Identifying dominant measurements errors in
fully automated water networksPWN Waterleidingbedrijf Noord-HollandWater technology
Lucyna Magda
2
Content
• Problem definition• Errors in mass balances• Flowmeter In-Situ calibration and its constraints• Vendors who sell this kind of equipment• PWN-state of the art• List of companies who use this kind of
equipment• Recommendations- advice on application.
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Scope of the presentation
3
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Water balance
4
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
∑(OUT-IN)-dS/dt=0
PWN-Validatie ruwwaterstrom 2002
• Up to 70% of water balances are doubtful
• All balances show systematic error-bias
• The errors are in the reach 3000 m3/day
• Possible causes:• Leakage• Additional inflow• Flowmeters
malfunctioning• RESULT OF THE ANALY
SIS
5
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
6
Problem definition
Malfunctioning field devices, including flowmeters cause process disturbances and errors in mass
balances
When such devices monitor themselves, faults can be detected and reported at an early stage,
greatly reducing their impact on the process.
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
7
Problem definition
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
8
Problem definition
“On
site
flow
cal
ibra
tion
is p
ainf
ul b
ut n
eces
sary
”
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
9
Errors in mass balances
Faults are frequently not the result of an instrument defect but application-related malfunctioning:
• device selection and sizing, • unsuitable installation,• application problems.
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
10
Type of the errors
1. Systematic Errors2. Accidental and Random Errors
Vendors: gross errors = systematic if proper installed.
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
11
Errors from the flowmeters
Gross error
• e - the manufactory error, • b - a systematic error • x - systematic component of the random error
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
12
Flowmeters types-choice dilemma
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
13
Flowmeters best application
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
14
Flowmeters surrounding errors
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
15
Electromagnetic Flowmeter
(1) U = K × B × v × D
K instrument constant B magnetic field strength v mean flow velocity D electrode spacing
The volumetric flow rate qv can be calculated according to
(2) qv = v × D² × π/4
It follows from equation (1) that
(3) v = U / K×B×D
Therefore:
(4) qv = (U / K×B) × D × π/4
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Flowmeter: Primary and Secondary
16
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Secondary
Primary
Examples of Primary and Secondary
17
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Wet Calibration
18
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
1.
2.
3.
19
Dry Calibration- Flowmeter Secundary
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
20
Verification techniques- Flowmeter Primary
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
21
Verification techniques- Flowmeter Secundary
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
22
Flowmeter calibration-a typical calibration curve
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
NameNumber of flowmeters
at PWNExpanded diagnostic
Verification techniques
161 CallMaster MagMaster
Emflux 2 - COMBINED EMFLUX
74 - Field Check
Heinrichs 2 - UMF
16 Optiflux MAGCHECK
Tokimec 8 - TOKYO KEIKI
- - SIMENS VERIFICATOR
Juergen - - COMBINED EMFLUX
23
Vendors
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
24
PWN-state of the art
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
25
Recommendations
• How to choose which flowmeters should be replaced:
• Water Balances that do not pass validationand the following set in the importance order:• Plenty control strategic points• Plenty Performance• Plenty Cardio• PT-Monthly Reports• Setpoint related flowmeters
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
26
PWN- Schematic representation of WRK
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
27
PWN- Schematic representation of WRK
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Plenty control biggest importance
Bed water mass balances
28
PWN- Schematic representation of WRK
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Plenty control biggest importance
Bed water mass balances
29
PWN- Schematic representation of WRK
• April 11, 2023 MSc: Water Resources Management , Lucyna Magda
Plenty control biggest importance
Bed water mass balances
30
Recommendations
• Electromagnetic flowmeters at Bergen should be replaced with the footprinted flowmeter
• Electromagnetic flowmeter at Secundairs 9-10 should be replaced with the ultrasonic 3-beams flowmeter
• I recommend periodic pipe inspecions near the extraction point
• I recommend structural changes where it is possible to increas the flushing of the sediments
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
31
Similar projects in The Netherlands
• Grolsh brewery in Enschede- Optiflux 4000 and mass flowmeters
• Detroit water and Sewage Department- Mag master and Call Master
• Both cases have been published with positive reviews
April 11, 2023 MSc: Water Resources Management , Lucyna Magda
April 11, 2023
32
QUESTIONS?
5 min
April 11, 2023
33
Thank you for you attention.
Special thanks to:Ignaz Worm, Eric de Vos, Henk van Duist, Harry Rolf, and everyone else from the Water Technology team