introduction (contract management) 1. general
TRANSCRIPT
INTRODUCTION (Contract Management)
1. General
1.1. University Brunei Darussalam - UBD is in operation s i nce October 1985. Today the Un ivers i ty accommodates app rox ima te ly 700 academic and support staffs and 4,000 students in the faculties, namely Sultan Hassanal Bolkiah Institute of Education, Faculty of Arts and Social Sciences, Faculty of Business, Economics and Policies Studies, Faculty of Academy of Brunei Studies, Faculty of Science, Academy of Brunei Studies and Peng iran Anak Puteri Rashidah Sa'adatul Bolkiah Institute of Health Sciences with associated facilities.
1.2. The University includes wide range of facilities whose age varies from 26 years to just recently completed and handed over and those buildings with ongoing construction. The buildings complete with their associated facilities that are part of the University and shall be deemed part of the scope of works as per tabulation indicated below
1.3. The Contractor shall take note that the below tabulation includes buildings that forms firm part of the scope of Works and Services, buildings that are deemed provisional under the scope of Works and Services for this Contract and those buildings that are part of the Master Plan for UBD which will be included as part of this Contract upon their completion of construction works and defects liability period as applicable
1.4. Buildings that are categorized as provisional shall commence at the beginning of the Contract upon the instruction of Client's Representative and may be omitted from the scope of Works and Services during the currency of this Contract. Any such instruction to remove the provisional buildings from the scope of Works and Services will be via a written instruction by the Client's Representative at least one (1) months prior to such omission from the scope of Works and Services. In such instance of omission from scope of Works and Service, the corresponding proportionate and outstanding commercial equivalent of the omitted scope of works and services (including proportionate preliminaries; please refer to Appendix ‘D' for the list of items in Bill No. A 1 with respect to preliminaries that are subject to adjustment for such omission). No further adjustments or any claims associated with such omission
1.5 Buildings that are identified as part of the Master Plan of University Brunei Darussalam with their corresponding anticipated roll out period shall be implemented under this Contract for applicable scope of Works and Services.
2 Firm Buildings (Main Buildings)
1. Faculty of Science (FOS) 2. Sultan Hassanal Bolkiah Institute of Education (SHBIE) 3. Faculty of Arts and Social Sciences (FASS) iv. Academy of Brunei Studies 4. Institute for Leadership, Innovation and Advancement (ILIA) 5. Pengiran Anak Puteri Rashidah Sa'adatul Bolkiah Institute of Health
Sciences (Institute of Medicine) 6. Information Communication Technology Centre (ICTC) 7. Central Lecture Theatres (CLT)
8. Student Staff Centre (Student Affairs Building) 9. Student Affairs Extension 10. Academic Service Centre
11. Administration and UBD Estate Office Building 12. Mosque
13. Chancellor Hall (Grand Hall) 14. Store and Maintenance Centre 15. Security (Main Gate) 16. Chillers Yard
17. Ancillary Buildings (Incinerator, pump house, Service tunnel, water tank, sub stations, etc)
18. Pengiran Anak Puteri Rashidah Sa'adatul Bolkiah Institute of Health Science (Institute of Medicine (Extension)
19. Faculty of Integrated Science (Extension)
20. Science and Technology Research Laboratories
21. Library Extension
22. Faculty of Business, Economic and Policy Studies (FBEPS
23. Male and Female amenities and Canteen dining room (hostel)
Offsite Campus
2. Technical Assistants (Mechanical & Electrical)
2.1. The Contractor shall provide throughout the Contract Period Technical Assistants (Mechanical & Electrical Works) in accordance to the qualifications and requirements Specifications and Facilities Data and elsewhere in the Contract.
2.2. In addition to the above shared roles, the Technician (Mechanical &
Electrical Works) shall also be responsible for assisting the supervisor in conducting regular facility audits updating the maintenance plans, supervising the Works and Services carried out by the Contractor throughout the Contract Period. Such supervision by superinterding officer is in addition to any of the supervisors provided by the Contractor's domestic sub-contractors and is to ensure that the work and services performed is in accordance with Contract Requirements, to the required safety and quality
standards and on time.
3. HSSE Coordinator
3.1. The Contractor shall ensure that all activities are carried out strictly in
accordance with Client's Health, Safety, Security and Environmental
standards (HSSE) or in the event of absence of such policy, the highest
industry standards applicable. The Contractor's HSSE Coordinator shall be
involved in the planning of any hazardous work and liaise with the Client's
Representative on all safety matters on a daily basis while the Work is carried out.
3.2. The HSSE Coordinator shall organise all HSSE training for Contractors' staffs and
monitor the performance of all the Contractor's staff with regards to Client and Contractor's HSSE standards and procedures. Any shortfall or non compliance shall be investigated for remedial actions such as training and/or discipline actions
3.3. The HSSE Coordinator shall be responsible for recording HSSE performance indicators of the Contractor and submitting them to Client as required in this Contract. He shall also be the focal point for communication on all HSSE matters between Client and the Contractor.
3.4. It shall be the responsibility of the HSSE Coordinator to ensure that the Contractor adheres to the proposed Contract specific HSE plan and report accordingly on the corresponding achievement, shortfalls and proposed recommendations for improvement.
3.5. The HSSE Coordinator shall conduct daily safety audits at work places and come up with a brief report that shall be consolidated as part of the monthly progress report.
4. Health, Safety, Security and Environment (HSSE) Plan
4.1. Contractor shall develop an annual HSSE plan for executing the scope of
work safely and without negative impact to health of its workers and the environment. The HSSE plan shall comprise but not limited to Targets, Roles and responsibilities, Procedures/Standard references, Incident management (injury/LTl/mass evacuation), Audit/visit, t ra in ing and induct ions . Monthly reports of implementation of the HSSE plan shall be submitted to Client’s Representative. Management reviews of HSSE plans implementation shall be conducted by Contractor on quarterly basis for performance appraisal and improvements. Minutes of Meetings of these management reviews shall be submitted to Client's Representative.
4.2. In addition, the Contractor shall ensure all the staffs are trained on all Health, Safety, Security and Environment (HSSE) policies and standards.
5. Planned Maintenance
5.1. Planned Maintenance of Air-Conditioning and Ventilation Installations
5.1.1. The Scope of works for this section is for the planned maintenance of Air-Conditioning and Ventilation Installation listed below, but not limited to the following:-
5.1.1.1. Air-Handling Units 5.1.1.2. Fan-Coil Units 5.1.1.3. Air-Cooled Condensing Units 5.1.1.4. Variable Air Volume (VAV) Terminal Units 5.1.1.5. Variable Refrigerant Flow (VRF) Units/ VRV Units 5.1.1.6. Split-Type Air-Conditioning Units (including any associated
indoor unit, outdoor units and respective ducting I insulation/drainpipes)
5.1.1.7. Close Control Units (including any associated indoor, outdoor units and accessories)
5.1.1.8. Precision Air Conditioning System 5.1.1.9. Room Air Conditioning Units (RAC)
5.1.1.10. Chilled water condensing Units 5.1.1.11. Exhaust Fans 5.1.1.12. Air Curtains 5.1.1.13. Ductworks and any other associated systems for the smooth 5.1.1.14. operation of Air Conditioning and Ventilation Systems
5.2. The Contractor shall refer to the attachment Facilities Data
5.3. The Contractor shall be fully responsible for maintaining all the equipment listed at the schedule of equipment as stated above in full working order throughout the Contract Period.
5.4. The Contractor shall carry out the maintenance works as set-out in Facilities Data and shall honor all the manufacturer's recommendation with
regards to the equipment’s I systems that are being maintained.
5.5. The specification provided under Facilities Data act only as guidelines. As
such the Contractor shall be fully responsible to ensure such maintenance
works are in compliance with the manufacturer's requirements and
recommendations. Any deviations forthwith shall be notified to the Client's
Representative at the Commence of the Contract prior to Commencement
of Full Operations.
5.6. The scope of works for this section is for the satisfactory maintenance of all
the air-conditioning and ventilation installations and its accessories within
the Site Area. All costs for scope of Works and Services for this Section
are deemed to be included as per month bill of quantity
5.7. The Contractor, at all times, during the maintenance works shall ensure that
the maintenance activities do not render the original supplier I manufacturer's warranty void or invalid. The Contractor shall always refer
to the terms and conditions of warranty I indemnity furnished by the
original supplier I manufacturer prior to performing any maintenance activities. Any defaults by the Contractor and
associated damages arising due to violation of warranty I indemnity terms and conditions shall make the Contractor liable for payment to the Client for the associated damages. The Client shall notify the Contractor of such damages and shall make necessary adjustments to any payment due for the Contractor.
5.8. The Contractor shall be responsible for maintaining any battery packs
associated with the air-conditioning and ventilation system including those
of remote controls.
5.9. The Contractor shall also be responsible for providing assistance and
troubleshooting configuration and set-point issues that arise in the central or
individual control systems during the Contract Period.
5 .10 . Where required Contractor shall add the appropriate refrigerant during the
maintenance works scheduled
5.11. Where applicable systems running on f lex ib le or V-belts shall be
replaced by the Contractor.
5.12. The Costs included under Bill quantity are deemed inclusive of all the
above Scope of Works. No additional claims or whatsoever will be
entertained by the Client in Contractor's failure to include any costs
associated therewith.
5.13. The contractor shall provided enough at least two technicians for standby
within campus compound during/before/after if required any UBD event
within the period of the contract as per S.O instruction
6. QUANTITY OF WORK AND EMERGENCY CONTACT
6.1. Quantity of Work
6.1.1. The Contractor shall, at its own cost, have available sufficient number of
suitably skilled staff and suitable Equipment on which the Client can call as Client requirements may demand, in accordance with the terms of Scope of Work and Services, and shall further maintain a management and administrative structure which facilities supplementing such staff and Equipment expeditiously in order to accommodate fluctuating demand for Work during the Contract period.
6.1.2. Notwithstanding the quantities or types of Work indicated in or which
may be implied from any Section of the Contractor, the Client does not bind itself to guarantee the amounts or types or ratios of different types of WORK which may be required to be performed or of Materials, Equipment, staff or Work which may be required to be furnished by the Contractor under or during the currency of the Contract.
6.1.3. The Client shall not reimburse any costs incurred by the Contractor as a
consequence of under-utilization of the Contractor's resources.
6.2. Emergency Contact.
6.2.1. The Contractor shall also be required to perform emergency Work
outside of normal working hours as and when requested by the Client.
6.2.2. The Contractor shall ensure that all times during normal working hours he is available and contactable at all times for emergency Work. The Supervisor shall be the principal contact at all times throughout the Contract period and is responsible for leading the Emergency Response Team (ERT) together with HSE officer. The Supervisor shall ensure that the Client is advised of his contact details including hand phone numbers which shall be 24/7 accessible by the Employer.
6.2.3. The costs related with the standby and support of an Emergency Response Team lead by the Supervisor and supported by the Team is deemed inclusive in the Contract Price under Bill of quantity. No
additional cost for any overtime work or emergency attendance I support will be entertained by the Client.
6.2.4. It is the total responsibility of the Contractor to ensure that adequate spares, materials, tools, equipments and labour are made available to perform such works and no additional claims will be entertained due to the emergency nature of any of the works and services to be executed.
TO TUTONG
COASTAL HIGWAY
TO MUARA....
LEG
1. Sultan Hassanal Bolkiah of
Education
2. Academy of Brunei Studies
3. School of Business Education
4. Faculty of Arts and Social Sciences
5. Faculty of Science
a. Faculty of Intergrated Science
6. Faculty of Medicine
a. Faculty of Medicine (Extension)
7. Central Lecture Theatre
8. ILIA
9. Simpur Cafe
10. Student Centre Affairs
a. Extension of Student Affairs
(inspiring Hall)
11. Male Ammenities
12. Female Residential
13. Female Amenities
14. Mosque
15. Administration
a. Administration Extension
16. Library
a. Extension of Library
b. ICTC building
17. Chancellory Hall
18. Store
19. Security Post
Section 4 - Scope of Works and Services SW/81/2 of 2 (Addendum No. 1)
APPENDIX ·Bl - FIRM BUILDINGS
No Buildings
Main Facilities
1 Faculty of Science (FOS) Ground Floor
First Floor
Second Floor
Third Floor & Roof
Animal House
Electrical Plant Room & Genset Room
Flammable House
Growth Chamber
2 Faculty of Integrated Science Ground Floor
First Floor
Second Floor
Third Floor & Roof
3 Science and Technology Research Ground Floor
First Floor
4 Sultan Hassanal Bolkiah Institute of Education Ground Floor (SHBIE) First Floor
Second Floor
Roof & Lift Motor Room
Rubbish Centre and Gas Cylinder Area
5 Faculty of Business, Economics and Policy Studies (FBEPS
Ground Floor
First Floor
6 Faculty of Arts and Social Science (FASS) Ground
Floor First
Floor
Second Floor
Roof & Lift Motor Room
Rubbish Centre and Gas Cylinder Area 7 Academy of Brunei Studies- The Language Centre
Ground Floor (Faculty of Islamic Studies) First Floor
Second Floor
Roof & Lift Motor Room
8 Institute for Leadership, Innovation and Ground Floor
Advancement (ILIA) First Floor
Second Floor
Third Floor
Roof & Lift Motor Room
Pump Room, Sub Station, Chiller Yard
Rubbish Centre
9 Pengiran Anak Puteri Rashidah Sa'adatul Bolkiah Ground Floor
Institute of Health Science (Institute of Medicine) First Floor
Second Floor
Pump Room, Sub Station
Chiller Yard
incinerator
10 Pengiran Anak Puteri Rashidah Sa'adatul Bolkiah Institute of Health Science (Institute of Medicine) Extension
Ground Floor
First Floor
Second Floor
Third Floor
Four floor
Fifth floor
11 Central Lecture Theatre Ground Floor
First Floor & Roof Level
Section 4 - Scope of Works and Services SW/81/2 of 2 (Addendum No. 1)
No Buildings
Main Facilities
12 Student Staff Centre Lower Ground Floor
Upper Ground Floor
First Floor,
Roof & Lift Motor Room
Sub Station
Rubbish Centres
13 Student Staff Centre (Extension) Ground Floor
14 Library
Basement
Ground Floor
First Floor
Second Floor
Third Floor
Roof & Lift Motor Rooms
1 5 Information Communication Technology Centre -
Sub Lower Ground Floor
ICTC New (No 178) Lower Ground Floor
Block A & B Upper Ground Floor
First Floor
Second Floor
Third Floor
Fourth Floor
Roof & Lift Motor Room
16 Administration Building - Administration Ground Floor
First Floor
Second Floor
Attic Floor and Roof
17 Administration Building - Extension
of Administration [Estate office)
Ground Floor
First Floor
Sub Station
18 Mosque Main Prayer Hall - Ground Floor
Male Ablution
Female Ablution
Minaret
Mezzanine Floor
Sub Station & Pump Room
Chiller Yard
19 Store and Maintenance Centre Central Store
Maintenance Centre
Lockable Compound
Vehicle Garage
Sub Station
20 Chancellor Hall Lower Ground Floor
Upper Ground Floor including Mezzanine Floor
First Floor
Roof
Pump Room I Water Tank Area
Chiller Yard
21 Security Main Gate Ground Floor 22 Service Tunnel Under Ground
24 Male and Female Amenities
25 Simpur café Ground Floor
General
The Contractor shall perform the Works and Services in accordance
with the requirements of the specifications detailed hereunder a n d the appendices
herewith. Any deviations to these specifications without prior written approval from the
Client's Representative may result in the Contractor to repeat and make good the job
without any compensation from the Client.
In case of conflict amongst the various documents, the following priority shall apply:
. Scope of Work and Services
B).Specification &Facilities Data Locally and internationally recognized Industry Standards
Any contradiction to any of these specifications and/or between specifications shall be
brought to the attention of the Client's Representative, prior to execution of such affected
Works, whose decision shall be final.
From time to time, depending on the Work and location, it may be considered
economical to deviate from the specifications specified in Clause 1 herein, and the
Contractor shall obtain the prior approval and agreement of the Client's Representative
for such d e v i a t i o n s . Any unauthorized deviations will not be accepted by the Client.
The Client shall have the right to update any of these specifications as and when the
Client considers it necessary. The Contractor shall ensure that all Work is performed in
accordance with the most recent revision of each specification.
The Contractor shall be deemed to have inspected and examined all premises to
understand and satisfy themselves of the requirements set forth in the Contract.
Health, Safety, Security and Environment
The contractor shall familiarize and perform all the works in compliance with the local
industry recognized standards for Health, Safety, Security and Environment and shall
adhere to the requirements and regulations of relevant local authorities.
Health and Safety
Contractor shall ensure that HSSE requirements, policies and local regulations are strictly
adhered at all times during the Work throughout the Contract Period.
Workers involved in the above works shall be briefed by the Contractor's Safety Officer
on prevailing HSSE strictly adhere to health and safety regulations. Where recommended
protective gloves, masks etc. shall be worn to avoid direct contact to body and inhaling of
chemicals, pesticides, fungicides, weed killers, etc. All costs incurred thereby in providing
these equipments to the workers are to be borne by the Contractor and no extra payment
shall be made for such provisions.
SPECIFICATION FOR THE MAINTENANCE OF AIR-CONDITIONING AND VENTILATION
INSTALLATIONS
General Requirements
The term 'Equipment’ mentioned below under this s e c t i o n is specific to maintenance
of Air-Conditioning a n d Ventilation installations.
The Contractor shall only employ qualified, trained, certified and experienced technicians
and mechanics in the type of work being undertaken.
All such maintenance works shall be carried out under the supervision of a competent
foreman I supervisor nominated by the Contractor.
The Contractor shall obtain prior approval from the Client's Representative on the employees
employed for such maintenance works.
The Contractor shall ensure that required level of laborer’s, technicians, mechanics
and supervisors are maintained throughout the Contract Period.
The Contractor shall notify the Client's Representative immediately without delay on
defective parts that are deemed to be hazardous and/or considered to affect the
equipment life. If the defect can be reasonably attributed to negligence or incompetence
on the part of the Contractor, the repair shall be entire at the Contractor's expense.
Where it is necessary to shut down equipment for routine maintenance this
shall be done in liaison with the Client's Representative in the place affected. This
will take the form of shutting down the equipment during the Core Service Hours at a
time it will cause least disturbance to the occupants and the operation. Occasions
where it is practical to shut down equipment only after Core Service Hours, the
Contractor shall make prior special arrangements for access and security clearance
with the Client's Representative.
The Contractor shall provide all labor, plant, tools, equipment’s , and materials etc. for
carrying out the maintenance works.
Where stand-by units are installed, such units shall be changed over each month or as
recommended by manufacturer in order that the stand by unit becomes the duty unit and
its operating performance can be checked. This wi l l a lso ensure that all p lan items
a re subjected to equal working times.
The following information is to be recorded every three months for each air-conditioned
area and the result submitted to the Client's Representative:-
Dry bulb temperature
Wet bulb temperature
Relative humidity
Service reports shall be submitted to the Client's Representative within two working
days of a service being carried out. The service report is to show full detail of the service
and is to state the exact condition of the equipment inspected. Any defects found during
the inspection are to be clearly described on the service report.
The Contractor shall provide 24/7 Emergency Response Team (ERT) in the case of
emergency.
Maintenance Works Schedule
The following schedules are to be considered as minimum requirements and in
performing the following works manufacturer's recommendation shall be strictly
adhered. All materials required for the maintenance activities, including but not
limited to, grease, oils, belts, filters, refrigerants etc. and all necessary works shall
be deemed inclusive of the respective rates for the maintenance activity under their
category. No additional claims or whatsoever will be entertained for such materials.
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Air Handling Belts
D
Units (AHU) Proper belt tensioning is required
to
ensure maximum bearing and drive
Monthly
Monthly
component life and is based on fan brake horsepower required. Belts would
reach their permanent stretch after 48 hours of operation. Belt tensions shall be
measured in accordance with manufacturer's recommendation.
Readjust the belts but care must be taken not to over-tight it.
Observation
Observe the unit weekly for any change
in running condition and any unusual
noise. All such observations shall be
reported to the Client's Representative
in a format agreed prior to the
Commencement of Full Operations.
B Weekly
Enclosure and Access Doors
Inspect the enclosing cabinet, isolators
and supporting structures. Tighten loose
bolts and fasteners. Ensure that access
door gaskets are effective.
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Filters
Check air filters. Clean or replace if clogged
or dirty. Coat permanent filters with oil after cleaning.
Change bag filters when pressure drop is 1-inch
W.G.
Throwaway filters - Replace throwaway filters
and install new filters with the directional arrows
pointing in direction of airflow.
Permanent filters - Clean permanent filters by
washing under a stream of water to remove dirt
and lint.
Remove oil filter (aluminum or grease filter) with
a wash of mild alkali solution. Rinse in a clean,
hot water and allow to dry. Coat both sides of
the filter by immersing or spraying it with Air
Maze Filter Late W or equivalent. Allow to drain
and dry for about 12 hours.
Cost of changing such filters (both
permanent/bag filters) during
maintenance activities shall be deemed
inclusive of the corresponding rates for the
periodic maintenance.
D
Monthly
Coils
Inspect for leads and corrosion. Repair or replace
as required. Check for dirty coils. Clean as
required; wash or blow clean with inert gas or
compressed a i r .
Steam, hot water and chilled water coils should
be kept clean to maintain maximum
performance. If fins become dirty, clean with
steam and detergent , hot water spray and
detergent, or one of the commercially available
chemical coil cleaners. Rinse coils thoroughly
after cleaning.
Refrigerant coils should be kept clean to
D
Monthly
Equipment
Maintenance Works Category of
Maintenance
Works
Frequency
maintain maximum performance. If fins become
dirty, clean with cold water and detergent or one
of the commercially available chemicals coil
cleaners. Rinse thoroughly after cleaning. Never
use steam or hot water to clean a refrigerant coil.
Dangerous pressures may be built up by
improper application of heat resulting in
equipment damage or personal injury.
Drain Pan
Clean condensate drain pan, drain connection
and piping. Brush or blow drain lines clean.
D
Monthly
Fans
Fan bearings are permanently sealed and
lubricated as such do not attempt to lubricate
bearings. However, check for unusual noise,
high temperatures or vibration; check for
tightness of fasteners (nuts, machine screws, set
screws, shaft collars, etc.) and tighten as
required.
Inspect fan blades (or fan wheel) for build-up of
dirt or scale, use soft brush or clean rags to
loosen or remove dirt, and flush surfaces with
clean water. Inspect components and repair or
replace as required. This includes repairing
defects in protective coatings. If work performed
on fan wheel, check balance and rebalance as
required.
Fan motors should be checked for vibration or
temperature.
D
Monthly
Dampers
Inspect damper assemblies, and report all
discrepancies to Client’s Representative.
Inspection shall include the following:-
1 Verify damper position relative to facility mode of operation. Adjust position indication switches as required.
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
2 Exercise dampers to verify free operation;
repair or adjusted as required.
3 Inspect seals and seal contacting surfaces for
full contact; adjust seals and/or repair
seals and sea l contacting surfaces as
required.
4 Wipe clean damper operator and
connecting linkages; apply a l i g h t coat
of oil.
Clean and inspect bearings; lubricate and
adjust bearings as required.
Operating Valves
Verify valve position relative to facility mode
of operation. Adjust position indication
switches as required. Clean rods on valve
operator and apply a light coat of protective
oil. Inspect seals; Inspect and tighten
packing as required.
D
Monthly
All Valves
Exercise all valves and perform routine
maintenance, and report all discrepancies to
Client's Representative. Grease stems on
OS&Y valves as applicable. Inspect packing
gland and tighten as necessary. Verify correct
position and operation. Check for leaking
seals.
D
Monthly
Any other manufacturer's recommendation D Monthly
Check Greasing on fan and motor.
Follow manufacturer’s recommendation for
lubrication (if necessary).
D Monthly
Align fan and motor sheaves (pulley).
Tighten sheaves setscrews to the proper
torque. D Monthly
Check and adjust fan belt tension D Monthly
Tighten electrical connections D Monthly
Inspect coils for dirt build-up or coil freeze
up D Monthly
Condensation on Units
Check for any condensation on unit and
ensure the fan is in operation. If fan
cycling is used, check the water flow
control valve which shuts-off the water
when fan stops.
D
Monthly
Fan Coil
Units Coil
Remove return-air grille access panel and
brush between coil fins with stiff wire brush.
Follow-up by cleaning with
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
vacuum cleaner. If the coil is cleaned with air
hose and nozzle, take care not to drive dirt
and dust into other components.
Coll Air-Vent
In manual coil air-vent systems turn vent
cap clockwise (closed) while filling system;
turn counter clockwise (open) to vent air.
Tighten clockwise after venting.
In automatic systems turn vent cap slightly
counter clockwise until water leaks at about
10 drops per minute. Leak will stop within
one-half minute
D
Monthly
Drain
Check drain pan, drain line and trap at start of each
cooling season. A standard pipe cleaner for
%-inch internal diameter can be used to
ensure that pipe is clear of obstruction so that
condensate is carried away. Check the
drain line at filter cleaning time during the
cooling season. Be sure that debris has not
fallen into unit through supply-air grille.
D
Monthly
Fan Motor Bearings
Lock open and tag unit electoral service switch.
Standard motors are permanently sealed and
lubricated. No lubrication is required unless
special motors have been supplied or unusual
operating conditions exist. Check for leaks
D
Monthly
Fan Wheel
Lock open and tag unit electrical switch. For
access to fan assembly, remove front or
bottom panel. Fan assembly may be
removed from its tracks if unit has a long
conduit lead. Use a stiff brush or vacuum to
remove dirt and debris from scroll. Wipe all
fan surfaces with a damp cloth.
D
Monthly
Electric Heater
Lock open and taq unit electrical switch.
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
frequency
Remove dust, dirt, or foreign material before
start-up. Do not block normal airflow to and
from units; blockage may damage electric
heaters. Clean heater elements with soft brush
or vacuum cleaner as necessary. To replace
blown fusible links (nichrome heaters only):
a. Remove fan deck (horizontal units only)
for access to heater.
b. Remove nut securing link at each end; install
new link; reinstall nuts.
c. Reinstall fan deck (if removed).
Clean or Replace Air Filters (as
necessary)
Lock open and tag unit electrical service switch.
Replace throwaway filter or clean permanent
filter.
THROWAWAY FlLTER - Replace filter with a
good quality filter of the size recommended by
the manufacturer. Do not attempt to clean and
reuse d i s p o s a b l e filters.
PERMANENT FILTER (FIBERGLASS TYPE)
1. Tap on solid surface to dislodge heavy
particles.
2. Wash in hot water. If needed, use mild solution
of commercial solvent such as sol soda or
trisodium phosphate.
3. Set filter on end so that water drains out
through slots in frame. Allow filter to dry
thoroughly.
4. Recharge filter with Film-Cor or similar
recharging oil. Three ounces is sufficient for
medium size filter. Oil may be applied by insect
spray gun. For easier spraying, the oil can be
warmed. If the filter is dipped in the recharging
oil, remove it immediately and allow draining
through slots in frame.
1. Replace filter in unit.
If another type of filter is used, follow the filter
manufacturer's instructions.
D
Monthly
Variable Air Ensure all the set-points are appropriate G Quarterly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Volume
(VAV)
Ensure electrical connections are intact G Quarterly
Any other manufacturer's recommendation G Quarterly
Variable
Refrigerant
Flow (VRF) and
Variable
Refrigerant
Volume
(VRV) System
indoor units
Ensure
the
clean
Indoor Cassette units are D Monthly
Remove the filters and clean thoroughly
and replace.
D Monthly
Clean drain outlets; brush or blow down
drain lines
D Monthly
Ensure the all fixings, bolts, screws etc. of
the indoor cassettes are intact
D Monthly
Ensure all the set-points are appropriate D Monthly
Ensure electrical connections are intact D Monthly
Check for any refrigerant leaks D Monthly
While servicing the ducted units ensure the
access is back in position firmly.
D Monthly
Replace filters
Variable
Refrigerant
Flow (VRF) and
Variable
Refrigerant
Volume (VRV) System
- Outdoor
Units
Compressors
1. Check for refrigerant leakage and
top-up as necessary.
2. Check oil level in sight glass. If low top-
up as necessary and record amount
used.
3. Leak test all joints with leak industry standard test lamp
4. Check for vibration and security of all
components (including compressor
holding down bolts).
5. Visually check alignment of pipes
6. Check capillaries, for rubbing damage, etc.
7. Checking operation of crankcase
heaters
8. Check compressor operation, take
pressure and temperature readings
9. Take and record motor amps
10. Random check of electrical
connections and contactor
operations
1 1. Inspect site glass for moisture and
record if not dry.
12. Visual check driers
13. VRF units operate with active oil
management system and if any oil
shortage is detected in any
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
compressor, oil can be transferred
automatically from a compressor in
another outdoor unit. Contractor shall
ensure the connections of such
balancing pipe between outdoor units
for uniform oil level.
14. Clean the air-filter and vacuum as
necessary. Ensure all such dirt or
foreign particles do not enter the
other systems.
15. Check drain pipes for cleanliness
16. Any other maintenance works recommended by manufacturer
D Monthly
Fan
1 • Check for smooth operation and if
there is any noise report to the
Superintending Officer and
recommend further ac t ion .
2. Open the grille in accordance to
manufacturer's recommendation.
3. Clean the fan for settlement of dust or
foreign particles.
4. Check the DC fan motor for its smooth
operation.
D Monthly
Electrical Connections
1. Check of electrical connections for
damage and secure re-tighten as
necessary or report
2. Check control operation
3. Check for noisy contactors 4. Check timer and change over relays
and overloads and record settinqs.
D
Monthly
Any other manufacturer's recommended
monthly maintenance D Monthly
Compressors
1. Check suction superheat and record
readings On open drive
compressors check security of
couplings pulleys and belts, etc.
G Quarterly
Any other manufacturer recommended
quarterly maintenance G Quarterly
Ensure the Indoor units are clean D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Split-Type
Air
Conditioning
Units (Indoor
Units)/Ceiling
Mounted
Cassette Type
Remove the filters and clean thoroughly
and replace.
D Monthly
Clean drain outlets; brush or blow down
drain lines
D Monthly
Ensure that all fixings, bolts, screws etc. of
the indoor cassettes are intact
D Monthly
Ensure all the set-points are appropriate D Monthly
Ensure electrical connections are intact D Monthly
Check for any refrigerant leaks D Monthly
Any other manufacturer's
recommendation
D Monthly
Split-Type
Air
Conditioning
Units (Outdoor
Units)
Compressors
l Check for refrigerant leakage and top-
up as necessary.
2 Check oil level in sight glass. If low top
up as necessary and record amount
used. 3 Leak test all joints with industry
standard leak test lamp.
4 Check for vibration and security of all
components (including compressor
holding down bolts).
5 Visually check alignment of pipes
6 Check capillaries, for rubbing damage,
etc.
7 Checking operation of crankcase
heaters.
8 Check compressor operation, take
pressure and temperature readings
9 Take and record motor amps.
10 Random check of electrical
connections and contactor operations.
1 1 Inspect site glass for moisture and record
if not dry.
12 Visual check driers.
13 Check for oil shortage and add as
D
Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
necessary in accordance to
manufacturer's recommendation.
14 Clean the air-filter and vacuum as
necessary. Ensure all such dirt or
foreign particles do not enter the other
systems.
15 Check drain pipes for cleanliness
16 Any other maintenance works
recommended by manufacturer
Check the impeller for build-up of material
or dirt which may cause an imbalance
with resulting undue wear on bearings
and belt drives. Clean as per
manufacturer's recommendation as
required.
D Monthly
Inspection of the rotating assembly must
be made to detect any indication of
weakening of the rotor because of
corrosion, erosion, or metal fatigue.
D Monthly
Any other
recommendation
manufacturer's
D Monthly
Split type Air-
Conditioning
System
(Standing
Type)
Isolate the unit
disconnect.
electrically and
D Monthly
Coil fins to be straightened by a fin comb. D Monthly
Chassis base, compressor and fan
mounting to be examine for rust or
deterioration. Affected area to be wire
brush and treated with bituminous paint or
other corrosion inhibitor.
D Monthly
Check the fans are located on the shaft
correctly and are secured.
D Monthly
Fans shaft to be cleared and greased. D Monthly
Test the fan motor insulation resistance
using a Mega Ohmmeter and record
value on the service report.
D Monthly
Test the compressor motor winding
insulation resistance of both start and run
D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
winding using a Mega Ohmmeter and
record value on the service report.
Check the drainage channels from the
evaporator section are clear.
D Monthly
Leak detects with halide or electronic leak
detector all refrigerant pipe work on the
unit. Report any leaks immediately to
Client's Representative.
D Monthly
Startup unit and record both the starting
and running current draw and record
these on the service record. Compare
values with manufacturer's data - note
any difference greater than 10%.
D Monthly
Filter and front cover to be washed and
dried thoroughly.
D Monthly
Check fan speed control at all speeds if
fitted for correct operation.
D Monthly
Check ventilation control for correct
operation.
D Monthly
Manually adjust thermostat to check
operation and readjusted to original
setting.
D Monthly
Check and record 'air on' and 'air off'
temperatures across condenser and
evaporator and record.
D Monthly
Where internal drains pans and hoses are
fitted, these are to be thoroughly washed
and hoses f lushed through with soapy
water. Ensure the drain pan is securely
fixed.
D Monthly
Any objects restricting airflow are to be
removed.
D Monthly
Any other defects are to be noted on the
service report.
D Monthly
Empty reservoir in regular basis. D Monthly
Portable Air-
Conditioning
System
Isolate the unit electrically and
disconnect.
D Monthly
Coil fins to be straightened by a fin comb. D Monthly
Chassis base, compressor and fan
mounting to be examine for rust or
deterioration. Affected area to be wire
D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
brush and treated with bituminous paint or
other corrosion inhibitor.
Check the fans are located on the shaft
correctly and are secured.
D Monthly
Fans shaft to be cleared and greased. D Monthly
Test the fan motor insulation resistance
using a Mega Ohmmeter and record value
on the service report.
D Monthly
Test the compressor motor winding
insulation resistance of both start and run
winding using a Mega Ohmmeter and
record value on the service report.
D Monthly
Check the drainage channels from the
evaporator section are clear.
D Monthly
Leak detects with halide or electronic leak
detector all refrigerant pipe work on the
unit. Report any leaks immediately to
Client's Representative.
D Monthly
Startup unit and record both the starting and
running current draw and record these on
the service record. Compare values with
manufacturer's data - note any difference
greater than 10%.
D Monthly
Filter and front cover to be washed and
dried thoroughly.
D Monthly
Check fan speed control at all speeds if
fitted for correct operation.
D Monthly
Check ventilation control for correct operation.
D Monthly
Manually adjust thermostat to check all
operation origin and readjusted setting.
D Monthly
Check and record 'air on' and 'air off'
temperatures across condenser and
evaporator and record.
D Monthly
Where internal drains pans and hoses are
fitted, these are to be thoroughly washed and
hoses flushed through with soapy water.
Ensure the drain pan is securely fixed.
D Monthly
Any objects restricting airflow are to be D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
removed.
Any other defects are to be noted on the
service report.
D Monthly
Empty reservoir in regular basis. D Monthly
Precision Air-
Conditioning
System
Check that the room values shown by the
control are accurate
D Monthly
Check the refrigerant load; make sure
that there are no more than a few bubbles
in the flow sight glass on the
refrigerant circuit
D Monthly
Check that the temperature and noise
emitted by the compressor and the fan
are normal
D Monthly
Check the air filter; clean or replace it if it
triggers the dirty filter alarm. Cost of such
filter replacements are deemed inclusive
of the rates for the respective
maintenance activity.
While cleaning the air filter, remove and
inspect the filter cartridge (whenever
there is a blocked filter alarm) . Tap the
filter to remove large particles of dust and
then clean with a vacuum cleaner. If the
filter is blocked, replace it with an
equivalent model filter.
D Monthly
Check the power supply voltage D Monthly
Check that the damper can move freely
and that the neoprene rubber a r o u n d
the edge of the damper gives a t i g h t
seal.
D Monthly
Check that the noise made by the unit is
normal
D Monthly
Any other manufacturer's
recommendation
D Monthly
Check that evaporation and condensation
pressures (or saturated temperatures) are
normal
D
Monthly
Check the correct flow of condensation
water to the drain
D
Monthly
Check whether the MRA condenser is
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
dirty, removing any obstructing materials
(leaves, paper, etc.) with a jet compressed air
or water
D
Monthly
Check that all terminal connections are tight
D
Monthly
Any other recommendation
manufacturer's D Monthly
Check and note the set values of the
regulation and safety devices in accordance
with manufacturer's recommendation.
D Monthly
Any other recommendation manufacturer's D Monthly
Room Air-
conditioning
(RAC)
Isolate the electrically and unit disconnect. D Monthly
Remove Chassis from cabinet. D Monthly
Coil fins to be straightened by a fin comb. D Monthly
Chassis base, compressor and fan mounting
to be examine for rust or deterioration.
Affected area to be wire brush and treated with
bituminous paint or other corrosion inhibitor.
D Monthly
Check the fans are located on the shaft
correctly and are secured. D Monthly
Fans shaft to be cleared and greased. D Monthly
Test the fan motor insulation resistance using
a Mega Ohmmeter and record value on the
service report.
D Monthly
Test the compressor motor winding insulation
resistance of both start and run winding using
a Mega Ohmmeter and record value on the
service report.
D Monthly
Check the drainage channels from the
evaporator section is clear. D Monthly
Leak detects with halide or electronic leak
detector all refrigerant pipe work on the unit.
Report any leaks immediately to
S.O.
D Monthly
Reinstall chassis in the cabinet, replacing any
missing screws or nuts and bolts and
reconnect electrically.
D Monthly
Startup unit and record both the starting and
running current draw and record these on the
service record. Compare values with
manufacturer's data - note any difference
meter than 10%.
D Monthly
Equipment Maintenance Works Category
of
Maintenan
ce
Works
Frequency
Filter and front cover to be washed and
dried thoroughly.
D Monthly
Check fan speed control at all speeds if
fitted for correct operation.
D Monthly
Check ventilation control
operation.
for correct D Monthly
Manually adjust thermostat
operation and readjusted
setting.
to
to
check
original
D Monthly
Check and record 'air on' and 'air off'
temperatures across condenser and
evaporator and record.
D Monthly
Where internal drains pans and hoses are
fitted, these are to be thoroughly washed and
hoses flushed through with soapy water.
Ensure the drain pan is securely fixed.
D Monthly
Any objects restricting airflow are to be
removed.
D Monthly
Any other defects are to be noted on the
service report.
D Monthly
Chilled
Water
Condensing
Units
Check all set-points for proper setting and
function.
D Monthly
Check all refrigerant joints and valves for
refrigerant leaks using industry standard
leak detectors. Add refrigerant as required.
D Monthly
Top-up with refrigerant if necessary. D Monthly
Check sight glass for moisture. D Monthly
Check all electrical connections for tightness, tighten as necessary.
D Monthly
Check electrical panels and controls for sign
of overheating, arcing and mechanical
damage and make necessary remedial works.
D Monthly
Check timer and change over relays and
record times
D Monthly
Check electrical panels for any dust and
dirt, which may have accumulated in the
control panel.
D Monthly
Equipment
Maintenance Works Category of
Maintenance
Works
Frequency
Contacts Spray contacts with contactor cleaner
D Monthly
Check and clean chilled water strainers D Monthly
. Check chilled water flow switch operation D Monthly
Assess proper water condenser evaporator
and flow in D Monthly
Check condenser fan operation and inspect pump seal
D Monthly
Check pressure in refrigerant circuits Check and fill chilled water loop with water or brine, if necessary. Check for proper antifreeze concentration &
corrosion inhibitor in chilled water loop
Check and test the cooler heater
circuit, if equipped
Check calibration of all transducers
each circuit. Check accuracy of all
thermistors
Check cooler approach {Cooler
Leaving Water Temperature -
Saturated Suction Temperature)
check pressure drop across filter driers, replace/clean as necessary
Perform the normal start up procedure.
Document system condition and further service needs Check condenser coils for debris, clean as necessary with approved coil cleaner
Check condenser coil fins, clean
and vacuum as necessary
Environment is within manufacturer-
specified operating conditions, including
but not limited to the operating
climate and clearances
Document any environmental
noncompliance issues and rec ommend appropriate action as necessary
Any other updated maintenance
recommendations by manufacturer
Any other manufacturer's
recommendation
D
Monthly
Conduct vibration analysis: Check all alignments to specifications. Check a l l seals. Lubricate where necessary G Quarterly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Check Motor amperage should not
exceed manufacturer's specification. D Monthly
Perform analysis on oil and filter. Change if
necessary. Check oil pump and seals Check
oil heater and thermostat
D Monthly
Check for condenser and evaporator
tube corrosion and clean as needed.
Indications include: poor water quality,
excessive fouling, and age of chillers.
Eddy current testing may be done to
assess tube condition.
D Monthly
Any other manufacturer's
recommendation D Monthly
Chilled
Water
Pumps
Checking for smooth operation of the pumps
D Monthly
Check all set-points for proper setting and
function D Monthly
monitor the meter on the system make-
up water inlet D Monthly
Check and verify the operating
parameters of valve chatters D Monthly
Any other manufacturer's
recommendation D Monthly
Ensure that all bearings are lubricated
according to manufacturer's
recommendations.
D Monthly
Clean motor vents as necessary D Monthly
Check couplings and pulleys for secure
fixing and wear D Monthly
Check packing for wear and repack as
necessary. Consider replacing packing
with mechanical seals.
D Monthly
Check for mechanical seals for leakage
that exceeds the manufacturer's
specifications. Replace if necessary. D Monthly
Check pump and pipe works for anti-
vibration connections, insulation and
brackets to be checked visually for
damage
D Monthly
Make-up tank to be checked for correct
level (i.e. 1/3rd of the height of tank)
Check and secure all pump mountings. D Monthly
Any other manufacturer's
recommendation D Monthly
Test the efficiency of pumps and
compare it to previous benchmarking data D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Inspect bearings and drive belts for wear.
Adjust, repair, or replace as necessary. D Monthly
Inspect expansion tanks to make sure
that the capacity is acceptance
adequate they function and that
properly
D Monthly
Check the condition of the motor through temperature or vibration analysis.
D Monthly
Propeller
Do not attempt any maintenance on a
D Monthly
fan unless the electrical supply has been
Wall locked out or tagged out and the
Mounted impeller has been secured.
Exhaust Fans,
Duct Check for smooth running. Ensure there is
Mounted no noise generated. Check the fan and
Exhaust Fans impeller for unusual accumulation. Clean
as per manufacturer's recommendation
as required.
Check the impeller for build-up of material
or dirt which may cause an imbalance
with resulting undue wear on bearings
and belt drives. Clean as per
manufacturer's recommendation as
required.
D Monthly
Inspection of the rotating assembly must
be made to detect any indication of
weakening of the rotor because of
corrosion, erosion, or metal fatigue.
D Monthly
Any other manufacturer's recommendation
D Monthly
Where applicable check belt tensions
and change worn-out belts D Monthly
Air Curtains. Ensure all the units are clean and free
from dust. D Monthly
Remove the filters and clean thoroughly
and replace. Replace filter if necessary. D Monthly
Ensure the all fixings, bolts, screws etc.
of the units are intact. D Monthly
Ensure all the set-points are appropriate. D Monthly
Equipment Maintenance Works Category of
Maintenance
Works
Frequency
Ensure electrical connections are intact. D Monthly
Any other manufacturer's
recommendation D Monthly
Ductworks Visually inspect for leaks, repair and
report D Monthly
Visually inspect external insulation for
damage and looseness D Monthly
All vapour seals shall be inspected for damage and repair
D Monthly
Flexible connections to be checked for security and damage
D Monthly
Diffusers and grills to be cleaned by soft brush or vacuum
D Monthly
Internal insulation to be visually inspected for looseness and damage
D Monthly
Vacuum clean ductwork where possible D Monthly
Wash all return and supply grilles and
diffusers with mild non-abrasive cleaner .
Do not dirty walls or ceiling whilst cleaning
grilles and diffusers.
D Monthly
2.5.2 GUIDELINES FOR MINIMUM REQUIRED FREQUENCIES
Work Area Frequency I Requirement
Air Handling Units In accordance with the
maintenance schedule above and
Schedule of Prices Bill of quantity-
Maintenance of Air- Conditioning
and Ventilation Installations.
Refer to Maintenance
Works Schedule in item
above
Fan Coil Units In accordance with the
maintenance schedule above and
Schedule of Prices Bill of quantity-
Maintenance of Air- Conditioning
and Ventilation Installations..
Refer to Maintenance
Works Schedule in item
above
Variable Air
Volume (VAV)
In accordance with the
maintenance schedule above and
Schedule of Prices Bill of quantity-
Maintenance of Air- Conditioning
and Ventilation Installations.
Refer to Maintenance
Works Schedule in item
above
Work Area Frequency / Requirement
Variable Refrigerant
Flow (VRF) and
Variable Refrigerant
Volume (VRV)
System indoor units
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Variable Refrigerant
Flow (VRF) and
Variable Refrigerant
Volume (VRV)
System indoor units
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Split-Type Air-
Conditioning Units
(Indoor Units)
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Split-Type Air-
Conditioning Units/
(Outdoor Units)
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Split-Type Air-
Conditioning Units
(Standing)
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Portable Air-
Conditioning In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Work Area Frequency I Requirement
Precision Air-
Conditioning
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Room Air-
Conditioning
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Air-Cooled
Condensing Units In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Chilled Water
pumps
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Propeller Wall
Mounted Exhaust
Fans, Duct
Mounted Axial
Exhaust Fans,
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Air Curtains In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above
Work Area Frequency / Requirement
Duct Works
(including all
types of
diffusers,
weather louvers,
Return Air Grilles)
In accordance with the
maintenance schedule above
and Schedule of Prices Bill of
quantity- Maintenance of Air-
Conditioning and Ventilation
Installations.
Refer to Maintenance Works
Schedule in item above