Issues with Codes and Steiner Tunnel ratings for
insulation foams
Don Lucas, Ph.D.Lawrence Berkeley National Laboratory
UC Berkeley
Green Science Policy Institute
1
![Page 2: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/2.jpg)
Flammability characteristics of foam plastics first regulated in 1961
Flame spread and smoke developed by the Steiner Tunnel test (ASTM E 84)
2
![Page 3: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/3.jpg)
The Steiner Tunnel test results for flame spread of foam plastics are not meaningful
WOOD
How fire travels on material determines the flame spread index
3
![Page 4: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/4.jpg)
The Steiner Tunnel test results for flame spread of foam plastics are not meaningful
POLYSTYRENE
Result = low flame spread
4Excessive smoke, intumescence, etc. also problematic for other types of foam plastic
![Page 5: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/5.jpg)
Why is ASTM E84 used for Foam?
5
![Page 6: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/6.jpg)
Research during the 1970s
• Important, full-scale fire test projects.
• Realistic test rooms with bare foams mounted on walls and ceiling.
• Flame Spread Index (FSI) did not correlate to a meaningful improvement.
6 Williamson and Baron, 1973; Castino et al., 1975; Rose, 1975.
![Page 7: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/7.jpg)
Lower flame spread does not mean longer time to flashover
Castino, 1975; Lee 1985; Rose 19758
![Page 8: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/8.jpg)
Research during the 1970s
• Code bodies concluded:
• Bare foam cannot be safely used inside a habitable space.
• Thermal barrier requirement added to Uniform Building Code in 1976.
9
![Page 9: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/9.jpg)
Thermal barrier provides fire safety
• No exposed foam can safely be used
• Protects foams for at least 15 minutes after flashover
@Moosicorn
10
Steiner Tunnel requirements retained without a demonstrated benefit.
Babrauskas 2003; Babrauskas 2012
![Page 10: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/10.jpg)
Fire spread in a cavity
Exterior Interior
Fire spread determined by size of gap
Flame spread rating of insulation not a determining factor
Choi and Taylor, 198411
![Page 11: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/11.jpg)
Potential spread in cavities
• Steiner Tunnel rating has no proven correlation to practical benefits.
• Flame spread in cavity determined by size of gap between insulation and walls
• Firestopping is essential, and is included in all the modern codes.
12
![Page 12: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/12.jpg)
Primary item contributing to flame spread in home structure fires
Ahrens, 2011Str
uctural
mem
ber or fr
aming
Unclassi
fied st
ructural
componen
t
Exter
ior wall
cove
ring
Interior w
all co
verin
g
Cabinetr
y
Interior c
eiling c
over o
r finish
Insulati
on with
in structu
ral ar
ea
Exter
ior roof c
overin
g or fi
nish0
5
10
15
20
25
30
Perc
ent,
2005
-09
aver
age
2%
14
![Page 13: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/13.jpg)
97% of XPS/EPS in Sweden, Norway is non-flame retarded
15
• Codes changed to allow for use of non-flame retarded insulations
• No observed increase in fire incidence, injuries, or deaths
Blomqvist et al., 2011; Lassen et al., 2011; POPRC 2011
![Page 14: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/14.jpg)
Conclusions
• Flame retardants in foam plastic insulation have no practical benefit in many applications• Needed to pass the Steiner Tunnel requirement • Does not improve safety or limit spread of flames
in wall cavities
• Thermal barrier and firestopping requirements are sufficient in many applications
16
![Page 15: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/15.jpg)
California AB 127 (Skinner)
17
![Page 16: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/16.jpg)
Our Goals for California AB 127
• Maintain fire safety• Remove Steiner Tunnel requirements for
• Insulation protected by a 15-minute thermal barrier
OR• Insulation used below grade of building
• Allow for use of insulation without added flame retardants where they do not improve safety
18
![Page 17: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/17.jpg)
RIGID INSULATIONS
Flame Retardants in Building Insulation:
Changing the Status Quo
Suzanne DrakePerkins + Will
San Francisco, CA19
![Page 18: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/18.jpg)
RIGID INSULATIONSFlame Retardants in Building Insulation:
Should Building Codes be Re-Evaluated?
Insulation below grade will not burn.
Wall insulation behind 15-minute thermal barrier.
Steiner Tunnel Test not effective for plastic insulations
Can the standards bechanged so retardants aren’t required where there is no benefit?
20
![Page 19: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/19.jpg)
Why Change the I-Codes?
Plastic foam insulation is increasingly being used to increase energy efficiency.
We need to address the presence of toxic flame retardants without undermining energy efficiency.
21
![Page 20: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/20.jpg)
Work with the system
22
![Page 21: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/21.jpg)
The International Code Council
• main U.S. organization of building code officials
• publishes a full set of building codes
• updated on three year cycles
• staggered code development cycles
23
![Page 22: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/22.jpg)
2012 I-Codes…2015…2018…
• 2015 Group A Codes development process completed in October 2012
• 2015 Group B codes, including the International Residential Code (IRC), concluded in October 2013
• Initial SIS code change effort started with the 2015 IRC, and continues with the IgCC in the 2015 Group C codes
24
![Page 23: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/23.jpg)
2015 IRC code change proposal
No flame spread or smoke development requirements as measured by Steiner Tunnel test/ ASTM E 84 when foam plastics are:
– protected by a 15-minute minimum thermal barrier, such as ½” gypsum board
OR– protected by concrete or used below grade
on the exterior of a building
25
![Page 24: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/24.jpg)
2015 IRC code change proposal
• Defeated during Final Action Hearings• Arguments against:
– Exterior fire safety concern– Complications from different product lines– “Minimal chemical risk” due to “low exposure”– Issues for code inspectors (where to use FR
versus non-FR insulation?)– Would not reduce toxicity of fires (other materials
produce toxic combustion products)– Outside the scope of the I-codes – EPA issue
26
![Page 25: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/25.jpg)
2015 IgCC code change proposalsAdd new text as follows:
508 Insulation
Section 508.x Surface-burning characteristics. Foam plastic insulation shall meet IBC Section 2603.3 or IRC Section 316.3.
Exception: Rigid foam plastic insulation board shall not be subject to flame spread or smoke developed requirements when installed below a concrete slab on grade that provides continuous separation from the interior of the building, or installed as below-grade exterior foundation insulation, or is installed in accordance with IBC Section 1809.5 Frost protection. This foam plastic insulation shall be clearly labeled as such in addition to the requirements of IBC Section 2603.2 Labeling and identification.
2727
![Page 26: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/26.jpg)
2015 IgCC code change proposals508 Insulation
Section 508.x Disclosure. All insulation must use one of the following programs to disclose contents of the product to at least 0.1% (1000 ppm).• Manufacturer Inventory. The manufacturer has published complete content inventory
for the product following these guidelines:
◦ A publicly available inventory of all ingredients identified by name and Chemical
Abstract Service Registration Number (CASRN)
◦ Materials defined as trade secret or intellectual property may withhold the name
and/or CASRN but must disclose role, amount and GreenScreen benchmark, as
defined in GreenScreen v1.2.
• Health Product Declaration - The end use product has a published, complete Health
Product Declaration with full disclosure of known hazards in compliance with the
Health Product Declaration Open Standard.
• Cradle to Cradle- The end product has been certified at the Cradle to Cradle v2
Basic Level or Cradle to Cradle v3 Bronze Level.
• Declare- The end use product has a valid Declare label.
• Pharos Project- The end use product is fully disclosed in the Pharos Project Building
Product Library.
28
![Page 27: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/27.jpg)
2015 IgCC code change proposalsRevise as follows:
806.6 Insulation.806.6.1 A minimum of 85 percent of insulation shall comply with
the requirements of Table 806.6(1) or Table 808.6(2). The test methodology used to determine compliance shall be from CDPH/EHLB/Standard Method V.1.1, Standard Method for Testing VOC Emissions From Indoor Sources, dated February 2010. The emissions testing shall be performed by a laboratory that has the CDPH/EHLB/Standard Method V1.1 test methodology in the
scope of its ISO 17025 Accreditation.
806.6.2 A minimum of 50 percent by volume of insulation shall not contain halogenated flame retardants.
2929
![Page 28: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/28.jpg)
2015 IgCC code change process
2014 ICC Group C code development cycle:
- Code Change Deadline: January 10, 2014- Deadline to make proposal changes February 10- Posting of Proposed Changes: March 10- Code Development Hearings: April 27 – May 4
Memphis, TN
- Report of Hearings (results): June 6
- Public Comments Due: July 15- Public Comment Hearings: Oct. 1 – 7
Ft. Lauderdale, FL
30
![Page 29: Issues with Codes and Steiner Tunnel ratings for insulation foams Don Lucas, Ph.D. Lawrence Berkeley National Laboratory UC Berkeley Green Science Policy](https://reader036.vdocuments.site/reader036/viewer/2022062312/551a40e0550346a4248b5ae1/html5/thumbnails/29.jpg)
With better flammability standards
We can have fire safety and a healthier world.
Google: Green Science Policywww.greensciencepolicy.org