installation manual - equinix-cummins manu… · installation manual generator set dqgaa (spec...

83
Installation Manual Generator Set DQGAA (Spec AC) DQGAB (Spec AC) with PowerCommand R 3201 Controller English Original Instructions 82010 961-0610 (Issue 3)

Upload: duongduong

Post on 06-Mar-2018

263 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

Installation Manual

Generator Set

DQGAA (Spec A−C)DQGAB (Spec A−C)

with PowerCommand� 3201 Controller

English − Original Instructions 8−2010 961-0610 (Issue 3)

Page 2: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

i

Table of ContentsSECTION PAGE

SAFETY PRECAUTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ABOUT THIS MANUAL 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION OVERVIEW 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2. SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3. MOUNTING THE GENERATOR SET 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

LOCATION 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IMPORTANT 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MOUNTING 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ACCESS TO SET 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

VIBRATION ISOLATORS 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ALIGNING GENERATOR WITH ENGINE 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4. MECHANICAL CONNECTIONS 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FUEL SYSTEM 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EXHAUST SYSTEM 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

VENTILATION AND COOLING 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5. DC CONTROL WIRING 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CONTROL WIRING 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

REMOTE MONITOR/CONTROL CONNECTIONS 5-2. . . . . . . . . . . . . . . . . . . . . . . . .

RUN RELAYS (K11, K12, K13) 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ALARM RELAY (K16) 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

POWER TRANSFER CONTROL (OPTIONAL) 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

6. AC ELECTICAL CONNECTIONS 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSULATION RESISTANCE (MEGGER) & POLARIZATION INDEX (PI) TESTING 6-2. . .

TRANSFER SWITCH 6-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AC WIRING 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 3: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

ii

CONTROL HEATER (OPTIONAL) 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SECTION PAGE

COOLANT HEATER (OPTIONAL) 6-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERATOR HEATER (OPTIONAL) 6-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7. PRESTART PREPARATION 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INPOWER SERVICE TOOL GENERAL INFORMATION 7-1. . . . . . . . . . . . . . . . . . .

ELECTRICAL SYSTEM 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CONTROL PRESTART CHECKS 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ADJUST SUBMENU 7-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

POWER TRANSFER CONTROL MAIN MENUS 7-8. . . . . . . . . . . . . . . . . . . . . . . . . .

UTILITY SENSORS SUBMENUS 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENSET SENSORS SUBMENUS 7-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TIMERS SUBMENU 7-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TEST/EXERCISE SUBMENU 7-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PTC DETAILED FIELD DESCRIPTIONS 7-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UNDER-VOLTAGE SENSING 7-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OVER-VOLTAGE SENSING 7-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FREQUENCY SENSING 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PROGRAMMED TRANSITION 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STARTING 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8. INSTALLATION CHECKLIST 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERATOR SET SUPPORT 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

COOLING AIR FLOW 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DIESEL FUEL SYSTEM 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EXHAUST SYSTEM 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AC AND DC WIRING 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERATOR SET PRESTART 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9. FAN BELT ALIGNMENT 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SPECIAL TOOLS 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

iii

SAFETY PRECAUTIONSSAVE THESE INSTRUCTIONS − This manual con-tains important instructions that should be followedduring installation and maintenance of the genera-tor set and batteries.

Before operating the generator set (genset),read the Operator’s Manual and become familiarwith it and the equipment. Safe and efficient op-eration can be achieved only if the equipment isproperly operated and maintained. Many acci-dents are caused by failure to follow fundamentalrules and precautions.

The following symbols alert you to potentially dan-gerous conditions to the operator, service person-nel, or the equipment.

DANGER This symbol warns of immediatehazards which will result in severe personal in-jury or death.

WARNING This symbol refers to a hazard or un-safe practice which can result in severe person-al injury or death.

CAUTION This symbol refers to a hazard or un-safe practice which can result in personal injuryor product or property damage.

FUEL AND FUMES ARE FLAMMABLE

Fire, explosion, and personal injury or death can re-sult from improper practices.

DO NOT fill fuel tanks while engine is running, un-less tanks are outside the engine compartment.Fuel contact with hot engine or exhaust is a potentialfire hazard.

DO NOT permit any flame, cigarette, pilot light,spark, arcing equipment, or other ignition sourcenear the generator set or fuel tank.

Fuel lines must be adequately secured and free ofleaks. Fuel connection at the engine should bemade with an approved flexible line. Do not use zinccoated or copper fuel lines with diesel fuel.

Be sure all fuel supplies have a positive shutoffvalve.

Be sure battery area has been well-ventilated priorto servicing near it. Lead-acid batteries emit a highly

explosive hydrogen gas that can be ignited by arc-ing, sparking, smoking, etc.

Page 5: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

iv

EXHAUST GASES ARE DEADLY

Provide an adequate exhaust system to properly ex-pel discharged gases away from enclosed or shel-tered areas and areas where individuals are likely tocongregate. Visually and audibly inspect the ex-haust daily for leaks per the maintenance schedule.Make sure that exhaust manifolds are secured andnot warped. Do not use exhaust gases to heat acompartment.

Be sure the unit is well ventilated.

Engine exhaust and some of its constituents areknown to the state of California to cause cancer,birth defects, and other reproductive harm.

MOVING PARTS CAN CAUSE SEVEREPERSONAL INJURY OR DEATH

Keep your hands, clothing, and jewelry away frommoving parts.

Before starting work on the generator set, discon-nect battery charger from its AC source, then dis-connect starting batteries, negative (−) cable first.This will prevent accidental starting.

Make sure that fasteners on the generator set aresecure. Tighten supports and clamps, keep guardsin position over fans, drive belts, etc.

Do not wear loose clothing or jewelry in the vicinity ofmoving parts, or while working on electrical equip-ment. Loose clothing and jewelry can becomecaught in moving parts.

If adjustment must be made while the unit is running,use extreme caution around hot manifolds, movingparts, etc.

DO NOT OPERATE IN FLAMMABLE ANDEXPLOSIVE ENVIRONMENTS

Flammable vapor can cause an engine to over-speed and become difficult to stop, resulting in pos-sible fire, explosion, severe personal injury anddeath. Do not operate a genset where a flammablevapor environment can be created by fuel spill, leak,etc., unless the genset is equipped with an automat-ic safety device to block the air intake and stop theengine. The owners and operators of the genset aresolely responsible for operating the genset safely.Contact your authorized Cummins Power Genera-tion distributor for more information.

Page 6: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

v

ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH

Remove electric power before removing protectiveshields or touching electrical equipment. Use rub-ber insulative mats placed on dry wood platformsover floors that are metal or concrete when aroundelectrical equipment. Do not wear damp clothing(particularly wet shoes) or allow skin surface to bedamp when handling electrical equipment. Do notwear jewelry. Jewelry can short out electrical con-tacts and cause shock or burning.

Use extreme caution when working on electricalcomponents. High voltages can cause injury ordeath. DO NOT tamper with interlocks.

Follow all applicable state and local electrical codes.Have all electrical installations performed by a quali-fied licensed electrician. Tag and lock openswitches to avoid accidental closure.

DO NOT CONNECT GENERATOR SET DIRECT-LY TO ANY BUILDING ELECTRICAL SYSTEM.Hazardous voltages can flow from the generator setinto the utility line. This creates a potential for elec-trocution or property damage. Connect only throughan approved isolation switch or an approved paral-leling device.

MEDIUM VOLTAGE GENERATOR SETS

(601V to 15kV)

Medium voltage acts differently than low voltage.Special equipment and training is required to workon or around medium voltage equipment. Operationand maintenance must be done only by personstrained and qualified to work on such devices. Im-proper use or procedures will result in severe per-sonal injury or death.

Do not work on energized equipment. Unauthorizedpersonnel must not be permitted near energizedequipment. Due to the nature of medium voltageelectrical equipment, induced voltage remains evenafter the equipment is disconnected from the powersource. Plan the time for maintenance with autho-rized personnel so that the equipment can be de-en-ergized and safely grounded.

GENERAL SAFETY PRECAUTIONS

Coolants under pressure have a higher boiling pointthan water. DO NOT open a radiator or heat ex-

changer pressure cap while the engine is running.To prevent severe scalding, let engine cool down be-fore removing coolant pressure cap. Turn cap slow-ly, and do not open it fully until the pressure has beenrelieved.

Used engine oils have been identified by some stateor federal agencies as causing cancer or reproduc-tive toxicity. When checking or changing engine oil,take care not to ingest, breathe the fumes, or contactused oil.

Keep multi-class ABC fire extinguishers handy.Class A fires involve ordinary combustible materialssuch as wood and cloth; Class B fires, combustibleand flammable liquid fuels and gaseous fuels; ClassC fires, live electrical equipment. (ref. NFPA No. 10).

Make sure that rags or combustible material are notleft on or near the generator set.

Make sure generator set is mounted in a manner toprevent combustible materials from accumulatingunder or near the unit.

Remove all unnecessary grease and oil from theunit. Accumulated grease and oil can cause over-heating and engine damage which present a poten-tial fire hazard.

Keep the generator set and the surrounding areaclean and free from obstructions. Remove any de-bris from the set and keep the floor clean and dry.

Do not work on this equipment when mentally orphysically fatigued, or after consuming any alcoholor drug that makes the operation of equipment un-safe.

Substances in exhaust gases have been identifiedby some state or federal agencies as causing can-cer or reproductive toxicity. Take care not to breathor ingest or come into contact with exhaust gases.

Do not store any flammable liquids, such as fuel,cleaners, oil, etc., near the generator set. A fire orexplosion could result.

Wear hearing protection when near an operatinggenerator set.

To prevent serious burns, avoid contact with hotmetal parts such as radiator system, turbo chargersystem and exhaust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

Page 7: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

1-1

1. Introduction

ABOUT THIS MANUAL

This manual provides installation instructions for thegenerator set models listed on the front cover. Thisincludes the following information:

Mounting Recommendations - for fasteninggenerator set to base and space requirementsfor normal operation and service.Mechanical and Electrical Connections -covers most aspects of the generator set instal-lation.Prestart − checklist of items or proceduresneeded to prepare generator set for operation.Initial Startup − test complete system to en-sure proper installation, satisfactory perfor-mance, and safe operation. Refer to OperatorsManual for troubleshooting information.Installation Checklist − reference checksupon completion of installation.

This manual DOES NOT provide application infor-mation for selecting a generator set or designing thecomplete installation. If it is necessary to design thevarious integrated systems (fuel, exhaust, cooling,etc.), additional information is required. Reviewstandard installation practices. For engineeringdata specific to the generator set, refer to the Speci-fication and Data Sheets. For application informa-tion, refer to Application Manual T-030, “LiquidCooled Generator Sets”.

INSTALLATION OVERVIEW

These installation recommendations apply to typi-cal installations with standard model generator sets.Whenever possible, these recommendations also

cover factory designed options or modifications.However, because of the many variables in anyinstallation, it is not possible to provide specific rec-ommendations for every situation. If there are anyquestions not answered by this manual, contactyour nearest Cummins Power Generation distribu-tor for assistance.

Application and Installation

A power system must be carefully planned and cor-rectly installed for proper operation. This involvestwo essential elements: application and installation.

Application (as it applies to generator set installa-tions) refers to the design of the complete powersystem that usually includes power distributionequipment, transfer switches, ventilation equip-ment, mounting pads, and cooling, exhaust, andfuel systems. Each component must be correctlydesigned so the complete system will function as in-tended. Application and design is an engineeringfunction generally done by specifying engineers orother trained specialists. Specifying engineers orother trained specialists are responsible for the de-sign of the complete power system and for selectingthe materials and products required.

Installation refers to the actual set-up and assem-bly of the power system. The installers set up andconnect the various components of the system asspecified in the system design plan. The complexityof the system normally requires the special skills ofqualified electricians, plumbers, sheetmetal work-ers, etc. to complete the various segments of theinstallation. This is necessary so all components areassembled using standard methods and practices.

Page 8: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

1-2

Safety Considerations

The generator set has been carefully designed toprovide safe and efficient service when properlyinstalled, maintained, and operated. However, theoverall safety and reliability of the complete systemis dependent on many factors outside the control ofthe generator set manufacturer. To avoid possiblesafety hazards, make all mechanical and electricalconnections to the generator set exactly as speci-fied in this manual. All systems external to the gen-erator (fuel, exhaust, electrical, etc.) must complywith all applicable codes. Make certain all requiredinspections and tests have been completed and allcode requirements have been satisfied before certi-fying the installation is complete and ready for ser-vice.

Standby Heating Devices

In accordance with NFPA 110, Cummins PowerGeneration recommends installing diesel standbygenerator sets (life safety systems) equipped withengine jacket water coolant heaters in locationswhere the minimum ambient temperature is above40F (4C). NFPA also requires that the engine beheated as necessary to maintain the water jackettemperature determined by the manufacturer forcold start and load acceptance for the type of sys-tem. Although most Cummins Power Generationgenerator sets will start in temperatures down to−25F (−32C) when equipped with engine jacket

water coolant heaters, it might take more than 10seconds to warm the engine before a load can beapplied when ambient temperatures are below 40F(4C).

The Engine Cold (Code 1435) message, in con-junction with illumination of the Warning LED, is pro-vided to meet the requirements of NFPA 110. Theengine cold sensing logic initiates a warning whenthe engine jacket water coolant temperature fallsbelow 70F (21C). In applications where the ambi-ent temperature falls below 40F (4C), a cold en-gine may be indicated even though the coolantheaters are connected and operating correctly. Un-der these conditions, although the generator setmay start, it may not be able to accept load within 10seconds. When this condition occurs, check thecoolant heaters for proper operation. If the coolantheaters are operating properly, other precautionsmay be necessary to warm the engine before apply-ing a load.

Product Modifications

Agency certified products purchased from Cum-mins Power Generation comply only with those spe-cific requirements and as noted on company prod-uct specification sheets. Subsequent modificationsmust meet commonly accepted engineering prac-tices and/or local and national codes and standards.Product modifications must be submitted to the lo-cal authority having jurisdiction for approval.

Copyright 2006 Cummins Power Generation. All rights reserved.

Cummins and PowerCommand are registered trademarks of Cummins Inc.

Page 9: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

2-1

2. Specifications

MODEL DQGAA, DQGAB

Cummins Diesel Series QSK50 (50/60 Hz)

Generator Kw Rating See Genset Nameplate for rating information.

Cooling System(Capacity Std. Raidiator) − Gal (L) 143 (541)

Lubricating SystemOil Cap. w/Filters Oil Type*

61.0 Gallons (231 L)

Engine Fuel ConnectionInlet/Outlet Thread Size Refer to Generator Outline Drawing

Fuel FlowMax. Fuel Inlet RestrictionMax. Fuel Return Restriction

8 in. Hg. (203.2 mm Hg)8 in. Hg. (203.2 mm Hg)

ExhaustOutlet SizeMaximum Allowable Back Pres.Exhaust Flow at Rated LoadExhaust Temperature

Refer to Generator Outline Drawing27 in. H2O (6.71 kPa)

12065 cfm (342 m3/min)915.0 F (491.0 C)

Electrical SystemStarting VoltageBattery

Group NumberCCA (minimum)

Cold Soak @ 0 F (-18 C)

24 Volts DCFour, 12 Volt

8D

1400

* Refer to Cummins engine Owners Manual for lubricating oil recommendations/specifications.

FUEL CONSUMPTION (STANDBY/FULL LOAD/60HZ)

MODEL DQGAA DQGAB

US gph (L/hr) 92.7 (350.9) 109.4 (414.1)

Page 10: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

2-2

THIS PAGE LEFT INTENTIONALLY BLANK

Page 11: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-1

3. Mounting the Generator Set

GENERAL

Generator set installations must be engineered sothe generator set will function properly under the ex-pected load conditions. Use these instructions as ageneral guide only. Follow the instructions of theconsulting engineer when locating or installing anycomponents. The complete installation must com-ply with all local and state building codes, fire ordi-nances, and other applicable regulations. A typicalgenerator set installation is shown in Figure 3-1.

Requirements to be considered prior to installation:

Level mounting surface

Adequate cooling air

Adequate fresh induction air

Discharge of generator set air

Discharge of exhaust gases

Non-combustible mounting surface.

Electrical connections

Accessibility for operation and servicing

Noise levels

Vibration isolation

CAUTION Alignment of the cooling system fandrive must be checked after the genset ismounted. Failure to check fan drive alignmentcan result in severe fan/radiator damage. Referto Section 9 for alignment procedure.

LOCATION

Generator set location is decided mainly by relatedsystems such as ventilation, wiring, fuel, and ex-haust. The set should be located as near as pos-sible to the main power breaker box. Exhaust mustnot be able to enter or accumulate around inhabitedareas.

Provide a location away from extreme ambient tem-peratures and protect the generator set from ad-verse weather conditions.

WARNING

INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVEREPERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUSTBE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM-PONENT INSTALLATION.

IMPORTANT

DEPENDING ON YOUR LOCATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWSAND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMITBEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCALPOLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOURCONSTRUCTION PLANS.

Page 12: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-2

DC CONTROLWIRING

CONDENSATIONDRAIN TRAP

AC POWER WIR-ING

MUFFLER

THIMBLE

AIR OUTLETDUCT (FLEXIBLE

BELLOWS)

IMPORTANT!COOLING AIR INLET MUST BE AT LEAST 1-1/2

TIMES LARGER THAN RADIATOR DUCT OUTLETAREA ON RADIATOR COOLED MODELS

FLOW OR COOLING AIR AND HEATED AIR CANBE CONTROLLED BY AUTOMATICALLY OPER-

ATED LOUVRES

AIRIN

LEVELCONCRETE

BASE

SWEEPING EL-BOW

FLEXIBLESECTION

FLEXIBLESECTION

FIGURE 3-1. TYPICAL INSTALLATION

Page 13: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-3

MOUNTING

Generator sets are mounted on a steel skid that pro-vides proper support. The engine-generator as-sembly is mounted directly to this steel skid. Vibra-tion isolation between the steel skid-base and thesupporting structure is always required, whetherthat supporting structure is a foundation, building, orsub-base fuel tank.

Note: The use of unapproved isolators may result inharmful resonances and may void the generator setwarranty.

For fuel tank mounted generator sets, it is requiredthat the tank be mounted such that an air space isprovided between the bottom of the tank and thefloor underneath to reduce corrosion and permitvisual inspections for leaks.

Mount the generator set on a substantial and levelbase such as a concrete pad. A non-combustiblematerial must be used for the pad.

Use 5/8 inch or 16 mm anchored mounting bolts tosecure the vibration isolators to the base. Securethe vibration isolators using a flat washer and hex-agonal nut for each bolt (see Figure 3-2). The 1-1/2x 6 inch pipe inserted over the mounting bolts allowsminor adjustment of the bolts to align them to theholes in the subbase or vibration isolator.

Locate the isolators as shown on the generator setOutline Drawing referenced in the Data Sheet.

ACCESS TO SET

Generally, at least 1 meter (3 feet) of clearanceshould be provided on all sides of the generator setfor maintenance and service access. A raisedfoundation or slab of 150 mm (6 inches) or moreabove floor level will make servicing easier.

Lighting should be adequate for operation, mainte-nance and service operations and should be con-nected on the load side of the transfer switch so thatit is available at all times.

FLATWASHER

MOUNTINGBOLT

12 IN.(305 MM)

MOUNTINGBASE

HEX NUT

CONCRETE

SKID

ÇÇÇÇÇÇÇÇ

ÇÇÇ

FIGURE 3-2. BOLT DIAGRAM

Page 14: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-4

VIBRATION ISOLATORS

Installation and Adjustment Procedure

1. Place the vibration isolators (Figure 3-3) on thegenset support structure. The isolators shouldbe shimmed or grouted to ensure that all of theisolator bases are within 0.25 inch (6 mm)elevation of each other. The surface that theisolator bases rest on must also be flat and lev-el.

2. Loosen the side snubber lock nuts so that thetop plate of the isolator is free to move verticallyand horizontally. Be sure that the top plate iscorrectly aligned with the base and springs.

3. Place the genset onto the isolators while align-ing the skid’s mounting with the threaded isola-tor hole. The top plates will move down and ap-proach the base of the isolator as load is ap-plied.

4. Once the genset is in position, the isolators mayrequire adjusting so that the set is level. Theisolators are adjusted by inserting the levelingbolt through the skid and into the isolator (the

leveling bolt’s locking nut should be threadedup towards the bolt head).

The leveling bolt will adjust the clearance be-tween the top plate and the isolator base. Anominal clearance of 0.25 inch (6 mm) or great-er is desired. This will provide sufficient clear-ance for the rocking that occurs during startupand shutdown. If the 0.25 inch (6 mm) clear-ance is not present, turn the leveling bolt untilthe desired clearance is achieved.

Make sure radiator skid and engine/alternatorskid are level with each other after adjusting iso-lators. If not level, proper fan belt alignment can-not be achieved (see Section 9).

5. The genset may not be level yet; therefore, ad-just the leveling bolts until the set is level andsufficient clearance still remains. (Clearanceon all isolators should be roughly equal). Onceall isolators have been set, lock the leveling boltin place with the lock nut.

6. The snubber nuts must remain loose and there-fore provide better isolation between the gen-set and support structure.

GENSET SKID

SNUBBER

LEVELING BOLT

LOCK NUT

CLEARANCE

BASE

FIGURE 3-3. VIBRATION ISOLATORS

Page 15: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-5

ALIGNING GENERATOR WITH ENGINE

Proper alignment of the generator and engine as-semblies is necessary to avoid premature wear andimproper operation of the genset. It is suggestedthat the angular alignment of the generator set bechecked before initial start-up.

Review the following alignment conditions and pro-cedures for aligning the generator assembly to en-gine flywheel housing.

Angular Misalignment: Is the result of the genera-tor bearing center axis not aligning with axis of theengine crankshaft. This condition creates an anglebetween the generator shaft axis and the crankshaftaxis. The cause of this type of misalignment is usu-ally shimming error.

Axial Misalignment: Is the result of the generatorshaft axis not aligning with engine crankshaft axis.The tolerances in the bolted flywheel and drive discconnection may add up to displace the generatoraxially relative to the crankshaft axis.

Misalignment Symptoms: If the assembly is al-lowed to run under these conditions, the discs mustflex in alternate directions twice for each engine rev-olution. It is important to minimize the amount of discflexing since, if it is excessive, the drive disc willcrack. Although perfect bearing alignment is desir-able, it is more important to keep disc deflection tothe minimum possible. This procedure assumesthat the pilot bore of the drive discs are in the exactcenter and the flywheel counterbore (pilot) has nopractical runout. Under these conditions, perfectAngular alignment will be attained when no deflec-tion of the disks is measured.

Excessive Axial misalignment will cause more gen-erator vibration than Angular misalignment.

Note: Axial misalignment should be checked onlywhen an objectionable vibration is present.

Either type of misalignment may be present in agenerator set assembly, with angular misalignmentbeing the most common problem. Angular align-ment may also be effected by set installation condi-tions and/or mishandling during shipping of the gen-set.

Page 16: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-6

Angular Alignment Procedure

WARNING Accidental starting of the generatorset during this procedure presents the hazard ofsevere personal injury or death. Make sure todisconnect the negative (−) battery cable(s) be-fore beginning.

Fasten a dial indicator to either the generator shaftor the cooling fan with the sensing point resting onthe capscrew head or the flat surface of the drive

disc at the bolt circle diameter, see Figure 3-4. Barthe engine over in a clockwise rotation as viewedfrom engine flywheel. Do not allow it to roll back oncompression at the end of the travel of each read-ing. It is unnecessary to zero the indicator since thetotal indicator reading (T.I.R.) of the deflection mea-surement to the bolt heads is what is required. T.I.R.will be the sum of the maximum positive and nega-tive dial indicator readings as the engine completesone revolution.

CLAMPDIAL

INDICATOR

FLEX

DISCS

GENERATOR AND

ENGINE

CRANKSHAFT

CENTERLINE

SHIMS

FIGURE 3-4. ANGULAR ALIGNMENT MEASUREMENT

Page 17: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-7

Sample Generator Runout Readings

When taking the deflection readings described,make a diagram similar to the example shown inFigure 3-5, where the total indicator reading is .025”.(The highest positive value of +.010 and the largestnegative value of -.015”.) The indicator is closer atthe top and further away at the bottom. This exam-ple indicates that the generator bearing is high.Since the side readings are equal, the generator iscentered side to side. To lower the generator, re-move equal shims from under the four generatormounting feet. To approximate the amount of shimsto remove or add:

1. Measure the distance between the center ofthe generator shaft to the point the indicator ismeasuring at. (For example; a SAE 18 Disccoupling distance is 10.7”).

2. Measure the distance from the generator sideof the flex discs to the center of the generatormounting bolt, refer to Figure 3-4. (For exam-ple; a HC6 Frame’s distance is 28.4”.)

3. Compare the distance measured in steps 1 and2. (28.4” vs 10.7” or a 2.65 to 1 ratio.) Multiplythis ratio times one half the T.I.R. (In our exam-ple, .025” divided by 2 is .0125”. This, times2.65 equals .033”. Therefore, remove .033” ofshims from under the four mounting feet of thegenerator.)

In general, the T.I.R. should not be more than .001”for each inch of radius (center of shaft to indicatoraxis). If we use our example of 10.7”, then the maxi-mum T.I.R. would be .011”. This would only require acorrection of .014” from the T.I.R. of .025”. (A read-ing of +.002 at the top and -.009 at the bottom wouldfall within the satisfactory range.)

+.010+.010

-.002

MEASURED AT

BOLT CIRCLE

DIAMETER

-.010

10.7 IN.

-.015-.015

-.010

-.004

FIGURE 3-5. ANGULAR ALIGNMENT MEASUREMENT READINGS (Example)

Page 18: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-8

HC4−7 Axial Alignment Procedure

Note: Axial misalignment needs to be checked onlywhen an objectionable vibration is present.

If excessive vibration remains after the angularalignment, check for concentric alignment of thegenerator shaft/engine crankshaft axes.

Fasten dial indicator holding device to skid base,engine block, or generator shell with a magneticbase or clamp and position so the sensor point of in-dicator rests on the generator shaft hub, see Figure6-18. Bar the engine over in a clockwise rotation asviewed from engine flywheel, through a couple ofrotations. Record indicator readings in eight equallyspaced points around the shaft diameter. This willprovide a T.I.R. for Axial shaft misalignment.

The maximum allowable T.I.R. runout is subjective,the optimal T.I.R. for runout would be .000”, howev-er, that may not be attainable. The recommendationof this procedure will be to reduce the measuredT.I.R. runout by one half. Specific out-of-tolerancerunout levels are difficult to establish due to the

varying surface quality of the generator shaft’s drivedisc mountain hub.

The goal of the Axial realignment is to reduce thevibration level of the genset while it is operating. Asmall improvement in the T.I.R. runout may havedramatic effects in the mechanically measured orphysically observed vibration levels.

To correct for an out of tolerance T.I.R. indication, re-move the capscrews connecting drive discs and fly-wheel. Mark the drive discs and flywheel with re-spect to each other. Rotate either the engine or gen-erator so that drive discs holes are repositioned 180degrees from their original location. Put the drivediscs capscrews back in and retorque. Recheckshaft alignment as before. If shaft T.I.R. runout re-mains unchanged then the discs should be rotatedto either 30, 60, or 90 degrees from original locationto correct the out of tolerance condition. If the T.I.R.does not improve after repositioning, a closer in-spection of the flywheel pilot and drive disc runoutsis required. This will help determine the cause of theAxial misalignment.

GENERATOR

AND ENGINE

CRANKSHAFT

CENTERLINE

ANGULAR ALIGNMENT,

SEE FIGURE 6-16

DETAIL A

SEE DETAIL A FAN HOUSING

CLAMP

GENERATOR

SHAFT HUB

DIAL

INDICATOR

FIGURE 6-18. HC4−7 AXIAL ALIGNMENT MEASUREMENT

Page 19: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-9

P7 Axial Alignment Procedure

Note: Axial misalignment needs to be checked onlywhen an objectionable vibration is present.

If excessive vibration remains after the angularalignment, concentric alignment of the generatorshaft/engine crankshaft axes may be at fault.

The goal of the axial realignment is to reduce thevibration level of the genset while it is operating. Asmall improvement in the axial alignment may havedramatic effects in the measured or physically ob-served vibration levels.

To correct for possible axial misalignment, removethe capscrews connecting drive discs and flywheel.Mark the drive discs and flywheel with respect toeach other. Rotate either the engine or generator sothat drive discs holes are repositioned two bolt holesfrom their original location. Put the drive discs caps-crews back in and retorque. Recheck/record vibra-tion levels as before. Repeat this test until the drivediscs holes are repositioned 180 degrees from theiroriginal location.

Review vibration data and position drive disc in low-est recorded level location.

Page 20: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

3-10

THIS PAGE LEFT INTENTIONALLY BLANK

Page 21: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-1

4. Mechanical Connections

GENERAL

The generator set mechanical system installationincludes connecting the fuel, exhaust, ventilationand cooling systems. Before starting any type of fuelinstallation, all pertinent state and local codes mustbe complied with and the installation must be in-spected before the unit is put in service.

FUEL SYSTEM

Cummins engines normally use ASTM No. 2 dieselfuel. They will, however, operate on alternate dieselfuels within the specifications shown in the Cum-mins engine Owners Manual.

In all fuel system installations, cleanliness is of theupmost importance. Make every effort to prevententrance of moisture, dirt or contaminants of anykind into the fuel system. Clean all fuel system com-ponents before installing.

Note: A fuel filter/strainer/water separator of 100-120mesh or equivalent (approximately 150 micronsnominal) must be fitted between either the main tankand day tank or between the main tank and the en-gine.

Use only compatible metal fuel lines to avoid elec-trolysis when fuel lines must be buried. Buried fuellines must be protected from corrosion.

CAUTION Never use galvanized or copper fuellines, fittings or fuel tanks. Condensation in thetank and lines combines with the sulfur in dieselfuel to produce sulfuric acid. The molecularstructure of the copper or galvanized lines ortanks reacts with the acid and contaminates thefuel.

An electric solenoid valve in the supply line is rec-ommended for all installations and required for in-door automatic or remote starting installations. Con-nect the solenoid wires to the genset “Switched B+”circuit to open the valve during generator set opera-tion.

Separate fuel return lines to the day tank or supplytank must be provided for each generator set in amultiple-set installation to prevent the return lines ofidle sets from being pressurized. Fuel return lines

must not contain a shutoff device. Engine damagewill occur if the engine is run with the return fuel linesblocked or restricted.

CAUTION Never install shutoff device in fuelreturn line(s). If fuel return line(s) is blocked orexceeds fuel restriction limit, engine damagewill occur.

Fuel Return Restriction (or Pressure) Limit: Fuelreturn drain restriction (consisting of friction headand static head) between the engine injector returnline connection and the fuel tank must not exceedthe limit stated in the model-specific genset DataSheet.

Fuel Lines − Routing

A flexible fuel hose(s) or section of flexible fuelhose(s) must be used between the engine’s fuelsystem and fuel supply and return line(s) to protectthe fuel system from damage caused by vibration,expansion and contraction. Flexible lines for con-necting between the engine and the stationary fuellines are supplied as standard equipment.

WARNING Fuel leaks create fire and explosionhazards which can result in severe personal in-jury or death. Always use flexible tubing be-tween engine and fuel supply and return toavoid line failure and leaks due to vibration. Thefuel system must meet all applicable codes.

Installation of the fuel hose must be done accordingto all applicable codes and standards, and installa-tion recommendations provided by the manufactur-er. The supplied flexible hose is approved by thehose manufacture for use with the genset fuel typeand product application.

Support fuel lines to restrain movement and preventchaffing or contact with sharp edges, electrical wir-ing and hot exhaust parts.

WARNING Sparks and hot surfaces can ignitefuel, leading to severe personal injury or death.Do not route fuel lines near electrical wiring orhot exhaust parts.

Fuel lines must be routed and secured to maintain a1/2 inch (12.7 mm) minimum clearance from electri-cal wiring and a 2 inch (51 mm) minimum clearancefrom hot exhaust parts.

Page 22: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-2

VENT LINE

FILL PIPE

FUEL TANK

INJECTOR FUELRETURN LINE

ENGINEFUELPUMP

DAY TANK

CONNECT TOAC OUTPUT

VENTEDFILL CAP

SUPPLYLINE

All models require a fuel returnline from injectors to tank.

SHUTOFFVALVE

1 INCH

FUEL TRANSFERPUMP ELECTRICMOTOR DRIVEN

LARGER OVER-FLOW LINE

120 MESH FUELSTRAINER

FLOATSWITCH

BAFFLE

FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION

Engine Fuel Connections

Identification tags are attached to the fuel supplyline and fuel return line connections.

Supply Tank

Locate the fuel tank as close as possible to the gen-erator set and within the restriction limitations of thefuel pump.

Install a fuel tank that has sufficient capacity to sup-ply the genset operating continuously at full ratedload for the planned period of operation or poweroutage. Refer to Data Sheet for fuel consumptiondata.

If the fuel inlet restriction exceeds the defined limitdue to the distance/customer-supplied plumbingbetween the genset and the main fuel tank, a trans-fer tank (sometimes referred to as a day tank) and

auxiliary pump will also be required. If an overheadmain fuel tank is installed, a transfer tank and floatvalve will be required to prevent fuel head pressuresfrom being placed on the fuel system components.

Note: For critical start applications, where generatorsets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tankor reservoir be located such that the lowest possiblefuel level is not less than 6 inches (150 mm) above thefuel pump inlet. This will prevent air from accumulat-ing in the fuel line while the set is not running, elimi-nating the period during startup when it has to bepurged.

Fuel Inlet Pressure/Restriction Limit:: Engineperformance and fuel system durability will be com-promised if the fuel inlet pressure or restriction limitsare not adhered to. Fuel inlet pressure or restrictionmust not exceed the limits stated in the model-spe-cific genset Data Sheet.

Page 23: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-3

Day Tank (If Used)

Fuel day tanks are used when fuel inlet restrictionlimits can not be met, or the supply tank is overheadand presents problems of high fuel head pressurefor the fuel inlet and return lines.

Supply Tank Lower Than Engine: With this instal-lation, the day tank is installed near the generatorset, below the fuel injection system and within thefuel inlet restriction limit. Install a fuel transfer pump,to pump fuel from the supply tank to the day tank. Afloat switch in the day tank controls operation of thefuel transfer pump.

Note: When using a fuel transfer pump, the supplytank top must be below the day tank top to preventsiphoning from the fuel supply to the day tank.

Provide a return line from the engine injection sys-tem return connection to the day tank. Plumb the re-turn line to the bottom of day tank as shown in Figure

4-1. Provide a day tank overflow line to the supplytank in case the float switch fails to shut off the fueltransfer pump.

WARNING Spilled fuel presents the hazard offire or explosion which can result in severe per-sonal injury or death. Provide an overflow line tothe supply tank from the day tank.

Supply Tank Higher Than Engine: With this instal-lation, the day tank is installed near the generatorset, below the fuel injection system and within thefuel inlet restriction limit. Include a automatic fuelshutoff valve in the fuel line between the fuel supplytank and the day tank to stop fuel flow when the gen-erator set is off.

Provide a return line from the engine injection sys-tem return connection to the day tank. Plumb the re-turn line to the bottom of day tank as shown in Figure4-1.

WARNING Spilled fuel can create environmental hazards. Check local requirements for containmentand prevention of draining to sewer and ground water.

Fuel Filter Installation

This section describes the installation proceduresfor the fuel filter. Read these instructions thoroughlyand become familiar with safety warnings, cautionsand procedures before starting the installation.

CAUTION Before disconnecting batterycable(s), press the Emergency Stop button andwait at least 30 seconds. Engine performancemay be affected (e.g., engine dying or hard start-ing) if battery cable(s) is removed during the 30second waiting period. Service personnel maybe required to correct fault.

WARNING Ignition of explosive battery gasescan cause severe personal injury or death. Arc-ing at battery terminals, light switch or otherequipment, flame, pilot lights and sparks can ig-nite battery gas. Do not smoke, or switch troublelight ON or OFF near battery. Discharge staticelectricity from body before touching batteriesby first touching a grounded metal surface.

Ventilate battery area before working on or nearbattery—Wear goggles—Stop genset and dis-connect charger before disconnecting batterycables—Disconnect negative (−) cable first andreconnect last.

CAUTION Disconnect battery charger from ACsource before disconnecting battery cables.Otherwise, disconnecting cables can result involtage spikes damaging to DC control circuitsof the set.

WARNING Accidental starting of the generatorset can cause severe personal injury or death.Prevent accidental starting by disconnectingthe negative (−) cable from the battery terminal.

WARNING Diesel fuel is combustible and cancause severe personal injury or death. Do notsmoke or allow any flame, spark, pilot light, arc-producing equipment, electrical switch or otherignition source around fuel or fuel components,or in areas sharing ventilation. Keep a type ABCfire extinguisher handy.

Page 24: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-4

1. Press the Emergency Stop button and wait atleast 30 seconds.

CAUTION Before disconnecting batterycable(s), press the Emergency Stop buttonand wait at least 30 seconds. Engine perfor-mance may be affected (e.g., engine dyingor hard starting) if battery cable(s) is re-moved during the 30 second waiting period.Service personnel may be required to cor-rect fault.

2. Place O/Manual/Auto switch in O (Off) position.

3. Turn off and disconnect battery charger (ifequipped).

4. Disconnect the negative (−) cable from the bat-tery to prevent accidental starting.

Note: See Figure 4-2 for installation site of fuel filteron the generator set.

SKID BRACKETFUEL LINE

STOCK BOX

LOCATION

FIGURE 4-2. FUEL FILTER ASSEMBLY LOCATIONON GENERATOR SET

5. For new installations − Remove the cap fromthe fuel inlet port of engine.

For existing installations − Make sure fuelshutoff valve is closed (if equipped) and re-move fuel hose from fuel inlet port. Use contain-er to collect any fuel in system.

6. Wall Mount - Continue with Step 8.

7. Skid Mount - Refer to Figure 4-4 for installationdiagram. In the following procedure, numbersin parentheses refer to the item numbers in Fig-ure 4-4.

a. Remove skid bracket and fasteners cur-rently mounted to skid. Keep the bracket,but discard the fasteners and stockbox.

Note: See Figure 4-5 for Fuel FilterBracket drawing and its measure-ments.

b. Disassemble the fuel filter assembly fromthe black bracket and discard the blackbracket.

c. Install the skid bracket removed in step 7ato the fuel filter assembly using screw (6)and flat washer (7). Check connections toensure tightness.

d. Install the priming pump with bolts as illus-trated in Figure 4-3 (Item A).

e. Place fuel filter (3) spacer on skid wherebracket will sit using hardware 7 and 8. SeeSection A-A of Figure 4-4 for details.

f. Secure fuel filter assembly to skid bracket(2) using hardware (9, 10, 11 and 12 as il-lustrated in Figure 4-4). Flat washer (9)and 3/8 -16 nut (10) should be installed atthe back-side of skid to secure mountingbracket and fuel filter assembly to the skid.

g. Bolt bracketed assembly to skid usinghardwares 9, 10, 11, and 12 as illustratedin Fig. 4-4.

FUEL LINE

A

FIGURE 4-3. DUAL HEAD FUEL FILTER

Page 25: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-5

8. Thread tube elbow (4) into fuel filter assembly.Position elbow as shown.

9. Install the reducer (13) at the checkvalve usingthread sealant (6).

10. Install the tube elbow into fuel filter as shown inCustomer Installation drawing in Figure 4-4.Position elbow as shown.

11. Connect the fuel line (5) and fuel inlet hose.

12. Connect the wire harness.

13. Connect the negative (−) cable to the battery.

14. Connect the battery charger (if applicable).

15. Open fuel shutoff valve (if applicable).

16. Prime the fuel system. Operate the set to checkfor fuel leaks. Do not place the set in service un-til all fuel leaks have been fixed.

Page 26: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-6

0179_5713_A_200802

SECTION A-A

CUSTOMER SITE INSTALLATION

FACTORY PACKAGING FOR SHIPPING

FIGURE 4-4. FUEL FILTER ASSEMBLY LOCATIONITEM QTY.* DESCRIPTION ITEM QTY.* DESCRIPTION

1 −− FUEL FILTER (INCLUDED) 3 1 FUEL FILTER SPACER

2 1 FUEL FILTER BRACKET (1/4 IN. THICK) 4 1 TUBE ELBOW

(Item identification table cont’d on next page...)

Page 27: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-7

(Cont’d. from previous page...)ITEM QTY.* DESCRIPTION ITEM QTY.* DESCRIPTION

5 1 FUEL LINE 12 5 SCREW (3/8 - 16NC x 1.5)

6 AR THREAD SEALANT 13 1 REDUCER

7 5 BEVEL WASHER 14 1 TUBE ELBOW (1” NPT−1 3/16 ORFS)

8 5 HEX HEAD CAP SCREW (1/2 - 13NCx1.5)

15 1 STOCK BOX (DISCARDED)

9 27 FLAT WASHER (3/8) 16 4 CABLE TIE

10 5 NUT (3/8 - 16UNC) 17 −− FUEL FITER HARNESS ACCESSORY(INCLUDED WITH ENGINE)

11 16 SCREW (3/8 - 16NC x 1) −−− −−− −−−−−−−

* Number reflects quantity for all items used for both factory packaging to be shipped and what is required for customer site installation.

Page 28: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-8

FUEL FILTER BRACKET

FUEL FILTER BRACKET MOUNTING HOLE LOCATIONS

ISOMETRIC VIEW

REAR VIEW

0149−2838_A_200703

FIGURE 4-5. FUEL FILTER BRACKET

Page 29: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-9

EXHAUST SYSTEM

Pipe exhaust gases to the outside of any enclosure.Locate the exhaust outlets away from any air inletsto avoid gases re-entering the enclosure. Exhaustinstallations are subject to various detrimental con-ditions such as extreme heat, infrequent operationand light loads. Regularly inspect the exhaust sys-tem both visually and audibly to see that the entiresystem remains fume tight and safe for operation.

WARNING Inhalation of exhaust gases can re-sult in severe personal injury or death. Use ex-treme care during installation to provide a tightexhaust system. Terminate exhaust pipe awayfrom enclosed or sheltered areas, windows,doors and vents.

For indoor installation, the exhaust system must usesealed joint type fittings, (for example NPT fittings)to provide a tight exhaust system. Use of slip typefittings (secured with a muffler clamp) may allowleakage of exhaust gases into the building.

WARNING Inhalation of exhaust gases can re-sult in severe personal injury or death. Use ex-treme care during installation to provide a tightexhaust system. Use NPT or equivalent type fit-tings for all indoor installations.

Use an approved thimble (Figure 4-6) where ex-haust pipes pass through wall or partitions. Insu-lated wall/roof thimbles are used where exhaustpipes pass through a combustible roof or wall. Thisincludes structures, such as wood framing or insu-lated steel decking, etc. Uninsulated wall/roofthimbles are used where exhaust pipes passthrough a non-combustible wall or roof, such asconcrete. Refer to NFPA 37, Section 6-3. “Station-ary Combustion Engines and Gas Turbines” for ac-

cepted design practices. Build according to thecode requirements in effect at the installation site.

WARNING Hot exhaust pipes can start a fireand cause severe injury or death if improperlyrouted through walls. Use an approved thimblewhere exhaust pipes pass through walls orpartitions.

WARNING Inhalation of exhaust gases can re-sult in severe personal injury or death. Do notuse exhaust heat to warm a room, compartmentor storage area.

Rain caps are available for the discharge end of ver-tical exhaust pipes. The rain cap clamps onto theend of the pipe and opens due to exhaust dischargeforce from the generator set. When the generatorset is stopped, the rain cap automatically closes,protecting the exhaust system from rain, snow, etc.

Use a section of flexible exhaust pipe between theengine and remainder of exhaust system. Supportexhaust system to prevent weight from being ap-plied to engine exhaust outlet elbow/turbochargerconnection.

CAUTION Weight applied to the engine man-ifold can result in turbocharger damage. Sup-port the muffler and exhaust piping so no weightor stress is applied to engine exhaust elbow.

The exhaust system design should meet local coderequirements.

Note: Liability for injury, death, damage, and warran-ty expense due to use of unapproved mufflers ormodifications becomes the responsibility of the per-son installing the unapproved muffler or performingthe modification. Contact a Cummins Power Genera-tion distributor for approved exhaust system parts.

Page 30: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-10

Avoid sharp bends by using sweeping, long radiuselbows and provide adequate support for mufflerand tailpipe. Pitch a horizontal run of exhaust pipeDOWNWARD (away from engine) to allow anymoisture condensation to drain away from the en-gine. If an exhaust pipe must be turned upward,install a condensation trap at the point where therise begins (Figure 4-7).

Shield or insulate exhaust lines if there is danger ofpersonal contact. Allow at least 12 inches (305 mm)of clearance if the pipes pass close to a combustiblewall or partition. Before installing insulation on ex-haust system components, check the exhaust sys-tem for leaks while operating the genset under fullload and correct all leaks.

WARNING Exhaust pipes are very hot and theycan cause severe personal injury or death fromdirect contact or from fire hazard. Shield or insu-late exhaust pipes if there is danger of personalcontact or when routed through walls or nearother combustible materials.

DRIP CAPRAIN CAP

ROOF

WALL OR PARTITION

HORIZONTAL

VERTICAL

9 INCH(230 MM)

HOLES INEND OF INNER

SLEEVE

9 INCH(230 MM)

FIGURE 4-6. MOUNTING EXHAUST THIMBLE

AVOIDSHARPBENDS

IF EXHAUST LINE MUST BEPITCHED UPWARD, CONSTRUCT

A TRAP AT POINT OF RISE

DRAIN CONDENSATIONTRAP PERIODICALLY

FIGURE 4-7. CONDENSATION TRAP

Page 31: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-11

VENTILATION AND COOLING

Generator sets create considerable heat that mustbe removed by proper ventilation. Outdoor installa-tions normally rely on natural air circulation but in-door installations need properly sized and posi-tioned vents for required airflow.

Vents and Ducts

For indoor installations, locate vents so incoming airpasses through the immediate area of the installa-tion before exhausting. Install the air outlet higherthan the air inlet to allow for convection air move-ment.

Size the vents and ducts so they are large enough toallow the required flow rate of air. The ”free area” ofducts must be as large as the exposed area of theradiator. Refer to the genset Data Sheet for the air-flow requirements and allowed airflow restriction.

Wind will restrict free airflow if it blows directly intothe air outlet vent. Locate the outlet vent so the ef-fects of wind are eliminated, or if outlet vent cannotbe located as mentioned, install wind barrier. SeeFigure 4-8.

PREVAILING WINDS PREVAILING WINDS

FIGURE 4-8. WIND BARRIER

Page 32: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-12

Dampers

Dampers or louvres protect the generator set andequipment room from the outside environment.Their operation of opening and closing should becontrolled by operation of the generator set.

In cold climates, the radiator exhaust air can be re-circulated to modulate the ambient air temperaturein the generator set room. This will help the genera-tor set warm up faster, and help to keep fuel temper-atures higher than the cloud point of the fuel. If recir-culation dampers are used, they should be de-signed to “fail closed”, with the main exhaust damp-ers open, so that the generator set can continue tooperate when required. Designers should be awarethat the generator set room operating temperaturewill be very close to the outdoor temperature, and ei-ther not route water piping through the generator setroom, or protect it from freezing.

Radiator Set Requirements

Note: Louvers and screens over air inlet and outletopenings restrict air flow and vary widely in perfor-

mance. A louver assembly with narrow vanes, for ex-ample, tends to be more restrictive than one withwide vanes. The effective open area specified by thelouver or screen manufacturer should be used.

Radiator set cooling air is drawn past the control endof the set by a pusher fan that blows air through theradiator. Locate the air inlet to the rear of the set.Make the inlet vent opening 1-1/2 times larger thanthe radiator area.

Locate the cooling air outlet directly in front of the ra-diator and as close as possible. The outlet openingmust be at least as large as the radiator area.Length and shape of the air outlet duct should offerminimum restriction to airflow.

Attach a canvas or sheet metal duct to the air outletopening using screws and nuts so duct can be re-moved for maintenance purposes. The duct pre-vents recirculation of heated air. Before installingthe duct, remove the radiator core guard.

COOLAIR

INLETAIR

DAMPER

HOTAIR

WIND/NOISE

BARRIER

D

ENGINE-DRIVENFAN

DISTANCE SHOULDNOT BE LESS THAN

HEIGHT OF RADIATOR

THERMOSTATICALLYCONTROLLED RECIRCU-

LATING DAMPER

FLEXIBLEDUCT CON-

NECTOR

RADIATOR

OUTLET AIRDAMPER

FIGURE 4-9. TYPICAL RADIATOR SET INSTALLATION

Page 33: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-13

Remote Radiator Cooling (Optional) substitutesa remote mounted radiator and an electrically drivenfan in place of genset mounted components. Re-moval of the radiator and the fan from the genset re-duces noise levels without forcing dependence on acontinuous cooling water supply (necessary withheat exchanger cooling). The remote radiatorinstallation must be completely protected againstfreezing.

Remote radiator plumbing will vary with installation.Follow recommendations given in ApplicationManual T-030. See product Data Sheet for frictionhead and static head limits.

Note: Before filling cooling system, check all hard-ware for security. This includes hose clamps, caps-crews, fittings and connections. Use flexible coolantlines with heat exchanger or remote mounted radia-tor.

Engine Coolant Heater (Optional)

An optional coolant heater is available to keep theengine warm for improved starting and code com-

pliance. Connect the heater to a power source thatwill be energized when the engine is NOT running.

Heat Exchanger (Optional)

The optional heat exchanger (Figure 4-10) uses ashell and tube type heat exchanger instead of thestandard radiator and fan. Engine jacket coolant cir-culates through the shell side of the heat exchangerwhile the cooling water is pumped through thetubes. Engine coolant and raw water do not mix.

This system may reduce set enclosure airflow re-quirements and noise levels. Proper operation de-pends on a constant supply of raw water for heat re-moval. Adjust the flow to maintain engine coolanttemperature between165 F and 195 F (74 C and91 C) while viewing the water temperature gauge.The engine coolant side of the system can be pro-tected from freezing; the raw water side cannot beprotected.

WARMAIR

COOL AIR

WATERSOLENOID

VALVE

VENTILATINGFAN

FLEXIBLE WA-TER

CONNECTIONS

MOUNTED HEATEXCHANGER

RAW WATERSUPPLY

RAW WATERDISCHARGE

FIGURE 4-10. TYPICAL HEAT EXCHANGER INSTALLATION

Page 34: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

4-14

THIS PAGE LEFT INTENTIONALLY BLANK

Page 35: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-1

5. DC Control Wiring

CONTROL WIRING

The generator set control box assembly (Figure5-1), contains connection points for remote controland monitor options.

CAUTION Do not attach conduit to the controlbox assembly for any reason. All conduit mustbe attached to the control housing. Attachingconduit to the control box assembly will com-press the control box vibration isolators, caus-ing the box to vibrate and damage the electroniccircuitry.

Use flexible conduit for all wiring connections to thegenerator set. All conduit used for control wiring

must be attached to the control housing, not to thecontrol box assembly. Route the control wiringthrough the control housing and into the access holeon the back panel of the control box assembly (Fig-ure 5-2). Use cable ties to keep control wiring awayfrom sharp edges and AC power cables within con-trol housing.

After completing all customer connections (wiresrouted and secured), heat shrink the boot that is lo-cated on backside of access hole, until sealed.

CAUTION Stranded copper wire must be usedfor all customer connections to the control box.Solid copper wire may break due to gensetvibration.

CONTROL BOXASSEMBLY

DO NOT ATTACH CON-DUIT TO CONTROL

BOX ASSEMBLY FORANY REASON

CONTROL HOUS-ING ASSEMBLY

VIBRATION ISO-LATORS (QTY 4)

FIGURE 5-1. CONTROL BOX − REAR MOUNT

Page 36: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-2

REMOTE MONITOR/CONTROLCONNECTIONS

Customer monitor/control connections are attachedto terminal blocks TB3 and TB8 (see Figure 5-2).Optional equipment such as a remote annunciatorpanel, sensing devices used to monitor genset op-eration, remote start/stop switches, control boxheater, and etc. are also attached to these terminalblocks. Driver signals for customer supplied relaysare also provided for several alarm and shut downconditions. Refer to Customer Connections dia-gram in Section 10.

CAUTION When removing terminal block con-nector TB8 from Base card, note orientation ofconnector. This terminal block connector is notkeyed and can be installed incorrectly, whichwill cause control failures.

Terminal Block Wiring

CAUTION Always run control circuit wiring ina separate metal conduit from AC power cablesto avoid inducing currents that could causeproblems within the control.

Digital Connections: Connection points, otherthen relayed outputs, network, switched B+ and B+are considered digital connections to the terminal

blocks. The type/gauge wire to use for these con-nections are:

Less than 1000 feet (305m), use 20 gaugestranded copper wire.

1000 to 2000 feet (305 to 610m), use 18 gaugestranded copper wire.

Relay Connections: Due to the wide variety of de-vices that can be attached to the relay outputs of ter-minal blocks, the electrical contractor must deter-mine the gauge of the stranded copper wire that isused at this installation site. Refer to Customer Con-nections diagram in Section 10 for the relay specifi-cations.

Switched B+: (Fused at 10 amps.) Same as RelayConnection description.

Delayed Switched B+: (Fused at 10 amps. with a10 second dropout) Use for external fuel shut-off so-lenoid. Same as Relay Connection description.

B+: (Fused at 10 amps.) Same as Relay Connec-tion description.

Network Connections: Refer to Cummins900-0366 PowerCommand Network Installationand Operation manual for the type/gauge wire touse for these connections.

Page 37: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-3

TB8

CARDCAGE

OPTIONAL SHUT-DOWN ALARM

RELAY K16

OPTIONALRUN RELAYS

K11, K12 & K13

CONTROL WIRINGACCESS

FIGURE 5-2. CONTROL BOX ASSEMBLY INTERIOR

Page 38: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-4

RUN RELAYS (K11, K12, K13)

The optional run relays are rail mounted inside thecontrol box (Figure 5-2). The rail mount allows youto easily remove and replace the snap-on relays.The generator set can be equipped with one, two orthree run relays.

The three-pole, double-throw run relays (Figure5-3) are used to control auxiliary equipment such as

fans, pumps and motorized air dampers. The run re-lays are energized when the generator set reachesoperating speed.

The contacts are rated:

10 amps at 28 VDC or 120 VAC, 80%PF

6 amps at 240 VAC, 80%PF

3 amps at 480/600 VAC, 80%PF

CUSTOMERCONNECTIONS

TB3-7(GND)

TB3-5(SWITCHED B+)

NO

COIL

COM

NC

K11, K12, K13

K11RUN RELAY

K11, K12, K13

K11, K12, K13

K12RUN RELAY

K13RUN RELAY

NO

NC

NO

NC

FIGURE 5-3. OPTIONAL RUN RELAYS (K11, K12, K13)

Page 39: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-5

ALARM RELAY (K16)

The optional alarm relay is rail mounted inside thecontrol box (Figure 5-2). The rail mount allows youto easily remove and replace the snap-on relay.

The three-pole, double-throw alarm relay (Figure5-4) is often used to energize warning devices such

as audible alarms. Any generator set shutdown willenergize the alarm relay.

The contacts are rated:

10 amps at 28 VDC or 120 VAC, 80%PF

6 amps at 240 VAC, 80%PF

3 amps at 480/600 VAC, 80%PF

CUSTOMERCONNECTIONS

TB3-18(GND)

TB3-17(COM ALARM)

NO

COIL

COM

NC

K16

K16

K16

K16SHUTDOWN ALARM

FIGURE 5-4. OPTIONAL ALARM RELAY (K16)

Page 40: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

5-6

POWER TRANSFER CONTROL(OPTIONAL)

The optional Power Transfer Control (PTC) featurerequires connecting the control relays of the PTCcircuit to the generator set and utility circuit break-ers. These relays are used to control the openingand closing of these circuit breakers via the PCC, fortransfer and retransfer of the load to the generatorset or the utility. A typical PTC installation is shownin Figure 5-5.

Relay Connections: Due to a wide verity of circuitbreakers that can be attached to the relay outputs ofPCC terminal block TB3, the system designer mustdetermine if the electrical requirements of the instal-lation does not exceed the limits of the PTC controlrelays. Relays that can handle larger switching cur-rent/voltage will need to be connected to the PTCcontrol relays if the electrical limits of the PTC relaysare exceeded.

The four PTC control relays are each rated at 16amps at 250 VAC or 24 VDC.

REMOTE (TEST) STARTTRANSFER INHIBITRETRANSFER INHIBITMANUAL MODE

PCC 3201

PT/CTMODULE

GENSETCIRCUIT

BREAKER

L1

LOAD

TO SERVICE

ALTERNATOR

OPEN COMMAND

CLOSE COMMAND

CB POSITION

PTC CONTROLRELAYS (4)

OPEN COMMAND

CLOSE COMMAND

CB POSITION

GENERATOR SET

BUS PTMODULE

UTILITYCIRCUIT

BREAKER

L2 L3 LN L1 L2 L3 LN

F

F

F

FIGURE 5-5. TYPICAL POWER TRANSFER CONTROL INSTALLATION

Page 41: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-1

6. AC Electical Connections

GENERAL

This section provides the procedure that is used toconnect the AC electrical system of the genset.

CAUTION Before disconnecting batterycable(s), press the Emergency Stop button andwait at least 30 seconds. Engine performancemay be affected (e.g., engine dying or hard start-ing) if battery cable(s) is removed during the 30second waiting period. Service personnel maybe required to correct fault.

WARNING Ignition of explosive battery gasescan cause severe personal injury or death. Arc-ing at battery terminals, light switch or otherequipment, flame, pilot lights and sparks can ig-nite battery gas. Do not smoke, or switch troublelight ON or OFF near battery. Discharge staticelectricity from body before touching batteriesby first touching a grounded metal surface.

Ventilate battery area before working on or nearbattery—Wear goggles—Stop genset and dis-connect charger before disconnecting batterycables—Disconnect negative (−) cable first andreconnect last.

CAUTION Disconnect battery charger from ACsource before disconnecting battery cables.Otherwise, disconnecting cables can result involtage spikes damaging to DC control circuitsof the set.

WARNING Accidental starting of the generatorset can cause severe personal injury or death.Prevent accidental starting by disconnectingthe negative (−) cable from the battery terminal.

Before making any AC electrical connections, makecertain the generator set cannot be accidentallystarted as follows:

1. 2. Move the O/Manual/Auto switch on the control panel to theO (OFF) position.

3. 4. Turn off or re-move AC power from the battery charger.

5. 6. Press the Emer-gency Stop button and wait at least 30 secondsbefore completing Step 4.

7. 8. Remove thenegative (−) battery cable from the generatorset starting battery.

Connecting the genset AC electrical system in-volves:

Installation of transfer switch

Generator output voltage selection and calibra-tion

Load cable connection

Standard and optional AC equipment connec-tions (e.g., control box heater, coolant heater,etc.

Local regulations often require that wiring connec-tions be made by a licensed electrician, and that theinstallation be inspected and approved before op-eration. All connections, wire sizes, materials used,etc. must conform to the requirements of electricalcodes in effect at the installation site.

WARNING Improper wiring can cause a fire orelectrical hazard, resulting in severe personalinjury or death and/or property and equipmentdamage.

Before starting the genset, check to make sure thatall electrical connections are secure, and that all wir-ing is complete. Replace and secure any accesspanels that have been removed during installation.Check that the load cables from the genset areproperly connected.

WARNING Backfeed to utility system cancause electrocution or property damage. Do notconnect to any building electrical system ex-cept through an approved device and afterbuilding main switch is opened.

Page 42: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-2

INSULATION RESISTANCE (MEGGER) &POLARIZATION INDEX (PI) TESTING

WARNING The windings of medium-voltage(601 through 15,000 volts) generator sets mustbe dry before the generator is operated. Failureto make sure windings are dry before start-upmay result in catastrophic equipment failure,severe personal injury or death.

The initial condition of the windings should be as-sessed both visually and by measurement of insula-tion resistance to earth using a 500v megger.

Megger and PI testing must be performed on allmedium voltage (601 through 15,000 volts) genera-tor sets before initial start-up. Failure to do so, mayvoid generator set warranty. PI testing for low volt-age (less than 600 volts) generator sets is also rec-ommended by Cummins Power Generation.

These tests are used to verify that the windings aredry before the generator set is operated and devel-ops a reference point for future test comparison.

Care should be taken when dealing with windingswhich are suspected of being excessively damp ordirty. The initial measurement of insulation resist-ance should be established using a low voltage(500V) megger type instrument and if manuallypowered the handle should initially be turned slowly.

Full voltage megger tests or any other form of highvoltage test should not be applied until the windingshave been dried out and if necessary cleaned.

CAUTION The AVR plus any voltage trans-formers should be disconnected, and any tem-perature detector leads (RTDs/thermistors)should be grounded during the test. Refer to thegenerator wiring diagram for details.

Before these tests can be performed on mediumvoltage generator sets, you must first perform thegenerator grounding procedure.

Generator Set Grounding Procedure

Prior to performing service or inspection proceduresthat may expose personnel to conductors normallyenergized with voltages greater than 600 volts, thefollowing generator set grounding procedure mustbe followed.

DANGER Do not perform these proceduresunless fully trained in medium voltage ground-ing procedures and have necessary safetyequipment. Severe injury or death due to highvoltage electrical shock may result.

1. Open, lock-out and tag-out all sources of powerto the immediate work area.

2. Disable the starting system of the generatorset:

a. Move the O/Manual/Auto switch on thecontrol panel to the O (OFF) position.

b. Turn off or remove AC power from the bat-tery charger.

c. Press the Emergency Stop button and waitat least 30 seconds before completingStep d.

d. Remove the negative battery cable (−)from the battery.

e. Install a lockout device on the battery cableend. (For engines equipped with an air-powered starting system, close air valveand install valve locking device.)

3. Put on high voltage gloves with leather protec-tors.

Page 43: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-3

4. Using two pre-tested voltage detection devices(of the proper rating), verify de-energized con-dition in the work area. (Retest voltage detec-tion devices immediately after verification ofde-energized condition.)

5, Remove the metal cover from the generatoroutput box to gain access to generator load ter-minals.

6. Securely install the Grounding Cluster groundclamp to a verified “grounded” conductor.

WARNING Hazardous voltage. Can causesevere personal injury or death. After DCvoltage from the test equipment has beenapplied to the windings and ground, therewill be a definite static charge on the wind-ings. Reconnect Grounding Cluster to re-move static charge from the winding aftereach generator test.

7. With the Grounding Cluster in place, you areprotected from static and/or induced chargesthat may have been present in the generatorstator.Leave grounds connected for at least one min-ute so static charge can dissipate. Removeground cluster and perform PI and/or any othertests required on the stator winding. Reconnectgrounds if additional generator service is nec-essary.

8. When work on the generator set is complete,remove the Grounding Cluster in the reverseorder of installation.

9. After getting clearance from all personnel in-volved in the lock-out/tag-out procedure, re-move all lock-out devices in reverse order ofinstallation.

Page 44: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-4

Megger and PI Test

DANGER Medium-voltage, 601 to 15,000 volts,present special hazards of severe personal inju-ry or death. Even after genset shutdown, anelectrical shock hazard may still exist, causedby induced voltage within the generator orcables. Service personnel must be well-trained/qualified to work with distribution voltages.(See Generator Set Grounding Procedure in thissection.)

IMPORTANT ! The windings have been H.V.tested during manufacture and further H.V. test-ing may degrade the insulation with consequentreduction in operating life. Should it be neces-sary to demonstrate H.V. testing, for customeracceptance, the tests must be carried out at re-duced voltage levels (i.e. Test Voltage = 0.8 [2 XRated voltage + 1000]).

Megger Test: The megger test consists of applyingvoltage for up to one minute. The highest resistancevalues shown in Table 6-1 should be obtained for anew generator with dry windings. For a set that hasbeen in service, the resistance reading should notbe less than the lower value shown.

The insulation resistance values quoted are forwindings at an ambient temperature of 20C. Itshould be noted that as winding temperature in-creases, values of insulation resistance will signifi-cantly reduce. Therefore, the reference values forinsulation resistance can only be properly estab-lished with windings at a temperature of approxi-mately 20C.

An approximate guide to allow comparison with val-ues taken at other temperatures is to assume thatthe IR reduces by 50% for every 10C increase intemperature. Thus the reduction factors are:

20C x 1.0

30C x 0.5

40C x 0.25

“ “

80C x 0.015 etc.

Should the values be less than the quoted limits,drying out the generator windings is essential.

PI Test: The PI test consists of applying a voltagebetween the winding and ground for ten mInutesand recording resistance values at one minute andat ten minutes. The PI is the ratio of a ten minute

reading in megohms divided by a one minute read-ing in megohms.

The polarization index should be in the order of 2 orgreater at 20C. (PI = IR10 min / IR1 min)

If low readings are obtained, the cause should be in-vestigated and corrected before the generator set isreturned to service. If moisture is determined to bethe cause of low test readings, a winding drying pro-cess will be required (refer to genset Service manu-al for drying procedure).

1. Perform the Generator Set Grounding Proce-dure in this section.

2. Open the control box door and remove connec-tor 10 from the AVR module.

3. Remove connector 9 from the PT/CT module(AC voltage sense leads and CT leads).

4. If the RTD (resistance temperature detector)option is installed, ground all six RTD tempera-ture leads. Each RTD has three leads, one redand two white leads. Total of 18 leads must begrounded.

Main Stator:

5. Remove and separate the neutral leads of thegenerator from the generator load terminalmarked “N”.

CAUTION Make sure megger voltage isset to voltage shown in Table 6-1. Failure touse correct test voltage may result in equip-ment damage.

6. Connect the megger between one phase of thestator and ground while grounding the othertwo phases and conduct the test. Refer to Table6-1 for megger voltage selection and requiredresistance values.Repeat this step in turn for the other twophases.

Main Rotor:

7. Disconnect the main rotor and voltage sup-pressor leads from terminals F1+ and F2− onthe rotating rectifier assemblies and isolatethem from ground. Tag and mark each lead withits terminal number (F1+ or F2−).

CAUTION Make sure megger voltage isset to voltage shown in Table 6-1. Failure touse correct test voltage may result in equip-ment damage.

8. Connect the megger between one of the rotorleads and ground and conduct the test. Refer to

Page 45: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-5

Table 6-1 for megger voltage selection and re-quired resistance values.

Page 46: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-6

TABLE 6-1. GENERATOR INSULATION RESISTANCE

FRAME GENERATOR MEGGER MINIMUM RESISTANCE (MEG OHMS)FRAME

SIZEGENERATOR

VOLTAGE

MEGGERVDC

SETTINGMAIN

STATOR MAIN ROTOR

P7 600 VAC orless 500 10 − 1 10 − 1

MV7601 thru 5000 2500 100 − 50

MV7601 thru 5000

VAC 500 10 − 1

TRANSFER SWITCH

If the installation is for standby service, a transferswitch must be used for switching the load from thenormal power source to the genset (see Figure 6-1).Either a manual or automatic transfer switch may beused. Follow the installation instructions providedwith the transfer switch when connecting the loadand control wiring.

LOAD

GENSETNORMALSOURCE

FIGURE 6-1. TYPICAL LOAD TRANSFERFUNCTION

Page 47: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-7

AC WIRING

Generator Voltage Connections

The available generator output voltages and maxi-mum current ratings are specified on the generatorset nameplate. Line-to-neutral voltage is always thelower voltage shown and line-to-line voltage is thehigher rating.

These generators can be configured to the name-plate voltages as shown on the Reconnection Dia-gram located on the side access cover of the controlhousing. Many of the voltages listed will require re-configuration of the generator output leads on theconnection terminal block. This reconfigurationmust only be done by service personnel that aretrained and experienced to perform electrical instal-lation. The generator set was adjusted to produce aspecified voltage during production verification test-ing prior to shipment. The installer must alwayscheck the stator lead terminal block connectionsand perform any necessary reconnect to obtain thevoltage required.

Some generator sets are capable of producing awide range of voltages and connection configura-tions, others have specific limited capabilities. Referto wiring diagram and generator voltages (from thenameplate) when reviewing the voltage connectioninformation and use the wiring diagram suppliedwith your generator set when actually performingload connections.

CAUTION Reconfiguring generator sets tohigher voltages can exceed the voltage capabil-ity of the specific generator windings and dam-age the generator and also decrease line cur-rent, rendering line circuit breakers too large.Consult with your distributor before performingreconnection for a different voltage.

CAUTION Reconfiguring generator sets tolower voltages can reduce generator set rat-ings, and also increase line current, renderingline circuit breakers too small. Consult withyour distributor before performing reconnec-tion for a different voltage.

Load Connections

Flexible conduit and stranded conductors must beused for connections to take up movement of thegenerator set.

All loads are connected to the generator by boltingstranded load wires to the appropriate terminals onthe generator reconnection terminal block or circuitbreaker lugs. The terminals are stamped U, V, Wand N to indicate the line and neutral connections.(Reference: U, V, and W correspond with L1, L2 andL3; and N with L0 respectively).

Load Balancing

When connecting loads to the generator set, bal-ance the loads so the current flow from each line ter-minal (L1, L2 and L3) is about the same. This is es-pecially important if both single phase and threephase loads are connected. Any combination ofsingle phase and three phase loading can be usedas long as each line current is about the same, with-in 10 percent of median value and no line current ex-ceeds the nameplate rating of the generator. Checkthe current flow from each line after connections byobserving the control panel ammeter.

Current Transformers

Current transformers (CT’s) are required on gen-sets that contain AC meters. The CT’s must beinstalled as noted in the following CT InstallationRequirements.

Refer to the Reconnection Diagram to identify theoutput leads/phase that must be routed througheach CT, and also appropriate transformer postselection for meter sensing leads. The transformersare labeled CT1, CT2 and CT3 on the reconnectionwiring diagram. (The Reconnection Diagram is lo-cated on the upper side cover of the control hous-ing.)

CT Installation Requirements:

A. The CT has a dot on one side. This dot must befacing toward the generator (conventional cur-rent flowing into the dot). A dot is also used toindicate pin 1 of the CT.

B. CT1 − U load leads (A phase),CT2 − V load leads (B phase)CT3 − W load leads (C phase)

C. Route the appropriate load wires through eachCT.

D. The CT’s have dual secondaries (3 pins). TheCT secondary wire marked 1 is connected topin 1 of the CT. CT secondary wire marked 2/3is connected to pin 2 for high voltage gensets orto pin 3 for low voltage gensets. (Refer to Re-connection Diagram.)

Page 48: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-8

Grounding

The following is a brief description of system andequipment grounding of permanently installed ACgenerators within a facility wiring system. It is impor-tant to follow the requirements of the local electricalcode.

Figure 6-2 illustrates typical system grounding for a3-pole and a 4-pole automatic transfer switch (ATS).In the 3-pole ATS, note that the generator neutral isconnected to the ATS and is NOT bonded to groundat the generator. In the 4-pole ATS system, agrounding electrode conductor and a bonding jump-er are used to connect the generator neutral toground.

Make sure the genset is grounded to earth in onelocation only. On generators without a circuit break-er, ground to the point indicated on the top of thegenerator. On gensets with circuit breakers, use theground lug provided in the circuit breaker box.

WARNING Electric current can cause severepersonal injury or death. Bonding and ground-ing must be done properly. All metallic parts thatcould become energized under abnormal condi-tions must be properly grounded.

Typical requirements for bonding and grounding aregiven in the National Electrical Code, Article 250. Allconnections, wire sizes, etc. must conform to the re-quirements of the electrical codes in effect at theinstallation site.

4-POLE ATSGENERATOR SETSERVICE ENTRANCE

LOAD

3-POLE ATSGENERATOR SETSERVICE ENTRANCE

LOADTHREE-PHASE, FOUR-WIRE UTILITY, THREE-POLE ATS

THREE-PHASE, FOUR-WIRE UTILITY, FOUR-POLE ATS

FIGURE 6-2. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS

Page 49: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-9

CONTROL HEATER (OPTIONAL)

A control heater (Figure 6-3) provides a means ofhumidity /temperature control of the control box in-terior. It protects the components when the genera-tor set is subjected to varying ambient air conditionsduring extended periods of non-use. Thermostat

control de−energizes the heater when the controlbox interior reaches 75 F (24 C).

Connect the heater to a source of power that will beon during the time the engine is not running. Be surethe supply voltage and circuit amperage is correctfor the heater rating.

INPUT POWERTB10 (240/120 VAC)

75 F (24 C)THERMOSTAT

150W STRIPHEATER

TO 120 VACSUPPLY

FIGURE 6-3. OPTIONAL CONTROL HEATER

Page 50: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-10

COOLANT HEATER (OPTIONAL)

Coolant heaters keep the engine coolant warmwhen the engine is shut down. It heats and circu-lates the coolant within the engine. This reducesstartup time and lessens engine wear caused bycold starts. It is electrically operated and thermo-statically controlled.

CAUTION The coolant heater must not be op-erated while the cooling system is empty orwhen ball valves are closed or damage to theheater will occur.

Figure 6-4 shows a typical coolant heater. Connectthe heater to a source of power that will be on during

the time the engine is not running. Be sure the sup-ply voltage and circuit amperage is correct for theheater element rating.

Make sure that all three ball valves are opened be-fore connecting power to the heaters. With ballvalves closed, heated coolant will not circulatethrough the engine. Extended operation with ballvalves closed can damage coolant heaters.

Note: A battery charger is required to prevent batterydischarge. The heater control relay draws 83 mA ofcurrent when the heater(s) is off. The heater is offwhen the engine has reached the proper temperatureor the engine is running.

COOLANTFLOW

AC ELECTRICAL CONNECTIONBOX (ELECTRICAL DIAGRAM

INSIDE COVER)

THERMOSTAT

COOLANT HEATERAC POWER LINE

DC CONTROLLINE

COOLANTFLOW

TO MAINHARNESS

BALL VALVE (OPENPOSITION SHOWN)

BALL VALVE (OPENPOSITION SHOWN)

BALL VALVE (OPENPOSITION SHOWN)

FIGURE 6-4. TYPICAL COOLANT HEATER

Page 51: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

6-11

GENERATOR HEATER (OPTIONAL)

A generator heater(s) is used to help keep the gen-erator free of condensation when the generator setis not running. During cool and humid conditions,condensation can form within a generator, creatingflashing and a shock hazard.

WARNING Water or moisture inside a genera-tor increases the possibility of flashing andelectrical shock, which can cause equipmentdamage and severe personal injury or death. Donot use a generator which is not dry inside andout.

Figure 6-5 illustrates the installation of two heaterelements. Connect the heater(s) to a source of pow-er that will be on during the time the engine is notrunning. Be sure the supply voltage and circuit am-perage is correct for the heater element rating.

HEATER LEADS

HEATER

TERMINALBLOCK

HEATERS

VOLT/WATTSLABEL

HEATER LEADS

TERMINAL BOXHEATER

FIGURE 6-5. TYPICAL GENERATOR HEATER INSTALLATION

Page 52: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-1

7. Prestart Preparation

GENERAL

Before attempting the initial start of the generatorset, be sure to complete the Installation Checklist inSection 8.

INPOWER SERVICE TOOLGENERAL INFORMATION

InPower is a PC based service tool for the Power-Command 3201 Control (PCC). Use InPower to:

Make adjustments to the controls trims and set-tings.

Perform diagnostics and monitoring.

Review event history.

Create a capture file of the controls trims andsettings.

Update control calibrations (InPower PRO ver-sion).

Refer to INPOWER User’s Guide for specifics.

InPower Adjust Mode

The adjustment feature allows you to make adjust-ments to genset parameters, calibrations and set-tings. There are several groups of adjustment pa-rameters; note that not all gensets will have thesame adjustments available.

InPower Capture File Description

InPower provides a method of extracting (capturing)a device’s parameter values. Capturing saves de-vice information in a file that is identified with a .CAPextension.

Capture files are used to store a copy of the genset’sparameter values. During genset installation, it issuggested that a capture file be made before and af-ter changes are made to the genset operating pa-rameters. This information can be a very usefulwhen troubleshooting the genset (determine if pa-rameters/settings have been modified after installa-tion) and when replacement of the Base board isnecessary. The capture file can be used as a tem-plate to write the previous settings to the new Baseboard software.

Page 53: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-2

ELECTRICAL SYSTEM

Make sure all electrical connections are secure andall wiring is complete and inspected. Replace andsecure any access panels that may have been re-moved during installation.

Battery Connections

WARNING Accidental starting of the generatorset can cause severe personal injury or death.Make sure that the Run/Off/Auto switch on thecontrol panel is set to the Off position beforeconnecting the battery cables.

Starting the unit requires 24 volt battery current, us-ing four, 12 volt batteries (see Specification sec-tion). Connect the batteries in series (negative postof first battery to the positive post of the second bat-tery) as shown in Figure 7-1.

Necessary battery cables are on the unit. Servicebatteries as necessary. Infrequent use (as in emer-

gency standby service), may allow battery to self-discharge to the point where it cannot start the unit.If installing an automatic transfer switch that has nobuilt-in charge circuit, connect a separate tricklecharger. Cummins Power Generation automatictransfer switches include such a battery chargingcircuit.

WARNING Ignition of explosive battery gasescan cause severe personal injury or death. Al-ways connect negative (−) battery cable last toprevent arcing.

WARNING Ventilate battery area before work-ing on or near battery. Arcing at battery termi-nals, light switch or other equipment, flame, pi-lot lights and sparks can ignite battery gas. Donot smoke, or switch trouble light ON or OFFnear battery. Discharge static electricity frombody before touching batteries by first touchinga grounded metal surface.

BATTERY POSITIVE(+) CONNECTION

BATTERY NEG-ATIVE (−) CON-

NECTION

USE TWO, 12VOLT BATTERIES

FOR EACHSTARTER

+

−−

+

FIGURE 7-1. GENSET BATTERY CONNECTIONS

Page 54: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-3

CONTROL PRESTART CHECKS

All generator set configuration options are set at thefactory except for site related options, (e.g., Start/Stop Delays, Cycle Crank, Customer Fault names,etc.) and the optional Power Transfer Control (PTC)feature.

Adjustments of these options are divided into twocategories within the menu driven system. Thesetwo categories are Setup and Adjust.

The Setup submenus are intended for qualified ser-vice personnel only. The Adjust submenu is in-tended for qualified service and site personnel only.For this reason, a separate password is required tomodify the Setup submenus. The Adjust submenumay or may not require a password (site depen-dent).

CAUTION Improper calibration or adjustmentof the control can cause equipment malfunctionor damage. Calibration and adjustment must beperformed by technically qualified personnelonly.

The following procedures describe how to modifythe Adjust submenu options and if installed, thePTC Setup submenus, which are required to com-plete the genset installation.

The Adjust submenu allows you to calibrate thegenerator set voltage/frequency and start/stop timedelays. For the prestart checks, adjustment of onlythe start/stop delays is required.

The PTC Setup submenus contain parameters withadjustable default values that should be checkedand modified if necessary for this site. The descrip-tions in this section include ranges for the parame-ters and default values for this feature.

Saving Menu Changes

Changes are automatically saved when the menu isexited.

Page 55: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-4

Language/Units Selection Menu

During any control panel operation, you can selectone of three languages and change how units aredisplayed by pressing the two lower menu buttons(one on each side of display). When pressing thesetwo buttons simultaneously, the language/unitsmenu will appear (Figure 7-2). After making desiredselections, press the ENTER button in this menu tochange and save the selections.

Note: Use the + button to select the desired option foreach field. Use the arrow () button to move to thenext field. Selected field is highlighted.

Language: Used to select desired language (de-fault = English).

Local/Remote Field: This selection must be set toLocal when the graphical display is mounted on thegenerator set front control panel or Remote whenmounted remotely of the generator set.

Temp: Used to select F or C for temperature read-ings.

Pressure Fluid: Used to select PSI, KPA, BAR or INfor pressure readings.

Pressure Gas: Used to select INHG or MMHG forpressure readings.

Flow Air: Used to select CFM or CMM for air flowreadings.

ENTER

LANGUAGE ENGLISHLOCATION LOCALTEMP FPRESS FLD PSIPRESS GAS INHGFLOW AIR CFM

+

FIGURE 7-2. LANGUAGE/UNITS MENU

Page 56: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-5

Password Menu

To allow the site personnel to modify only the Adjustsubmenu and not the Setup submenus, two pass-words are assigned within the system software. AnApplication password is used for the Setup subme-nus and a User password is used for the Adjust sub-menu.

The two passwords are assigned during the initialinstallation of the generator set (via InPower) andwill vary between sites. The installer must makesure that the passwords are available to the ap-propriate personnel.

Note: When the generator set is first installed, the Ap-plication and User password are both set to GENSETto allow initial modification of the Setup and Adjustsubmenus. Assign new passwords when site instal-lation is complete.

When viewing the Adjust menu, pressing the + or −button will display the User Password menu.

When viewing a Setup menu, pressing the + or −button will always display the Application Passwordmenu.

After entering the correct password, the system willallow you to modify the submenus. To help prevent

unauthorized adjustment, the entered password isvalid for 10 minutes after the last button is pressed(i.e., the password will need to be reentered afterthe ten minute time−out.

Entering Password

To enter the password:

1. Display submenu to modify.

2. Press either the + or − button within the dis-played submenu. The Password menu ap-pears.

3. Press the + and − button to select the first char-acter of the password (A−Z or 0−9). (Enter Ap-plication password for Setup submenus; EnterUser password for Adjust submenu.)

4. Press the button to select the next characterfield. Selected character field is highlighted.

5. Repeat steps 3 and 4 to enter remaining pass-word characters.

6. Press the Enter button after entering the pass-word. The submenu selected in step 1 will re-appear.

7. After making desired changes to submenu, exitsubmenu to save changes.

+ OR − BUTTON

ENTER

ENTER APPLICATIONPASSWORD

+

XXXXXXXX

+ OR − BUTTON

ENTER

ENTER USER PASSWORD

+

XXXXXXXX

SETUP SUBMENU PASSWORD MENU ADJUST SUBMENU PASSWORD MENU

FIGURE 7-3. PASSWORD MENUS

Page 57: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-6

ADJUST SUBMENU

Figure 7-4 shows the main menus (Menu A andMenu B) of the system control and the Adjust sub-menu.

To display the Adjust submenu, press the MORE>>button in Menu A and then the ADJUST button inMenu B.

The Adjust procedure is intended for qualified ser-vice personnel and site personnel only and may re-quire a USER password. If a password is required,the USER password menu will appear when you tryto modify the Adjust submenu. (Refer to PASS-WORD Menu in this section to enter password.

Changes are automatically saved when you exit thismenu.

Note: Use the + and − buttons to increase or decreasethe values in the following fields. Use the arrow ()button to move the cursor within a field or to the nextfield.

START DELAY: This delay applies only to remotestarting in the Auto mode. The Start Delay adjust-ment range is 0 to 300 seconds.

STOP DELAY: This delay applies only to remotestopping in the Auto mode. The Stop Delay adjust-ment range is 0 to 600 seconds.

VOLTAGE: Used to adjust the output voltage 5%.

FREQUENCY: Used to adjust the frequency 3 Hz.

VOLTAGE/SPEED DROOP: These two submenusapply to a genset that has the paralleling option andis configured to operate in droop mode. These ad-justments must be performed by technically quali-fied personnel only.

Page 58: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-7

ENGINE

ALTERNATOR

CONTROL

MORE>>

_\_

HISTORY/ABOUT

SETUP

ADJUST

BUS DATA

BACK<<

MENU A

MENU B

+

ADJUST

ADJUST:START DELAY 5 SECSTOP DELAY 11 SECVOLTAGE 208 1.2 %FREQ 60.0 HZ -0.0 HZ

+

ADJUST:STANDBYVOLTAGE DROOP OFFBUS L1 480 VPOWER FACTOR 0.80VOLT 4.99 %

+

ADJUST:STANDBYSPEED DROOP OFFBUS FREQ 60.0 HZ TOTAL KW 300 KWFREQ 60.0 0.40 HZ

MENUB

ADJUST

FIGURE 7-4. ADJUST SUBMENU

Page 59: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-8

POWER TRANSFER CONTROL MAINMENUS

Figure 7-5 shows the main menus (Menu A andMenu B) of the system control, the two setup menusand the two main menus of the optional PowerTransfer Control (PTC) feature.

To adjust PTC system parameters, press the ap-propriate PTC main menu button and refer to thepage number shown in Figure 7-5 for detailed infor-mation related to the submenu selected.

GOVERNING/VOLT REG

CUSTOMER FAULTS

CALIBRATION

ISOLATED BUS

UTILITY

ENGINE

ALTERNATOR

CONTROL

MORE>>

_\_

HISTORY/ABOUT SETUP

ADJUST

BUS DATA

BACK<<

MENU A MENU B

NEXTMENU

MENUB

�POWER TRANSFER SETUP

NEXTMENU

UTILITY SENSORS

GENSET SENSORS

TIMERS

PAGE7-8

PAGE7-10

PAGE7-12

NEXTMENU

TEST/EXERCISE �PAGE7-13

PTC MAIN MENU 1

PTC MAIN MENU 2

FIGURE 7-5. PTC SETUP MAIN MENUS

Page 60: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-9

UTILITY SENSORS SUBMENUS

If you press the “UTILITY SENSORS” button in thePTC Main Menu 1, the Utility Sensors submenuswill appear (Figure 7-6).

The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field. For a complete explanation of thesefields, refer to heading “PTC Detailed Field Descrip-tions“ in this section.

Note: Use the + and − buttons to increase or decreasethe values in the following fields. Use the arrow ()button to move the cursor within a field or to the nextfield. Exit menu to save changes.

U PT VOLT LL: Enter the value of the utility line-to-line voltage which yields 100% voltage at the termi-nals of the utility (bus) PT module.

Range: 1−15000V, adjustable by standard nominalvoltage values, 100V, 10V and 1V increments (1V).

The 100% voltages for each of the four possible util-ity (bus) PT modules are as follows, based on mod-ule dash number:−01 = 208 volts LL−02 = 416 volts LL−03 = 600 volts LL−04 = 120 volts LL

Example 1: Nominal Utility voltage is 480V. Thismeans that utility (bus) PT module number −02should be used. The voltage which will yield 100%volts at this PT module is 416 per the above table.Thus enter 416V.

Example 2: Nominal Utility voltage is 4160V. A pri-mary stage transformer with a ratio of 4200/240 isused. This means that utility (bus) PT module num-ber −01 should be used. The voltage which will yieldthe 100% volts (208V from above table) is calcu-lated as follows:208 x (4200/240) = 3640. Thus enter 3640V.

U NOM VOLT LL: Enter the nominal utility line-to-line voltage. For example, 480, 4160, etc.. Range:1−15000 V, adjustable by standard nominal voltagevalues, 100V, 10V and 1V increments (1V).

U CT RATIO: Enter the CT Ratio of the Utility L2 CT.This is the Ratio to 1 Amp. Range: 1−18000 (1A).

CAUTION This CT must be rated for 1 Amp out-put (e.g. NOT 5 Amp). Be sure CT secondary cir-cuit has burden resistor or a shorting jumper inplace before putting power through the CT. Ex-ample: CT Ratio = 2650:1. Thus enter 2650.

U SENSOR TYPE: Enter the line-to-line (L-N) for 3phase line-neutral voltage sensing or line-to-line(L-L) for 3 phase line-line voltage sensing. This ap-plies to both the utility undervoltage and overvoltagesensors. Range: L−L, L−N (L−N).

U <wye> <delta>: Enter utility connection type.Range: Delta, Wye (Wye).

U UNLOADED KW: Enter the kW on utility Line 2 atwhich the utility is considered as unloaded. This isthe L2 kW level at which a closed transition softtransfer will disconnect from the utility.

UTILITY UNDERVOLTAGE: Non-adjustable field,always enabled.

UTILITY OVERVOLTAGE, FREQUENCY: Used toenable or disable menu function. Choose Enabledor Disabled (Enabled).

UV PICKUP: Enter a number between 85 and 100%of the nominal voltage (90%).

UV DROP OUT: Enter a number between 75 and98% of the under-voltage pick-up percentage(90%).

UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (0.5 seconds).

UV MIN PHASE: Displays the lowest line voltage ofthe three utility phases.

Page 61: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-10

OV PICKUP: This adjusts the over-voltage pickupas a percentage of the over-voltage drop-out. Entera number between 95 and 99% (95%).

OV DROP OUT: Enter a percentage between 105and 135% of the nominal voltage (110%).

OV DELAY: Enter a range between 0 and 120 sec-onds (3 seconds).

OV MAX PHASE: Displays the highest line voltageof the three utility phases.

CENTER (FREQ): Enter a frequency between 45and 65 Hz (60 Hz).

PICK UP (FREQ): Enter a percentage between 5and 20% of the nominal frequency (10%).

DROP OUT (FREQ): Enter a percentage between 1and 5% of the nominal frequency (1%).

DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0 seconds).

FREQUENCY: This field displays the sensed utilityline frequency.

UTILITY SENSORS

U PT VOLT LL 416U NOM VOLT LL 480U CT RATIO: 1 1000U SENSOR TYPE L−L

U UNLOADED KW 50 KW

+

UTILITY UV: ENABLED% VLL

PICK UP 95 475DROP OUT 85 465DELAY 0.5 SMIN PHASE 470

+

UTILITY OV: DISABLED% VLL

PICK UP 95 487DROP OUT 110 490DELAY 3.0 SMAX PHASE 485

+

UTILITY FREQ: DISABLEDCENTER 60 HZPICK UP 10 %DROP OUT 1 %DELAY 1.0 SFREQUENCY 60.5 HZ

+

FIGURE 7-6. UTILITY SENSORS SUBMENUS

Page 62: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-11

GENSET SENSORS SUBMENUS

If you press the “GENSET SENSORS” button in thePTC Main Menu 1, the Genset Sensors submenuswill appear (Figure 7-7).

The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field. For additional information regardingthese fields, refer to heading “PTC Detailed FieldDescriptions“ in this section.

Note: Use the + and − buttons to increase or decreasethe values in the following fields. Use the arrow ()button to move the cursor within a field or to the nextfield. Exit menu to save changes.

G NOM VOLT LL: Non-adjustable field, displayscurrent setting of genset nominal voltage. (See Ad-just submenu to adjust the output voltage 5%.)

G SENSOR TYPE: Enter the line-to-line (L-N) for 3phase line-neutral voltage sensing or line-to-line(L-L) for 3 phase line-line voltage sensing. This ap-plies to both the genset undervoltage and overvol-tage sensors. Range: L−L, L−N (L−N).

G BASE LOAD: Enter the maximum load the gen-set will carry during a closed transition. Range:0−100% (80%).

G RAMP LOAD: Enter the ramp time for the gensetramp load rate during a closed transition soft loadtransfer. Ramp rate is +100%kW divided by this timesetting. Range: 0−900 seconds (20 sec).

G RAMP UNLOAD: Enter the ramp time for thegenset ramp unload rate during a closed transtionsoft load retransfer. Ramp rate is −100%kW dividedby this time setting. Range: 0−900 seconds (20sec).

G UNLOADED KW: Enter the %kW (based onstandby rating) that the genset is considered un-loaded. This is the %kW level at which a closed tran-sition soft retransfer will disconnect from the genset.Range: 0−100% (5%).

GEN UNDERVOLTAGE: Non-adjustable field, al-ways enabled.

GEN OVERVOLTAGE, FREQUENCY: Used to en-able or disable menu function. Choose Enabled orDisabled (Enabled).

UV PICKUP: Enter a number between 85 and 100%of the nominal voltage (90%).

UV DROP OUT: Enter a number between 75 and98% of the under-voltage pick-up percentage(90%).

UV DELAY: Enter a time between 0.1 and 5.0 sec-onds (4 seconds).

UV MIN PHASE: Displays the lowest line voltage ofthe three genset phases.

Page 63: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-12

OV PICKUP: This adjusts the over-voltage pickupas a percentage of the over-voltage drop-out. Entera number between 95 and 99% (95%).

OV DROP OUT: Enter a percentage between 105and 135% of the nominal voltage (110%).

OV DELAY: Enter a range between 0 and 120 sec-onds (3 seconds).

OV MAX PHASE: Displays the highest line voltageof the three genset phases.

CENTER (FREQ): Enter a frequency between 45and 65 Hz (60 Hz).

PICK UP (FREQ): Enter a percentage between 5and 20% of the nominal frequency (10%).

DROP OUT (FREQ): Enter a percentage between 1and 5% of the nominal frequency (1%).

DELAY (FREQ): Enter a time between 0.1 and 15.0seconds (5.0 seconds).

FREQUENCY: Displays the sensed genset line fre-quency.

GENSET SENSORS

G NOM VOLT LL 480G SENSOR TYPE L−LG BASE LOAD 80.0%G RAMP LOAD 20 SG RAMP UNLOAD 20 SG UNLOADED KW 5 %

+

GEN UV: ENABLED% VLL

PICK UP 95 475DROP OUT 85 465DELAY 1.0 SMIN PHASE 470

+

GEN OV: DISABLED% VLL

PICK UP 95 487DROP OUT 110 490DELAY 8.0 SMAX PHASE 485

+

GEN FREQ: DISABLEDCENTER 59 HZPICK UP 12 %DROP OUT 2 %DELAY 5.0 SFREQUENCY 60.0 HZ

+

FIGURE 7-7. GENSET SENSORS SUBMENUS

Page 64: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-13

TIMERS SUBMENU

If you press the “TIMERS” button in the PTC MainMenu 1, the Timers submenu will appear (Figure7-8).

The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field. For a complete explanation of thesefields, refer to heading “PTC Detailed Field Descrip-tions“ in this section.

Note: Use the + and − buttons to increase or decreasethe values in the following fields. Use the arrow ()button to move the cursor within a field or to the nextfield. Exit menu to save changes.

START DELAY: Sets time delay for genset enginestart. Prevents nuisance genset starting during briefpower interruptions.

Enter a range from 0 to 300 seconds (0 seconds).

STOP DELAY: Sets the time delay for engine cool-down following a re-transfer. This stop delay worksin conjunction with and is activated at the same timeas the normal cooldown timer. (Will extend normalcooldown timer if entered time is greater.)

Enter a time from 0 to 600 seconds (0 seconds).

TRANSFER: In a Normal to Emergency transferthis function allows the genset to stabilize before theload is applied. Enter a time from 0 to 120 seconds(10 seconds).

RETRANSFER: In a Emergency to Normal transferthis function allows the utility to stabilize before theload is applied.

Enter a time from 0 to 1800 seconds (600 seconds).

PGM TRANSIT: Sets the time delay for Pro-grammed Transition. A setting of 0.0 disables theprogram.

Enter a time from 0 to 60 seconds (0 seconds).

MAX PARALLEL: Sets the maximum time duringclosed transition that utility and genset can be paral-leled.

Enter a time from 0 to 1800 seconds (20 seconds).

TIMERS

START DELAY 60 SSTOP DELAY 60 STRANSFER 10 SRETRANSFER 900 SPGM TRANSIT 5 SMAX PARALLEL 30 S

+

FIGURE 7-8. TIMERS SUBMENU

Page 65: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-14

TEST/EXERCISE SUBMENU

If you press the “TEST/EXERCISE” button in thePTC Main Menu 2, the Test/Exercise submenu willappear (Figure 7-9).

The following field descriptions show the valid fieldentries and default value (shown in parenthesis) foreach field.

Note: Use the + and − buttons to increase or decreasethe values in the following fields. Use the arrow ()button to move the cursor within a field or to the nextfield. Exit menu to save changes.

MODE: Indicates the generator set application typefor PTC option.

OT-PGM TRAN − Open transition load transfer.CT-MOMENT − Closed transition load transferwith momentary (<100ms) overlap.CT-SOFT − Closed transition load transfer withload ramping.

TEST WITH LOAD: Feature allows genset Test se-quence, which is initiated through the Remote Start(TEST) switch, to operate with or without load. De-fault: OFF

EXER WITH LOAD: Feature allows genset Exer-cise sequence, which is initiated through controlpanel Exercise button to operate with or withoutload. Default: OFF

TEST/EXERCISE

MODE CT-SOFT

TEST WITH LOAD OFFEXER WITH LOAD OFF

+

FIGURE 7-9. TIMERS SUBMENU

Page 66: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-15

PTC DETAILED FIELD DESCRIPTIONS

WARNING Improper calibration or adjustmentof electronic control modules can cause death,severe personal injury, and equipment or prop-erty damage. Calibration and adjustment ofthese components must be performed by tech-nically qualified personnel only.

Start Delay: This start time delay is adjustable from0 to 300 seconds. This brief time delay prevents thegenerator set from starting during short power inter-ruptions. Timing starts at the utility power interrup-tion. If the duration of interruption exceeds the delaytime, the control system starts the generator.

Stop Delay: This stop time delay is adjustable from0 to 600 seconds. The Stop Delay begins timingwhen the load is retransferred to the utility.

At the end of the delay, the stop signal is sent to thegenerator set. This stop delay works in conjunctionwith and is activated at the same time as the normalcooldown timer. (Will extend normal cooldown timerif entered time for Stop Delay is greater.)

Transfer: This transfer time delay begins whengenset voltage and frequency reach the settings ofthe control. After the delay, the PTC transfers theload to the utility. This brief time delay allows thegenerator set to stabilize before the load is applied.It has an adjustable range of 0 to 120 seconds. Thedefault value is 10 seconds.

Retransfer: This retransfer time delay begins themoment utility line voltage and frequency return tospecified values. After the delay, the PTC can re-transfer the load to the utility. The delay allows theutility to stabilize before retransfer. It has an adjust-able range of 0 to 1800 seconds. The default valueis 600 seconds.

Page 67: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-16

Under-Voltage Sensing

The PTC feature includes under-voltage sensors forthe utility and the genset. When a sensor detects alow voltage condition over a specified time period, itinitiates a transfer. When the source voltage returnsto an acceptable value again, the sensor initiates aretransfer.

These parameters are adjustable. The under-volt-age sensing range for a falling voltage (drop-out) is75 to 98% of the pick-up voltage setting. The defaultvalue is 90%. The pick-up range for a rising voltageis 85 to 100% of the nominal voltage setpoint. Thedefault value is 90%. The adjustable range for thetime delay period is 0.1 to 5.0 seconds. The defaultdelay time is 4 seconds. See Figure 7-10 for an ex-ample using the default values.

FIGURE 7-1.

VOLTS

NOMINALSETPOINT(240V)

PICK-UPSETTING(216V)

DROP-OUTSETTING(194V)

90% OFNOMINAL

90% OFPICK-UP

EXAMPLE USING DEFAULT SETTINGSFOR NOMINAL VOLTAGE OF 240 VAC

FIGURE 7-10. UNDER-VOLTAGE SENSING

Over-Voltage Sensing

The PTC feature includes over-voltage sensors forthe utility and the genset that can be disabled andnot used. When a sensor detects a high voltagecondition over a specified time period (delay), it initi-ates a transfer. When the source voltage falls to anacceptable value again, the sensor initiates a re-transfer.

These parameters are adjustable. The over-voltagesensing range (drop-out) for a rising voltage is 105to 135% of the nominal voltage setpoint. The defaultvalue is 110%. The pick-up range for a falling volt-age is 95 to 99% of the drop-out setting. The defaultvalue is 95%. The adjustable range for the delaytime period is 0.0 to 120.0 seconds. The defaultdelay time is 3.0 seconds. See Figure 7-11 for anexample using the default values.

FIGURE 7-2.

NOMINALSETPOINT(240V)

PICK-UPSETTING(251V)

DROP-OUTSETTING(264V)

110% OFNOMINAL

95% OFDROP-OUT

EXAMPLE USING DEFAULT SETTINGSFOR NOMINAL VOLTAGE OF 240 VAC

VOLTS

FIGURE 7-11. OVER-VOLTAGE SENSING

Page 68: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

7-17

Frequency Sensing

The PTC feature includes frequency sensors for theutility and the genset that can be disabled and notused. When a sensor detects a high or low frequen-cy condition over a specified delay time period, it ini-tiates a transfer. When the frequency returns to anacceptable value again, the sensor initiates a re-transfer.

FIGURE 7-3.

EXAMPLE USING DEFAULT SETTINGSFOR NOMINAL FREQUENCY OF 60 HZ

60 HZ

66 HZ

66.7 HZ

54 HZ

53.5 HZDROP-OUT FREQUENCIES

PICK-UP FREQUENCIES

FIGURE 7-12. FREQUENCY SETTING

These parameters are adjustable. The nominal fre-quency can be set between 45.0 and 65.0 Hz. Thedefault frequency is 60 Hz. The acceptable frequen-cy bandwidth (pick-up) is 5 to 20% of the nominalfrequency setpoint. The default value is 10%. Thedrop-out frequency is 1 to 5% beyond the pick-up.

The default value is 1%. The range for the delaytime period is 0.1 to 15 seconds. The default delaytime is 5 seconds. The frequency sensing feature isenabled by default. This feature can also be dis-abled.

Programmed Transition

Programmed Transition introduces a delay (TDPT)during an “open transition” transfer or retransfer.Programmed transition causes a pause in the neu-tral position for an adjustable interval of time. In thisposition, the load is not connected to either the utilityor the genset. This delay allows residual currentfrom inductive loads to decay to an acceptable levelbefore transfer is completed.

The length of time that the utility or genset breaker/contactors are both in the neutral (open) positioncan be adjusted from 0 to 60 seconds. The defaultvalue is 0 seconds. The proper adjustment is a func-tion of the load. This feature is enabled by default.

This feature is not used in closed transition parallel-ing applications.

STARTING

Refer to the generator set Operator’s manual for im-portant safety precautions and recommended pro-cedures for starting the genset and verifying properoperation. Start the generator set and verify all en-gine and generator gauges are displaying the cor-rect values.

Page 69: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

8-1

8. Installation Checklist

GENERAL

� Generator set wattage capacity is sufficient tohandle maximum anticipated load.

� At least 3 feet of clearance (or greater for hous-ing door) is provided around entire generatorset for servicing and ventilation.

� Generator set is located in an area not subjectto flooding.

� All operating personnel have read and are fa-miliar with Operator’s manual.

� All operators have been thoroughly briefed onpreventive maintenance procedures.

� All operators have read and understand all Im-portant Safety Instructions in Operator’s manu-al.

GENERATOR SET SUPPORT

� Floor, roof or earth on which the generator setrests is strong enough and will not allow shiftingor movement. Observe local codes on soilbearing capacity due to freezing and thawing.

� Generator set is properly supported and re-tained to approved base.

� Supporting base is large enough and is of non-combustible material − extends 6-inches allaround set.

COOLING AIR FLOW

� Generator set air inlet is faced into direction ofstrongest, prevailing winds.

� Air inlet openings are unrestricted and at least1−1/2 times larger than air outlet area.

� Cooling air outlet is on downwind side of build-ing (if not, wind barrier is constructed).

� Proper ducting material (sheet metal, canvas)is used between radiator and air outlet.

DIESEL FUEL SYSTEM

� Fuel tanks meet or exceed all Local, State orNational codes.

� Fuel lines are properly installed, supported andprotected against damage.

� Approved flexible fuel line is installed betweenmain fuel supply line and generator set’s fuelsystem, near the generator set, to protect thefuel system from damage caused by vibration,expansion and contraction.

� Strainer or fuel screen (100 to 120 mesh) isinstalled in the fuel supply line to protect the fuellift pump, day tank transfer pump or float valveseat from fuel supply tank debris.

� Automatic fuel supply line shutoff valves areinstalled to prevent fuel flow in case of leaks.

� No shutoff valves are installed on engine fuelreturn line.

� External fuel pumps are connected and opera-tional at all times (generator set started or shutdown).

� Fuel system is properly primed.

� No fuel leaks are found in supply line or enginefuel system.

Page 70: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

8-2

EXHAUST SYSTEM

� Operators are thoroughly briefed on the dan-gers of carbon monoxide gas.

� Areas around set are well ventilated. No possi-bility of exhaust fumes entering building doors,windows, or intake fans.

� Exhaust gases are piped safely outside andaway from building.

� The correct length of approved rigid pipe is con-nected to the generator set flexible pipe usingapproved securing methods with no weightresting on engine exhaust components. Thereare no bends in flex section.

� Condensation drain is provided in lowest sec-tion of exhaust piping.

� Exhaust piping is insulated to guard againstburns to personnel.

� Exhaust piping passing through walls or ceil-ings have approved fire-proof materials andare in compliance with all codes.

� Exhaust piping is large enough in diameter toprevent excessive back pressure on engine.

AC AND DC WIRING

� Wire sizes, insulation, conduits and connectionmethods all meet applicable codes.

� AC and DC wires are separated in their ownconduit to prevent electrical induction.

� All load, line and generator connections areproper and correct.

� Flexible conduit between generator set andbuilding or surrounding structure.

GENERATOR SET PRESTART

� Generator set engine is properly serviced withoil and coolant.

� Batteries are properly installed, serviced andcharged.

� Battery charger and engine coolant heater areconnected and operational.

� All generator set covers and safety shields areinstalled properly.

� All fuel and coolant shutoff valves are opera-tional.

� Created control capture file of the genset’s pa-rameter values before and after modifications.

Page 71: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-1

9. Fan Belt Alignment

GENERAL

The following procedure describes how to align thefan drive pulleys of the radiator cooling system.

SPECIAL TOOLS

This installation requires the following tools:

8 mm hexagon wrench

Straightedge at least 48 inches (1219 mm) long

Large pry bar to align radiator to skid

CAUTION Before disconnecting batterycable(s), press the Emergency Stop button andwait at least 30 seconds. Engine performancemay be affected (e.g., engine dying or hard start-ing) if battery cable(s) is removed during the 30second waiting period. Service personnel maybe required to correct fault.

WARNING Ignition of explosive battery gasescan cause severe personal injury or death. Arc-ing at battery terminals, light switch or otherequipment, flame, pilot lights and sparks can ig-nite battery gas. Do not smoke, or switch troublelight ON or OFF near battery. Discharge staticelectricity from body before touching batteriesby first touching a grounded metal surface.

Ventilate battery area before working on or nearbattery—Wear goggles—Stop genset and dis-connect charger before disconnecting batterycables—Disconnect negative (−) cable first andreconnect last.

CAUTION Disconnect battery charger from ACsource before disconnecting battery cables.Otherwise, disconnecting cables can result involtage spikes damaging to DC control circuitsof the set.

WARNING Accidental starting of the generatorset can cause severe personal injury or death.Prevent accidental starting by disconnectingthe negative (−) cable from the battery terminal.

Align Cooling System Fan Drive

Align the fan drive after the genset is mounted, filledwith coolant and leveled (see Section 3). The fandrive pulleys must be aligned for proper fan driveoperation.

1. Place the O/Manua/Auto switch on the controlpanel to the O (Off) position.

2. Disable the starting system of the generatorset:

a. Disconnect the battery charger from its ACsource.

b. Press the Emergency Stop button and waitat least 30 seconds before completingStep c.

c. Disconnect negative (−) cables from thestarting batteries and install a lockout de-vice on the battery cable ends. (For en-gines equipped with an air-powered start-ing system, close air valve and install valvelocking device.)

3. Remove the left and right side fan drive guards(Figure 9-1) to access fan drive system.

Page 72: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-2

RIGHT SIDEGUARD

LEFT SIDEGUARD

FIGURE 9-1. FAN DRIVE GUARD (LEFT/RIGHT SIDE)

Page 73: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-3

4. 5. Check the align-ment using a long straightedge (not supplied).The straightedge should be flat against the ver-tical surface of the engine pulley near the cen-ter. See Figure 9-2. The fan drive pulley shouldbe 0.25” nominal toward engine from straightedge.

6. If alignment isrequired, continue with step 8. If OK, continuewith step 14.

FAN

PILLOW BLOCKBEARING

FANPULLEY

ENGINECRANKSHAFT

PULLEY

STRAIGHTEDGE

FANSHROUD

RING

FAN PULLEYBUSHING

THREADEDHOLE

FANSHROUD

RING

0.25 INCH

BUSHINGSCREWS

FIGURE 9-2. FAN DRIVE PULLEY ALIGNMENT

Page 74: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-4

7. 8. Remove the fanbelt. This procedure requires two people.

WARNING The fan belt idler is under ten-sion and can cause severe personal injury.Do not allow your hands to get between theidler and the belt or the fan hub.

Use an 8-point socket and breaker bar or alarge wrench to hold the idler in position againstthe spring tension (Figure 9-3). Turn thewrench until the idler pulley position is sufficientto remove the belt. With the belt removed fromthe pulley, slowly release spring tension of idlerarm.

9. 10. To align the fandrive pulley so that it is 0.25” toward enginefrom the crankshaft pulley:

A. Use pencil to mark current location of fandrive pulley on shaft.

B. Mark estimated (new) location on shaft,determined by width of gap found inStep 1.

C. Remove the two screws from the fan pulleybushing. Install one of these screws intothe threaded hole located between the twoscrews that were removed. (Figure 9-2).Tighten the screw to separate bushingfrom pulley and remove the screw.

D. Move bushing to the new location mark.E. Install the two screws into the bushing and

tighten alternately to 67 ft-lbs (91 Nm)torque.

F. Recheck alignment and repeat procedureuntil alignment is achieved.

Perform a final check by rotating the fan slowlyby hand and make sure the specified clearanceis achieved. Make sure any loosened shroud orsafety guard fasteners are retightened.

11. 12. Install the drivebelt. This procedure requires two people.

WARNING The fan belt idler is under ten-sion. Do not allow your hands to get be-tween the idler and the belt or the fan hub.Personal injury will result.

Use an 8-point socket and breaker bar or alarge wrench to hold the idler in position againstthe spring tension (Figure 9-3). Turn thewrench until the idler pulley position is sufficientto position the belt in front of the idler pulley.Align the grooves of the belt on the ribs of thepulley and shaft and then slowly release springtension onto belt.

The spring-loaded idler used on this design au-tomatically maintains the correct belt tension.

13. 14. Install the leftand right side fan drive guards (Figure 9-1) thatwere removed in step NO TAG.

15. 16. Check to makesure that all fan guards are in place and secure.You should not be able to touch any moving partwith guards properly installed.

WARNING Contact with fan, belt, or pul-leys can result in severe personal injury. Allshroud and guard pieces must be properlyfastened in place to prevent unintendedcontact.

TURN WRENCH IN DIRECTION OF ARROWUNTIL SPRING TENSION IS RELIEVED

FIGURE 9-3. FAN BELT INSTALLATION

Page 75: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-5

Run The Generator Set

The final check is to observe the drive belt when thegenset is running.

1. When starting the engine for the first time aftercompleting the generator set site installation,confirm that the drive belt is properly seated inall grooves in both pulleys. This only requiresvisual inspection.

WARNING Wear safety glasses and standfar from the running fan drive withoutguards installed. A misaligned fan drive orimproperly installed drive belt can causethe belt to break, causing severe injury tonear by personnel. A properly aligned andinstalled belt can grab loose clothing orbody parts causing severe personal injury.

2. If the belt “wanders”, “walks”, or jumps betweenpulleys, either the fan drive needs to be re-aligned, or the belt was improperly installed.

3. If the belt or drive should be corrected, stop theengine, disconnect the negative lead (−) of the

starting batteries (or close the pneumatic sup-ply valve and bleed pressurized air if equippedwith air starters). Disassemble the fan driveguard, realign the fan drive pulley, and checkthe alignment again.

4. After the belt is properly installed, start the gen-set and check belt walk again.

WARNING Contact with fan, belt, or pul-leys can result in severe personal injury. Allshroud and guard pieces must be properlyfastened in place to prevent unintendedcontact.

5. Attach and secure all fan guard pieces thatwere removed for belt adjustment.

WARNING Contact with hot coolant can re-sult in serious burns. Allow the engine tocool before loosening the radiator cap orcoolant drain.

6. Recheck coolant levels after engine cools. Addcoolant if required.

Page 76: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-6

THIS PAGE LEFT INTENTIONALLY BLANK

Page 77: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

9-1

10. Wiring Diagrams

GENERAL

This section consists of the schematic and connec-tion wiring diagrams referenced in the text. The fol-lowing drawings are included.

Page 10-2 thru 10-6 − Customer Connections

Page 78: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

10-2

(SEE PAGE 10-3 FOR TERMI-NAL DESCRIPTIONS)

NO. 900-0298SH 1OF 4

REV. BMODIFIED 01-05

CUSTOMER CONNECTIONS (PAGE 1 OF 4)

Page 79: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

10-3

TERMINAL BLOCK TB3

(SEE PAGE 10-1 FOR TB3 LOCATION)

CUSTOMER CONNECTIONS (PAGE 2 OF 4)

Page 80: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

10-4

DOOR INTERIOR LEFT SIDE INTERIOR

CUSTOMER CONNECTIONS (PAGE 3 OF 4)

Page 81: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

10-5

LONWORKS PCB (OPTIONAL)

STANDARD PCBCUSTOMER CONNECTION INFORMATION

MISCELLANEOUS

12 TO 22 AWG (2.5−.75MM ) USE MINIMUM 60C RATED STRANDED COPPER WIRE ONLY. TORQUE 9 IN.−LB. (1.0 NM)

12 − 16 AWG (25 − 1.0 MM ) USE MINIMUM 60C RATED STRANDED COPPER WIRE ONLY. TORQUE 11 IN.−LB. (1.2 NM)

CONTACT RATINGS: 10 AMP = 28VDC / 120 VAC, 6 AMP = 240 VAC .8 PF, 3 AMP = 480 / 680 VAC .8 PF

CUSTOMER CONNECTIONS (PAGE 4 OF 4)

Page 82: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

10-6

NO. 630-3226SH 1OF 1

REV. AMODIFIED 11-10-05

CUSTOMER CONNECTIONS

Page 83: Installation Manual - Equinix-Cummins Manu… · Installation Manual Generator Set DQGAA (Spec A−C) DQGAB (Spec A−C) with PowerCommand 3201 Controller English − Original Instructions

Cummins Power Generation1400 73rd Ave. NEMinneapolis, MN 55432 USA

Phone 1 763 574 5000Toll-free 1 800 888 6626Fax 1 763 574 5298Email [email protected]�, the “C” logo, and “Our energy working for you.”are trademarks of Cummins Inc.

�2010 Cummins Power Generation, Inc. All rights reserved.