Internal Partition Unbraced Twin WallDetails

Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952 581 150 F: 01952 585 147 E: [email protected] www.librasystemsuk.com

Page 2: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

Contents

Metal Stud Partition System (Unbraced Twin Walls)

ML/TYP/080ML/TYP/081ML/TYP/082ML/TYP/083ML/TYP/084ML/TYP/085ML/TYP/086 ML/TYP/087 ML/TYP/088ML/TYP/089ML/TYP/090

30 / 60 minute 15 ‐ 25mm deflection head

90 / 120 minute 15 - 25mm deflection headbase detail

internal and external corner

abutment detail

T junction

horizontal joint ‐ options 1 & 2

heavy / severe door opening ‐ elevation

heavy / severe door opening - section AAdoor head restraint letter box opening over door head

Page 3: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

APR (as per 

specification) 

mechanically fixed 

at the head

15 ‐ 25mm

15 ‐ 25mm

15 ‐ 25mm

30 / 60 minute 15 ‐ 25mm deflection head

uppermost 

board fixing

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

ML/TYP/080

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017

minimum 200mm

unbraced twinwall partition

plasterboard dropped soffits formed from 2 x 15mm 

plasterboard

Libra DC channel fixed to soffit at 

maximum 600mm centres

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

max 150mm

Libra I studs at 

600mm centres

lining boards as per 

specification

Libra flat plate ‐ option 

1 (inserted between 

layers)

Libra flat plate 

option 2 (fixed to 

face of studs with 

2no wafer head 

screws

firestrip or intumescent 

mastic mastic seals

Page 4: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

mastic sealsdeflection head filled with 

mineral wool insulation 

33kg/m3

unbraced twinwall partition

90 / 120 minute 15 ‐ 25mm deflection head

firestrip or intumescent 

masticplasterboard dropped soffits formed 

from 2 x 15mm impact boards

Libra DC channel fixed to soffit at 

maximum 600mm centres

Libra 25mm x 50mm angle fixed 

to the soffit at 600mm centres

max 150mm

15 ‐ 25mm

15 ‐ 25mm

15 ‐ 25mm

uppermost 

board fixing

Libra flat plate 

option 2 (fixed to 

face of studs with 

2no wafer head 

screws

Libra flat plate ‐ option 

1 (inserted between 

layers)

APR (as per 

specification) 

mechanically fixed 

at the headImpact boards as per 

specificationLibra I studs at 

600mm centres

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

minimum 200mm

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

01/03/2017 ML/TYP/081

for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects.

Page 5: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

ML/TYP/082

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

Libra standard 

channels fixed to 

floor at maximum 

600mm centres

mastic seals

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

gaps over 5mm to be bulk filled with a 

gypsum based product

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

lining boards as per 

specification

APR (as per 

specification) 

mechanically fixed 

at the head

Libra I studs at 

600mm centres

unbraced twinwall partition

base detail

minimum 200mm

Page 6: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

APR (as per 

specification) 

mechanically fixed 

at the head

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

mastic seal

ML/TYP/083

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017

minimum 200mm

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

lining boards as per 

specification

Libra I studs at 

600mm centres

unbraced twinwall partition

internal and external corner Libra standard 

channels fixed to 

structural floor at 

600mm centres

Libra C studs fixed 

together at 

maximum 600mm 

centres

Page 7: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/084

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centresminimum 200mm

Libra standard channel 

fixed to the structural 

floor at maximum 

600mm centres

Libra I studs at 

600mm centres

Libra C studs fixed at 

maximum 600mm 

centres

lining boards as per 

specification

APR (as per 

specification) 

mechanically fixed 

at the head

mastic seals

unbraced twinwall partition

abutment detail

Page 8: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

Libra I studs at 

600mm centres

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/085

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

mastic seal

Libra I studs at 

600mm centres

Libra standard 

channels fixed to 

structural floor at 

600mm centres

lining boards as per 

specificationLibra C studs fixed 

together at 

maximum 600mm 

centres

unbraced twinwall partition

T junction

minimum 200mm

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

APR (as per 

specification) 

mechanically 

fixed at the head

Page 9: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/086

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

APR (as per 

specification) 

mechanically 

fixed at the head

lining boards as per 

specification

horizontal joint ‐ 

option 2

Libra flat plate 

(fixed to face of 

studs with 2no 

wafer head 

screws

Libra flat plate (inserted 

between layers)

Libra I studs at 

600mm centres

horizontal joint ‐ 

option 1

unbraced twinwall partition

horizontal joint ‐ options 1 & 2

minimum 200mm

Page 10: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/087

A

Libra standard 

channels fixed to 

structural floor at 

600mm centresadditional pair of 

fixings 150mm 

from door opening300mm

Libra floor channel cut, bent and 

fixed to the door stud

Libra flat plate installed below 

deflection head150mm

Libra C studs as per 

specification

lining boards continued 

around opening 

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

A

Door weights up to 

60kg

no fixings into deflection head

unbraced twinwall partition deflection head detail fixed to soffit at 

600mm centresheavy / severe door opening ‐ elevation

600mm centres maintained over opening

Page 11: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/088

Libra floor channel 

cut, bent and fixed 

to the door stud

Libra standard 

channels fixed to 

structural floor at 

600mm centres

additional pair of 

fixings 150mm 

from door opening

Libra I studs fixed at 

600mm centres

lining boards fixed to their entire 

perimeter to partition framing 

with drywall screws at maximum 

300mm centres

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

APR (as per 

specification) 

mechanically 

fixed at the 

head

unbraced twinwall partition

heavy / severe door opening ‐ section AA

Libra C stud with softwood 

timber insert to provide fixing 

ground for the door lining

lining boards (and Plywood 

where applicable) as per 

specification

Page 12: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

ML/TYP/089

unbraced twinwall partition

deflection head boards as 

per specification

crimps or wafer head screws

minimum 150mm

no fixingsoffcuts of Libra C stud fixed into 

deflection head channel to trap door 

studs and prevent twisting or horizontal 

movement

Libra DC channel

Libra door stud

door head restraint (deflection heads)

Page 13: Internal Partition Unbraced Twin Wall Details · 2019. 5. 7. · Internal Partition Unbraced Twin Wall Details. Unit E, Halesfield 10, Telford, Shropshire TF7 4QP England T: 01952

we would draw your attention to the Construction (Design and Management) Regulations 1994 and the Approved Code of 

Practice which detail the legal duties of clients, client's agents designers and contractors involved in construction projects. for discussion purposes only / do not scale

project:

Typical Detail

initials: date: drg no:

ML 01/03/2017 ML/TYP/090

Notes: This drawing should be read in conjunction with the relevant sections of the manufacturers current product literature

unbraced twinwall partitionmineral wool fire batt

Libra flat plate 

twice fixed to each 

stud

letterbox opening over door head

ensure all gaps are sealed to 

prevent the passage of hot gasses

no fixings or 

crimps to 

deflection head 

channel

opening lined with the same spec 

plasterboard as wall linings

section of Libra 

channel fixed to 

door head channel

Libra channel cut, bent and 

twice fixed to nearest full 

height studs

min 150mm

Libra studs as per 

specification, set out for 

board edges