intrinsic safety
TRANSCRIPT
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare1
Intrinsic
Safety
& Hazardous Areas
by
Steve Mackay
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
EIT Micro-Course Series• Every two weeks we present a 35 to 45
minute interactive course
• Practical, useful with Q & A throughout
• PID loop Tuning / Arc Flash Protection, Functional Safety, Troubleshooting conveyors presented so far
• Upcoming: – Electrical Troubleshooting and much,
much more…..
• Go to:http://www.idc-online.com/slideshare
• You get the recording and slides
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare3
Overall Presentation
The focus of this session is the building blocksof electrical engineering, the fundamentals ofelectrical design and integrating electricalengineering know-how into the other disciplineswithin an organisation.
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare4
ObjectivesThe identification of: Terminology Fundamentals of Ex i Protection
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare5
Ex Protection DefinitionExplosion Protection:
The measures applied in the construction of electrical apparatus to prevent ignition of surrounding explosive atmosphere by such apparatus.
Need to understand: ‘ignition’
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare6
InspectorateInspectorate
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare7
The Fire TriangleThe Fire Triangle
Airwith
21% OxygenFuel
Sufficient Vapour
27.2
!Bang
Source of IgnitionSource of Ignition
O2
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare8
Electricity as a Source of Ignition
Sources of IgnitionSources of Ignition
HeatHeatSparksSparks
Electrical SourcesElectrical Sources
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare9
Spark Ignition Characteristic
(LEL)Lower Explosive Limit
(UEL)Upper Explosive Limit
Minimum Ignition Energy (MIE)
IgnitionEnergy
(milliJoules)
Volumeconcentration (%)
1.0
0.1
0.01 0 10 20 30 40 50 60 70 80 90 100
Flammable Range
Propane-air (1 atmos.)
Most-easily ignitable mixture
Hydrogen-air(1 atmos.)
Ethylene-air(1 atmos.)
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare10
Explosive limits for materials Gas/air mixtures are ignitable over a range of concentrations called the
“Flammable Range”
Material Lower Explosive Limit Upper Explosive Limit Minimum
LEL UELignition
energy*
Propane 2 % 9.5 %180µJ
Ethylene 2.7 % 34 % 60µJ
Hydrogen 4 % 76 % 20µJ
* of most easily ignitable mixture (Note: MESG assessed for Ex d)
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare11
Ignition Temperature Definition
The lowest temperature of a flammable gas or vapour at which ignition occurs.
Ignition Temperature
Sometimes referred to as:
Auto-ignition temperature
Or
Spontaneous ignition temperature
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare12
Flashpoint Definition
The temperature at which the free surface of a liquid emits sufficient vapour to be ignited by a small flame
Flashpoint
Kerosene:Flashpoint = 38°C; Ignition Temp. = 210°C) Only liquids have flashpoints
Operation below Flashpoint constitutes no actual hazard
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare13
Personnel HazardsFor Hydrogen Sulphide, H2S:
a very common danger when dealing with oil products
Property VolumeConcentration
Smell detection level 0.1 ppm
Safe working level 10
Serious health danger level 50
Lower Flammable Limit 40,000 (4%)
Upper Flammable Limit 460,000 (46%)
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare14
Area Classification
Nature of the Hazard
Locations of hazard
Probability of presence
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare15
Requirement for plant classification Plant and Installations
are classified according to:-
The nature of the Hazardous Atmosphere
The probability that the Hazardous Atmosphere will be present
- Gas Classification- Ignition Temperature
- Area Classification
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare16
Requirement for equipment classification
- Apparatus Group
- Temperature Classification
Equipment is classified according to:-
The maximum spark energy it can produce
Its maximum surface temperature
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare17
Gas classification: the two main systems
Representative(Test) gas
Gas classification
IgnitabilityIEC countries(including Europe) USA & Canada
AcetyleneHydrogenEthylenePropane
Methane
Metal dustCarbon dustFlour, starch,Grain
Fibres & Flyings
Group IICGroup IICGroup IIBGroup IIA
Group I(Mining)
(IEC 1241)
(No classification)
Class I, Group AClass I, Group BClass I, Group CClass I, Group D
(No classification)
Class II, Group EClass II, Group FClass II, Group G
Class III
Moreeasilyignited
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare18
Temperature classification (IEC/European)
450°C T1
300°C T2
200°C T3
135°C T4
100°C T5
85°C T6
Temperatureclassification
Maximumsurface
temperature
Tamb = 40oCunless otherwise
stated
Operation abovestated Tamb mayde-rate T Class
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare19
Temperature classification in North America
T1 450
T2 300
T2A 280
T2B 260
T2C 230
T2D 215
T3 200
T3A 180
T3B 165
T3C 160
T4 135
T4A 120
T5 100
T6 85
T class
Apparatus is marked with either T rating or maximum surface temperature
User has responsibility to ensure that the T-rating is below the Spontaneous
Ignition Temperature ( SIT )
°C
Tamb = 40oC
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare20
Gas/Apparatus compatibility Ammonia 630
Gas Ignition Temperature
600
500
400
300
200
100
ApparatusTemperatureClassification
Carbon Disulphide 105
T1T1
T2T2
T4T4
T6T6T5T5
T3T3
Hydrogen 560 Methane 595
Propane 470Ethylene 425
Butane 365
Cyclohexane 259
Diethyl Ether 170
T4 for apparatus is usually OKException:Carbon Disulphide, requiring T5Don't confuse T Class with maximum operating temperature!
TAMB=40oCoC
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare21
Properties of Gases
Extract from IEC79-18
Compound Vapour LFL UFL Ignition T Apparatus Density Temp °C Class Group
AcetoneAmmoniaButaneCarbon DisulphideCyclohexaneDiethyl EtherEthyleneHydrogenKeroseneMethanePropane
2.000.592.052.642.902.550.970.07
0.551.56
2.015 1.5 1.0 1.2 1.7 2.7 4.0 0.7 5.0 2.0
1328 8.560 7.8363475.6 515 9.5
535630365100259170425560210595470
T1T1T2T5T3T4T2T1T3T1T1
IIAIIAIIAIICIIAIIBIIBIICIIAI / IIAIIA
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare22
Area classification in IEC/European countriesAreas classification:
The probability of a potentially explosive atmosphere being present
and
The length of time for which it is likely to exist
Zone 0:
Zone 1:
Zone 2:
in which an explosive gas-air mixture is continuously present or present for long periods
in which an explosive gas-air mixture is likely to occur in normal operation
in which an explosive gas-air mixture is not likely occur in normal operation, and if it occurs it will exist only for a short time
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare23
Area classification in North America
Division 1Hazardous atmosphere is likely to be present in normal operation
Division 2Hazardous atmosphere is unlikely to be present in normal operation
Zone 0:
Zone 1:
Zone 2:
Div.1 Zone 0 sometimes specified
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare24
Area Classification Example
Bund wall
Tank vents
Liquid surface
Area Classificationfor a fixed-roof tank
withheavier than air
vapour
Zone 1
Zone 0
Zone 2
Key
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare25
Typical Area Classification Plan Drawing
T1
T2 T3
T4
IIB T3 Hazard
T1-4Tanks
Zone 2 Radius4.5 metres
Zone 1 Radiusto bund wall2.5 metres
4 Flow ValvesZone 1: in pipetrench 1.75metres wideacross CL
Zone 2: 3 metresacross CL
Boudary
Fence
Name and Location of Company
N
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare26
Thermocouple in a hazardous are
Inside of pipe orprocess vessel
Zone 0Zone 1
Outside of pipe
Zone 2
Division 2
Division 1
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare27
Why Area Classify?Probability of
Gas/Air Mixturebeing present
Probability ofSource ofIgnitionX = Acceptable
Risk
Matched to
Type ofProtection
d, i, q, o, p, m, e, n, s
Zone 0,1,2 Nothing is100% Safe
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare28
Methods of Explosion ProtectionE Technique: IEC Description: Zone: Application:x 79-p Separation (Gas) 2 Pressurisation 1,2 Control rooms, analyserso (Liquid) 6 Oil-filling 2 Transformers switchgearq (Semi-solid) 5 Quartz/Sand 2 Instrumentationm (Solid) 18 Encapsulation 1,2 Instrumentation, control gearn Construction 15 Non-incendive 2 Transformers, switchgeare Construction 7 Increased Safety 1,2 Motors, lighting, boxes (Draft)d Containment 1 Flameproof 1,2 Switchgear, motors, pumpsi Electrical design 11 Intrinsic Safety 0,1,2 Instrumentation, control gears Special Special 0,1,2 Gas detection
0 GeneralRequirements
Ex s Not adoptedZones are ‘permitted Zone of use’
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Intrinsic Safety
Ex i
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Definition of ‘intrinsic’
Intrinsic:“in-built”
or “of its nature”
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Definition
“A circuit in which no spark or thermal effect in any part of
the circuit intended for use in a hazardous area is capable
of causing ignition.”
Intrinsically Safe Circuit
IEC79-11
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
V & I Limiting Network
Current limiting resistor
RCLR
Vinput VZ
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Energy limiting arrangement
Current limiting resistor
VZ
RCLR
HazardousArea
Safe AreaCircuit
FUSE
Vinput
Infallible Components
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Intrinsic safety categories
Intrinsic safety is the only protection concept which considers failure of the field wiring
Ex ia Ex ibIntrinsically safe
withtwo countable faults
Intrinsically safe with
one countable fault
Zones 0, 1 and 2 Zones 1 and 2
Countable Faults: Faults in infallible components
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
System
+
-
RELAY
Hazardous
N LE
Fault 1
Fault 2
Note! Earth Connection
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Current Limiting from C V Supply
SupplySupply
+
-
RelayHazardous
N L E
Barrier
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Component Failure
Current limiting resistor
VZ
RCLR
Hazardous area Safe area
FUSE
Vinput
Infallible Components
Technology Training that worksTechnology Training that Workswww.idc-online.com/slideshare
Thank You For Your Interest