S&C IntelliLink ® Remote Setup Software Instruction Sheet 1032-500 © S&C Electric Company 2013-2017, all rights reserved August 28, 2017 Section Page Section Page Introduction Overview 2 Qualified Persons 2 Read this Instruction Sheet 3 Retain this Instruction Sheet 3 Special Warranty Provisions 3 Warranty Qualifications 3 End User License Agreement 3 Safety Information Understanding Safety-Alert Messages 4 Following Safety Instructions 4 Replacement Instructions and Labels 4 License Key for IntelliLink 5 and Below IntelliRupter ® PulseCloser ® Fault Interrupter Software 5 Other S&C Automatic Control Software 6 Installing an IntelliLink 6 Activation File IntelliLink Remote License Activation 7 Installing a License Activation File 8 Using IntelliLink Remote Setup Software Connecting to an IntelliRupter Fault Interrupter 10 Serial Connection to a 6800 Series Control 10 Connecting to a DNP Network Entry Point 11 Connecting Via DNP 12 Configuring IntelliLink Remote Setup Software Setting Screen Refresh Options 15 Setting Security Options for Legacy Products 16 Security Options Setup 17 Remote Operation IntelliRupter Fault Interrupter Operation 17 Table of Contents Installation

Upload: dinhbao

Post on 14-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

S&C IntelliLink® Remote Setup Software

Instruction Sheet 1032-500© S&C Electric Company 2013-2017, all rights reservedAugust 28, 2017

Section Page Section Page

IntroductionOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . 3Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . 3Special Warranty Provisions . . . . . . . . . . . . . . . . . . . . . . 3Warranty Qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . 3End User License Agreement . . . . . . . . . . . . . . . . . . . . . 3

Safety InformationUnderstanding Safety-Alert Messages . . . . . . . . . . . . . . 4Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . 4Replacement Instructions and Labels . . . . . . . . . . . . . . . 4

License Key for IntelliLink 5 and BelowIntelliRupter® PulseCloser® Fault Interrupter Software . . 5Other S&C Automatic Control Software . . . . . . . . . . . . . 6

Installing an IntelliLink 6 Activation FileIntelliLink Remote License Activation . . . . . . . . . . . . . . . 7Installing a License Activation File . . . . . . . . . . . . . . . . . 8

Using IntelliLink Remote Setup SoftwareConnecting to an IntelliRupter Fault Interrupter . . . . . . 10Serial Connection to a 6800 Series Control . . . . . . . . . 10Connecting to a DNP Network Entry Point . . . . . . . . . . 11 Connecting Via DNP . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Configuring IntelliLink Remote Setup SoftwareSetting Screen Refresh Options . . . . . . . . . . . . . . . . . . 15 Setting Security Options for Legacy Products . . . . . . . . 16Security Options Setup . . . . . . . . . . . . . . . . . . . . . . . . . 17

Remote OperationIntelliRupter Fault Interrupter Operation . . . . . . . . . . . . 17

Table of Contents

Installation

2 S&C Instruction Sheet 1032-500

Introduction

With S&C IntelliLink Remote Setup Software, you can access every S&C automation product that communicates using the DNP 3.0 protocol remotely from a computer connected to your DNP network. You will be able to configure controls, access historical and real-time data, and troubleshoot equipment. Optional password protection can be activated to prevent unauthorized use of IntelliLink Remote software.

To activate IntelliLink Remote software, you need to download a software license from the S&C Automation Customer Support Portal. S&C automation controls with software revision 3.4.x and lower register the version 5.0 of IntelliLInk Remote software with a license key. Controls with software revision 3.5.x and above register the version 6.0 of IntelliLink Remote software by registering the MAC address of the computer onto which the IntelliLink Remote software is installed. Contact your local S&C Sales Office for more information.

IntelliLink Remote software communicates with the following S&C products operating under the DNP 3 protocol:

• IntelliRupter® PulseCloser® Fault Interrupters

• 5800 Series and 6800 Series Automatic Switch Controls

• 6801M Automatic Switch Operators

• IntelliNode™ Interface Modules and Universal Interface Modules

• M Series® Switch Operators

• Model 4801 Remote Switch Controls

• BankGuard Plus® Controls

• IntelliCap® Plus and IntelliCap® 2000 Automatic Capacitor Controls

• Superseded EnergyLine® 1000 Series Capacitor Controls

• Superseded EnergyLine® 2851 and 2852 Automatic Switch Controls

NOTICE

The IntelliLink software will work with a specific type of S&C control only if it is configured for that type of control . In particular, an appropriate screenset must be installed for each control type with which you want to be able to communicate . A screenset is essentially a definition of product-specific user interface screens designed for a particular type of control . IntelliLink screensets are normally installed as part of the S&C product-installation procedure . They provide the user with a product-specific graphical interface for interacting with S&C controls .

NOTICE

The latest software version 7 .1 .x can run on any PC that has Microsoft Windows 7 or Windows 10 . It requires Microsoft .Net Framework 4 .5 on Windows 7 and Windows 10 . Please confirm that these requirements are met before running the installation .

WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and main-tenance of overhead electric power distribution equipment along with the associated hazards . A qualified person is one who is trained and competent in:

• The skills and techniques necessary to distinguish exposed live parts from nonlive parts of electrical equipment .

• The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed .

• The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment .

These instructions are intended only for such qualified persons . They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment .

Qualified Persons

Overview

S&C Instruction Sheet 1032-500 3

Read this instruction sheet thoroughly and carefully before installing or operating your S&C IntelliLink Remote Setup Software. Familiarize yourself with the Safety Information section on page 4. The latest version of this publication is available online in PDF format at sandc.com/en/support/product-literature/ .

This instruction sheet is a permanent part of your S&C automation product installation. Designate a location where you can easily retrieve and refer to this publication.

Read this Instruction Sheet

Retain this Instruction Sheet

Special Warranty Provisions

Introduction

The standard warranty contained in S&C’s standard conditions of sale, as set forth in Price Sheet 150, applies to S&C IntelliLink Remote Setup Software. The first paragraph of said warranty is replaced by the following:

(1) General: The seller warrants to the immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract description and will be free of defects of workmanship and material. Should any failure to conform to this warranty appear under proper and normal use within 10 years after the date of shipment, the seller agrees, upon prompt notification thereof and confirmation that the equipment has been stored, installed, operated, and maintained in accordance with recommendations of the seller and standard industry practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at the seller’s option) by shipment of necessary replacement parts. The seller’s warranty does not apply to any equipment that has been disassembled, repaired, or altered by anyone other than the seller. This limited warranty is granted only to the immediate purchaser or, if the equipment is purchased by a third party for installation in third-party equipment, the end user of the equipment. The seller’s duty to perform under any warranty may be delayed, at the seller’s sole option, until the seller has been paid in full for all goods purchased by the immediate purchaser. No such delay shall extend the warranty period.

The seller further warrants to the immediate purchaser or end user that for a period of two years from the date of shipment the software will perform substantially in accordance with the then-current release of specifications if properly used in accordance with the procedures described in the seller’s instructions. The seller’s liability regarding any of the software is expressly limited to exercising its reasonable efforts in supplying or replacing any media found to be physically defective or in correcting defects in the software during the warranty period. The seller does not warrant the use of the Software will be uninter-rupted or error-free

Warranty of S&C IntelliLink Remote Setup Software is contingent upon the installation, configuration, and use of the control or software in accordance with S&C’s applicable instruction sheets. This warranty does not apply to major components not of S&C manufacture, such as batteries, communication devices, and remote terminal units. However, S&C will assign to the immediate purchaser or end user all manufacturers’ warranties that apply to such major components.

The end user is granted a nontransferable, non-sublicensable, nonexclusive license to use the LinkStart Connection Management Software, IntelliLink Remote Setup Software, IntelliTeam® Automatic Restoration software, and/or other software furnished with the IntelliTeam® SG Automatic Restoration System only upon acceptance of all the terms and conditions of the seller’s end user license agreement set forth in Price Sheet 155.

Warranty Qualifications

End User License Agreement

4 S&C Instruction Sheet 1032-500

Safety Information

Understanding Safety-Alert Messages

Following Safety Instructions

Replacement Instructions and Labels

Several types of safety-alert messages may appear throughout this instruction sheet and on labels and tags attached to the S&C IntelliLink Remote Setup Software. Familiarize yourself with these types of messages and the importance of these various signal words:

DANGER

“DANGER” identifies the most serious and immediate hazards that will likely result in serious personal injury or death if in structions, including recommended precautions, are not followed .

WARNING

“WARNING” identifies hazards or unsafe practices that can re sult in serious personal injury or death if instructions, including recommended precautions, are not followed .

CAUTION

“CAUTION” identifies hazards or unsafe practices that can result in minor personal injury if instruc tions, including recommended precautions, are not followed .

NOTICE“NOTICE” identifies important procedures or requirements that, if not followed, can result in product or property damage if instruc tions are not followed .

If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Autho rized Distributor, or call S&C Headquarters at (888) 762-1100 (answered 24/7). (In Canada, call S&C Electric Canada Ltd. at (416) 249-9171, Monday through Friday between 8 a.m. and 5 p.m. Eastern Standard Time.)

NOTICE

Read this instruction sheet thoroughly and carefully before installing and op erating your S&C IntelliLink Remote Setup Software .

If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Head quarters, or S&C Electric Canada Ltd.

It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distrib utor, S&C Headquarters, or S&C Electric Canada Ltd.

S&C Instruction Sheet 1032-500 5

License Key for IntelliLink 5 and Below

The IntelliRupter software installer for software versions below 3.5.x also installs the correct version of the IntelliLink Setup Software for IntelliRupter fault interrupters. IntelliLink Remote functionality is built into all IntelliLink software, but is not available until activated with a license key. Follow these steps to enter the license key and activate IntelliLink Remote functionality. If you also operate other S&C controls, use the instructions on page 6 to enable IntelliLink Remote functionality for these devices.

STEP 1. Obtain a license key from S&C Electric Company. Contact the S&C Global Monitoring Support Center, [email protected], or call (888) 762-1100.

STEP 2. Open Windows Explorer, and go to the C:\Program Files\S&C Electric\ IntelliLink screen. Look for the program OptionSetup.exe.

STEP 3. To enable IntelliLink Remote functionality, run OptionSetup.exe. Open the Options Setup program by double-clicking it. If you are using Windows® 7, right-click on OptionsSetup.exe entry and select the Run as administrator option. (If you double-click, it will not activate the license key and will return an error.) When the Option Setup dialog box opens, enter the license key supplied by S&C (the entry is case-sensitive), and click on the Activate button. See Figure 1.

You start the IntelliLink software by selecting the Start button>Programs>S&C Electric>IntelliLink. See Figure 2. If IntelliLink Remote software has been activated, the dialog box that opens will give you the choice to select the Remote Connection option. See Figure 3.

Figure 2. Selection path to IntelliLink software from the desktop Start button.

Figure 3. The Remote Connection button starts an IntelliLink Remote session and is available when the IntelliLink Setup Software starts after the IntelliLink Remote Software has been enabled. The Remote Connection button starts the IntelliLink Remote Software session.

IntelliRupter® PulseCloser® Fault Interrupter Software

Figure 1. Option Setup dialog box for entering your software license key.

6 S&C Instruction Sheet 1032-500

License Key for IntelliLink 5 and Below

S&C software installers also install the correct version of the IntelliLink Setup Software. IntelliLink Remote functionality is built into all IntelliLink software but is not available until activated with a license key. For software versions below 3.5.x, follow these steps to enter the license key and activate IntelliLink Remote functionality. If you also operate IntelliRupter® fault interrupters, use the instructions on page 5 to enable IntelliLink Remote functionality for these devices.

STEP 1. Obtain a license key from S&C Electric Company. Contact the S&C Global Monitoring Support Center, [email protected], or call (888) 762-1100.

STEP 2. Open Windows Explorer, and go to the C:\ELine folder or the folder where you have installed your S&C software. Look for the program OptionSetup.exe. If it is listed, proceed to Step 4 to enter your IntelliLink Remote license key.

If OptionSetup.exe is not listed, you will need to upgrade your version of IntelliLink software. To upgrade, go to the S&C Automation Customer Support Portal★, open the IntelliLink Update Utility folder located in the IntelliLink Soft-ware workspace. Download the program ILUpdatennn.exe to your computer. Run this program and install the software in the folder on your hard drive where you have installed IntelliLink software (c:\ELine is the default). The ILUpdatennn.exe program will update the IntelliLink software to the most recent revision and install the program OptionSetup.exe on your hard drive.

NOTICEWhen very old S&C product software is installed on your computer, the IntelliLink soft-ware may not start after having been updated with the ILUpdate326.exe program . Contact S&C Electric Company at (888) 762-1100 to resolve this problem .

STEP 3. To enable IntelliLink Remote functionality, run the OptionSetup.exe utility in your C:\ELine folder (or the folder where you have installed IntelliLink software). Open the OptionsSetup.exe program by double-clicking on it. If you are using Windows® 7, right-click on the OptionsSetup.exe option and select the Run as administrator option. (If you double-click, it will not activate the license key and will return an error.) When the Option Setup dialog box appears, enter the license key supplied by S&C (the entry is case-sensitive), and click on the Activate button. See Figure 4.

NOTICEIf a license key was activated for products other than an IntelliRupter fault interrupter and the IntelliNode™ Interface Module, installing IntelliRupter fault interrupter or IntelliNode software will require re-activation of the IntelliLink Remote Software license key .

★ The S&C Automation Customer Support Portal is a password-protected online library of software and documen-tation for S&C automation products and is accessible from the S&C website: sandc.com at the Support tab . To obtain your User ID and password for the portal, submit the online password request form .

Figure 4. Option Setup dialog box for entering your software license key.

Other S&C Automatic Control Software

S&C Instruction Sheet 1032-500 7

Installing an IntelliLink 6 Activation File

NOTICEIf you are already using IntelliLink Remote software, you need to obtain a License Acti-vation File to enable the IntelliLink Remote software for S&C controls using Software versions 3 .5 .x and above . If you are using IntelliLink Remote software with the IntelliCap® Plus Automatic Capacitor Control or any other products with older software versions in conjunction with products using software versions 3 .5 .x and above, you need to use both the IntelliLink Remote software license key and an activation file .

You need an account on the S&C Automation Customer Support Portal to obtain a license activation file used with software versions 3.5.x or above. If you do not have an account, use this link to request a password: sandc.com/en/support/sc-customer-portal/.

Register the computers that will use Intell iLink Remote software with the M AC add ress for the Loca l A rea Ethernet adapter. The M AC add ress can be obtained by entering “ipconfig/all” in the command prompt. Make sure you use the MAC address for the onboard physical Ethernet adapter and not the add-on or wireless adapter. If you are unfamiliar with the command prompt, you can download the CheckMacAddress.exe utility from the “IntelliTeam SG Software” workspace on the S&C Automation Customer Support Portal. See Figure 5. When you have the MAC address, send an email to [email protected] with the name of the company that owns the IntelliLink Remote License, the name of the primary computer user, and the computer user’s email address and phone number. To see whether your computer has already been registered, select the Licensing tab to view a list of computers registered to your account. Look for the designation “IntelliLink Remote” next to the computer’s MAC address.

IntelliLink Remote License Activation

Then, download and save your license activation file ActivationFile.xml, as directed in the “Installing a License Activation File” section on page 8. You will receive an email notification that your activation file is ready. Then, you log in to your S&C Automation Customer Support Portal account and follow the instructions on page 8. After you have installed your S&C control software version 3.5.x or above and saved your license activation file, you can use IntelliLink Remote software with S&C products.

Figure 5. IntelliTeam SG Software workspace on the S&C Automation Customer Support Portal.

8 S&C Instruction Sheet 1032-500

To install your license activation file, follow these steps:

STEP 1. Go to sandc.com, click on the Support tab, and then click on S&C Automation Customer Support Portal in the left column. Enter your username and password to gain access.

STEP 2. Select the Licensing tab and verify you have a valid license association and the correct MAC address for your computer.

STEP 3. Select the Activation File tab. This generates a new license activation file with the present information displayed at the Licensing tab. The File Download dialog box will open.

STEP 4. Click on the Save button and the Save As dialog box will open, save the file ActivationFile.xml on your desktop.

STEP 5. Copy ActivationFile.xml, and paste it in the folder(s) shown on page 9. The username is your name as registered for your computer. Note that AppData is a hidden system file and will need to be exposed for this step.

STEP 6. In Windows File Explorer, select Tools>Folder options… to access the Folder Options dialog box. See Figure 6.

STEP 7. On the View tab select Show hidden files, folders, and drives to expose the AppData folder. See Figure 7.

Installing a License Activation File

Figure 6. Windows File Explore Tools > Folder options.

Figure 7. Windows Folder Options dialog box.

Installing an IntelliLink 6 Activation File

S&C Instruction Sheet 1032-500 9

For Windows 7, Windows 8, and Windows 10, save the ActivationFile.xml at:

(for 32 bit) C:\Program Files\S&C Electric\IntelliLink6 and

C:\Program Files\S&C Electric\IntelliTeam Designer

(for 64 bit) C:\Program Files (x86)\S&C Electric\IntelliLink6 and

C:\Program Files (x86)\S&C Electric\IntelliTeam Designer

or, if you do not have administrative privilege, save the ActivationFile.xml at:

C:\Users\username\AppData\Local\S&C Electric

For Windows XP, save the ActivationFile.xml at:

(for 32 bit) C:\Program Files\S&C Electric\IntelliLink6 and

C:\Program Files\S&C Electric\IntelliTeam Designer

(for 64 bit) C:\Program Files (x86)\S&C Electric\IntelliLink6 and

C:\Program Files (x86)\S&C Electric\IntelliTeam Designer

or, if you do not have administrative privilege, save the ActivationFile.xml at:

C:\Documents and Settings\username\Local Settings\Application Data\S&C Electric

For Windows 2008 Server R2, save the ActivationFile.xml at:

(for 32 bit) C:\Program Files\S&C Electric\IntelliLink6 and

C:\Program Files\S&C Electric\IntelliTeam Designer

(for 64 bit) C:\Program Files (x86)\S&C Electric\IntelliLink6 and

C:\Program Files (x86)\S&C Electric\IntelliTeam Designer

or, if you do not have administrative privilege, save ActivationFile.xml at:

C:\Users\username\AppData\Local\S&C Electric

To enable one activation file for many users for Windows 7, Windows 8, Windows 10 and Windows 2008 Server R2, save the ActivationFile.xml at:

C:\Users\Public\PublicDocuments\S&C Electric

Note: The new multi-user directory is only supported by version 6.0 of the IntelliLink software, revision 608.8 and later.

Installing an IntelliLink 6 Activation File

10 S&C Instruction Sheet 1032-500

Using IntelliLink Remote Setup Software

When you connect to an IntelliRupter fault interrupter with the Wi-Fi link, the IntelliRupter fault interrupter does not function as a DNP network entry point. You can configure that IntelliRupter fault interrupter, but you cannot use IntelliLink Remote software to connect to other IntelliRupter fault interrupters or S&C controls.

With an all IntelliRupter system, your computer will be connected to a gateway or headend radio for IntelliLink Remote software access to the DNP network. See Figure 8. Then, you can connect to a specific IntelliRupter fault interrupter or other S&C control, by entering its DNP address.

Connecting to an IntelliRupter Fault Interrupter

Serial Connection to a 6800 Series Control

S&C IntelliLink Remote software can be used with a variety of S&C controls.

Figure 9 on page 11 shows a computer connected to the SCADA communication port of a 6800 Series Automatic Switch Control. An S&C serial-to-SCADA port cable is required, catalog number 07-001355-01. The serial link to the SCADA port can also be sent over a fiber-optic transceiver, point-to-point radio, or modem. Your computer must have a DNP address registered with the S&C controls it will contact through IntelliLink Remote software.

The 6800 Series Automatic Switch Control is the DNP router, sending messages through its other SCADA port to its DNP radio, which communicates with the other S&C controls. With this setup, you can configure and troubleshoot all your DNP controls by connecting to one control. You do not affect this control’s participation in an IntelliTeam® Automatic Restoration System, and its team does not go to an Out-of-Ready state.

S&C6800 Series

Control&

SpeedNetRadio

IntelliCap®2000

Control&

SpeedNetRadio

S&C6801M Switch

Operator&

SpeedNetRadio

SpeedNet/DNPCommunication

Link

IntelliRupter® Fault Interrupter

DNPover

UDP/IP,TCP/IP,

orSerial

SpeedNetHeadend

Radio

DNPEntryPoint

or direct DNPconnection

& SpeedNet™ Radio

Computer

DNP

Figure 8. Connected to a DNP entry point or to the headend radio.

S&C Instruction Sheet 1032-500 11

Figure 9. Connected to the SCADA communication port of a 6800 Series Automatic Switch Control.

S&C6800 Series

Control

& SpeedNetRadio

SpeedNet/DNPCommunication

Link

Serial/DNP

IntelliRupter Fault Interrupter& SpeedNet Radio

IntelliCap2000

Control&

SpeedNetRadio

S&C6800 Series

Control

& SpeedNetRadio

S&C6800 Series

Control

& SpeedNetRadio

Computer

Using IntelliLink Remote Setup Software

NOTICEWhen you connect your computer to a radio in a switch control (or the headend radio) and disconnect the control (or SCADA system), the IntelliTeam Automatic Restoration System (or SCADA system) normally connected to that radio will not perform its normal function . The team of devices will go to the Out-of-Ready state, or the SCADA system will not be able to communicate .

S&C recommends that you connect your computer to a separate, dedicated radio . For UtiliNet Radios, the DNP address of this radio must be listed in the Frame Recognition DCW of each radio with which you will communicate . For S&C SpeedNet Radios, the DNP and IP address of the dedicated radio must be listed in the routing table .

Figure 8 on page 10 shows a computer connected via Ethernet UDP/IP, Ethernet TCP/IP, or a serial connection through a DNP network entry point to the headend radio. The DNP network entry point can be a device terminal server or a DNP proxy server, or the computer can also be directly connected to a dedicated radio. You can configure and troubleshoot an entire network through a DNP radio.

When a DNP master station is also accessing information from the S&C control equipment, the communication link must be capable of properly routing both DNP message streams. Please contact your local S&C Sales Office for information about applications that involve more complex communication systems.

Connecting to a DNP Network Entry Point

12 S&C Instruction Sheet 1032-500

IntelliLink Remote software allows you to connect locally to a device that uses the DNP 3 protocol and to remotely access another control by calling its DNP address. Then, you can change setpoints, monitor real-time data, view event logs, and generate reports as if you were connected directly to the faceplate of that control.

Follow these steps to connect via a control’s DNP address:

STEP 1. Connect your computer to the device that is your entry point to the DNP network.

S&C Automation Device—Use the SCADA port (Port A) on the control. You will need a DB9 to 6-pin IDC cable; S&C catalog number 007-001355-01.

Headend DNP Radio—Use the appropriate cable.

Remote Terminal Server—Configure your computer to communicate with the server.

STEP 2. Start the IntelliLink software, if it is not already running. The IntelliLink software will attempt to connect using the communication parameters that it saved the last time it connected. If you want to change to a different DNP address, click on the Cancel button and change parameters. See Figure 10.

Figure 10. Communication dialog box for version 5 of IntelliLink software and below. If you have an S&C Universal Interface Module installed, this dialog box will look different.

Connecting Via DNP

STEP 3. From IntelliLink software, select the Tools option. See Figure 10 for version 5 of IntelliLink software and below, or Figure 11 on page 13 for version 6 of IntelliLink software.

STEP 4. In the Communications tab of the Options dialog box, select the DNP setting as the Protocol option.

STEP 5. Set the Connection type. If you are connecting directly to a 6800 Series Control or to a DNP radio, select the Serial option. If you are connecting to a server, select the TCP/IP or UDP/IP option, depending on your network configuration.

STEP 6. If you selected the Serial option in Step 5, enter the following:

Port—This is the port on your computer to which the DNP communication cable is connected.

Baud Rate—This is the baud rate between the switch control and the directly connected communication device (radio, modem, etc.).

STEP 7. If you selected the TCP/IP or UDP/IP option in Step 5, enter the following:

Peer IP or DNS Name—Enter the IP or DNS name of the server.

Peer Port—Enter the server’s TCP or UDP port number.

Our Port—Enter your computer’s UDP port number.

Using IntelliLink Remote Setup Software

S&C Instruction Sheet 1032-500 13

Figure 11. Communication dialog box for version 6 of IntelliLink software and above.

STEP 8. Use Default Timeout—Check this box to use the default Timeout value. Unless you are connecting directly to a control (TTY for software versions below 3.5.x), it is recommended that you set the Timeout value manually:

Timeout—The timeout duration (in milliseconds) for communications.

Retries —The number of times that the switch control tries to connect with the remote device or send a request when there is no response.

Our Address—The DNP address associated with the local computer (the master station address). Set this unique value according to the routing configuration in your DNP network.

STEP 9. Set the Destination Address—This is the DNP/RTU address for the control with which you want to communicate. (To communicate with a control you are locally connected to, and when you do not know its DNP/RTU address, set the Destination Address value to the Self setting.)

The Destination Address field is actually a drop-down menu that automati-cally stores the last several DNP addresses that have been visited.

STEP 10. Click on the Connect button. Once connected, you can view IntelliLink Software screens as if connected directly to the remote switch control.

Using IntelliLink Remote Setup Software

14 S&C Instruction Sheet 1032-500

NOTICEIntelliLink Remote Setup Software will communicate with all versions of DNP control software installed in these S&C Automation Products:

• IntelliCap® Plus and IntelliCap® 2000 Automatic Capacitor Controls

• 6800 Series Automatic Switch Controls

• 6801M Automatic Switch Operators

• IntelliRupter® PulseCloser® Fault Interrupters

• IntelliNode™ Interface Modules

• BankGuard Plus® Controls

• M Series Switch Operators

IntelliLink Remote Setup Software will communicate with the following and later versions of DNP control software installed in these S&C Automation Products:

• S&C 5800 Series Automatic Switch Control Software Revision 2 .16

• EnergyLine 2851 and 2852 Automatic Switch Control Software Revision 2 .16

• S&C Model 4801 Remote Switch Control Software Revision 2 .23

• EnergyLine 1000 Series Capacitor Control Software Revisions C35Dxxxx, K41Dxxxx, N47Dxxxx, and V47Dxxxx

If IntelliLink Remote Setup Software does not communicate with your controls, please contact S&C Electric Company at (888) 762-1100 for further information and assistance .

STEP 11. Repeat Steps 8 through 10 for each switch control whose status you wish to review.

Using IntelliLink Remote Setup Software

S&C Instruction Sheet 1032-500 15

Configuring IntelliLink Remote Setup Software

Setting Screen Refresh Options

NOTICEThe default refresh rate of 1000 ms is intended for use with local connections where the channel bandwidth is dedicated to the connection . When connecting over a network, it is recommended that the manual refresh be used or the refresh rate extended to avoid putting excessive strain on the network .

IntelliLink Remote software offers several options for refreshing data:

From an IntelliLink software screen, select the Tools>Options entry. Click on the Screen Refresh tab of the Options dialog box. See Figure 12 and Figure 13 on page 16. The parameters on these screens include:

• Fill On Open (“Fill Screen on Open for Manual Refresh Mode” for software 3.5 and above)—When checked or the Yes option is selected, all the data on a screen is requested whenever a new screen is called up.

• Refresh Mode Effective (for software versions 3.5 and above)—This allows you to toggle between Manual and Auto mode at any time. It also is available at the bottom of the IntelliLink Remote data screen.

• Refresh Mode On Start Up—By selecting the Once option, the data on a screen is requested only when a new screen is called up. By selecting Auto, the screen is updated after the interval specified in Delay between consecutive screen refreshes setpoint. You can also toggle between the Once and Auto settings by using the buttons at the bottom of the IntelliLink Remote data screen.

• Delay between consecutive screen refreshes—If the Refresh Mode option is set to the Auto setting, the data are gathered at this interval.

• Show Refresh Progress (software versions below 3.5.x)—When checked, the status bar at the bottom right of the IntelliLink Remote data screen shows the progress of the Refresh operation.

If the Refresh Mode option is not set to the Auto setting, you may refresh the screen manually by clicking the Once button at the bottom of the IntelliLink Remote data screen. For software versions below 3.5.x, you can also refresh just one specific parameter by right-clicking the parameter and selecting the Refresh Item option.

Figure 12. Refresh screen setpoints for software versions below 3.5.x.

16 S&C Instruction Sheet 1032-500

For software versions below 3.5.x, IntelliLink software has three Access Password levels. From an IntelliLink software screen, select the Tools>Security menu option. The Set Access Passwords dialog box will open. See Figure 14. The parameters on this screen include:

• Master Password—Setting a master password enables password security. Once the master password has been set, you will not be able to start IntelliLink Remote Setup Software again without using the master password or one of the other configured pass-words. The master password is required to enable, disable, or change other passwords, and to disable the master password itself—which will remove password protection.

NOTICEBe sure to record your master password . Without it you will not be able to change passwords or remove password protection .

• Read/Write Password—A user who logs in with this password can view screens and change setpoints but not change passwords. This password cannot be set until you have set the master password.

• Read-Only Password—A user who logs in with this password can view screens but can-not change set points. This password cannot be set until you have set the master password.

Figure 14. The Set Access Passwords dialog box.

Setting Security Options for Legacy Products

Figure 13. Refresh screen setpoints for software version 3.5.x and above.

Configuring IntelliLink Remote Setup Software

S&C Instruction Sheet 1032-500 17

Security Options Setup

IntelliRupter Fault Interrupter Operation

Remote Operation

The security setting for S&C controls is set on the Setup>Security screen. See the “Security” section of S&C Instruction Sheet 766-530 for IntelliRupter fault interrupters, 1045-530 for 6800 Series Automatic Switch controls, and 1045M-530 for 6801M Automatic Switch Operators.

IntelliLink Remote software can remotely operate IntelliCap Plus and IntelliCap 2000 Automatic Capacitor Controls. Other S&C automatic controls cannot be operated by Intel-liLink Remote software but can be operated over a SCADA system by device-specific DNP commands.

IntelliCap 2000 Automatic Capacitor Controls, IntelliRupter fault interrupters, 6800 Series Automatic Switch Controls, 6801M Automatic Switch Operators, and IntelliNode Interface Modules using software revision 3.5.x and above can be operated by IntelliLink Remote software commands when the IntelliLink Remote Commands setting on the Setup>Security screen has been set to the Enabled state.

Because these commands do not operate the IntelliRupter fault interrupter, they can always be used by IntelliLink Remote software:

• Validate settings

• Apply settings

• Reset buffer

• All log screen functions

• Functions on all File, Connections, Data, and Tools menus

These commands operate the IntelliRupter fault interrupter, and can only be used by IntelliLink Remote software when the IntelliLink Remote Commands setting on the Setup > Security screen has been set to the Enabled mode:

• Open operation

• Close operation

• Ground trip enable or disable

• Second closing profile on or off

• Circuit testing enable or disable

• Test on backfeed enable or disable

• Protection profile selection

• Hot line tag enable or disable

• Remote operation on or off

• Run PulseClose test

• Run battery test

• Prohibit or enable restoration

• Clear manual operation

• SEF trip enable or disable

• Single phase trip enable or disable

• Loop restoration enable or disable

Configuring IntelliLink Remote Setup Software