187 g

[1] Excluding surface mount.

Page 2: KAL455 Manual Call Point Installation R4.0 (Multilingual)

2 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

Regulatory information

Manufacturer KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Authorized EU manufacturing representative: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, Netherlands

Year of manufacture The first two digits of the product serial number (located on the product identification label) are the year of manufacture.

The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture.

Certification

CPD certificates KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN 54 EN 54-11 Type A

2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.

Contact information

For contact information, see www.utcfireandsecurity.com.

DE: Installations Beschreibung

Beschreibung

Diese Beschreibung beinhaltet Installationsinformationen für UTC Fire & Security KAL455 Druckknopfmelder. Diese Druckknopfmelder sind für den Gebrauch in UTC Fire & Security Kilsen analogen Brandmeldesystemen und sind für den Außen- und Innenbereich geeignet.

Installation

Warnung: Dieses Produkt muss von qualifiziertem Personal gemäß der Norm CEN/TS 54-14 sowie aller anderen vor Ort geltenden gesetzlichen Bestimmungen und behördlichen Vorschriften installiert werden.

Elektrische Verbindung

C Verdrahtung des KAL455 Anschlussblock (Abbildung 2) wie folgt:

1. Eingang (positiv) 2. Ausgang (positiv) 3. Eingang (negativ) 4. Ausgang (negativ)

Adressierung

Verwenden Sie zur Zuweisung (Abbildung 1) einer Geräteadresse zwischen 128 und 252 den DIP-Schalter (vgl. 9).

Wartung

Grundlegend sollte einmal jährlich eine Wartung erfolgen. Die interne Verdrahtung nicht verändern.

Technische Daten

Netzspannung 22 bis 35 VDC

Stromentnahme Ruhezustand Alarm

max. 250 ųA max. 2.5 mA

Kabelgröße Min. Max.

0.8 mm2 2.5 mm2

IP-Schutzklasse KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Betriebstemperatur −10°C bis +70°C

Lagertemperatur −20°C bis +70°C

Relative Luftfeuchtigkeit 10% bis 95%

Abmessungen (B × H × T) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Gewicht 187 g

[1] Ohne Montagegehäuse.

Regulatorische Informationen

Hersteller KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Autorisierter EU-Herstellungsrepräsentant: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, Niederlande

Herstellungsjahr Das Jahr der Herstellung ist in den beiden ersten Ziffern der Produkt-Seriennummer enthalten (auf dem Produkt-Identifizierungslabel).

Zertifikation

CPD Zertifikat KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

Page 3: KAL455 Manual Call Point Installation R4.0 (Multilingual)

P/N 55300829-04 • REV 4.0 • ISS 14NOV11 3 / 12

Produkte die mit diesem Symbol gekennzeichnet sind, dürfen nicht als unsortierter städtischer Abfall in der europäischen Union entsorgt werden. Für die korrekte Wiederverwertung bringen Sie dieses Produkt zu Ihrem lokalen Lieferanten nach dem Kauf der gleichwertigen neuen Ausrüstung zurück, oder entsorgen Sie das Produkt an den gekennzeichneten Sammelstellen. Weitere Informationen hierzu finden Sie auf der folgenden Website: www.recyclethis.info.

Kontaktinformationen

Kontaktinformationen finden Sie auf unserer Website www.utcfireandsecurity.com

ES Intrucciónes de Instalación

Descripción

Este documento incluye instrucciones de instalación para el pulsador de UTC Fire & Security KAL455. Este pulsador está diseñado para ser empleado con sistemas analógicos de detección de incendio de UTC Fire & Security Kilsen e incluye modelos para uso en interiores y exteriores.

Instalación

Precaución: Este producto lo debe instalar personal cualificado según la normativa CEN/TS 54-14 y cualquier otra ley del organismo local pertinente.

Conexiones eléctricas

Conectar el regletero de KAL455 (Figura 2) como se indica:

1. Entrada de línea (positivo) 2. Salida de línea (positivo) 3. Entrada de línea (negativo) 4. Salida de línea (negativo)

Direccionamiento

Utilice el microinterruptor DIP (Figura 1) para asignar una dirección al dispositivo entre la 128 y la 252 (ver página 9).

Mantenimiento

El mantenimiento consistirá en una inspección tanto visual como de funcionamiento a realizar anualmente. No deberá manipularse el interior del dispositivo.

Especificaciones técnicas

Tensión de alimentación 22 a 35 VDC

Consumo de corriente Reposo Alarma

max. 250 ųA max. 2.5 mA

Tamaño del cable Mínimo Máximo

0.8 mm2 2.5 mm2

Índice de IP KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Temperatura de funcionamiento

De −10°C a +70°C

Temperatura de almacenamiento

De −20°C a +70°C

Humedad relativa De 10% a 95% (sin condensación)

Dimensiones (An x Al x Pro) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Peso 187 g

[1] Excluyendo montaje de superficie.

Información relativa a las normativas

Fabricante KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Representante de fabricación autorizado en Europa: UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Países Bajos

Año de fabricación El año de la fabricación está indicado en los dos primeros dígitos del número de serie del producto (situado en la etiqueta del producto).

Certificación

Certificado CPD KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

Los productos marcados con este símbolo no se pueden eliminar como basura normal sin clasificar en la Unión Europea. Para el reciclaje apropiado, devuelva este producto a su distribuidor al comprar el nuevo equipo equivalente, o deshágase de él en los puntos de reciclaje designados. Para mas información : www.recyclethis.info.

Información de contacto

Para obtener información de contacto, consulte nuestro sitio Web: www.utcfireandsecurity.com.

Page 4: KAL455 Manual Call Point Installation R4.0 (Multilingual)

4 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

IT: Istruzioni di installazione

Descrizione

Questo documento contiene le informazioni per l’installazione dei pulsanti di allarme manuale KAL455 UTC Fire & Security. Questi pulsanti sono stati progettati per essere utilizzati con i sistemi di rivelazione incendio analogico indirizzati UTC Fire & Security Kilsen e includono modelli per uso interno ed esterno.

Installazione

Attenzione: Questo prodotto deve essere installato da personale qualificato in conformità alla norma CEN/TS 54-14 e a tutte le leggi locali in vigore.

Collegamenti elettrici

Collegare la morsettiera di connessione del KAL455 (figura 2) come indicato di seguito:

1. Ingresso linea (positivo) 2. Uscita linea (positivo) 3. Ingresso linea (negativo) 4. Uscita linea (negativo)

Indirizzamento

Utilizzare l'interruttore DIP (figura 1) per assegnare un indirizzo da 128 a 252 (vedere pagina 9).

Manutenzione

La manutenzione richiede un'ispezione annuale. Non manipolare il cablaggio o i circuiti interni.

Specifiche tecniche

Alimentazione Da 22 a 35 VDC

Consumo di corrente Riposo Allarme

max. 250 ųA max. 2.5 mA

Dimensioni cavi Min. Max.

0.8 mm2 2.5 mm2

Grado di protezione IP KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Temperatura di funzionamento

Da −10°C a +70°C

Temperatura di stoccaggio Da −20°C a +70°C

Umidità relative Da 10% a 95% (senza condensa)

Dimensioni (L x A x P) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Peso 187 g

[1] Esclusa la base di fissaggio.

Informazioni sulle normative

Fabbricante KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Rappresentante di produzione autorizzato per l'UE: UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Paesi Bassi

Anno di produzione Per conoscere l'anno di produzione del prodotto verificare le prime due cifre del numero di serie del prodotto stesso. Riferirsi all'etichetta di identificazione prodotto.

Certificazione

CPD Certificato KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

I prodotti contrassegnati con questo simbolo, non possono essere smaltiti nei comuni contenitori per lo smaltimento rifiuti, nell' Unione Europea. Per il loro corretto smaltimento, potete restituirli al vostro fornitore locale a seguito dell'acquisto di un prodotto nuovo equivalente, oppure rivolgervi e consegnarli presso i centri di raccolta preposti. Per maggiori informazioni vedere: ww.recyclethis.info.

Informazioni di contatto

Le informazioni di contatto sono disponibili sul sito www.utcfireandsecurity.com

NL: Installatie instructies

Omschrijving

Dit document bevat installatie informatie voor UTC Fire & Security KAL455 handmelders. Deze handmelders zijn ontwikkeld voor gebruik in UTC Fire & Security Kilsen analoge addresseerbare brandsystemen en bevat modellen voor binnen en buiten gebruik.

Installatie

Let op: Dit product moet worden geïnstalleerd door geautoriseerd personeel volgens de CEN/TS 54-14-standaard en eventuele andere toepasselijke wetten van de plaatselijke overheid.

Page 5: KAL455 Manual Call Point Installation R4.0 (Multilingual)

P/N 55300829-04 • REV 4.0 • ISS 14NOV11 5 / 12

Elektrische aansluitingen

Aansluiting op de KAL455 connector (figuur 2) als volgt:

1. Lijn in (positief) 2. Lijn uit (positief) 3. Lijn in (negatief) 4. Lijn uit (negativ)

Adressering

Gebruik de DIP-switch (figuur 1) om een apparaatadres van 128 tot 252 toe te wijzen (zie pagina 9).

Onderhoud

Basis onderhoud is teruggebracht tot jaarlijkse inspectie. Wijzig geen interne bedrading of circuits.

Technische specificaties

Aansluitspanning 22 tot 35 VDC

Stroomverbruik Standby Alarm

max. 250 ųA max. 2.5 mA

Kabeldikte Min. Max.

0.8 mm2 2.5 mm2

IP-klasse KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Werkingstemperatuur −10°C tot +70°C

Opslagtemperatuur −20°C tot +70°C

Relatieve vochtigheid 10% tot 95% (geen condensatie)

Afmetingen (B × H × T) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Gewicht 187 g

[1] Exclusief opbouw behuizing.

Informatie over regelgeving

Fabrikant KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

EU-geautoriseerde vertegenwoordiger:UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Nederland

Productiejaar Het productiejaar wordt vermeld door de eerste twee getallen in het serienummer van het product (zichtbaar op de product identificatie label).

Certificatie

CPD certificatie KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

Producten met deze label mogen niet verwijdert worden via de gemeentelijke huisvuilscheiding in de Europese Gemeenschap. Voor correcte vorm van kringloop, geef je de producten terug aan jou locale leverancier tijdens het aankopen van een gelijkaardige nieuw toestel, of geef het af aan een gespecialiseerde verzamelpunt. Meer informatie vindt u op de volgende website: www.recyclethis.info.

Contactgegevens

Bezoek onze website voor onze contactgegevens:www.utcfireandsecurity.com

PL: Instrukcja instalacji

Opis

Dokument opisuje instalację przycisku ROP typu KAL455. Jest on przeznaczony do stosowania z analogowymi, adresowalnymi czujkami rodziny UTC Fire & Security Kilsen, opisanymi w oddzielnych instrukcjach. ROP jest dostępny w wersji do montażu wewnętrznego i zewnętrznego.

Instalacja

Uwaga: Produkt musi montowac wykwalifikowany technik. Podczas montazu nalezy stosowac sie do normy CEN/TS 54-14 oraz innych obowiazujacych przepisów lokalnych.

Przyłączenia s

Przyłączyć ROP KAL455 do instalacji zaciskami w kostce połączeniowej (rysunek 2) następująco:

1. Wejście pętli (plus) 2. Wyjście pętli (plus) 3. Wejście pętli (minus) 4. Wyjście pętli (minus)

Adresowanie

Adres urzadzenia (od 128 do 252) mozna przypisac za pomoca przelacznika DIP (rysunek 1). Wiecej informacji na ten temat znajduje sie na stronie 9).

Konserwacja

Konserwacja jest ograniczona do corocznego przeglądu. Nie należy zmieniać okablowania ani rozbierać urządzenia.

Dane techniczne

Napięcie zasilające Od 22 do 35 VDC

Prąd Spoczynkowy W alarmie

maks. 250 ųA maks. 2.5 mA

Przekrój przewodu Min. Maks.

0.8 mm2 2.5 mm2

Page 6: KAL455 Manual Call Point Installation R4.0 (Multilingual)

6 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

Klasa IP KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Temperatura robocza Od −10°C do +70°C

Temperatura przechowywania

Od −20°C do +70°C

Wilgotność względna Od 10% do 95% (bez kondensacji)

Wymiary (Sz x W x G) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Waga 187 g

[1] bez zestawu do montażu natynkowego.

Informacje prawne

Wytwórca KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Autoryzowany przedstawiciel producenta na terenie Unii Europejskiej: UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, Holandia.

Rok produkcji Rok produkcji reprezentują dwie pierwsze cyfry numeru seryjnego produktu (zlokalizowanego na etykiecie identyfikacyjnej produktu).

Certyfikat

Certyfikatu CPD KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

W Unii Europejskiej produkty oznaczone tym symbolem mogą być usuwane tylko jako posegregowane odpady komunalne. Dla zapewnienia właściwej utylizacji, należy zwrócić ten produkt do dostawcy przy zakupie ekwiwalentnego, nowego urządzenia albo dostarczyć go do wyznaczonego punktu zbiórki. Więcej informacji można znaleźć na stronie internetowej www.recyclethis.info.

Informacje kontaktowe

Informacje kontaktowe zawiera witryna internetowa: www.utcfireandsecurity.com.

PT: Instruções de Instalação

Descrição

Este documento incluíi informação de instalação referente ás botoneiras KAL455 da UTC Fire & Security. Estas botoneiras com modelos para utilização interior e exterior, destinam-se a ser utilizadas com as centrais de incêndio analógicas e endereçáveis Kilsen da UTC Fire & Security.

Instalação

Advertência: Este produto tem de ser instalado por pessoal qualificado que adira à norma CEN/TS 54-14 e a quaisquer outras normas de entidades locais aplicáveis.

Ligações eléctricas

Ligue os terminais de ligação da KAL455 (figura 2) da seguinte forma:

1. Line in (positivo) 2. Line out (positivo) 3. Line in (negativo) 4. Line out (negativo)

Endereçamento

Utilize o interruptor DIP (figura 1) para atribuir um endereço de dispositivo entre 128 e 252 (consulte a página 9).

Manutenção

A manutenção básica encontra-se reduzida a uma inspecção anual. Não modificar as ligações ou circuitos internos.

Especificações Técnicas

Tensão de alimentação 22 a 35 VDC

Consumo de corrente Quiescente Alarme

max. 250 ųA max. 2.5 mA

Dimensões do cabo Mín. Máx.

0.8 mm2 2.5 mm2

Classe IP KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Temperatura de funcionamento −10°C a +70°C

Temperatura de armazenamento

−20°C a +70°C

Humidade relativa 10% a 95% (não condensado)

Dimensões (L x A x P) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Peso 187 g

[1] Excluindo montagem de superficie.

Page 7: KAL455 Manual Call Point Installation R4.0 (Multilingual)

P/N 55300829-04 • REV 4.0 • ISS 14NOV11 7 / 12

Informação reguladora

Fabricante KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Representante de fabrico autorizado na UE: UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, The Netherlands

Ano de fabrico O ano de fabrico é indicado pelos primeiros 2 dígitos do número de série do equipamento (localizado na etiqueta de identificação do produto).

Certificação

Certificado CPD KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

Produtos marcados com este símbolo não podem ser eliminados como resíduos urbanos indiferenciados na União Europeia. Para proceder à reciclagem adequada, devolva este produto ao seu fornecedor local na compra de novo equipamento equivalente, ou entregue-o nos pontos de recolha designados para o efeito. Para mais informações, ver www.recyclethis.info.

Informação de contacto

Para informações de contacto, consulte o nosso Web site www.utcfireandsecurity.com.

RU: Инструкции по установке

Описание

Этот документ содержит информацию по установке ручного пожарного извещателя KAL455 производства UTC Fire & Security. Эти ручные пожарные извещатели разработаны для использования в составе адресно-аналоговых систем пожарной сигнализации UTC Fire & Security Kilsen и включают в себя модели внутреннего и уличного исполнения.

Установка

Внимание: Данное изделие должно быть установлено квалифицированным персоналом в соответствии со стандартом CEN/TS 54-14, а также с другими действующими локальными нормами и правилами.

Электрические соединения

Произведите подключение к разъему KAL455 (рис. 2) следующим образом:

1. Входная линия (положительный контакт) 2. Выходная линия (положительный контакт) 3. Входная линия (отрицательный контакт) 4. Выходная линия (отрицательный контакт)

Адресация

Назначьте устройству адрес от 128 до 252 с помощью DIP-переключателя (см. стр. 9).

Техническое обслуживание

Базовое техническое обслуживание предполагает только ежегодную проверку. Внутренние схемы и проводка не подлежат изменению.

Адресация

Назначьте устройству адрес от 128 до 252 с помощью DIP-переключателя (см. стр. 8).

Техническое обслуживание

Базовое техническое обслуживание предполагает только ежегодную проверку. Внутренние схемы и проводка не подлежат изменению.

Технические характеристики s

Напряжение источника питания от 22 до 35 В пост. тока

Токопотребление (в состоянии покоя)

250 мкА максимум

Потребление тока (в состоянии тревоги).

2,5 мА максимум

Размер кабеля минимум максимум

0.8 mm2 2.5 mm2

Класс защиты KAL455, KAL455-18 KAL455E, KAL455E-18

IP24D IP67

Рабочая температура от −10°C до +70°C

Температура хранения от −20°C до +70°C

Относительная влажность от 10% до 95%

Габаритные размеры (Ш х В х Г) KAL455, KAL455-18 KAL455E, KAL455E-18

89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]

Вес 187 g

[1] Не включая монтажное основание.

Page 8: KAL455 Manual Call Point Installation R4.0 (Multilingual)

8 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

Нормативная информация

Завод‐изготовитель KAC Alarm Company Ltd. KAC House, Thornhill Road, North Moons Moat, Redditch, Worcestershire, 898 9ND, England

Полномочный представитель компании в ЕС: UTC Fire & Security B.V., Kelvinstraat 7, 6003 DH Weert, The Netherlands

Год производства Первые две цифры в серийном номере (расположенном на этикетке) обозначают год производства

Сертификация

Номер сертификата CPD KAL455, KAL455-18 KAL455E, KAL455E-18

0832-CPD-0750 0832-CPD-0752

EN54 EN 54-11 Type A

Согласно европейской директиве об отходах электрического и электронного оборудования (WEEE), помеченное этим символом оборудование нельзя утилизировать как обычные отходы на территории ЕС. Для надлежащей утилизации по окончании срока эксплуатации пользователь должен возвратить данное оборудование локальному поставщику в момент покупки аналогичного нового оборудования, или сдать в специальный пункт приема. Подробности можно найти на веб-сайте: www.recyclethis.info.

Контактная информация

Для получения контактной информации посетите сайт: www.utcfireandsecurity.com.

Page 9: KAL455 Manual Call Point Installation R4.0 (Multilingual)

P/N 55300829-04 • REV 4.0 • ISS 14NOV11 9 / 12

128 129 130 131 132 133 134

135 136 137 138 139 140 141

142 143 144 145 146 147 148

149 150 151 152 153 154 155

156 157 158 159 160 161 162

163 164 165 166 167 168 169

170 171 172 173 174 175 176

177 178 179 180 181 182 183

184 185 186 187 188 189 190

191 192 193 194 195 196 197

198 199 200 201 202 203 204

205 206 207 208 209 210 211

212 213 214 215 216 217 218

219 220 221 222 223 224 225

226 227 228 229 230 231 232

233 234 235 236 237 238 239

240 241 242 243 244 245 246

247 248 249 250 251 252

Page 10: KAL455 Manual Call Point Installation R4.0 (Multilingual)

10 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11

Page 11: KAL455 Manual Call Point Installation R4.0 (Multilingual)

P/N 55300829-04 • REV 4.0 • ISS 14NOV11 11 / 12

Page 12: KAL455 Manual Call Point Installation R4.0 (Multilingual)

12 / 12 P/N 55300829-04 • REV 4.0 • ISS 14NOV11