international gas detectors m20 side entry points 104 · 2020. 4. 17. · 420hz 0.625s on/0.625s...

2
Ref BEASOU-002 023827 OLIVER IGD Triton House Tel: +44(0)161 483 1415 CO HS 2 CO2 SO2 NO NO2 CH4 International Gas Detectors Crosby St Stockport SK2 6SH England Fax: +44 (0) 161 484 2345 Email: [email protected] Website: www.internationalgasdetectors.com Part Number Base Colour Lens Colour Audibility @ 1M Tones Voltage Sounder Current Beacon Current IP Rating Cable Entries Temperature Rating Frequency Construction 5083101 Red Amber Up to 106 dB 32 17-60V DC 45mA Max 5mA IP65 2 x 20mm -25ºC to 70ºC Continuous 400 to 2850 Hz Flame Retardant Polycarbonate Beacon - Sounder PN 5083101 User Instructions Specifications Physical Connection Details to 4 Wire Nodes Connection Details to 2 Wire Nodes Connection Details General GND 24V DC The internal node 24V DC supply is fused at 100mA. This supply is intended for switching piezo sounders and LED low power beacons only. Note the unit requires a permanent 24V DC Supply and individual switched 0V DC for Beacon and Sounder functions IGD Supplied Beacon Sounder PN 5083101 Draws 11mA in Operation using default settings Allowing a number of Beacon Sounders to be Slaved Together 1 2 3 4 IN+ OUT+ 1 2 3 4 IN+ OUT+ Beacon Sounder Beacon Sounder Typically 3 Core 0.5mmSQ CY Cable or FP200 Style Cable This example Relay 1 is Controlling The Beacon Function and Relay 2 The Sounder Function. This Allows The Controller To Be Able to ‘Mute’ Sounders Whilst Leaving Beacons Running. 17 to 60 V DC Switched 0 V DC Switched 0 V DC International Gas Detectors 97.5 104 39 28 17 50 M20 Rear Entry Point M20 Side Entry Points 4.2 Fixings V+ 4-20mA 1 2 3 4 IN+ OUT+ Beacon Sounder Refer to 2-Wire Installers Guide For Full Details Screen all Field Cabling I-O Port 1 I-O Port 2

Upload: others

Post on 21-Apr-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: International Gas Detectors M20 Side Entry Points 104 · 2020. 4. 17. · 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670

Ref BEASOU-002

023827

OLIVER IGDTriton House Tel: +44 (0)161 483 1415

COH S2 CO2

SO2NO NO2CH4

International Gas Detectors Crosby StStockportSK2 6SHEngland

Fax: +44 (0) 161 484 2345Email: [email protected]: www.internationalgasdetectors.com

Part Number

Base Colour

Lens Colour

Audibility @ 1M

Tones

Voltage

Sounder Current

Beacon Current

IP Rating

Cable Entries

Temperature

Rating

Frequency

Construction

5083101

Red

Amber

Up to 106 dB

32

17-60V DC

45mA Max

5mA

IP65

2 x 20mm

-25ºC to 70ºC

Continuous

400 to 2850 Hz

Flame Retardant Polycarbonate

Beacon - Sounder PN 5083101 User Instructions

Specifications Physical

Connection Details to 4 Wire Nodes

Connection Details to 2 Wire Nodes

Connection Details General

GND 24V DC

The internal node 24V DC supply is fused at 100mA. This supply is intended for switching piezo sounders and LED low power beacons only.Note the unit requires a permanent 24V DC Supply and individual switched 0V DC for Beacon and Sounder functions

IGD Supplied Beacon Sounder PN 5083101 Draws 11mA in Operation using default settings Allowing a number of Beacon Sounders to be Slaved Together

1 2 3 4IN+ OUT+

1 2 3 4IN+ OUT+

BeaconSounder

BeaconSounder

Typically 3 Core0.5mmSQ CY Cable or FP200Style Cable

This example Relay 1 is Controlling The Beacon Function and Relay 2 The Sounder Function. This Allows The Controller To Be Able to ‘Mute’ Sounders Whilst Leaving Beacons Running.

17 to 60 V DC

Switched 0 V DC

Switched 0 V DC

International Gas Detectors

97.5104

39

28

17

50

M20 Rear Entry Point

M20 Side Entry Points

4.2 Fixings

V+

4-20mA

1 2 3 4IN+ OUT+

BeaconSounderRefer to 2-Wire Installers Guide

For Full Details

Screen all Field Cabling

I-O Port 1I-O Port 2

Page 2: International Gas Detectors M20 Side Entry Points 104 · 2020. 4. 17. · 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

970Hz

800Hz/970Hz @ 2Hz

800Hz – 970Hz @ 1Hz

970Hz 1s OFF/1s ON

970Hz, 0.5s/ 630Hz, 0.5s

554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001 )

500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000)

420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)

500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)

550Hz/440Hz @ 0.5Hz

970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 )

2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)

1200Hz – 500Hz @ 1Hz (DIN 33 404)

400Hz

550Hz, 0.7s/1000Hz, 0.33s

1500Hz – 2700Hz @ 3Hz

750Hz

2400Hz

660Hz

660Hz 1.8s ON/1.8s OFF

510Hz, 0.25s/ 610Hz, 0.25s

800/1000Hz 0.5s each (1Hz)

250Hz – 1200Hz @ 12Hz

500Hz – 1200Hz @ 0.33Hz

2400Hz – 2900Hz @ 9Hz

2400Hz – 2900Hz @ 3Hz

800Hz – 970Hz @ 100Hz

800Hz – 970Hz @ 9Hz

800Hz – 970Hz @ 3Hz

800Hz, 0.25s ON/1s OFF

500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)

O - O - O - O - O

O - O - O - O - I

O - O - O - I - O

O - O - O - I - I

O - O - I - O - O

O - O - I - O - I

O - O - I - I - O

O - O - I - I - I

O - I - O - O - O

O - I - O - O - I

O - I - O - I - O

O - I - O - I - I

O - I - I - O - O

O - I - I - O - I

O - I - I - I - O

O - I - I - I - I

I - O - O - O - O

I - O - O - O - I

I - O - O - I - O

I - O - O - I - I

I - O - I - O - I

I - O - I - I - O

I - O - I - I - I

I - I - O - O - O

I - I - O - O - I

I - I - O - I - O

I - I - O - I - I

I - I - I - O - O

I - I - I - O - I

I - I - I - I - O

I - I - I - I - I

99

100

100

99

99

97

99

96

98

97

98

94

99

95

98

104

99

106

96

96

98

100

98

99

101

104

100

99

100

99

99

21

20

20

14

19

13

16

9

10

14

12

21

17

13

17

34

18

45

17

12

15

21

13

17

40

40

20

20

20

8

17

Tone Selection

Installation

Tone Tone Type Tone Description - Application DIP Switch dB @ 1M mA

Locking Screw

Gas Alarm Legend

If required the beacon sounder can be locked to its base

using its locking screw.The O ring supplied must be fitted and suitable glands

fitted to achieve IP65 Sealing.A separate earth terminal is provided for the continuous

connection of screens or functional earthing‘Gas Alarm’ legends are provided as standard and are

fitted using the beacon sounder fixings.

The default setting minimises power requirements for addressable installations. Check power usagebefore making changes that could affect system operation

Beacon - Sounder PN 5083101 User Instructions

International Gas Detectors

21. 660Hz 0.15s ON/0.15s OFF I - O - I - O - O 96 11 Default