installation of mags
DESCRIPTION
Installation of Mags. What details need to be planned out? Manufacture requirements IDWR requirements Site selection for installation Examples of good and bad installations. Application Considerations. Size? Piping Configurations? Meter Mounting or Remote? Available power supply? - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/1.jpg)
Installation of Mags
• What details need to be planned out?• Manufacture requirements• IDWR requirements• Site selection for installation• Examples of good and bad installations
![Page 2: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/2.jpg)
Application Considerations• Size?• Piping Configurations?• Meter Mounting or Remote?• Available power supply?• Grounding !!
![Page 3: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/3.jpg)
Details• Electronics
– Can be direct mount or remote mounted– Generally have a NEMA 4 (IP 66)or better rating for enclosure
and protection of the electronics from dust, and spray down• DC operated verses AC operation
– DC operation runs 3-6 years on a battery pack– Hard wired to 110 AC voltage
• The use of dry transformers to get voltage down from 480 to 110
• Remote mount– LCD and sunlight– A little care will go a long way
![Page 4: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/4.jpg)
Manufacture requirements
• Most require 3 diameters of straight unobstructed pipe above and 2 diameters below.– The meter its self acts as a portion of those
lengths due to unobstructed flow through the flow tube
– Example- 10 inch diameter meter would require 30 inches upstream of the meter and 20 inches below the meter
![Page 5: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/5.jpg)
Manufacture requirements
• Grounding!!!• If stray voltage is present in the system (generally
electrically derived not mechanically) the mag sensors will pick up any change in voltage due to strays and give erroneous readings.– Grounding rings are easier to install initially rather
than after the fact– Must have grounding rings as part of the installation
if: • Meter is installed in PVC• A VFD drive operates the system
![Page 6: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/6.jpg)
Manufacture Requirements
• Meter orientation– May have some specific
requirements.
– Meter must be installed at a 10 or 2 in the pipe
• Ask questions if you are unsure of how to proceed.
![Page 7: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/7.jpg)
IDWR Requirements
• Clamp on Ultrasonic measurements• Need 10 diameters upstream and 5
downstream to achieve 1% accuracy• The more straight run of unobstructed pipe
the better
![Page 8: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/8.jpg)
Site Selection
![Page 9: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/9.jpg)
Good installations
![Page 10: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/10.jpg)
Good installations
![Page 11: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/11.jpg)
Good installations
![Page 12: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/12.jpg)
Not so good installations
![Page 13: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/13.jpg)
Not so good installations
![Page 14: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/14.jpg)
Not so good installations
![Page 15: Installation of Mags](https://reader036.vdocuments.site/reader036/viewer/2022062323/568164e3550346895dd746c9/html5/thumbnails/15.jpg)
Wrap up
• Measurement plans for each well will help to insure installation is done right the first time
• If you have questions ask someone • Accurate measurements begin with a good
meters and better installation• Water users are ultimately responsible for
install and maintenance of flow meters