An Introduction to IO-Link
Russell SmithBalluff Limited
![Page 2: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/2.jpg)
WHAT IS IO-LINK?
2
![Page 3: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/3.jpg)
not another bus system!
3
point to point communications protocol from the fieldbus to the sensor and actuator level.
up to
20M
Pulse-width modulated 24V
Baud rates: 4.8 kBit/s (COM1), 38.4 kBit/s (COM2), 230,4 kBits/s (COM3)
Pin Signal Description1 L + 24 Volt
2
3 L - 0 Volt
4 C / QIO-Link
communication+ switching signal
![Page 4: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/4.jpg)
standard - IEC 61131-9network neutral
an open standard
4
![Page 5: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/5.jpg)
5
IO-Link master… acts as a gateway between the IO-Link device and the higher level communication system, such as a fieldbus (Profinet, EtherNet/IP, etc.) or a device-specific backplane bus.
IO-Link device… is the field device with communication capability: sensors, switching devices, valve terminals, RFID devices, indicator lights, etc.
3-core unshielded standard cable – up to 20M long… is the standard interface between IO-Link master and device
IODD and engineering tool… are used to configure and assign parameters to the IO-Link system and devices.
an IO-Link system generally consists of the following basic components:
![Page 6: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/6.jpg)
IO-Link devices
6
many different IO-Link devices are available.
![Page 7: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/7.jpg)
IO-Link masters
7
panel mounted unit with terminals
IP67 field I/O module
additional slice on existing PLC
![Page 8: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/8.jpg)
WHY IO-LINK?
![Page 9: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/9.jpg)
easier handling of measurement devices
9
traditionally
better
best
lower cost – no analogue card
lower cost vs IE networked device
less wiring effort
![Page 10: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/10.jpg)
10
low cost
high density
less addresses
low cost per I/O point – 136 I/O on one IP address
![Page 11: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/11.jpg)
extensive diagnostics
11
available on sensors/devices and sensor hubs
troubleshoot problems quickly
maximise up-time
![Page 12: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/12.jpg)
• Short circuit – LED for each I/O port• Short circuit does not impair the unit• Sensor/actuator under voltage LED for each I/O port
extensive diagnostics:
12
![Page 13: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/13.jpg)
simplify valve manifold wiring
13
reduced installation time
reduced cost
![Page 14: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/14.jpg)
• World´s first combination of IO-Link and Safety
• Communication via one Topology
• Open System on the sensor level
• Connection of the safety IO-Link device to the standard BalluffIO-Link-Master
• Parameterization via PLC
SAFETY OVER IO-LINK
14Balluff GmbH | BN
![Page 15: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/15.jpg)
PROFISAFE IO HUB
15Balluff GmbH | BN Safety, M. Bristle
&Further features• Profisafe over IO-Link• PLe / SIL CL 3• standardized wiring concept (AIDA)• Diagnostic and Display integrated• CE, TÜV, (UL in preparation)
technical data (extract)• Cycle time: 20 ms• Temperature range: -5°C…55°C• Inputs: 2 pcs.• Safe Inputs: 12 pcs.• Outputs: 2 pcs.• Safe Outputs: 2 pcs.• Sum current (Aktors): 8 A• Sum current (Sensors): 4,8 A
![Page 16: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/16.jpg)
PORT CONFIGURATION
16Balluff GmbH | BN Safety, M. Bristle
Cable length IO-Link:max. 20 m
(acc. IO-Link Specification)
Cable length Device:max. 30 m
(s. Specification Device)
Cable length UB:max. 30 m
![Page 17: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/17.jpg)
extends communication
17
ERP
MES
SCADA
PLC
Network
Sensors and Actuators
Enterprise Level
Control Level
Management Level
Plant Control Level
Field Level
Sensor / Actuator Level
![Page 18: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/18.jpg)
HMIparameterisation – std pressure sensor
18
HMI
HMIHMIHMIHMI
![Page 19: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/19.jpg)
Time consuming configuration of 10 – 15 Parameter.(e.g. upper/lower Pressure point, Hysteresis, Time – or Pressure window)
Machine Tools have often more than 10 Pressure sensors
Error prone due to manual entry
Very bad when Sensor failure / Sensor exchange (especially during night shift)
parameterisation – std pressure sensor
19
Manualconfiguration
![Page 20: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/20.jpg)
parameterisation – std pressure sensor
20
HMI
HMI
HMI
HMI
![Page 21: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/21.jpg)
HMI integrated in sensor for set upmeans additional cost.
Expensive high-pressure hydraulichoses
parameterisation – std pressure sensor
21
machine tool
Additional cost for protectivehousing for sensors in the machine
![Page 22: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/22.jpg)
E.g. machine tool
parameterisation – pressure sensor with IO-Link
22
![Page 23: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/23.jpg)
PLCFunction-
blocks
Vendor_IDDevice_ID
Param1: 50barParam2: 100barParam3: 200ms
Step 1Identify device
Step 3Get Parameter Set
Step 2Check identity
Step 4Write Parameter Set
parameterisation – pressure sensor with IO-Link
23
![Page 24: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/24.jpg)
sensor installed at point of measurement
no expensive measurement cables - use std un-shielded 3-wire standard cables
no protection case
no sensors with HMI but reliable parameterisation via controller and HMI of the machine
decentralised diagnostics for sensors
parameterisation – pressure sensor with IO-Link
24
![Page 25: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/25.jpg)
parameter server
25
IO-Link V1.1 master
![Page 26: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/26.jpg)
automated tool changes
26
IO-Link inductive couplers fornon-contact signal transmission
![Page 27: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/27.jpg)
an i4.0 enabler
27
ERP
MES
SCADA
PLC
Network
Sensors and Actuators
Enterprise Level
Control Level
Management Level
Plant Control Level
Field Level
Sensor / Actuator Level
![Page 28: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/28.jpg)
unabated IO-Link success!
28
![Page 29: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/29.jpg)
HOW IO-LINK?
![Page 30: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/30.jpg)
device configuration
30
1. controller parameter storage –parameterisation from the PLC using the function block
2. IO-Link master ver 1.1 parameter server
3. PC storage with USB master
4. webserver entry with IO-Link master
5. Manual configuration
![Page 31: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/31.jpg)
IO-Link master configuration
connect the master and install GSDML file
drag and drop the relevant file
![Page 32: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/32.jpg)
Drag the appropriate (process data length) IOL input / output byte from the catalogue and name & address the module
IO-Link master configuration
32
![Page 33: Introduction to IO-Link - Russell Smith](https://reader031.vdocuments.site/reader031/viewer/2022021507/58ef5ace1a28ab7b068b45c5/html5/thumbnails/33.jpg)
THANKS FOR LISTENING!