international gas detectors m20 side entry points 104 · 2020. 4. 17. · 420hz 0.625s on/0.625s...
TRANSCRIPT
Ref BEASOU-002
023827
OLIVER IGDTriton House Tel: +44 (0)161 483 1415
COH S2 CO2
SO2NO NO2CH4
International Gas Detectors Crosby StStockportSK2 6SHEngland
Fax: +44 (0) 161 484 2345Email: [email protected]: www.internationalgasdetectors.com
Part Number
Base Colour
Lens Colour
Audibility @ 1M
Tones
Voltage
Sounder Current
Beacon Current
IP Rating
Cable Entries
Temperature
Rating
Frequency
Construction
5083101
Red
Amber
Up to 106 dB
32
17-60V DC
45mA Max
5mA
IP65
2 x 20mm
-25ºC to 70ºC
Continuous
400 to 2850 Hz
Flame Retardant Polycarbonate
Beacon - Sounder PN 5083101 User Instructions
Specifications Physical
Connection Details to 4 Wire Nodes
Connection Details to 2 Wire Nodes
Connection Details General
GND 24V DC
The internal node 24V DC supply is fused at 100mA. This supply is intended for switching piezo sounders and LED low power beacons only.Note the unit requires a permanent 24V DC Supply and individual switched 0V DC for Beacon and Sounder functions
IGD Supplied Beacon Sounder PN 5083101 Draws 11mA in Operation using default settings Allowing a number of Beacon Sounders to be Slaved Together
1 2 3 4IN+ OUT+
1 2 3 4IN+ OUT+
BeaconSounder
BeaconSounder
Typically 3 Core0.5mmSQ CY Cable or FP200Style Cable
This example Relay 1 is Controlling The Beacon Function and Relay 2 The Sounder Function. This Allows The Controller To Be Able to ‘Mute’ Sounders Whilst Leaving Beacons Running.
17 to 60 V DC
Switched 0 V DC
Switched 0 V DC
International Gas Detectors
97.5104
39
28
17
50
M20 Rear Entry Point
M20 Side Entry Points
4.2 Fixings
V+
4-20mA
1 2 3 4IN+ OUT+
BeaconSounderRefer to 2-Wire Installers Guide
For Full Details
Screen all Field Cabling
I-O Port 1I-O Port 2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
970Hz
800Hz/970Hz @ 2Hz
800Hz – 970Hz @ 1Hz
970Hz 1s OFF/1s ON
970Hz, 0.5s/ 630Hz, 0.5s
554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001 )
500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000)
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)
550Hz/440Hz @ 0.5Hz
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 )
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)
1200Hz – 500Hz @ 1Hz (DIN 33 404)
400Hz
550Hz, 0.7s/1000Hz, 0.33s
1500Hz – 2700Hz @ 3Hz
750Hz
2400Hz
660Hz
660Hz 1.8s ON/1.8s OFF
510Hz, 0.25s/ 610Hz, 0.25s
800/1000Hz 0.5s each (1Hz)
250Hz – 1200Hz @ 12Hz
500Hz – 1200Hz @ 0.33Hz
2400Hz – 2900Hz @ 9Hz
2400Hz – 2900Hz @ 3Hz
800Hz – 970Hz @ 100Hz
800Hz – 970Hz @ 9Hz
800Hz – 970Hz @ 3Hz
800Hz, 0.25s ON/1s OFF
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
O - O - O - O - O
O - O - O - O - I
O - O - O - I - O
O - O - O - I - I
O - O - I - O - O
O - O - I - O - I
O - O - I - I - O
O - O - I - I - I
O - I - O - O - O
O - I - O - O - I
O - I - O - I - O
O - I - O - I - I
O - I - I - O - O
O - I - I - O - I
O - I - I - I - O
O - I - I - I - I
I - O - O - O - O
I - O - O - O - I
I - O - O - I - O
I - O - O - I - I
I - O - I - O - I
I - O - I - I - O
I - O - I - I - I
I - I - O - O - O
I - I - O - O - I
I - I - O - I - O
I - I - O - I - I
I - I - I - O - O
I - I - I - O - I
I - I - I - I - O
I - I - I - I - I
99
100
100
99
99
97
99
96
98
97
98
94
99
95
98
104
99
106
96
96
98
100
98
99
101
104
100
99
100
99
99
21
20
20
14
19
13
16
9
10
14
12
21
17
13
17
34
18
45
17
12
15
21
13
17
40
40
20
20
20
8
17
Tone Selection
Installation
Tone Tone Type Tone Description - Application DIP Switch dB @ 1M mA
Locking Screw
Gas Alarm Legend
If required the beacon sounder can be locked to its base
using its locking screw.The O ring supplied must be fitted and suitable glands
fitted to achieve IP65 Sealing.A separate earth terminal is provided for the continuous
connection of screens or functional earthing‘Gas Alarm’ legends are provided as standard and are
fitted using the beacon sounder fixings.
The default setting minimises power requirements for addressable installations. Check power usagebefore making changes that could affect system operation
Beacon - Sounder PN 5083101 User Instructions
International Gas Detectors
21. 660Hz 0.15s ON/0.15s OFF I - O - I - O - O 96 11 Default