Introducing the Biggest Breakthrough in Ventilation Since…
Fresh Air…
![Page 2: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/2.jpg)
1972 – First commercialization of cross flow fixed plate energy recovery ventilator
1981 – Lawrence Berkley Labs identifies the advantages of ERV cores for residential ventilation
1983 – RenewAire begins manufacturing ERVs in Madison, Wisconsin – other manufacturers follow with similar unit layouts
![Page 3: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/3.jpg)
1999 – RenewAire’s EV series sets the standard for performance, quality and value
2003 – The breakthrough everyone has been waiting for – dramatically lower installed cost - and only available with Breeze
![Page 4: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/4.jpg)
“Field trials confirm Breeze units install in one-half to one third the time of traditional ERVs.”
![Page 5: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/5.jpg)
What is Breeze?A line of residential ERVs
BR70 70 CFM ERV BR130 130 CFM ERV TW Kits Through-the-Wall duct and
hood kit
Economical and effective ventilation for condominiums, town homes and smaller homes
![Page 6: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/6.jpg)
A New Line of Residential ERV
![Page 7: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/7.jpg)
How is Breeze Different?Mounts to furnace (AC) return air ductworkHas only two duct connections
The other two connections are out the back directly into the RA duct
Has integrated automatic proportional runtime control
Can be mounted to exterior wall with TW Kit requiring only two indoor duct connections
![Page 8: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/8.jpg)
![Page 9: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/9.jpg)
Two Ways to Install ERVs
Central Exhaust – Use EV Series
General Ventilation – Use BR Series
EV Series may be used
![Page 10: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/10.jpg)
Central Exhaust20 CFM continuous per bathroom50 CFM intermittent per bathroom
Must have control in each bathroom served (PB24)
Other possible exhaust locations Kitchen area (cannot exhaust range hood) Utility room, smoking room, hobby room, etc.
![Page 11: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/11.jpg)
EV130 Centrally Ducted
![Page 12: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/12.jpg)
Exhaust From Bathroom
![Page 13: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/13.jpg)
Exhaust From Kitchen
![Page 14: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/14.jpg)
Central Exhaust Con’t
Small ductwork system to collect air from each exhaust location
Fresh air may be supplied to furnace (AC) return air duct
EV130=2 bathrooms, EV200=3 bathrooms, EV300=5 bathrooms
Replaces bathroom exhaust fans
![Page 15: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/15.jpg)
General Ventilation
ERV selected based on size of home and/or number of residents
ASHRAE 62-1998 – 0.35 air changes/hour BR70 = 1500 square feet living space BR130/EV130 = 2700 square feet living space EV200 = 4000 square feet living space EV300 = 6000 square feet living space
![Page 16: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/16.jpg)
General Ventilation Con’t
ERV selected based on size of home and/or number of residents
ASHRAE 62.2-2003 7.5 CFM/occupant (# of bedrooms +1) Plus 0.01 CFM/ square foot of living space Example: 3 bedroom, 1500 sq ft home requires 4
times 7.5=30 CFM plus 1500 times 0.01=15CFM for a total of 45 CFM
![Page 17: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/17.jpg)
General Ventilation Con’t
Bathroom exhaust fans are also requiredAir may be drawn from and supplied to the
furnace (AC) return air duct as long as short circuiting is avoided (by running furnace blower)
The majority of ERV installations are used for General Ventilation most likely due to lower cost
![Page 18: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/18.jpg)
• Cut hole in Return Air Duct – bend flange in.• Mount hanging bracket on duct.
![Page 19: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/19.jpg)
• Mount Hinge Bar in proper location on unit.
![Page 20: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/20.jpg)
• Hang unit on duct.
• Wire Breeze to furnace control.
![Page 21: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/21.jpg)
• Swing Breeze into position and screw in place.
![Page 22: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/22.jpg)
• Locate Fresh Air Hood away from all exhausts.
![Page 23: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/23.jpg)
• Exhaust Hood location is not critical.
![Page 24: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/24.jpg)
• Installation is generally completed in under two hours!
![Page 25: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/25.jpg)
• Neat and Clean!
![Page 26: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/26.jpg)
• Breeze can be mounted on Return Air drop.
![Page 27: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/27.jpg)
• Hole cut.
![Page 28: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/28.jpg)
• Hang and fasten unit to drop.
![Page 29: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/29.jpg)
• Alternate Return Air drop orientation.
![Page 30: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/30.jpg)
Easy InstallationMounted to furnace or AC return air ductwork
Under duct lengthwise Under duct crosswise Side of duct On return drop (with some cautions)
Mounted to exterior wall with thru-the-wall kitMounted to ceiling to conceal two ducts
![Page 31: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/31.jpg)
![Page 32: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/32.jpg)
TW Kit
![Page 33: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/33.jpg)
TW Installation
![Page 34: Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…](https://reader036.vdocuments.site/reader036/viewer/2022062519/56649cb75503460f9497ca09/html5/thumbnails/34.jpg)
Effective, efficient ventilation… made easy!