ixing and circulation group - icma s.p.a

7
Mixing and circulation group R001 TECHNICAL DATA SHEET - 07/2020 - ENG Icma SpA - Via Garavaglia, 4 20012 Cuggiono (MI) ITALIA Tel: +39 02 97249134 - +39 02 97249135 www.icmaspa.it - [email protected] 1 Description Components List Technical features The mixing and circulation groups are used to adjust distribution and temperature of the heat carrying fluid in multi-storey and/or multi-zone systems. They are ideal for underfloor heating systems and/or high temperature heating systems. The groups R001 can be installed on a special “inlet-outlet” distribution manifold (art. 785), after the hydraulic separator. The groups are supplied with insulation shells and fastening brackets. Group advantages: - Right/Left adaptability. - Manual/automatic servomor functioning. - Compatible with every 125mm axis manifold (With shell type 93). Mixing group with variable point regulation unit complete with: 1. Ball valve G3/4” or G 1”M with blue hand-wheel for connection to the return pipes, thermometer 0-120°C and incorporated check valve. 2. Ball valve G3/4” or G 1”M with red hand-wheel and thermometer 0-120°C for connection to the return pipes. 3. Steel pipe with ends threaded G1”1/2M. 4. 3-Speed circulating unit or variable speed electronic circulating unit, class “A”, with union connection G1”1/2 and 130 mm. distance between centers. 5. Electric modulating 24 Volt or 230 Volt servomotor, for mixing valve regulation. TECHNICAL DATA: Fluids used: Water and glycol based solutions Maximum percentage of glicole: 30% Maximum operating pressure: 10 bar Working range: 5 ° C ÷ 95° C Thermometers scale: 0÷120 °C Circolators: See specifications below MATERIALS: Bodies: Brass CW617N - EN 12165 Caps and unions: Brass CW617N - EN 12165 Stub: Tropicalized steel Thermometer: Steel/Aluminium Locking brackets: Galvanized steel Flat gaskets: EPDM Perox Sealing gaskets: PTFE Sealing components: EPDM Perox Insulation shell: EPP Density Ver. 93: 40 kg/m3 Density Ver. 94: 60 kg/m3 Conducibility of shell λ (ΔT) Ver. 93: 0,036 W/(m·k) at 10°C Conducibility of shell λ (ΔT) Ver. 94: 0,039 W/(m·k) at 10°C CONNECTIONS: Upper connections: G 3/4” F - 1”M Lower connections: G 1”1/2 M MODULATING SERVOMOTOR: Electric power supply: 230V - 50Hz Max current absorption: 3,5 VA Execution time on 90°: 135 sec Nominal load torque: 10 Nm Operating temperature: -10 / +50°C Protection degree: IP 40 External shell material: Polycarbonate 2 1 4 3 6 2 L1 L2 N Marrone Brown Nero Black Blu Blue 3 4 High T° Ready UFH Ready

Upload: others

Post on 16-Oct-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Description

Components List

Technical features

The mixing and circulation groups are used to adjust distribution and temperature of the heat carrying fluid in multi-storey and/or multi-zone systems.They are ideal for underfloor heating systems and/or high temperature heating systems. The groups R001 can be installed on a special “inlet-outlet” distribution manifold (art. 785), after the hydraulic separator.The groups are supplied with insulation shells and fastening brackets.

Group advantages:- Right/Left adaptability.- Manual/automatic servomor functioning.- Compatible with every 125mm axis manifold (With shell type 93).

Mixing group with variable point regulation unit complete with:1. Ball valve G3/4” or G 1”M with blue hand-wheel for connection to the return pipes, thermometer 0-120°C and incorporated check valve.2. Ball valve G3/4” or G 1”M with red hand-wheel and thermometer 0-120°C for connection to the return pipes.3. Steel pipe with ends threaded G1”1/2M.4. 3-Speed circulating unit or variable speed electronic circulating unit, class “A”, with union connection G1”1/2 and 130 mm. distance between centers.5. Electric modulating 24 Volt or 230 Volt servomotor, for mixing valve regulation.

TECHNICAL DATA:Fluids used: Water and glycol based solutionsMaximum percentage of glicole: 30%Maximum operating pressure: 10 barWorking range: 5 ° C ÷ 95° C Thermometers scale: 0÷120 °CCircolators: See specifications below

MATERIALS:Bodies: Brass CW617N - EN 12165Caps and unions: Brass CW617N - EN 12165Stub: Tropicalized steelThermometer: Steel/AluminiumLocking brackets: Galvanized steelFlat gaskets: EPDM Perox Sealing gaskets: PTFESealing components: EPDM PeroxInsulation shell: EPPDensity Ver. 93: 40 kg/m3Density Ver. 94: 60 kg/m3Conducibility of shell λ (ΔT) Ver. 93: 0,036 W/(m·k) at 10°CConducibility of shell λ (ΔT) Ver. 94: 0,039 W/(m·k) at 10°C

CONNECTIONS:Upper connections: G 3/4” F - 1”MLower connections: G 1”1/2 M

MODULATING SERVOMOTOR:Electric power supply: 230V - 50HzMax current absorption: 3,5 VAExecution time on 90°: 135 secNominal load torque: 10 NmOperating temperature: -10 / +50°CProtection degree: IP 40External shell material: Polycarbonate

21

43

6

2

L1 L2 N

MarroneBrown

NeroBlack

BluBlue

3 4

High T°Ready

UFHReady

Page 2: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Tmix>Tset

Functioning

FULLY OPEN POSITION:With the handle “M” of the servomotor in this position, the mixing valve is fully open. The heat carrying fluid coming from the boiler is conveyed directly to the heating system.

The three-way valve can work in three different positions during its operation:

REGULATION POSITION:With the handle “M” of the servomotor in this position, the mixing valve is under regulation. The heat carrying fluid coming from the boiler is mixed with the return fluid from the heating system.

FULLY CLOSED POSITION:With the handle “M” of the servomotorin this position, the 3 way valve excludes the heat-carrying fluid coming from the boiler completely to let the underfloor heating return fluid recirculate.

The 3-way valve has an adjustable BY-PASS. Its main function is to keep the temperature in the system not too high, connecting the system return flow with the mixed flow. The by-pass makes the regulation more stable and prevent possible damages to the system.

The Variable point mixing and circulation group art. R001, in combination with the RT thermostat and EP temperature probe, maintains the delivery temperature of the heat-transfer fluid stable.The electronic control station EC controls directly both the recirculating pump and 3-point servomotor. The temperature of the heat conveying fluid is adjusted according to the set environmental conditions. (A right-configuration R001 is shown as an example below).

P M

Dimensions

CCB

A

D

Ø1 Ø1

Ø2 Ø2 SHELL 94SHELL 93

ART.A B C

DØ 1

Ø 293 94 93 94 93 94 93 94

R001 350 360 248 270 200 180 125 3/4”F G 1” M G 1”1/2 M

RT: Room ThermostatEP: External ProbeEC: Electroing control unitBO: BoilerHY: Hydraulic SeparatorST: Safety thermostat

BO

HS

EC

ST

EP

RT

BY-PASS OPENKv 3.5

BY-PASS 50%Kv 1.5

BY-PASS CLOSEDKv 0

Tmix<Tset

RETURN DELIVERY

RETURN DELIVERY RETURN DELIVERY

Page 3: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Circulation pumps (Saleable in UE countries)

Group customization

Art. P326 - Circulation pump PWM:

TECHNICAL SPECIFICATIONS:Brand: GrundfosModel: UMP3 PWM 25 70 130Centre to centre distance: 130 mmConnections: G 1”1/2 MElectrical power supply: 230V – 50HzOperating temperature: +2° / +95°C.Max operating pressure: 10 barProtection level: IP44Energy class (EEI): ≤0.23

Art. P327 - Circulator with ΔP constant and ΔP variable:

TECHNICAL SPECIFICATIONS:Brand: WiloModel: CIRCULATOR PARA 25/8 130Centre to centre distance: 130 mmConnections: G 1”1/2 MElectrical power supply: 230V – 50/60HzOperating temperature: 0°C / 100°C.Max operating pressure: 10 barProtection level: IPx4DEnergy class (EEI): ≤0.21

Art. P328 - Circolator with PP (proportional pressure), CP (constantpressure) CC (constant curves), PWM (profile A o C), AA (auto adapt):

TECHNICAL SPECIFICATIONS:Brand: GrundfosModel: UPSO 25 – 65 130 mmCentre to centre distance: 130 mmConnections: G 1”1/2 MElectrical power supply: 230V – 50HzOperating temperature: +2° / +110°C.Max operating pressure: 10 barProtection level: IP44

Art. P330 - Circulator with fixed ΔP , variable ΔP and 3 costant speed:

TECHNICAL SPECIFICATIONS:Brand: WiloModel: CIRCULATOR PARA 25/8 130Centre to centre distance: 130 mmConnections: G 1 “1/2 MElectrical power supply: 230V - 50 / 60HzWorking temperature: 0 ° C / 100 ° C.Max operating pressure: 10 barProtection level: IPx4DEnergy Class (EEI): ≤0.21

Version 93 Version 94

Circulation pumps (Saleable in Extra-EU countries only)

Art. P321 - Synchronous circulation pump with 3 speeds:

TECHNICAL SPECIFICATIONS:Brand: GrundfosModel: UPSO 25 – 65 130 mmCentre to centre distance: 130 mmConnections: G 1”1/2 MElectrical power supply: 230V – 50HzOperating temperature: +2°C ÷ +110°C.Max operating pressure: 10 barProtection level: IP44

Shells

Page 4: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

5,5

6

6,5

7

7,5

8

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8

Prev

alen

za-H

ead

pres

sure

[m]

Portata-Flow rate [m³/h]

Prevalenza residua-Remaining head Art.R001 - Grundfos UMP3 PWM 25-70

Grundfos UMP3 PWM 25-70 MAX (usable)

Hydraulical SpecificationsArt. P326

Accessories

Art. 789G 1” F X G 1” 1/2 F plane seat union with nut and gasket. It reduces from G 1” 1/2 F to G 1” F.

Art. 790Head cap for manifold art. 785.

Art. 173End cap with O-ring to close 1” exits of manifold art. 785.

Art. 785Modular brass double chamber manifold equipped with black EPP insulation shell, suitable for circulation modules art. R001-R002-R003-R004. Manifolds art. 785 can be used as single units or connected in series up to a maximum of 6 (Nuts, bolts and two O-ring included in the package).

*

*

..

Art. R001

Art.789

Art.785 x3

Art. R003

Art. R002

Art. 789

Art. 790

Art. 173

Art. R001

PWM ZONE

Page 5: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Art. P328

Art. P327

Art. P330

*

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

5,5

6

6,5

7

7,5

8

8,5

9

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8

Prev

alen

za-H

ead

pres

sure

[m]

Portata-Flow rate [m³/h]

Prevalenza residua-Remaining head Art.R001 - WILO PARA 25/8 130

WILO PARA 25/8 130 Constant curve III (usable) Constant curve II (usable) Constant curve I (usable)

*

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

5,5

6

6,5

7

7,5

8

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8

Prev

alen

za-H

ead

pres

sure

[m]

Portata-Flow rate [m³/h]

Prevalenza residua-Remaining head Art.R001 - WILO PARA 25/7 130

WILO PARA 25/7 130 Constant curve III (usable) Constant curve II (usable) Constant curve I (usable)

*

*

*

*

Page 6: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Positioning

2020 3030 4040 5050 6060 7070 8080 9090 100

100

200

200

300

300

400

400

500

500

600

600

700

700

800

800

900

900

1000

1000

2000

2000

3000

3000

4000

4000

5000

5000

6000

6000

7000

7000

8000

8000

9000

9000

10001000800800

600600500500400400

300300

200200

1001008080

606050504040

3030

2020

1010

20002000

30003000

40004000500050006000600080008000

1000010000

2000020000

3000030000

4000040000500005000060000600008000080000

100000100000

2000

020

000

3000

030

000

4000

040

000

Hydraulical Specifications

Circulation Unit Art. R001PRESSURE DROP DIAGRAM

KV1

WATER FLOW (Q) [l/h]

PR

ESSU

RE

DR

OP

(Δp)

[Pa]

10 P

a=1

mm

H2O

KV2

KV1 m3/hAngled way 5.2

KV2 m3/hStraight way 5.85

Group orientation

CH54

CH4

CH54

CH37 CH37CH4

Page 7: ixing and circulation group - Icma S.p.a

Mixing and circulation groupR001 TECHNICAL DATA SHEET - 07/2020 - ENG

Icma SpA - Via Garavaglia, 420012 Cuggiono (MI) ITALIA

Tel: +39 02 97249134 - +39 02 97249135www.icmaspa.it - [email protected]

Right-Left SwitchingThe unit is supplied in two versions:- with right side delivery and upwards flow direction (equivalent, if reversed, to a left side delivery and flow downwards)- with left side delivery and upwards flow direction (equivalent, if reversed, to a right side delivery and flow downwards).The delivery and return way can be easily reversed.Below are the steps to be carried out in order to achieve a right-to-left delivery reversal.

1) Remove the insulatioans shells that are slightly paired to each other.

5) Unscrew the marked screws on the picture, remove the impeller, rotate it by 180° and reassemble it on the pump body. Finally, rotate the pump body upside down.

7) Assemble the unit according to the new layout with pump located on the left side, as shown in the picture.Tighten all the caps using suitable wrenches; carefully check the correct positioning of the gaskets.

2) Unscrew the Servomotor screw. 6) The layout of the mixing valve must be reversed. 6.1) Unscrew the 4 screws “A”.6.2) Pull out the cap “B” and the regulation unit “F”.6.3) Pull out the two elements of the by-pass “C” and “E”.

8) Reassemble the Servomotor.

3) Unscrew the nuts by using the wrenches shown in the picture. Be careful to avoid damages to the gaskets.

6.4) Reverse the elements “C” and “E”; be careful to avoid damages to the gaskets.6.5) Install the cap “B” and the regulation unit “F”; reverse the position of this unit, as well. Both elements are provided with a small reference slot “D” on the outer edge which must always match the notch on the valve body “G”. Care must be taken in avoidingdamages to the sealing O-Rings.6.6) Fasten the whole assembly with the 4 screws “A”.

9) Finally replace the insulation shells by slotting them in to each other.

4) Reverse the position of both on/off valves RED/ BLU.

AA

A

A

AB

FC

D

EG

CH4

CH54

CH54

CH54

CH4