Installation of RFS FLEXWELL ® waveguides Part 3 of 3 P3 -1 RFS /HSR/ ah / 2003-4 Designed for very easy and time saving installation Feed thru plate Incl. Screws & plugs High speed wall gland Filler plug Per ulteriori Info: SITEL s.r.l. Via Della Chimica, 12 20867 Caponago (MB) Tel. +39 02 95743609 Fax +39 0295740631 [email protected] P3 -2 RFS /HSR/ ah / 2003-4TRANSCRIPT
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-1
Installation of WaveguidesPart 3 of 3
Installation of RFS FLEXWELL® waveguides
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-2
• Wall glands- HSW High Speed Wall gland
Designed for very easy and time saving installation
High speed wall gland
Filler plug
Feed thru plateIncl. Screws & plugs
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-3
• Wall glands- Installation of HSW Connecting plate
Dic
htm
asse
Sea
lant
Sealing tape
Dichtmasse
Sealant
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-4
• Wall glands- BOOT / FTP - series
Feed Through AssembliesBOOT-series
6 & 8 Hole Wall/Roof Feed Through Entry Panels
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-5
• Wall glands- Single wall gland
For big waveguides, if it is not necessary to pull the waveguide
through the wallgland
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-6
• Wall glands- SIGMAFORM
5 different sizes available
hot shrink partwith glue inside
O - ringWall - plate
Inner partwith thread
70,0 – 36,0 mm85,0 mm-CES 5
40,0 – 19,0 mm51,0 mmCES 4
28,0 – 13,0 mm35,0 mmCES 3
19,0 – 6,0 mm25,5 mmCES 2
14,0 – 3,0 mm25,5 mmCES 1
Shrinkingzone Ø
Requireddrilling Ø
Part No.
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-7
• Wall glands- System Brattberg & Roxtec
Do not feed a waveguide directly through this kind of wallglands, because of the high pressure to seal it.
If the high fire protection is required we recommend to fill fire protection material into the long steel tube, even the use of protection coating is recommend.
We recommend to put a steel tube into the inlet and feed the waveguide through this tube.
Afterwards it is possible to seal this section with a heat shrinking tube.
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-8
• Wall glands- System Hauf
Do not feed a waveguide directly through this kind of wallglands, because of the high pressure to seal it.We recommend to put a steel tube into the inlet and feed the waveguide through this tube.Afterwards it is possible to seal this section with a shrinking tube.
The waveguide can be entered directly through this kind of wallgland.Afterwards it can closed with a shrinking sleeve.
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-9
• Dehydration concepts for waveguides- The closed system without additional measures
- Highly trained installation staff has to be required.
- This method is recommended only for short waveguide lengths, which are assembled in the factory and sealed for transportation.
- The air inside the waveguide must be dry.
- Both ends of the waveguide run are closed with pressure windows (or at one end by the pressure tight antenna).
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-10
• Dehydration concepts for waveguides- The closed system with purging seal test
- The maximum length of waveguide is determined by the size of the nitrogen bottle.
- Moisture is eliminated from the waveguide.
- Both ends of the waveguide run are closed with pressure window (or at one end by the pressure tight antenna).
- The system is purged with dry nitrogen and seal tested after installation – with a transportable purge and sealing device.
Purging andseal test
Open the gas inletduring purging test
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-11
• Dehydration concepts for waveguides- The closed systems with purging, seal and humidity indicator
- The maximum length of waveguide is determined by the size of the nitrogen bottle (same length as before)
- In case of leakage the desiccant cartridge will provide an early warning (changing colour from blue to violet).
- Both ends of the waveguide run are closed with pressure windows (or at one end by the pressure tight antenna).
- The system is purged with dry nitrogen and seal tested after installation – with a transportable purge and sealing device.
Open thegas inletduring purging
Purging andseal test
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-12
• Dehydration concepts for waveguides- The closed systems with dehydrator
- Different dehydrators can be used, but the maximum pressure of 0,3 bar has to be noted.
- Dehydrators with an additional alarm connection saved the system very well. The max. length of waveguide is dependent on the capacity of the dehydrator
- Both ends of the waveguide run are closed with pressure windows (or at one end by the pressure tight antenna).
- The dehydrator is used to remove any moisture from the system.
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-13
• Dehydration concepts for waveguides- Different methods – list of maximum lengths
FLEXWELLwaveguide
The closed systemwithout addidional
measures
The closed systemwith purging and seal test
The closed systemwith purging and seal test and
humidity indicatorE 380 < 30 m < 75 m < 75 m
E 250 < 12 m < 30 m < 30 m
E 220 < 10 m < 25 m < 25 m
EO 38 < 10 m < 25 m < 25 m
E 185 < 7 m < 16 m < 16 m
E 150 < 4 m < 10 m < 10 m
E 130 < 2,5 m < 8 m < 8 m
EO 22 < 2,5 m < 8 m < 8 m
E 105 / < 6 m < 6 m
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-14
• Dehydration concepts for waveguides- Transportable purge and sealing device
Use only nitrogen 5.0Max bottle pressure 10 barIf antenna or pressure window are
installed the max. pressure is 0,3 bar
Rinsing
Seal test
Rinsing
Seal test
Closed system with purging and
seal test
Closed system with purging and seal test and
humidity indicator
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-15
• Dehydration concepts for waveguides- Determining the nitrogen consumption for the rinsing process
Stickstoffbedarf für den SpülvorgangNitrogen Consumption for the Rinsing Process
0
0,5
1
1,5
2
2,5
3
3,5
2 4 6 8 10 12 14 16 18 20 25 30 35 40
Hohlleiterlänge in mLength of Waveguides in m
Dru
ckab
fall
des
Fla
sche
ndru
ckm
anom
eter
s in
ba
rP
ress
ure
Dro
p S
how
on
Bot
tle P
ress
ure
Gag
e in
bar
E130
E150
E185
E220
E250
E380
• From this point go straight up until intersecting the plotted line.
• Go left from the point of intersection until encountering the minimum value for pressure (y-axis) loss to be indicated on the procedure. For short waveguides it is recommend that the value indicated by the chart is rounded up to the next integer (for example 0,4 = 1bar).y-axis
• Go along the x-axis to the corresponding length of waveguide to be rinsed.
X-axis
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-16
• Dehydration concepts for waveguides- Desiccant cartridge
Body for Cartridge Desiccant Cartridge
Installation example
The changing of the colour from blue to violet provide an early warning (long before link failure) if moisture is entered the system
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-17
• Dehydration concepts for waveguides- Desiccant cartridge direct installation
Model Number: DC-KIT-B
Direct installation on FLEXWELL® waveguideconnectors for E100 – E220, installed in up standing or lying position (with bow)
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-18
• Dehydration concepts for waveguides- Desiccant cartridge on small waveguides with adaptor
Installation with DC-KIT adaptor for:Square flange PBR220* (waveguide E185*/220*/250) Model Number: DC-KIT-220-Bsquare flange PBR260 (waveguide E250) Model Number: DC-KIT-260-Bsquare flange PBR320 (waveguide E380) Model Number: DC-KIT-320-B*installation directly with DC-KIT-B or with DC-KIT-220-B is possible
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-19
• Dehydration concepts for waveguides- Dehydrator LAB2
The air is dried through chemical absorption by granular substances in a disposable cartridge
accessible from the front panel
Tube-01-G18 (tube adapter)for Waveguide minimum size E220
Before beginning of operation it is recommend to make a rinsing process (triple of waveguide volume),Therefore remove the gas inlet of the connector on the opposite.
Tube-01 (Butyl tube 6 x 3mm)
Programmable from 0,1kPa up to 4,0kPa (0,001bar-0,04bar)Recommended max. Volume of waveguide 400 L
Manual regeneration,230 V AC or 36-72 V DC4 Outlets (not expandable)
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-20
Knob for shutoff valves in parking
positionLED’s
• Dehydration concepts for waveguides- Dehydrator LAB 2 (B version) – Front view
Display
ShutoffvalvesDetector
The cartridge must be replaced when the color changes from
blue to pink
SwitchPower Function keys
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-21
• Dehydration concepts for waveguides- Dehydrator LAB 2 – Back & inside view
Air outlets
Catridge
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-22
• Dehydration concepts for waveguides- Dehydrator LAB 2 – Desiccant cartridge
Remove the tube before replace the cartridge
Remove red plastic tag from desiccant cartridge before use
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-23
• Dehydration concepts for waveguides- Dehydrator LAB 2 – Installation versions
Wall mounting rack
ETSI-N3 mounting
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-24
• Dehydration concepts for waveguides- Dehydrator LAB 4
Automatic regeneration(by an automatic heating process)
230V AC or 36-72 V DC
4 Outlets expandable to 8 outlets
Programmable from 0,1kPa up to 6,0kPa
Recommended max. Volume of waveguide 400 L
Before beginning of operation it is recommend to make a rinsing process (triple of waveguide volume),Therefore remove the gas inlet of the connector on the opposite.
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-25
• Dehydration concepts for waveguides- Dehydrator LAB 4 – Air flow diagram
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-26
• Dehydration concepts for waveguides- Dehydrator LAB 4 – Installation versions
Remove the metallic case for rack 19” mounting
Because of humidity coming out on top of the equipment during regeneration and the high temperature (100°C) leave an upper free space of at least four units from the dehydrator to the closed equipment
With metallic case for wall mounting
ETSI-N3 brackets
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-27
• Dehydration concepts for waveguides- Dehydrator LAB 4 – Extension Manifold kit
ADD-ON4
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-28
• Dehydration concepts for waveguides- Gas volume of waveguides
ADD-ON4Overmoded waveguidesWaveguide
Type EO 11 EO 15 EO 19 EO 22 EO 38
Gas Volume
l/m0,89 0,58 0,31 0,24 0,074
Standard waveguidesWaveguide
Type E 20 E 30 E 38 E 46 ES 46 E 58 E 60 E 65 E 70 E 78 E 100 E 105 E 130 E 150 E 185 E 220 E 250 E 380
Gas Volume
l/m7,04 4,25 2,34 1,68 1,58 1,08 1,02 0,83 0,72 0,60 0,38 0,31 0,24 0,18 0,11 0,074 0,06 0,026
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-29
• Installation examples- Waveguide installed inside towers
Step 1:Pre-Installed clamps
Step 2:Installed waveguides
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-30
• Installation examples- Waveguide installed outside towers
Waveguide fixed on 1” tubes
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-31
• Installation examples- Working on platforms
Waveguide fixed on 1” tubes
Installation of connector
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-32
• Installation examples- Wall glands
Different ways to enter buildings
RFS /HSR/ ah / 2003-4
Installation of RFS FLEXWELL® waveguides
P3-33
Wherever you have to work, RFS wishes you a complete success at your work.Enjoy the panorama from towers and buildings without accident.
• Finally
If you have any questions, please don’t hesitate to ask us.