----------------------- Page 1-----------------------  DATE 01.11.2012 MICROMAX SYSTEMS PRIVATE LIMITED W.O No. 12 - 031 TRICHY SHEET No. 01 OF 13 PLC I/O LIST  PROJECT: ET200S NON REDUNDANT PLC - ASH (1 x 60MW Thermal Power Plant) P.O REF : MBK069/0290/S/27.6.12 M/s.CL A/C ARS METAL REV NIL A B C D ANALOG INPUT S. Panel PLC Card Ch. Ch. Tag Description Process Value Display Value Signal Signal Card Panel TB Client No. No. Tier No. No. Add. Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg. 1 1 1 1 1 PIW256 AISPARE1 AIC1 - 1,3 X1- 1, 2 2 1 1 1 2 PIW258 AISPARE2 AIC1 - 5,7 X1 - 3,4 3 1 1 2 1 PIW260 AISPARE3 AIC2 - 1,3 X2- 1, 2 4 1 1 2 2 PIW262 AISPARE4 AIC2 - 5,7 X2 - 3,4

Upload: advikniru

Post on 05-Jul-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 1/24

----------------------- Page 1-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 01 OF 13

PLC I/O LIST PROJECT: ET200S NON REDUNDANT PLC - ASH (1 x 60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12

M/s.CL A/C ARS METAL

REV NIL A B C D

ANALOG INPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value SignalSignal Card Panel TB Client

No. No. Tier No. No. Add.

Unit Min. Max. Unit Min. Max. TypeSo./Des. TB Nos. Nos. Ref. Dwg.

1 1 1 1 1 PIW256 AISPARE1

AIC1 - 1,3 X1- 1, 2

2 1 1 1 2 PIW258 AISPARE2

AIC1 - 5,7 X1 - 3,4

3 1 1 2 1 PIW260 AISPARE3

AIC2 - 1,3 X2- 1, 2

4 1 1 2 2 PIW262 AISPARE4

AIC2 - 5,7 X2 - 3,4

Page 2: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 2/24

MICROMAX

CUSTOMER

----------------------- Page 2-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 06 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL INPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value Signal Signal Card Panel TB ClientNo. No. Tier No. No. Add.

Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.

1 1 1 1 1 I0.0 DPC-SYSON-111 BED ASH COOLERS AT HOOPER-I ON/OFF SELECTOR SWITCH SYS-I(MV)

DIC1-1 X3 -1,2

2 1 1 1 2 I0.1 DPC-PUR-111 LINE PURG

E PUSH BUTTON SYS-I (MV)

DIC1-5 X3 - 3 ,4

3 1 1 1 3 I0.2 DPC-OVDPOR-111 PROBE OVER RIDE PUSH BUTTON SYS-I (MV)

DIC1-2 X3-5,6

4 1 1 1 4 I0.3 DPC-HLS-111 SURGE HOP

Page 3: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 3/24

LEVEL SWITCH SYS-I (MV)

DIC1-6 X3-7,8

5 1 1 1 5 I0.4 DPC-IVSP-111 INLET VALVE SEAL PRESSURE SWITCH SYS-I (MV)

DIC1-3 X3-9,10

6 1 1 1 6 I0.5 DPC-VLPS-111 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-I (MV)

DIC1-7 X3-11,12

7 1 1 1 7 I0.6 DPC-VHPS-111 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-I (MV)

DIC1-4 X3-13,14

8 1 1 1 8 I0.7 DPC-IBSW-111 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-I (MV)

DIC1-8 X3-15,16

9 1 1 2 1 I1.0 DPC-HLS-132 SURGE HOPPER LEVEL SWITCH SYS-I (SV)

DIC2-1 X4-1,2

10 1 1 2 2 I1.1 DPC-IVSP-132 INLET VALVE SEAL PRESSURE SWITCH SYS-I (SV)

DIC2-5 X4-3,4

11 1 1 2 3 I1.2 DPC-IBSW-132 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-I (SV)

DIC2-2 X4-5,612 1 1 2 4 I1.3 DPC-SYSON-121 BED ASH C

OOLERS AT HOOPER-I ON/OFF S S/W SYS-II(MV)

DIC2-6 X4-7,8

13 1 1 2 5 I1.4 DPC-PUR-121 LINE PURGE PUSH BUTTON SYS-II (MV)

DIC2-3 X4-9,10

14 1 1 2 6 I1.5 DPC-OVDPOR-121 PROBE OVE

R RIDE PUSH BUTTON SYS-II (MV)

DIC2-7 X4-11,12

15 1 1 2 7 I1.6 DPC-HLS-121 SURGE HOP LEVEL SWITCH SYS-II (MV)

DIC2-4 X4-13,14

16 1 1 2 8 I1.7 DPC-IVSP-121 INLET VAL

Page 4: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 4/24

VE SEAL PRESSURE SWITCH SYS-II (MV)

DIC2-8 X4-15,16

17 1 1 3 1 I2.0 DPC-VLPS-121 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-II (MV)

DIC3-1 X5-1,2

18 1 1 3 2 I2.1 DPC-VHPS-121 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-II (MV)

DIC3-5 X5-3,4

19 1 1 3 3 I2.2 DPC-IBSW-121 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-II (MV)

DIC3-2 X5-5,6

20 1 1 3 4 I2.3 DPC-HLS-122 SURGE HOPPER LEVEL SWITCH SYS-II (SV)

DIC3-6 X5-7,8

21 1 1 3 5 I2.4 DPC-IVSP-122 INLET VALVE SEAL PRESSURE SWITCH SYS-II (SV)

DIC3-3 X5-9,10

22 1 1 3 6 I2.5 DPC-IBSW-122 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-II (SV)

DIC3-7 X5-11,12

23 1 1 3 7 I2.6 DPC-SYSON-131 BUFFER HOOPER-I ON/OFF SELECTOR SWITCH (DPV)

DIC3-4 X5-13,1424 1 1 3 8 I2.7 DPC-PUR-131 LINE PURG

E PUSH BUTTON (DPV)

DIC3-8 X5-15,16

25 1 1 4 1 I3.0 DPC-OVDPOR-131 PROBE OVER RIDE PUSH BUTTON (DPV)

DIC4-1 X6-1,2

26 1 1 4 2 I3.1 DPC-HLS-131 SURGE HOP

LEVEL SWITCH (DPV)

DIC4-5 X6-3,4

27 1 1 4 3 I3.2 DPC-IVSP-131 INLET VALVE SEAL PRESSURE SWITCH (DPV)

DIC4-2 X6-5,6

28 1 1 4 4 I3.3 DPC-VLPS-131 CONVEYING

Page 5: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 5/24

VESSEL LOW PRESSURE SWITCH (DPV)

DIC4-6 X6-7,8

29 1 1 4 5 I3.4 DPC-VHPS-131 CONVEYING VESSEL HIGH PRESSURE SWITCH (DPV)

DIC4-3 X6-9,10

30 1 1 4 6 I3.5 DPC-SYSON-141 BUFFER HOOPER-II ON/OFF SELECTOR SWITCH(DPV)

DIC4-7 X6-11,12

31 1 1 4 7 I3.6 DPC-PUR-141 LINE PURGE PUSH BUTTON (DPV)

DIC4-4 X6-13,14

32 1 1 4 8 I3.7 DPC-OVDPOR-141 PROBE OVER RIDE PUSH BUTTON (DPV)

DIC4-8 X6-15,16

MICROMAX

CUSTOMER

----------------------- Page 3-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 07 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL INPUT

S. Panel PLC Card Ch. Ch. TagDescription

Page 6: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 6/24

Process Value Display Value SignalSignal Card Panel TB ClientNo. No. Tier No. No. Add.

Unit Min. Max. Unit Min. Max. TypeSo./Des. TB Nos. Nos. Ref. Dwg.

33 1 1 5 1 I4.0 DPC-HLS-141 SURGE HOP LEVEL SWITCH (DPV)

DIC5-1 X7-1,2

34 1 1 5 2 I4.1 DPC-IVSP-141 INLET VALVE SEAL PRESSURE SWITCH (DPV)

DIC5-5 X7-3,4

35 1 1 5 3 I4.2 DPC-VLPS-141 CONVEYING VESSEL LOW PRESSURE SWITCH (DPV)

DIC5-2 X7-5,6

36 1 1 5 4 I4.3 DPC-VHPS-141 CONVEYING VESSEL HIGH PRESSURE SWITCH (DPV)

DIC5-6 X7-7,8

37 1 1 5 5 I4.4 DPC-SYSON-151 SYSTEM ON/OFF SELECTOR SWITCH SYS-V (MV)

DIC5-3 X7-9,10

28 1 1 5 6 I4.5 DPC-PUR-151 LINE PURGE PUSH BUTTON SYS-V (MV)

DIC5-7 X7-11,12

39 1 1 5 7 I4.6 DPC-OVDPOR-151 PROBE OVER RIDE PUSH BUTTON SYS-V (MV)

DIC5-4 X7-13,14

40 1 1 5 8 I4.7 DPC-HLS-151 SURGE HOPPER LEVEL SWITCH SYS-V (MV)

DIC5-8 X7-15,16

41 1 1 6 1 I5.0 DPC-IVSP-151 INLET VALVE SEAL PRESSURE SWITCH SYS-V (MV)

DIC6-1 X8-1,2

42 1 1 6 2 I5.1 DPC-VLPS-151 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-V (MV)

DIC6-5 X8-3,4

43 1 1 6 3 I5.2 DPC-VHPS-151 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-V (MV)

Page 7: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 7/24

DIC6-2 X8-5,6

44 1 1 6 4 I5.3 DPC-IBSW-151 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (MV)

DIC6-6 X8-7,8

45 1 1 6 5 I5.4 DPC-HLS-152 SURGE HOPPER LEVEL SWITCH SYS-V (SV)

DIC6-3 X8-9,10

46 1 1 6 6 I5.5 DPC-IVSP-152 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)

DIC6-7 X8-11,12

47 1 1 6 7 I5.6 DPC-IBSW-152 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)

DIC6-4 X8-13,14

48 1 1 6 8 I5.7 DPC-HLS-153 SURGE HOPPER LEVEL SWITCH SYS-V (SV)

DIC6-8 X8-15,16

49 1 1 7 1 I6.0 DPC-IVSP-153 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)

DIC7-1 X9-1,2

50 1 1 7 2 I6.1 DPC-IBSW-153 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)

DIC7-5 X9-3,4

51 1 1 7 3 I6.2 DPC-HLS-154 SURGE HOPPER LEVEL SWITCH SYS-V (SV)

DIC7-2 X9-5,6

52 1 1 7 4 I6.3 DPC-IVSP-154 INLET VALVE SEAL PRESSURE SWITCH SYS-V (SV)

DIC7-6 X9-7,8

53 1 1 7 5 I6.4 DPC-IBSW-154 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-V (SV)

DIC7-3 X9-9,10

54 1 1 7 6 I6.5 DPC-SYSON-161 SYSTEM ON/OFF SELECTOR SWITCH SYS-VI (MV)

DIC7-7 X9-11,12

55 1 1 7 7 I6.6 DPC-PUR-161 LINE PURGE PUSH BUTTON SYS-VI (MV)

Page 8: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 8/24

DIC7-4 X9-13,14

56 1 1 7 8 I6.7 DPC-OVDPOR-161 PROBE OVER RIDE PUSH BUTTON SYS-VI (MV)

DIC7-8 X9-15,16

57 1 1 8 1 I7.0 DPC-HLS-161 SURGE HOPPER LEVEL SWITCH SYS-VI (MV)

DIC8-1 X10-1,2

58 1 1 8 2 I7.1 DPC-IVSP-161 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (MV)

DIC8-5 X10-3,4

59 1 1 8 3 I7.2 DPC-VLPS-161 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-VI (MV)

DIC8-2 X10-5,6

60 1 1 8 4 I7.3 DPC-VHPS-161 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-VI (MV)

DIC8-6 X10-7,8

61 1 1 8 5 I7.4 DPC-IBSW-161 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (MV)

DIC8-3 X10-9,10

62 1 1 8 6 I7.5 DPC-HLS-162 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)

DIC8-7 X10-11,12

63 1 1 8 7 I7.6 DPC-IVSP-162 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (SV)

DIC8-4 X10-13,14

64 1 1 8 8 I7.7 DPC-IBSW-162 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)

DIC8-8 X10-15,16

MICROMAX

CUSTOMER

----------------------- Page 4-----------------------

DATE 01.11.2012

Page 9: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 9/24

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 08 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL INPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value SignalSignal Card Panel TB ClientNo. No. Tier No. No. Add.

Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.

65 1 1 9 1 I8.0 DPC-HLS-163 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)

DIC9-1 X11-1,2

66 1 1 9 2 I8.1 DPC-IVSP-163 INLET VA

LVE SEAL PRESSURE SWITCH SYS-VI (SV)DIC9-5 X11-3,4

67 1 1 9 3 I8.2 DPC-IBSW-163 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)

DIC9-2 X11-5,6

68 1 1 9 4 I8.3 DPC-HLS-164 SURGE HOPPER LEVEL SWITCH SYS-VI (SV)

DIC9-6 X11-7,8

69 1 1 9 5 I8.4 DPC-IVSP-164 INLET VALVE SEAL PRESSURE SWITCH SYS-VI (SV)

DIC9-3 X11-9,10

70 1 1 9 6 I8.5 DPC-IBSW-164 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VI (SV)

DIC9-7 X11-11,12

Page 10: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 10/24

71 1 1 9 7 I8.6 DPC-SYSON-171 SYSTEM ON/OFF SELECTOR SWITCH SYS-VII (MV)

DIC9-4 X11-13,14

72 1 1 9 8 I8.7 DPC-PUR-171 LINE PURGE PUSH BUTTON SYS-VII (MV)

DIC9-8 X11-15,16

73 1 1 10 1 I9.0 DPC-OVDPOR-171 PROBE OVER RIDE PUSH BUTTON SYS-VII (MV)

DIC10-1 X12-1,2

74 1 1 10 2 I9.1 DPC-HLS-171 FEED HOPPER LEVEL SWITCH SYS-VII (MV)

DIC10-5 X12-3,4

75 1 1 10 3 I9.2 DPC-IVSP-171 INLET VALVE SEAL PRESSURE SWITCH SYS-VII (MV)

DIC10-2 X12-5,676 1 1 10 4 I9.3 DPC-VLPS-171 CONVEYIN

G VESSEL LOW PRESSURE SWITCH SYS-VII (MV)

DIC10-6 X12-7,8

77 1 1 10 5 I9.4 DPC-VHPS-171 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-VII (MV)

DIC10-3 X12-9,10

78 1 1 10 6 I9.5 DPC-IBSW-171 IN-CIRCU

IT/BYPASS SELECTOR SWITCH SYS-VII (MV)DIC10-7 X12-11,12

79 1 1 10 7 I9.6 DPC-HLS-172 FEED HOPPER LEVEL SWITCH SYS-VII (SV)

DIC10-4 X12-13,14

80 1 1 10 8 I9.7 DPC-IVSP-172 INLET VALVE SEAL PRESSURE SWITCH SYS-VII (SV)

DIC10-8 X12-15,16

81 1 1 11 1 I10.0 DPC-IBSW-172 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VII (SV)

DIC11-1 X13-1,2

82 1 1 11 2 I10.1 DPC-SYSON-181 SYSTEM ON/OFF SELECTOR SWITCH SYS-VIII (MV)

DIC11-5 X13-3,4

Page 11: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 11/24

83 1 1 11 3 I10.2 DPC-PUR-181 LINE PURGE PUSH BUTTON SYS-VIII (MV)

DIC11-2 X13-5,6

84 1 1 11 4 I10.3 DPC-OVDPOR-181 PROBE OVER RIDE PUSH BUTTON SYS-VIII (MV)

DIC11-6 X13-7,8

85 1 1 11 5 I10.4 DPC-HLS-181 FEED HOPPER LEVEL SWITCH SYS-VIII (MV)

DIC11-3 X13-9,10

86 1 1 11 6 I10.5 DPC-IVSP-181 INLET VALVE SEAL PRESSURE SWITCH SYS-VIII (MV)

DIC11-7 X13-11,12

87 1 1 11 7 I10.6 DPC-VLPS-181 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-VIII (MV)

DIC11-4 X13-13,1488 1 1 11 8 I10.7 DPC-VHPS-181 CONVEYIN

G VESSEL HIGH PRESSURE SWITCH SYS-VIII (MV)

DIC11-8 X13-15,16

89 1 1 12 1 I11.0 DPC-IBSW-181 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VIII (MV)

DIC12-1 X14-1,2

90 1 1 12 2 I11.1 DPC-HLS-182 FEED HOP

PER LEVEL SWITCH SYS-VIII (SV)DIC12-5 X14-3,4

91 1 1 12 3 I11.2 DPC-IVSP-182 INLET VALVE SEAL PRESSURE SWITCH SYS-VIII (SV)

DIC12-2 X14-5,6

92 1 1 12 4 I11.3 DPC-IBSW-182 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-VIII (SV)

DIC12-6 X14-7,8

93 1 1 12 5 I11.4 DISPARE1 RESERVE

DIC12-3 X14-9,10

94 1 1 12 6 I11.5 DISPARE2 RESERVE

DIC12-7 X14-11,12

Page 12: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 12/24

95 1 1 12 7 I11.6 DISPARE3 RESERVE

DIC12-4 X14-13,14

96 1 1 12 8 I11.7 DISPARE4 RESERVE

DIC12-8 X14-15,16

MICROMAX

CUSTOMER

----------------------- Page 5-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 09 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL INPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value Signal Signal Card Panel TB Client

No. No. Tier No. No. Add.

Unit Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.

97 1 1 13 1 I12.0 DPC-SYSON-191 SYSTEM ON/OFF SELECTOR SWITCH SYS-IX (MV)

DIC13-1 X15-1,2

98 1 1 13 2 I12.1 DPC-PUR-191 LINE PURG

Page 13: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 13/24

E PUSH BUTTON SYS-IX (MV)

DIC13-5 X15-3,4

99 1 1 13 3 I12.2 DPC-OVDPOR-191 PROBE OVER RIDE PUSH BUTTON SYS-IX (MV)

DIC13-2 X15-5,6

100 1 1 13 4 I12.3 DPC-HLS-191 FEED HOPPER LEVEL SWITCH SYS-IX (MV)

DIC13-6 X15-7,8

101 1 1 13 5 I12.4 DPC-IVSP-191 INLET VALVE SEAL PRESSURE SWITCH SYS-IX (MV)

DIC13-3 X15-9,10

102 1 1 13 6 I12.5 DPC-VLPS-191 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-IX (MV)

DIC13-7 X15-11,12

103 1 1 13 7 I12.6 DPC-VHPS-191 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-IX (MV)

DIC13-4 X15-13,14

104 1 1 13 8 I12.7 DPC-IBSW-191 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-IX (MV)

DIC13-8 X15-15,16

105 1 1 14 1 I13.0 DPC-HLS-192 FEED HOPPER LEVEL SWITCH SYS-IX (SV)

DIC14-1 X16-1,2106 1 1 14 2 I13.1 DPC-IVSP-192 INLET VAL

VE SEAL PRESSURE SWITCH SYS-IX (SV)

DIC14-5 X16-3,4

107 1 1 14 3 I13.2 DPC-IBSW-192 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-IX (SV)

DIC14-2 X16-5,6

108 1 1 14 4 I13.3 DPC-SYSON-211 SYSTEM ON

/OFF SELECTOR SWITCH SYS-X (MV)

DIC14-6 X16-7,8

109 1 1 14 5 I13.4 DPC-PUR-211 LINE PURGE PUSH BUTTON SYS-X (MV)

DIC14-3 X16-9,10

110 1 1 14 6 I13.5 DPC-OVDPOR-211 PROBE OVE

Page 14: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 14/24

R RIDE PUSH BUTTON SYS-X (MV)

DIC14-7 X16-11,12

111 1 1 14 7 I13.6 DPC-HLS-211 FEED HOPPER LEVEL SWITCH SYS-X (MV)

DIC14-4 X16-13,14

112 1 1 14 8 I13.7 DPC-IVSP-211 INLET VALVE SEAL PRESSURE SWITCH SYS-X (MV)

DIC14-8 X16-15,16

113 1 1 15 1 I14.0 DPC-VLPS-211 CONVEYING VESSEL LOW PRESSURE SWITCH SYS-X (MV)

DIC15-1 X17-1,2

114 1 1 15 2 I14.1 DPC-VHPS-211 CONVEYING VESSEL HIGH PRESSURE SWITCH SYS-X (MV)

DIC15-5 X17-3,4

115 1 1 15 3 I14.2 DPC-IBSW-211 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (MV)

DIC15-2 X17-5,6

116 1 1 15 4 I14.3 DPC-HLS-212 FEED HOPPER LEVEL SWITCH SYS-X (SV-1)

DIC15-6 X17-7,8

117 1 1 15 5 I14.4 DPC-IVSP-212 INLET VALVE SEAL PRESSURE SWITCH SYS-X (SV-1)

DIC15-3 X17-9,10118 1 1 15 6 I14.5 DPC-IBSW-212 IN-CIRCUI

T/BYPASS SELECTOR SWITCH SYS-X (SV-1)

DIC15-7 X17-11,12

119 1 1 15 7 I14.6 DPC-HLS-213 FEED HOPPER LEVEL SWITCH SYS-X (SV-2)

DIC15-4 X17-13,14

120 1 1 15 8 I14.7 DPC-IVSP-213 INLET VAL

VE SEAL PRESSURE SWITCH SYS-X (SV-2)

DIC15-8 X17-15,16

121 1 1 16 1 I15.0 DPC-IBSW-213 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (SV-2)

DIC16-1 X18-1,2

122 1 1 16 2 I15.1 DPC-HLS-214 FEED HOPP

Page 15: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 15/24

ER LEVEL SWITCH SYS-X (SV-3)

DIC16-5 X18-3,4

123 1 1 16 3 I15.2 DPC-IVSP-214 INLET VALVE SEAL PRESSURE SWITCH SYS-X (SV-3)

DIC16-2 X18-5,6

124 1 1 16 4 I15.3 DPC-IBSW-214 IN-CIRCUIT/BYPASS SELECTOR SWITCH SYS-X (SV-3)

DIC16-6 X18-7,8

125 1 1 16 5 I15.4 DISPARE5 RESERVE

DIC16-3 X18-9,10

126 1 1 16 6 I15.5 DISPARE6 RESERVE

DIC16-7 X18-11,12

127 1 1 16 7 I15.6 DISPARE7 RESERVE

DIC16-4 X18-13,14

128 1 1 16 8 I15.7 DISPARE8 RESERVE

DIC16-8 X18-15,16

MICROMAX

CUSTOMER----------------------- Page 6-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 10 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF: MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

Page 16: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 16/24

REV NIL A B C D

DIGITAL INPUT

S. Panel PLC Card Ch. Ch.Description P

rocess Value Display Value Signal SignalCard Panel TB ClientNo. No. Tier No. No. Add.

UnitMin. Max. Unit Min. Max. Type So./Des.

TB Nos. Nos. Ref. Dwg.

1 1 1 17 1 I16.0 DPC-BASHLS-802 BED ASH SILO LEVEL SWITCH

DIC17-1 X19-1,2

2 1 1 17 2 I16.1 DPC-FASHLS-802 FLY ASH SILO LEVEL SWITCH

DIC17-5 X19-3,4

3 1 1 17 3 I16.2 DPC-BSBFOF-801 BED ASH SILO BAG FILTER ON FEED BACK

DIC17-2 X19-5,6

4 1 1 17 4 I16.3 DPC-FSBFOF-801 FLY ASH SILO BAG FILTER ON FEED BACK

DIC17-6 X19-7,8

5 1 1 17 5 I16.4 DPC-ARPS-201 CONVEYING AIR RECIEVER PRESSURE SWITCH

DIC17-3 X19-9,10

6 1 1 17 6 I16.5 DPC-CWPS-201 COOLING WATER HEADER PRESSURE SWITCH

DIC17-7 X19-11,12

7 1 1 17 7 I16.6 DPC-RWPS-201 RETURN WATER HEADER PRESSURE SWITCH

DIC17-4 X19-13,14

8 1 1 17 8 I16.7 DPC-IBSHLS-802 INTERMEDIATE BED ASH SILO LEVEL SWITCH HIGH

DIC17-8 X19-15,16

9 1 1 18 1 I17.0 DPC-BMSHLS-802 BED MATERIAL BUNKER LEVEL SWITCH HIGH

Page 17: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 17/24

DIC18-1 X20-1,2

10 1 1 18 2 I17.1 DPC-IBSBFOF-801 INTERMEDIATE BED ASH SILO BAG FILTER ON FEED BACK

DIC18-5 X20-3,4

11 1 1 18 3 I17.2 DPC-BMBFOF-801 BED MATERIAL BUNKER BAG FILTER ON FEED BACK

DIC18-2 X20-5,6

12 1 1 18 4 I17.3 DISPARE9 RESERVE

DIC18-6 X20-7,8

13 1 1 18 5 I17.4 DISPARE10 RESERVE

DIC18-3 X20-9,10

14 1 1 18 6 I17.5 DISPARE11 RESERVE

DIC18-7 X20-11,12

15 1 1 18 7 I17.6 DISPARE12 RESERVE

DIC18-4 X20-13,14

16 1 1 18 8 I17.7 DISPARE13 RESERVE

DIC18-8 X20-15,16

17 1 1 19 1 I18.0 DISPARE14 RESERVE

DIC19-1 X21-1,2

18 1 1 19 2 I18.1 DISPARE15 RESERVE

DIC19-5 X21-3,4

19 1 1 19 3 I18.2 DISPARE16 RESERVE

DIC19-2 X21-5,6

20 1 1 19 4 I18.3 DISPARE17 RESERVE

DIC19-6 X21-7,8

21 1 1 19 5 I18.4 DISPARE18 RESERVE

Page 18: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 18/24

DIC19-3 X21-9,10

22 1 1 19 6 I18.5 DISPARE19 RESERVE

DIC19-7 X21-11,12

23 1 1 19 7 I18.6 DISPARE20 RESERVE

DIC19-4 X21-13,14

24 1 1 19 8 I18.7 DISPARE21 RESERVE

DIC19-8 X21-15,16

MICROMAX

CUSTOMER

----------------------- Page 7-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 11 OF 13

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL OUTPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value Signal Signal Card Panel TB Client

No. No. Tier No. No. Add.Unit

Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg. REMARKS

Page 19: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 19/24

33 1 1 1 1 Q0.0 DPC-SOI-111 SYSTEM ONINDICATION SYS-I (DPV)

DOC1-1 X22-2, DPV-1 Wet contact

34 1 1 1 2 Q0.1 DPC-IVS-111 INLET VALVE SOLENOID COIL SYS-I (DPV)

DOC1-5 X22-4 , DPV-2 Wet contact

35 1 1 1 3 Q0.2 DPC-CVS-111 CONVEYINGAIR VALVE SOLENOID COIL SYS-I (DPV)

DOC1-2 X22-6, DPV-3 Wet contact

36 1 1 1 4 Q0.3 DPC-IVS-112 INLET VALVE SOLENOID COIL SYS-I (DPV)

DOC1-6 X22-8, DPV-4 Wet contact

37 1 1 1 5 Q0.4 DPC-SOI-121 SYSTEM ONINDICATION SYS-II (DPV)

DOC1-3 X22-10,DPV-5 Wet contact

38 1 1 1 6 Q0.5 DPC-IVS-121 INLET VALVE SOLENOID COIL SYS-II (DPV)

DOC1-7 X22-12 , DPV-6 Wet contact

39 1 1 1 7 Q0.6 DPC-CVS-121 CONVEYINGAIR VALVE SOLENOID COIL SYS-II (DPV)

DOC1-4 X22-14, DPV - 7 Wet contact

40 1 1 1 8 Q0.7 DPC-IVS-122 INLET VALVE SOLENOID COIL SYS-II (DPV)

DOC1-8 X22-16, DPV-8 Wet contact

41 1 1 1 1 Q1.0 DPC-SOI-131 SYSTEM ONINDICATION (MV)

DOC2-1 X23-2 , DPV-9 Wet contact

42 1 1 2 2 Q1.1 DPC-IVS-131 INLET VALVE SOLENOID COIL (MV)

DOC2-5 X23-4,DPV-10 Wet contact

43 1 1 2 3 Q1.2 DPC-CVS-131 CONVEYINGAIR VALVE SOLENOID COIL (MV)

DOC2-2 X23-6, DPV-11 Wet contact

44 1 1 2 4 Q1.3 DPC-SOI-141 SYSTEM ONINDICATION (MV)

DOC2-6 X23-8 , DPV-12 Wet contact

Page 20: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 20/24

45 1 1 2 5 Q1.4 DPC-IVS-141 INLET VALVE SOLENOID COIL (MV)

DOC2-3 X23-10, DPV -13 Wet contact

46 1 1 2 6 Q1.5 DPC-CVS-141 CONVEYINGAIR VALVE SOLENOID COIL (MV)

DOC2-7 X23-12,DPV-14 Wet contact

47 1 1 2 7 Q1.6 DPC-SOI-151 SYSTEM ONINDICATION SYS-V (MV)

DOC2-4 X23-14,DPV-15 Wet contact

48 1 1 2 8 Q1.7 DPC-IVS-151 INLET VALVE SOLENOID COIL SYS-V (MV)

DOC2-8 X23-16, DPV-16 Wet contact

49 1 1 3 1 Q2.0 DPC-CVS-151 CONVEYINGAIR VALVE SOLENOID COIL SYS-V (MV)

DOC3-1 X24-2, DPV-17 Wet contact

50 1 1 3 2 Q2.1 DPC-IVS-152 INLET VALVE SOLENOID COIL SYS-V (SV-1)

DOC3-5 X24-4,DPV-18 Wet contact

51 1 1 3 3 Q2.2 DPC-IVS-153 INLET VALVE SOLENOID COIL SYS-V (SV-2)

DOC3-2 X24-6, DPV-19 Wet contact

52 1 1 3 4 Q2.3 DPC-IVS-154 INLET VALVE SOLENOID COIL SYS-V (SV-3)

DOC3-6 X24-8, DPV-20 Wet contact

53 1 1 3 5 Q2.4 DPC-SOI-161 SYSTEM ONINDICATION SYS-VI (MV)

DOC3-3 X24-10, DPV-21 Wet contact

54 1 1 3 6 Q2.5 DPC-IVS-161 INLET VALVE SOLENOID COIL SYS-VI (MV)

DOC3-7 X24-12, DPV-22 Wet contact

55 1 1 3 7 Q2.6 DPC-CVS-161 CONVEYINGAIR VALVE SOLENOID COIL SYS-VI (MV)

DOC3-4 X24-14, DPV-23 Wet contact

56 1 1 3 8 Q2.7 DPC-IVS-162 INLET VALVE SOLENOID COIL SYS-VI (SV-1)

DOC3-8 X24-16, DPV-24 Wet contact

Page 21: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 21/24

57 1 1 4 1 Q3.0 DPC-IVS-163 INLET VALVE SOLENOID COIL SYS-VI (SV-2)

DOC4-1 X25-2, DPV-25 Wet contact

58 1 1 4 2 Q3.1 DPC-IVS-164 INLET VALVE SOLENOID COIL SYS-VI (SV-3)

DOC4-5 X25-4, DPV-26 Wet contact

59 1 1 4 3 Q3.2 DPC-SOI-171 SYSTEM ONINDICATION SYS-VII (MV)

DOC4-2 X25-6, DPV-27 Wet contact

60 1 1 4 4 Q3.3 DPC-IVS-171 INLET VALVE SOLENOID COIL SYS-VII (MV)

DOC4-6 X25-8, DPV-28 Wet contact

61 1 1 4 5 Q3.4 DPC-CVS-171 CONVEYINGAIR VALVE SOLENOID COIL SYS-VII (MV)

DOC4-3 X25-10, DPV-29 Wet contact

62 1 1 4 6 Q3.5 DPC-IVS-172 INLET VALVE SOLENOID COIL SYS-VII (SV-1)

DOC4-7 X25-12,DPV-30 Wet contact

63 1 1 4 7 Q3.6 DOSPARE1 RESERVE

DOC4-4 X25-12, DPV -31

64 1 1 4 8 Q3.7 DOSPARE2 RESERVE

DOC4-8 X25-16, DPV-32

MICROMAX

CUSTOMER

----------------------- Page 8-----------------------

DATE 01.11.2012

MICROMAX SYSTEMS PRIVATE LIMITED

W.O No. 12 - 031

TRICHY

SHEET No. 12 OF 13

Page 22: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 22/24

PLC I/O LISTPROJECT: ET200S NON REDUNDANT PLC - ASH (1x60MW Thermal Power Plant)

P.O REF : MBK069/0290/S/27.6.12

M/s.CL A/C ARS METAL

REV NIL A B C D

DIGITAL OUTPUT

S. Panel PLC Card Ch. Ch. TagDescription

Process Value Display Value Signal Signal Card Panel TB Client REMARKS

No. No. Tier No. No. Add.Uni

t Min. Max. Unit Min. Max. Type So./Des. TB Nos. Nos. Ref. Dwg.

65 1 1 5 1 Q4.0 DPC-SOI-181 SYSTEMON INDICATION SYS-VIII (MV)

DOC5-1 X26-2,DPV-33 Wet contact

66 1 1 5 2 Q4.1 DPC-IVS-181 INLET VALVE SOLENOID COIL SYS-VIII (MV)

DOC5-5 X26-4,DPV-34 Wet contact

67 1 1 5 3 Q4.2 DPC-CVS-181 CONVEYING AIR VALVE SOLENOID COIL SYS-VIII (MV)

DOC5-2 X26-6 ,DPV-35 Wet contact

68 1 1 5 4 Q4.3 DPC-IVS-182 INLET VALVE SOLENOID COIL SYS-VIII (SV-1)

DOC5-6 X26-8 ,DPV-36 Wet contact

69 1 1 5 5 Q4.4 DPC-SOI-191 SYSTEMON INDICATION SYS-IX (MV)

DOC5-3 X26-10,DPV-37 Wet contact

70 1 1 5 6 Q4.5 DPC-IVS-191 INLET VALVE SOLENOID COIL SYS-IX (MV)

DOC5-7 X26-12,DPV-38 Wet contact

71 1 1 5 7 Q4.6 DPC-CVS-191 CONVEYING AIR VALVE SOLENOID COIL SYS-IX (MV)

DOC5-4 X26-14,DPV-39 Wet contact

Page 23: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 23/24

72 1 1 5 8 Q4.7 DPC-IVS-192 INLET VALVE SOLENOID COIL SYS-IX (SV-1)

DOC5-8 X26-16,DPV-40 Wet contact

73 1 1 6 1 Q5.0 DPC-SOI-211 SYSTEMON INDICATION SYS-X (MV)

DOC6-1 X27- 2,DPV-41 Wet contact

74 1 1 6 2 Q5.1 DPC-IVS-211 INLET VALVE SOLENOID COIL SYS-X (MV)

DOC6-5 X27-4,DPV-42 Wet contact

75 1 1 6 3 Q5.2 DPC-CVS-211 CONVEYING AIR VALVE SOLENOID COIL SYS-X (MV)

DOC6-2 X27- 6,DPV-43 Wet contact

76 1 1 6 4 Q5.3 DPC-IVS-212 INLET VALVE SOLENOID COIL SYS-X (SV-1)

DOC6-6 X27- 8,DPV-44 Wet contact

77 1 1 6 5 Q5.4 DPC-IVS-213 INLET VALVE SOLENOID COIL SYS-X (SV-2)

DOC6-3 X27- 10,DPV-45 Wet contact

78 1 1 6 6 Q5.5 DPC-IVS-214 INLET VALVE SOLENOID COIL SYS-X (SV-1)

DOC6-7 X27- 12 ,DPV-46 Wet contact

79 1 1 6 7 Q5.6 DPC-BBFST2-801 BED ASH SILO BAG FILTER SEQUENTIAL TIMER

DOC6-4 X27- 13 ,14 Dry contact

80 1 1 6 8 Q5.7 DPC-FBFST-801 FLY ASH SILO BAG FILTER SEQUENTIAL TIMER

DOC6-8 X27- 15,16 Dry contact

81 1 1 6 1 Q6.0 DPC-IBBFST2-801 INTERMEDIATE BED ASH SILO BAG FILTER SEQUENTIAL TIMER

DOC7-1 X28- 1,2 Dry contact

82 1 1 7 2 Q6.1 DPC-BMBFST2-801 BED MATERIAL BUNKER BAG FILTER SEQUENTIAL TIMER

DOC7-5 X28-3,4 Dry contact

83 1 1 7 3 Q6.2 DOSPARE4 RESERVE

DOC7-2 X28- 5,6

Page 24: Io List (Ash) - Rev d - 01.11.12

8/16/2019 Io List (Ash) - Rev d - 01.11.12

http://slidepdf.com/reader/full/io-list-ash-rev-d-011112 24/24

84 1 1 7 4 Q6.3 DOSPARE5 RESERVE

DOC7-6 X28- 7,8

85 1 1 7 5 Q6.4 DOSPARE6 RESERVE

DOC7-3 X28- 9,10

86 1 1 7 6 Q6.5 DOSPARE7 RESERVE

DOC7-7 X28- 11,12

87 1 1 7 7 Q6.6 DOSPARE8 RESERVE

DOC7-4 X28- 13,14

88 1 1 7 8 Q6.7 DOSPARE9 RESERVE

DOC7-8 X28- 15,16

:CONTACT RATING FOR INTERPOSSING RELAYS RELATED TO DIGITAL OUTPUT COMMANDS FROMPLC TO PNEUMATIC PANELS SHALL BE 230V AC .AND ITS POWER SUPPLY SHALL BE DERIVED FROM PLC ONLY.

DRY CONTACT:CONTACT RATING FOR INTERPOSSING RELAYS RELATED TO DIGITAL OUTPUT COMMANDS FROM PLC TO Bag filter timer panel SHALL BE 230V AC.

MICROMAX

CUSTOMER