installation and service instructions unipower mpg series

19
Installation and Service Instructions Midco ® International Inc. 4140 West Victoria Street Chicago, Illinois 60646 toll free 866.705.0514 tel 773.604.8700 fax 773.604.4070 web www.midcointernational.com e-mail [email protected] Quality Designed for Proven Performance Printed in USA 8471 51 In the United States, installation must conform with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1-latest edition available from American National Standard Institute. Further reference should be made to the recommendation of your fuel supplier. In Canada, installation must conform with local codes or in the absence of local codes, with Installation Codes for Gas Burning Appliances and Equipment, CGA Standard CAN/CGA 1-B-149.1 or 2. WARNING: Additions, changes, conversions and service must be performed by an authorized Midco representative, service agency or the fuel supplier. Use only MIDCO specified and approved parts. INSTALLER: Inform and demonstrate to the user the correct operation and maintenance of the gas utilization equipment. Inform the user of the hazards of storing flammable liquids and vapors in the vicinity of this gas utilization equipment and remove such hazards. Ax this manual and associated literature to the burner. CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER. USER: Retain this manual for future reference. If other than routine service or maintenance as described in this manual and associated literature is required, contact a qualified service agency. DO NOT ATTEMPT REPAIRS. An inadvertent service error could result in a dangerous condition. WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury or death. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately phone your gas supplier from another building. Follow the gas supplier’s instructions. If you cannot reach your gas supplier call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. BURNER MODEL: ___________________________________ BILL OF MATERIAL NUMBER: ___________________________________ SERIAL NUMBER #: ___________________________________ WIRING DIAGRAM: ___________________________________ FOR SERVICE CONTACT Name: ____________________________________________ Address: ____________________________________________ ____________________________________________ Phone: ____________________________________________ Date of Installation: ___________________________________ AVOID ERROR IN PARTS SELECTION. When ordering use complete MIDCO Part Number and Description. Furnish Burner Model Number, Bill of Material Number and Serial Number (if available) from the specification plate found on the product. IMPORTANT: Availability of parts as well as specifications are subject to change without notice. Please consult factory for item availability. MADE in the USA SAFETY INFORMATION TERMS: The following terms are used to identify hazards, safety precaution of special notations and have standard meanings throughout this manual. They are printed in all capital letters using a bold type face as shown below, and preceded by the exclamation mark symbol. When you see the safety alert symbol and one of the safety information terms as shown below, be aware of the hazard potential. DANGER: Identifies the most serious hazards which will result in severe personal injury or death. WARNING: Signifies a hazard that could result in personal injury or death. CAUTION: Identifies unsafe practices which would result in minor personal injury or product and property damage. 220 Unipower MPG Series Gas Burners

Upload: others

Post on 10-Dec-2021

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation and Service Instructions Unipower MPG Series

Installation and Service Instructions

Midco® International Inc. 4140 West Victoria StreetChicago, Illinois 60646toll free 866.705.0514tel 773.604.8700fax 773.604.4070web www.midcointernational.come-mail [email protected] Quality Designed for Proven Performance Printed in USA

8471 51

• In the United States, installation must conform with local codesor in the absence of local codes, with the National Fuel GasCode, ANSI Z223.1-latest edition available from AmericanNational Standard Institute. Further reference should be madeto the recommendation of your fuel supplier.

• In Canada, installation must conform with local codes or in theabsence of local codes, with Installation Codes for Gas BurningAppliances and Equipment, CGA Standard CAN/CGA 1-B-149.1or 2.

• WARNING: Additions, changes, conversions and service must be performed by an authorized Midco representative, service agency or the fuel supplier. Use only MIDCO specifi ed and approved parts.

• INSTALLER: Inform and demonstrate to the user the correctoperation and maintenance of the gas utilization equipment.Inform the user of the hazards of storing fl ammable liquidsand vapors in the vicinity of this gas utilization equipmentand remove such hazards. Affi x this manual and associatedliterature to the burner.CODE COMPLIANCE IS THE SOLERESPONSIBILITY OF THE INSTALLER.

• USER: Retain this manual for future reference. If other thanroutine service or maintenance as described in this manualand associated literature is required, contact a qualifi ed serviceagency. DO NOT ATTEMPT REPAIRS. An inadvertent serviceerror could result in a dangerous condition.

WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result, causing property damage, personal injury or death.

Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:• Do not try to light any appliance.• Do not touch any electrical switch; do not use any

phone in your building.• Immediately phone your gas supplier from another

building. Follow the gas supplier’s instructions. Ifyou cannot reach your gas supplier call the fi redepartment.

Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.

BURNER MODEL: ___________________________________

BILL OF MATERIALNUMBER: ___________________________________

SERIAL NUMBER #: ___________________________________

WIRING DIAGRAM: ___________________________________

FOR SERVICE CONTACT

Name: ____________________________________________

Address: ____________________________________________

____________________________________________

Phone: ____________________________________________

Date of Installation: ___________________________________

AVOID ERROR IN PARTS SELECTION. When ordering use complete MIDCO Part Number and Description. Furnish Burner Model Number, Bill of Material Number and Serial Number (if available) from the specifi cation plate found on the product.

IMPORTANT: Availability of parts as well as specifi cations are subject to change without notice. Please consult factory for item availability.

MADE in the USA

SAFETY INFORMATION TERMS: The following terms are used to identify hazards, safety precaution of special notations and have standard meanings throughout this manual. They are printed in all capital letters using a bold type face as shown below, and preceded by the exclamation mark symbol. When you see the safety alert symbol and one of the safety information terms as shown below, be aware of the hazard potential.

DANGER: Identifi es the most serious hazards which will result in severe personal injury or death.WARNING: Signifi es a hazard that could result in personal injury or death.CAUTION: Identifi es unsafe practices which would result in minor personal injury or

product and property damage.

220

UnipowerMPG SeriesGas Burners

Page 2: Installation and Service Instructions Unipower MPG Series

2Midco International Inc.

8471 51

I Ventilation

Part 1 Installation

Part 1 Installation

Specifi cations 1

Burner Style Power Type SensingPilot Type Intermittent; Flame Rod Sensing, Spark Ignition(Standard) Intermittent; UV Sensing, Spark Ignition (Optional) Interrupted; Flame Rod Sensing, UV Flame Scanner (Optional)Pilot Safety Instantaneous Electronic Flame Safeguard

Voltage Standard Controls 120/1/60 Motor 115/1/60 230/1/60 (Optional) U.L. Listed -U.L.C. Listed Non UL 220V / 50HZ - Contact Factory

Minimum Maximum Maximum Inlet Gas Pressure Input 1 Input 1 Air Required 2

Models MBH/HR * MBH/HR * SCFM 3 Natural PropaneMPG 1.5G ** 500 1500 325 4″ W.C.4 4″ W.C. 4MPG 2.5G ** 850 2500 540 4″ W.C. 4″ W.C. Recommended Burner Manifold Pressure 1 Combustion Motor HP ChamberModels Natural Propane (3450 RPM) SizeMPG 1.5G 0.13 - 1.20″ W.C. 0.80 - 0.70″ W.C. 1/2 See Table 3MPG 2.5G 0.09 - 0.80″ W.C. 0.06 - 0.50″ W.C. 3/4 See Table 3

*1 MBH=1,000 BTU/HR ** High Turn Down Models available - contact factory1. Values given based on 0″ W.C. fi rebox pressure, altitudes to 2,000 feet. Derate burner for altitudes over 2,000 feet by 4% for each 1,000 feet over sea level. 2. Maximum inlet pressure both gases: 14″ W.C. Refer to Section VI Piping for high pressure.3. SCFM=Standard Cubic Feet/Minute4. Requires special valve train - contact factory

Table 1: Burner Specifi cations

Minimum Maximum Capacity in MBH at Maximum Maximum Firing Combustion Chamber Back MBH * atModels Rate Back Pressure Pressure Maximum MBH * 0″ W.C. .25″ W.C. .50″ W.C. in W.C. Back PressureMPG 1.5G 500 1500 1500 1400 1.0″ 1200MPG 2.5G 850 2500 2500 2450 1.0″ 2000

*1 MBH=1,000 BTU/HR. See Table 6 for gas pressure and air shutter settingsTable 2: Maximum Capacity at Specifi ed Back Pressures

The Midco power gas burner, MPG Series, is designed for fi ring natural gas or propane gas in most applications. The burner is a self-contained unit including a blower housing assembly, a burner gas manifold assembly, a burner cartridge, a fl ame safeguard, and a main and pilot gas train. The burner is easy to install, it includes mounting the burner to the gas utilization equipment, piping the main and pilot gas train and connecting the power supply. Before shipment every burner is operationally fi re tested at the factory, for unassembled valve trains the pilot solenoid and ignition system is tested. _________________________________

CAUTION: MPG-Series are not intended for outdoor installation and must be protected from excessive moisture. Provide adequate clearance for service and proper operation.

- Open basements will generally allow suffi cient air infi ltration, so special provisions will seldom be required. If the heating plant is located in a separate furnace room or in an unusually tight basement, permanent means must be provided to supply an ample volume of fresh air for combustion and boiler room ventilation. A direct opening to the outside air should be provided sized on the basis of 1/2 square foot of free opening for each 1,000,000 BTU of burner rating when the vent connector is equipped with a barometric draft control, 11/2 square feet when equipped with a draft hood. If the ventilation opening is screened, it should be of 11/4″ mesh.

Page 3: Installation and Service Instructions Unipower MPG Series

Midco International Inc.38471 51

Part 1 Installation

III Combustion Chamber

II Preparation of the Gas Utilization Equipment

I Ventilation Continued

The opening should be located at least six feet above ground level to prevent accidental obstruction. If a direct opening to the outside air is not available, an amply sized air duct can be run to the nearest outside air source or if practical, open stairwells or building corridors connecting to an outside wall having a ventilating opening can be used for this purpose, provided that no possibility of accidental closure exists. While the spark ignition pilot system performs successfully under moderate or momentary back draft conditions, it is not intended for operation under sustained reverse draft, for example, in a building with large ventilating fans but with insuffi cient make-up air. Even if burner operation is successful under these conditions, they must be corrected to prevent the hazard of drawing fl ue gases into the building. Consult your local gas company when doubt exists concerning boiler room ventilation. ___________________________

- The heating system, both the gas utilization equipment and the distribution system, should be in good operating conditions and suffi cient to properly heat the building. It should be determined if any serious faults are present that would cause excessive fuel consumption, unsafe operation or improper heating, and measures taken to correct them. Firing door catches should be fi led off or otherwise arranged so that the door will open easily to relieve pressure. No positive catches should be used. The use of a spring-type door holder is recommended. ___________________________

- Mount the burner to the gas utilization equipment. A tight seal between the mounting fl ange and the front plate should be accomplished using the supplied high temperature rope. When installing the gas burner the distance from the fl ange to the blast tube edge should be the same as the gas utilization equipment wall thickness plus the fl ange gasket or rope thickness. That means the burner blast tube will be fl ush with the inner chamber wall after the burner has been installed. If the blast tube is extended into the combustion chamber possible damage to the burner may happen. See Figure 1 & 2 for reference.

_________________________________

BURNER

BURNER

EXISTING PREFABRICATEDCOMBUSTION CHAMBERLINER

TO PROTECTAND PROPERLYLOCATE END OFBURNER TUBE,SEAL FLUSH WITH INSIDE OF COMBUSTIONCHAMBER LINER(REFER TOSECTION III)

TO PROTECTAND PROPERLYLOCATE END OFBURNER TUBE,SEAL FLUSHWITH INSIDE OF COMBUSTIONCHAMBER(REFER TOSECTION III)

1

87

6

54

3 2 0

FURNACE FRONT

AIR PASSAGE

AIR COOLEDSURFACE

COMBUSTIONCHAMBER

FILLER SECTION WITHREFRACTORY OR HIGHTEMP, MINERAL WOOL

INSULATION

0"0"

FURNACE FRONT

BLOCKINSULATION

BOILERFRONT

LOOSE BRICKFOR

PEEPSIGHT

INSULATINGFIREBRICK

AIR COOLEDSURFACE

SEAL WITHREFRACTORY CEMENT

SEAL WITHREFRACTORY CEMENT

1

87

6

54

32 0

Figure 1: Dry Base Boiler with Combustion Chamber Liner (Warm Air Furnace Construction is Similar)

Figure 2: Wet Base Boiler with Unlined Combustion Chamber

Figure 3: Scotch Marine Boiler Figure 4: Warm Air Furnaces

Page 4: Installation and Service Instructions Unipower MPG Series

4Midco International Inc.

8471 51

Part 1 Installation

IV Chimney, VentConnector and Draft

Control

III Combustion Chamber

Continued

- The MPG gas burner is designed for “in-shot” fi ring. It can be fi red into the ash pit of a boilerdesigned for solid fuels, or it can be fi red into the primary heat exchanger of a boiler designed forliquid or gaseous fuels. The ash pit installation requires a refractory lining.- The combustion chamber serves to contain and promote combustion and to protect non-heatexchange surfaces from direct fl ame contact. Built-up combustion chambers should be made of2600° insulating fi rebrick. As an alternative, a monolithic fl oor can be cast in place, using a hightemperature (2400°) light weight insulating refractory. Check with your supplier to determine thethickness which will yield equivalent insulating qualities.- The combustion chamber sizes given in Table 3 are based on the maximum rated burner capacity.If the input is to be permanently set at a reduced rate the combustion chamber fl oor area can bereduced proportionately to the proposed input, with the length as closely proportioned to twice thewidth as possible.- Where recommended size combustion chambers (225,000 BTU/sq. ft.) can be accommodated,the type of construction shown in Figure 1 should be used. If lack of space prohibits use of thisconstruction, higher BTU values per square foot can be allowed for by using the constructionsshown in Figures 2 and 3.- The back wall of the combustion chamber should be carried 2 or 3 courses higher and overhungto defl ect the fl ames from direct impingement on the rear heat exchanger surface. Hard fi rebrickshould be used to prevent erosion of the brick by high velocity gases.- The burner is equipped with a mounting fl ange for direct attachment to the boiler front. The burnernozzle must not extend into the combustion chamber. It should be sealed into the opening as shownin Figures 1 - 4.- The refractory lined combustion chamber can be omitted in “Scotch Marine” and “SteamGenerator” boilers or warm air furnaces that do not include ash pits. The burner is fi red directly intothe heat exchanger, requiring no refractory unless the combustion chamber is so short that fl amewould impinge excessively on the rear heat exchanger wall (this is particularly important in a warmair furnace). Refractory protection is recommended if the length of the primary chamber is less than20% larger than the length given in Table 3. In any case, the burner entry wall must be refractorylined if it is not a heat exchanger surface.

___________________________

Gas Input Max Input Flue PipeMBH/Hr .. Width/Height″ Length ″ MBH/Hr Diameter ″500 12″ 26″ 700 9″1000 15″ 34″ 950 10″1500 18″ 42″ 1400 12″2000 21″ 50″ 1950 14″2500 24″ 58″ 2500 16″Table 3 Recommended Combustion Table 4: Recommended Size of Flue Pipe andChamber Minimum Required Dimension Chimney - Based on Maximum Height of 15′

and Lateral Run of 15′

WARNING: The chimney shall be inspected for unsafe conditions such as deteriorated masonry and excessive soot or other blockage or potential blockage. Installation must conform with local codes or in the absence of local codes with NFPA, ANSI Z223.1-latest edition.

WARNING: No movable vent connector damper is permitted on any power gas burner installation. The chimney should be inspected for unsafe conditions such as deteriorated masonry and excessive soot or other blockage or potential blockage. Check your local authorities for regulations covering barometric draft regulators on gas equipment.

WARNING: The vent connector shall not be connected to a chimney already venting solid fuel burning equipment, an incinerator or an open fi re place.- The MPG burner does not depend on chimney draft. Combustion air is supplied by the forcedair blower, which is suffi cient to supply adequate air for any normal application. This reduces thefunction of the chimney to remove of fl ue products from the boiler. A chimney height of 15′ abovethe boiler fl ue outlet will generally prove ample if the recommended or larger vent connector andchimney diameters are used. The chimney must of course, extend several feet over the roof ofthe building, or adjacent buildings. Vent connector material should be 24 gauge or heavier steel,galvanized to resist corrosion. The horizontal run of vent connector should be pitched upwardfrom the appliance fl ue outlet at least 1/4″ to the foot. Avoid excess elbows or other constructionalfeatures that would create excessive resistance to fl ow of fl ue products. Fasten joints with sheetmetal screws to prevent sagging. The vent connector should be maintained at least 6″ fromcombustible building materials; more if it is uninsulated. Where it passes through partitionsconstructed of combustible materials a ventilated thimble should be used. Refer to your localbuilding codes. The vent connector should be fi rmly cemented into the chimney but must not extend

NOTE: For actual vent diameter information refer to the National Fuel Gas Code Handbook - Latest Edition

Page 5: Installation and Service Instructions Unipower MPG Series

Midco International Inc.58471 51

Part 1 InstallationIV Chimney, Vent

Connector and Draft Control Continued

beyond the inner face. Where two or more appliances use the same chimney, be sure not to enter the chimney with both fl ue pipes at the same level.- Do not arbitrarily reduce the vent connector size, since a back pressure can build up, leading to possible leakage of fl ue products into the room. - Chimney construction can be either of brick, preferably tile lined, or of steel. Joints in the chimney should be smooth and leak free to prevent uncontrollable air infi ltration. They should be made so that condensation if any, will not collect in the joints or leak to the outside.- If the vent connector must be extra long, the area of the pipe and chimneyshould be increased or the chimneyheight must be increased, or both.Never allow the horizontal length ofthe vent connector to exceed the height of the chimney.- Two kinds of draft control are acceptable; an A.G.A. type draft hood as illustrated in Figure 5, or a barometric damper as shown in Figure 6. Use of a draft hood is usually limited to burners with lower range capacities, while a barometric draft control is suitable for all capacities. Application should depend on the requirements of the installation.- If a draft hood is used, it should be of the same size as the vent connector and is free swinging without interference from surrounding objects so that the velocity pressure of the fl ue gases does not interfere with its operation. See Figure 5 for proper installation.- When any vent connector passes through a partition the draft control must be located in the same room as the heating appliance. A device which will automatically shut off gas to the burner in the event of sustained backdraft is recommended if such backdraft might adversely aff ect burner operation or if fl ue gas spillage might introduce a hazard. If such a device is used, it shall be of

CORRECT LOCATIONS

INCORRECT LOCATIONS

NOTE:Figures 5 and 6:Copyright by American Gas Association. Used by permission of the copyright holder.

Figure 5: Recommended Locations for Draft Hoods

Figure 6: Location for Barometric Draft Regulators

Note: Figures 5 and 6 :Copyright by American Gas Association. Used by permission of the copyright

holder

Page 6: Installation and Service Instructions Unipower MPG Series

6Midco International Inc.

8471 51

the listed type and installed and adjusted by a qualifi ed service technician in accordance with the manufacturer’s instructions.

___________________________

Electrical installation must be made in accordance with the United States to National Electric Code, ANSI/NFPA No.70-latest edition or Canadian Electrical Code, Part 1, CSA Standard C22.1. and applicable local code. If the burner is a part of a gas utilization equipment system, check the wiring diagram as supplied by the manufacturer.- The burner when installed, must be wired and grounded in accordance with local codes or in theabsence of local codes, with the National Electric Code ANSI/NFPA No. 70-latest edition. In Canada,refer to CSA Standard C22.1, “Canadian Electrical Code Part 1”.

CAUTION: Refer to the wiring diagram included with each burner.- When wiring, be sure that the electrical power take-off is connected to a permanently live circuitand use multiple 14 gage copper wire conductors. Provide a fused disconnect switch in the burnercircuit. Each installation must include a limit control to guard against excess temperature or steampressure. Steam or vapor systems will require a low water cut-off .

WARNING: Wiring shown is for standard burners. Consult the factory for specifi c wiring and have the Bill of Material Number ready when calling.

___________________________

V Electrical

Part 1 Installation

BL BLUEBK BLACKBR BROWNO ORANGER REDW WHITEP PURPLEY YELLOWG GREEN/BK BK STRIPE/W W STRIPENU NOT USEDPGT PIG TAIL

ABBREVIATION

444

3F

PILOT GAS VALVE

10

9

REDUNDANT VALVE

10

9

88

OPTIONAL VENT VALVE

SPARK GENERATOR

DASHED WIRING ANDCOMPONENTS BY INSTALLEROPTIONAL WIRING AND COMPONENTSBY MIDCO

LEGENDSOLID WIRING ANDCOMPONENTS BY MIDCO

M MOTOR CONTRACTOR

SPARK ROD

MAIN GAS VALVE

OPTIONAL ALARM

FLAME ROD

OFF ON

BLBL

BL / W BK

BR / BKY

R R

STEP DOWN TRANSFORMER

ENCIRCLED: FLAME SAFEGUARD

SOLID ROUND: BURNER STRIP

OPEN ROUND: COMPONENT

LIGHT (LOCATED IN GAS SWITCH ENCLOSURE)

O O

W

BL / W

BK

W

BK

L2 W

( - )

( + )M3

M1

MODULATING CONTROLLER4 - 20 MA SIGNAL INPUT(BY OTHERS)

500 OHMRESISTOR(BY MIDCO)

OPTIONAL

BELI

MO

COMMON+ HOT

Y W

R

BK

M3

BELIMO ACTUATOR

M2

M13O O

OPTIONAL UV SCANNER

M1 M2

W

BL Y

SAFETY &OPERATINGCONTROLS

G

L2

L1

BLOWER AIR SWITCH

6

(1)C(2)NO

(3)NC

NEUTRAL

120/1/60

HOT

5

BR

R / W

BR / WON-OFF SWITCH

GROUND TERMINAL

GBK

R / W(3)C (2)NO

(1)NC

(3)C(2)NO

(1)NCG

N N

BR / W

OPITIONAL HI-LO GAS PRESSURESWITCHES. IF NOT USED, JUMPER

G

R/BK

11 TO 5 WITH RED WIRE.

11

BRR/BK

3

HI-LO CONTROLLER

M3M2

(BY OTHERS)

( - )

( + ) M3

M1

MODULATING CONTROLLER2 - 10 VDC SIGNAL INPUT(BY OTHERS)

7

5

120V

24V5

F

6

7

F

W

BK

W BLOWER MOTOR

120 / 1 / 60

6 8

2 4

0 1

MOTOR CONTACTOR

R

GRN

OPTIONAL GRN

Figure 7: Wiring Diagram for MPG 1.5 and MPG 2.5 - 120V

Page 7: Installation and Service Instructions Unipower MPG Series

Midco International Inc.78471 51

VI Piping- Piping must comply with national and local codes.- Provide a sediment trap, manual safety shut-off valve and union in piping close to burner as shown in Figure 8:- To obtain the maximum fi ring rate of the burner, the fuel gas supply piping must be sized to provide a minimum of 5″ W.C. pressure to the inlet of the combination valve when the burner and all other gas appliances are on based on valve train size. For the usual low pressure gas supply system, 5″ to 14″ W.C. NATURAL (11″ to 14″ W.C. PROPANE) use Table 5 to fi nd the recommended gas supply line size.- Piping follows normal practices and should be connected to the burner in the manner shown in Figure 8. If the piping must be rearranged because of space limitations be sure to carry out the sequence of components illustrated. While the pilot regulator can be mounted in any position, the main regulator should be mounted upright and in a horizontal run of pipe.- Run full size pipe or tubing from regulator vent openings to outside of building. Provide no traps in the vent lines and terminate away from all doors and windows; also make provisions for keeping rain and foreign objects from entering the vent piping.- When high supply gas pressure is encountered, as in the case in many industrial plants, the gas line size can be reduced to allow for a greater pressure drop; however, the size must be suffi cient to deliver the necessary burner gas inlet pressure. CAUTION: High gas pressure supply lines require the proper pressure reducing regulators. Install two separate high pressure regulators, of the Tight Shut-Off type upstream of the low pressure regulators. One sized for main gas input, and one suitable for the minimum fl ow regulating capacity of the pilot.- The high pressure regulators may be substituted for the low pressure regulators. If high pressure regulators are used as substitutes, they must be adjustable down to a minimum of 2″ W.C. outlet pressure for the pilot and 5″ W.C. for the main gas. They must be adjustable down to the maximum burner inlet pressure rating (14″ W.C.).

DANGER: Explosion hazard. Do not use oxygen for pressure testing. An explosion could occur during initial start-up.- When the gas supply line is about to be put into service it must be tested to insure that it is gas tight. Use air or inert gas under pressure and test with soap and water or other liquids to locate leaks. CAUTION: Because it is diffi cult to accurately control pressure, disconnect all low pressure (14″ W.C. max.) components (main and pilot) during supply pipe leak testing. Exposing low pressure regulators and valves to a pressure over 1/2 PSIG (14″ W.C.) will damage components and void their warranties.

Part 1 Installation

0

2

3

4

67

8

PilotManual Valve

Main GasPressure Tap Pilot

Regulator

Gas Supply

Pilot Solenoid Valve

Blower Air Switch (Inside Cabinet)

Air

Main Manual Test Cock

Blower Motor

Manifold Pressure Tap

Main

Redundant Gas Valve

Main

Valve with Regulator

Drip Leg

Main Manual Valve

Quick Actuated Ball Valve

Figure 8: Standard Piping Diagram MPG BurnerPilot components and manual valves are shipped loose

Page 8: Installation and Service Instructions Unipower MPG Series

8Midco International Inc.

8471 51

CAUTION: Do not exceed maximum rated capacity of burner model-See Tables 1 & 2.- Before gas is introduced to the system, a check must be made to see that there are no open fi ttings and to make sure the burner main and pilot manual valves are closed. After checking above, purge the gas line up to the burner inlet. Purging the air from the gas supply line at this step will expedite the fi rst light-off . CAUTION: Purge outside the building. Do not purge into the gas utilization equipment combustion chamber.

Pipe Type Approximate Capacity - MBH Size of Gas Pipe Length 20 40 60 100 200 1 1/4 Natural 730 500 400 300 1 1/4 Propane 1150 785 630 480 330 1 1/2 Natural 1100 760 610 460 320 1 1/2 Propane 1730 1200 960 725 500 2 Natural 2100 1450 1150 870 610 2 Propane 2500 2280 1800 1370 960 2 1/2 Natural 2500 2300 1850 1400 980 2 1/2 Propane 2500 2500 2500 2200 1550 3 Natural 2500 2500 2500 2500 1700 3 Propane 2500 2500 2500 2500 2500

___________________________

Burners are approved for use with NATURAL gas or PROPANE gas and should be used only with the gas specifi ed on the rating plate.- The gas input should be set at the heating rate determined by the building heat loss and/or heating plant survey, but not exceeding the rated maximum input of the gas utilization equipment.

MPG1.5G with 1.5″ train (On-Off ) Gas Flow & Air Shutter Setting

MPG2.5G with 2″ train (On-Off ) Gas Flow & Air Shutter Setting

* 1 MBH=1,000 BTU/HR** Based on zero chamber pressure at sea level (Chamber pressure can be measured at pilot gas pressure tap with pilot gas off

VII Main Gas Input Selection

VI Piping Continued

Part 1 Installation

Table 6: Manifold Gas Pressure and Air Shutter Settings

For actual Capacities shown are for a total pressure drop of 0.3″W.C. For 0.5″W.C. pressure drop, multiply capacity shown by 1.3 . Propane capacities shown are for a total pressure drop of 0.5″ W.C. For higher permissible pressure drops, consult your gas supplier. Source: Gas Engineers Handbook - 1974

Table 5: Schedule 40 NPT Pipe-Capacity Chart

Firing Rate (MBH/Hr)* 850 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500Natural GasManifold Pressure″ W.C. **

0.09 0.29 0.33 0.37 0.41 0.46 0.51 0.56 0.62 0.68 0.74 0.80

Propane GasManifold Pressure″ W.C. **

0.06 0.18 0.20 0.23 0.26 0.29 0.32 0.35 0.39 0.42 0.46 0.50

Air ShutterPosition 0.0 0.7 0.9 1.1 1.3 1.6 1.8 2.0 2.2 2.5 2.9 3.5

Firing Rate (MBH/Hr)* 500 700 800 900 1000 1100 1200 1300 1400 1500Natural GasManifold Pressure″ W.C. **

0.13 0.26 0.34 0.43 0.53 0.65 0.77 0.90 1.05 1.20

Propane GasManifold Pressure″ W.C. **

0.08 0.15 0.20 0.25 0.31 0.38 0.45 0.53 0.61 0.70

Air ShutterPosition 0.0 0.0 0.2 0.3 0.5 0.8 1.4 2.3 4.0 6.8

Page 9: Installation and Service Instructions Unipower MPG Series

Midco International Inc.98471 51

VIII Initial Start- up /Adjustment

On-Off Burners

Part 1 InstallationVII Main Gas

Input Selection Continued

MPG1.5G with 1.5″ train (2 Stage and Full Modulation) Gas Flow & Air Shutter Setting

MPG2.5G with 2″ train (2 Stage and Full Modulation) Gas Flow & Air Shutter Setting

* 1 MBH=1,000 BTU/HR** Based on zero chamber pressure at sea level (Chamber pressure can be

measured at pilot gas pressure tap with pilot gas off

___________________________

1) Check the gas piping for leaks. If a leak is detected it should be located with asoap suds test and repaired.

2) Make sure that the burner main and pilot gas lines are both completely purged of air.Don’t purge into the combustion chamber. Purge outside the building.

3) Make sure the burner power switch is off , manual valves of main gas and pilot gasare closed, and motor is free to rotate.

4) Make the proper settings on all limit controls and set controller to call for heat.5) Set air shutter to the correct position according to Table 6 and tighten in place.6) Energize Power On-Off switch, and allow motor to run through the pre-purge of 30

seconds and the pilot ignition cycle. Check the blower wheel for proper rotation.Viewing from blower inlet side, rotation should be counter-clockwise. With no pilotgas, the fl ame safeguard will lock out, stopping the motor.

7) Wait one minute, reset the fl ame safeguard and open the pilot manual valve withmain manual valve still closed. When pre-purge period of 30 seconds has beencompleted the pilot solenoid valve and spark generator will be energized. The pilotshould light and the fl ame rod senses pilot fl ame. Adjust the pilot gas pressure toreach a strong and stable pilot fl ame according to Table 8. Test for ignition andstability of pilot several times.

8) Turn off Power On-Off switch. Open Main Manual Shut-off Valve half way.9) Find the required main gas manifold pressure from the Table 6. Use a Digital Gas

Manometer to measure the main gas manifold pressure.10) Turn on Power On-Off switch. The burner will start and go through the 30 second

pre-purge period and you should have pilot ignition and then the Main fl ame shouldlight

11) Slowly open the Main Manual Shut-off Valve and adjust the gas pressure regulator onthe Main Gas Combination Valve, until the main gas manifold pressure reaches therequired value as shown in Table 6 and the Main Manual Shut-off Valve is wide open.

12) Check the emissions in the fl ue with a Gas Analyzer, adjust the Air Shutter untilthe O2 level of fl ue gas is approximately 3.5-4.5 %.

13) Cycle the burner on and off several times and check for Pilot ignition, Main gasignition, main gas manifold pressure and O , CO , and CO readings.

For Hi-Low and Full Mod startup instructions see section XVI

Firing Rate (MBH/Hr) * 500 600 700 800 900 1000 1100 1200 1300 1400 1500Natural gas pressure dropbetween 2nd valve and main gas fl ow control valve, ″ W.C. **

0.06 0.09 0.12 0.16 0.20 0.24 0.30 0.35 0.41 0.48 0.55

Propane gas pressure dropbetween 2nd valve and main gas fl ow control valve, ″ W.C. **

0.03 0.05 0.07 0.09 0.11 0.13 0.16 0.19 0.23 0.26 0.30

Air Shutter Position 0.0 0.0 0.0 0.2 0.3 0.5 0.8 1.4 2.3 4.0 6.8

Firing Rate (MBH/Hr) * 850 900 1100 1300 1500 1700 1900 2100 1300 2500Natural gas pressure dropbetween 2nd valve and main gas fl ow control valve, ″ W.C. **

0.06 0.09 0.12 0.16 0.20 0.24 0.30 0.35 0.41 0.48

Propane gas pressure dropbetween 2nd valve and main gas fl ow control valve, ″ W.C. **

0.03 0.05 0.07 0.09 0.11 0.13 0.16 0.19 0.23 0.26

Air Shutter Position 0.0 0.0 0.0 0.2 0.3 0.5 0.8 1.4 2.3 4.0

Table 7: Manifold Gas Pressure and Air Shutter Settings

Page 10: Installation and Service Instructions Unipower MPG Series

10Midco International Inc.

8471 51

Drawer Assembly with Flame Rod

Drawer Assembly with UV Scanner

___________________________

- The blower functions to supply a constant and positive supply of air for complete combustion. Airvolume is controlled by an adjustable shutter in the blower inlet.- No routine service is necessary on the blower other than occasionally cleaning the blower wheel.If the blower wheel must be replaced, be sure to check the replacement for proper rotation. Theconcave sides of the blades must face the blower outlet, and rotation of the wheel must be towardthe outlet. Motor sizes and specifi cations are given in Table 1. All motors contain integral motoroverload protection, usually manual, occasionallyautomatic reset.- Proof of blower operation is provided by thediaphragm air switch, which must close its contacts and maintain them closed when the blower is running. In case of malfunction, the diaphragm air switch must be replaced.- The pilot gas pressure will be measured at theoutlet of pilot gas solenoid valve.

___________________________

A combination integrated redundant main gas valve with an integrated gas pressure regulator is used on the standard MPG burner.- The gas pressure regulator is used to automatically reduce and maintain constant gas pressureto the burner. To vary the outlet pressure, remove the seal cap for access to the adjusting screw.Turning the screw clockwise will increase outlet pressure, counter-clockwise will decrease outletpressure.- Maximum and minimum allowable gas pressures are shown in Table 1.

___________________________

Note: All burners are equipped with dual valves. Burner construction for special codes and/or insurance requirements such as Factory Mutual or Industrial Risk Insurers (GAP) may require alternate construction. (Refer to Section XV Special Equipment.)

XII Gas Pressure Regulator

XI Blower and Motor

VIII Initial Start- up /Adjustment

On-Off BurnersContinued

Part 1 Installation

AMPI

5/8"

5/16"

Flame rod position: Align flame rod with bottom edge of pilot burner tip

5/16"

DJ7J

OPEN TO 7/64” GAP

Figure 9: Drawer Assembly MPG Burner

ModelOrifi ceType

Orifi ce Size ″

Drill Size

Pilot Gas Pressure

On-Off A 0.11″ #35 2.0″-3.5″Low Fire Start(Full Mod and2-Stage)

B 0.076″ #48 2.0″-3.5″

XIII Main Automatic Valves

SLOT

SLOT

POSITION TIP OF SPARKPLUG'S GROUND ROD INBETWEEN AIR SLOTS.

Page 11: Installation and Service Instructions Unipower MPG Series

Midco International Inc.118471 51

3. Redundant SolenoidGas Safety Valve

2. Motorized MainAutomatic Valve

1. Diaphragm MainAutomatic Valve

Part 1 Installation- The Honeywell diaphragm valve supplied on standard burners is of the slow opening, fast closingtype. Closing force combines a gas pressure diff erential, diaphragm weight and spring.- When the controller is not calling for heat, the coil is de-energized. The plunger of the three wayactuator is in the down position, so that the bleed is closed and the supply port is open. Gas fl ows tothe top diaphragm, causing the gas pressure and spring to hold the valve closed.- With a call for heat, the fl ame safeguard energizes the coil. This pulls the plunger to the upposition, opening the bleed valve and closing the supply port. The gas then bleeds off the top of thediaphragm, allowing the gas pressure below to lift the diaphragm, and open the valve. When all thegas has bled off the top of the diaphragm, the valve is fully opened. In the event of a power failureduring operation, the valve will close. Normal operation will resume upon restoration of power.- For general service, tests for gas tightness and proper operation will suffi ce. If leakage isobserved, replace valve. If the valve will not open, make sure that normal gas pressure is availableat the valve, the bleed line is unobstructed and power is available at the terminals.- If the valve fails to close, make sure power is off at the terminals and gas fl ow is in the direction ofthe arrow on the valve body. When a malfunction is found to be caused by the valve operator head,the entire valve must be replaced.- If the valve will not open, make sure normal gas pressure is available at the valve, the bleed line isunobstructed, and power is available at the terminals.

___________________________

- Motorized Main On-Off Valves are available on special order burners.- When the actuator is energized, hydraulic fl uid is pumped from a reservoir to a metal bellows. Thebellows transfers the resulting pressure through the drive stem to open the valve.

___________________________

- MPG burners may feature a redundant solenoid gas safety valve. This valve is an On-Off (2position) valve.- When the valve operator is electrically energized, a plunger lifts the valve disk off the valve seat,allowing gas to fl ow. When the current is broken the valve closes. It will normally require no service.If the operator malfunctions or the valve leaks replace the entire valve. After replacement check forleakage.

___________________________

WARNING: Explosion hazard. Do not use this device if it gets wet. It can malfunction and cause serious injury or death. Replace any device that has been wet.- Standard MPG burners are equipped with a Honeywell RM7895 microprocessor based burnercontrol, employing a fl ame rectifi cation system of fl ame detection. Burner construction for specialcodes and/or insurance requirements such as Factory Mutual or Industrial Risk Insurers (GAP) mayrequire alternate controls. Refer to Section XV Special Equipment. A safe start and run controlsequence is provided with instantaneous response to presence or loss of fl ame signal. Flame failureresponse time is 3 seconds. Pilot Flame Establishing Period (PFEP) is fi eld selectable from 4 or10-seconds. The RM7895 features a pre-purge time (30-seconds for On-Off , 90-seconds for 2-Stepor Modulating burners) and a plug-in amplifi er. An airfl ow circuit is also fi eld selectable to allow eitherlockout or recycle upon loss of airfl ow. Five LED’s (light emitting diodes) are provided to displaysequence information. Refer to the Honeywell RM7895 literature for detailed operating information,confi guration requirements, testing and service.

INITIATE (“POWER” LED is lit).- The RM7895 enters the INITIATE sequence when it is powered. The INITIATE sequence lasts forten seconds unless the voltage or frequency tolerances are not met (refer to Honeywell RM7895literature for criteria). When tolerances are met, the INITIATE sequence will restart. If the conditionis not corrected and the hold condition exists for four minutes, the RM7895 will lock-out. Causes forhold conditions in the INITIATE sequence are in the Honeywell RM7895 literature.

STANDBY (“POWER” LED is lit).- The RM7895 is idle in this state of sequencing. When the burner switch, limits, operating limitcontrols and all microprocessor monitored circuits are in the correct state for the RM7895 tocontinue, sequencing will advance to pre-purge.

XIV Flame Safeguard

Page 12: Installation and Service Instructions Unipower MPG Series

12Midco International Inc.

8471 51

PRE-PURGE (“POWER” LED is lit).- The RM7895 in this application features a pre-purge time of 30-seconds for On-Off , 90-secondsfor 2-Step or Modulating burners.- Once the STANDBY sequence has a “CALL FOR HEAT” input, normal start-up pre-purge will beinitiated.

A. The blower motor is powered to start the pre-purge sequence.B. The airfl ow interlock switch must close in ten seconds of pre-purge or within the

specifi ed purge card timing. Otherwise a recycle to the beginning of pre-purgeor lockout will occur, depending on how the airfl ow switch selectable jumper isconfi gured. Refer to Honeywell RM7895 literature for confi guration requirements.

IGNITION TRIAL1. PILOT FLAME ESTABLISHING PERIOD (PFEP)

A. The pilot valve and spark generator are energized.B. Flame must be proven by the end of the 4 or 10-second PFEP to allow the

sequence to continue. If fl ame is not proven by the end of PFEP, a safetyshutdown occurs.

2. MAIN FLAME ESTABLISHING PERIOD (MFEP)- After the ignition trials, and with the presence of fl ame, the main valve is energized.(“MAIN” LED will be lit.) If a fl ame-out occurs, the RM7895 will lockout or recycle within 3-seconds, depending on “jumper” confi guration. Refer to Honeywell literature for properconfi guration.

RUN- The RM7895 is now in RUN mode and will remain in run mode until the controller input opens,indicating that the call for heat has been satisfi ed or a limit has opened. Once this occurs theRM7895 will sequence back to the STANDBY mode.Notes: 1. During STANDBY and during RM7895 sequencing the “POWER” LED will blink

every four seconds. This is normal.2. The “ALARM” LED will be lit in the event of any fl ame failure.3. To maintain proper operation of this device it MUST be electrically grounded. Refer

to Honeywell RM7895 literature for grounding requirements.___________________________

- Special equipment, either factory or fi eld installed, can cause variations in the procedures anddescriptions given in this manual. Generally, any burner ordered with special factory installedequipment will be supplied with the appropriate wiring diagram and related instruction manualsfrom the special equipment manufacturer. Consult these manuals to identify any diff erences inconstruction, operation and testing. Field installed special equipment is the responsibility of theinstalling contractor.- For example, when a high/low gas pressure switch is used, the high gas pressure setting must behigher than the maximum manifold pressure during initial start-up and the low pressure setting mustbe set below the normal minimum inlet pressure to prevent nuisance shutdowns during the start-upprocedure.- After the burner is started, the low pressure setting should be raised until the burner shuts off .Reduce the setting and set the low pressure switch to restart the burner. Reduce the high pressuresetting until the burner shuts off . Then raise the setting slightly and reset the high pressure switch torestart the burner. Do not make the adjustments too close to trip points or nuisance shut downs mayoccur. Anytime the burner gas supply is shut off with the main manual valve, the low pressure switchwill require resetting.- If any doubt exists concerning burner operation when special equipment is involved, contact theinstalling contractor or MIDCO INTERNATIONAL INC. (front cover).

___________________________

Note: These Instructions are designed for experienced combustion contractors/ technicians.

1) Check the gas piping for leaks. If a leak is detected, it should be repaired.2) Make sure that the burner main and pilot gas lines are both completely purged of air.

Do not purge into the combustion chamber. Purge outside the building.3) Make sure the burner power On-Off switch is OFF, manual main gas valve and manual

pilot gas valves are closed and the motor is free to rotate.4) Make the proper settings on all limit controls and set the operating controller (by others)

to call for heat.

XVI Initial Start Up Instructions

2-Stage and FullModulating Burner

XV Special Equipment (OEM Versions)

XIV Flame Safeguard Continued

Part 1 Installation

Page 13: Installation and Service Instructions Unipower MPG Series

Midco International Inc.138471 51

Part 1 Installation5) Loosen the linkage connecting rod at the ball joint (7/16″ wrench) nearest to the

motorized actuator and the U clamp (5/16″ deep socket) of the motorized actuator, and set:a. air shutter at minimum opening positionb. gas fl ow control valve at 2 O′clockc. both crank arms at 7 O′clock

Note: Linkage connecting rod should be parallel to blower scroll housing face.

6) Turn the burner power On-Off switch to ON and allow the motor to run through the pre-purge and ignition cycle. Check the blower wheel for proper rotation. Viewing from theblower inlet screen, rotation should be counter-clockwise. After approximately 90 seconds,the fl ame safe guard will lock out, stopping the motor.

7) Open the pilot manual gas valve leaving the main manual gas valve closed. Reset thefl ame safe guard. Motor will start. When the pre-purge period (90 seconds) has completed,the fl ame safe guard will energize the pilot solenoid valve and the spark generator. Thepilot should be ignited and the fl ame rod or UV scanner senses the pilot fl ame. Adjustthe pilot gas pressure to reach the strongest and most stable pilot fl ame signal. See Table 8for preliminary pilot gas pressure settings. Test several times for pilot ignition, stability andfl ame sensing signal.

8) Measure the main gas diff erential pressure by installing a digital manometer. One gaspressure tap should be installed in the downstream port of the downstream automatic maingas safety shutoff valve. The second gas pressure tap should be installed in the manifoldtest tap that is located just upstream of the gas fl ow control valve. See Table 7 for initialdiff erential manifold gas pressure & air shutter settings.

9) Slowly open the main manual gas valve with the main valves energized and watch throughthe peep sight glass located on the back of the pilot drawer assembly to make sure that themain fl ame ignites.

10) Check the fl ue gas readings with a combustion gas analyzer. Slowly and manually adjustthe gas fl ow control valve and/or air shutter to achieve the correct burner low fi re fi ring rateand proper preliminary fl ue gas readings (approximately 4 - 5% O and approximately 9 -9 ½% CO ).

11) Slowly and manually adjust the gas fl ow control valve and/or air shutter to achieve thecorrect burner high fi re fi ring rate and proper preliminary fl ue gas readings (approximately4 - 5% O and approximately 9 - 9 ½% CO ). Tighten the linkage connecting rod at the balljoint (7/16” wrench) nearest to the motorized actuator.

12) Check the fl ue gas readings with a combustion gas analyzer. Adjust the regulator of themain gas combination valve or the independent main gas pressure regulator and/or theair shutter to achieve the correct burner high fi re fi ring rate and proper fl ue gas readings(approximately 4 - 5% O and approximately 9½ - 10% CO ).

NOTE: For a full modulating burner, check the burner combustion performance at mid range fi ring rate and adjust as necessary.

13) Turn the burner power On-Off switch to OFF. Manually move the gas fl ow control valve,connecting rod and air shutter to the low fi re position. Tighten the U clamp of the motorizedactuator. Move the adjustable stop block of the motorized actuator to the 3 O’clock positionand lock it in place. At the Midco control cabinet terminal strips, disconnect the signal inputwires from the remote temperature controller. Place a temporary jumper from terminal M2 toM3 (this simulates a call for high fi re heat).

Note: Circuit from terminal strip 5 to 6 must be closed in order for the burner to fi re.

14) Turn the burner power On-Off switch to ON. The burner should start andsequence as follows:

a. 10 second initiationb. 90 second pre-purge periodc. Pilot ignition, fl ame provingd. Main fl ame ignition, low fi re starte. Main fl ame, high fi re operation

15 If the measured high fi re fi ring rate is less (more) than the desired value, turn the burner power On-Off switch to OFF, move the adjustable stop block of the motorized actuator up (down) and try again until reaching the desired high fi re fi ring rate.

Page 14: Installation and Service Instructions Unipower MPG Series

14Midco International Inc.

8471 51

16) Cycle the burner several times and verify:a. 10 second initiation periodb. 90 second purge periodc. pilot ignitionb. pilot fl ame sensing signal is strong and stablec. main gas ignitiond. low fi re fi ring ratee. high fi re fi ring ratef. combustion gas analyzer readings

Adjust if necessary.17) Turn the burner power On-Off switch to OFF and remove the temporary jumper that

was placed from terminal M2 to M3. Remove the digital monometer and connectorsand replace the plugs on the main gas valve and the main manifold test tap.Reconnect the signal input wires from the remote temperature controller.

Make sure the thermostat and operating controls are calling for heat. Defective wiring or loose connections can simulate the component defects outlined below. Check associated wiring before replacing a component. ELECTRICAL AND FLAME CHECKS MUST BE MADE IN THE ORDER LISTED.

___________________________

A. No power to fl ame safeguardB. Flame safeguard locked outC. Defective fl ame safeguardD. Defective motor relayE. Motor overload “out”

A. Motor overload “outB. Defective motorC. Defective fl ame safeguard

A. Defective air switchB. No air pressure at air switchC. Defective purge timerD. Defective fl ame safeguard

A. No pilot gasB. Low pilot gas pressureC. Defective pilot gas regulatorD. Mis-adjusted pilot regulatorE. Blocked pilot regulator ventF. Defective pilot solenoid valveG. Defective spark electrodeH. Mis-adjusted spark electrodeI. Defective spark cableJ. Defective spark generatorK. Clogged or incorrect pilot orifi ceL. Air orifi ce missingM. Clogged pilot air tubeN. Defective fl ame safeguard

Trouble Chart

Part 2Service

XVI InitialStart Up Instructions

2-Stage and FullModulating Burner

Continued

Part 1 Installation

Part 2 Service

IV Pilot Does Not Light, Flame

Safeguard Locks Out

III Motor Runs Continuously ,

No Lighting Attempt

II Motor Fails to Start, Flame, Safeguard

Energized

I Motor Fails

Page 15: Installation and Service Instructions Unipower MPG Series

Midco International Inc.158471 51

Part 2 ServiceA. Poor fl ame signalB. Poor pilot fl ameC. Misadjusted pilot regulatorD. Low gas pressureE. Misadjusted air shutterF. Defective fl ame rod wireG. Defective or Mis-adjusted fl ame rodH. Defective amplifi erI. Defective fl ame safeguard

A. Low gas pressureB. Mis-adjusted main regulatorC. Blocked regulator ventD. Defective main regulatorE. No power at main valve(s)F. Blocked main valve bleed line (if equipped)G. Defective main valve(s)H. Closed test cockI. Defective fl ame safeguard

A. Poor pilotB. Pilot gas pressure drops severely when main gas valve opensC. Mis-adjusted pilot regulator

A. Low gas pressureB. Defective main regulatorC. Mis-adjusted main regulatorD. Too much airE. Partially closed test cock

A. High gas pressureB. Defective main regulatorC. Mis-adjusted main regulatorD. Too little airE. Dirty blower wheel

A. Defective valve(s)B. Defective valve actuatorC. Dirty valve seat

A. Low voltageB. Defective motorC. High ambient temperatureD. Dirty blower wheel

A. See IV aboveB. See V aboveC. See VI above

Note: Some of the probable causes listed above apply only to certain models as indicated,therefore some may not apply to your particular case.

VI Pilot Lights, No Lockout on Flame

Safeguard, No Main Gas

V Pilot Lights, Flame safeguard Locks Out

VII Main FlameLights, But Goes out,

Pilot Re-lights

VIII Short Main Flame

IX Long Hazy Flame

X Main Valve(s) Fail to Shut

Off or Leaks

XI Flame Safeguard Needs Frequent

Re-setting

XI Motor Overload Frequently

Trips Out

Page 16: Installation and Service Instructions Unipower MPG Series

Midco® International Inc. 4140 West Victoria StreetChicago, Illinois 60646toll free 866.705.0514tel 773.604.8700fax 866.580.8700web www.midcointernational.come-mail [email protected] Quality Designed for Proven Performance Printed in USA

COMPANY

RE

GISTER

ED

Replacement Parts List

AVOID ERROR IN PARTS SELECTION. When ordering use complete MIDCO Part Number and Description. Furnish Burner Model Number, Bill of Material Number and Serial Number (if available) from the specifi cation plate found on the product. IMPORTANT: Availability of parts as well as specifi cations are subject to change without notice. Please consult factory for item availability.

MADE in the USA

418 8472 95

UnipowerMPG 1.5G and MPG 2.5G

0

2

3

4

67

8

MPG SeriesInstallation and Service Manual - 8471-51

Page 17: Installation and Service Instructions Unipower MPG Series

2Midco International Inc. MADE in the USA 8472 95

Exploded View - MPG 1.5G & MPG 2.5G

24

27 2526

3

21

0

4

67

8

12

5

3*

2*6

7

4

1*

28

29

30

11*

10

9*

2223

21

20

8

13

14B

14A

15B

15A

(On-Off Only) 16B16A 16D16C17B17A 17D17C

18B18A 18D18C

19B19A 19D19C

16B16A 16D16C

Cartridge Assemblies and Gas Flow Control -See page 4

Page 18: Installation and Service Instructions Unipower MPG Series

Midco International Inc.3

Item Part # Description Qty Item Part # Description Qty

MADE in the USA

Parts List - MPG 1.5G & MPG 2.5G

8472 95

1A 8429-27 R7847A Rect Flame Amplifi er 1

1B 8429-30 R7849A UV Amplifi er 1

2A 8429-25 ST7800A1062 90-Sec Timer 1

2B 8429-22 ST7800A1039 30-Sec Timer 1

3A 8429-56 RM7895E Controller (Flame Rect) 1

3B 8429-19 RM7895A Controller (UV only) 1

4 8429-16 Q7800B Sub Base 1

5 8408-94 10-32 Terminal Nut 1

6 8447-22 Ignitor Spark Generator 1

7 5244-50 MPG Control Box (Approx. 9″x7.5″x3.5″) 1

8 5238-06 MPG 1.5/2.5 Blower Housing 1

9A 3627-50 MPG 1.5 Blower Wheel 7″ X 3.5″ 1

9B 7349-00 MPG 2.5 Blower Wheel 7″ X 4″ 1

10 3197-50 Motor Adaptor Flange 1

11A 8437-15 MPG 1.5 1/2 Hp Motor,

Single Phase, 115V/230V 60Hz 1

11B 8437-25 MPG 2.5 3/4 Hp Motor,

Single Phase, 115V/230V 60Hz 1

12 5238-07 MPG 1.5/2.5 Air Shutter 1

13 5238-36 MPG Housing Gasket 1

14A 5238-08R MPG 1.5 Blast Tube 1

14B 5239-08R MPG 2.5 Blast Tube 1

15A 2020800 6″ Mounting Flange MPG 1.5 1

15B 5239-15 8″ Mounting Flange MPG 2.5 1

16A 8404-67 1″ Ball Valve without Side Tap 1

16B 8404-66 1- 1/4″ Ball Valve without Side Tap 1

16C 8404-65 1- 1/2″ Ball Valve without Side Tap 1

16D 8404-64 2″ Ball Valve without Side Tap 1

17A 8404-38 1″ Quick Activated

Ball Valve (On-Off Only) 1

17B 8404-40 1-1/4″ Quick Activated

Ball Valve (On-Off Only) 1

17C 8404-41 1-1/2″ Quick Activated

Ball Valve (On-Off Only) 1

17D 8404-42 2″ Quick Activated

Ball Valve (On-Off Only) 1

18A 8418-03 1″ Solenoid Gas Valve 120V 1

18B 8402-06 1-1/4″ Solenoid Gas Valve 120V 1

18C 8402-07 1-1/2″ Solenoid Gas Valve 120V 1

18D 8402-18 2″ Solenoid Gas Valve 120V 1

19A 8419-24 1″ 2-Way Comb Dv Valve 120V 1

19B 8419-81 1-1/4″ 2-Way Comb Dv Valve 120V 1

19C 8419-82 1-1/2″ 2-Way Comb Dv Valve 120V 1

19D 8419-83 2″ 2-Way Comb Dv Valve 120V 1

20 5238-22 MPG 1.5/2.5 Inlet Ring 1

21 5238-72 MPG 1.5/2.5 Air Screen 1

22 5238-73 MPG Blower Gasket 1

23 8437-62 Inlet Ring 1

24 8483-00 1/8″ M X 1/4″ Tube Elbow 1

25 8483-11 1/4″ M X 5/16″ Tube Elbow 1

26 8400-10 1/4″ Pilot Regulator 1

27 8404-28 1/4″ Ball Valve 1

28 8483-30 1/8″ M X 5/16″ Tube Straight Fitting 5

29 8402-00 1/8″ NPT Solenoid Valve, 120V 1

30 8483-01 1/8″ M X 5/16″ Tube Elbow 1

Not Shown

5238-39 Leak Test Cock Kit

5238-77 MPG Pilot Orifi ce Assembly Stamped B

5238-79 MPG Pilot Orifi ce Assembly Stamped A

5239-13 Rope Gasket, 8″ Tube (MPG 2.5)

5240-89 Rope Gasket, 6″ Tube (MPG 1.5)

5243-42 500 Ohm Resistor Kit

8406-68 DPST Relay - 120V (Motor Contactor)

8425-52 Pressure Diff Switch

5238-50 HTD Shutter Weldment

8419-95 Belimo Actuator

5243-49 1-1/2″ Flow Control Valve 10-1

5238-61 MPG 1.5G Cartridge Assembly 10-1 UV

5238-86 C Pilot Orifi ce

5238-50 HTD Shutter Weldment

8419-95 Belimo Actuator

5243-54 2″ Flow Control Valve 10-1

5239-83 MPG 2.5G Cartridge Assembly 10-1 UV

5238-86 C Pilot Orifi ce

8429-42 EC7895A Controller

8437-25 3/4 Hp Motor 230V 50/60Hz

8402-09 1-1/2″ Solenoid Gas Valve 240V

8402-46 1/8″ Pilot Solenoid Valve 220V/240V

8447-24 Ignitor Spark Generator 230V

Special Parts MPG 1.5G HTD

MPG 2.5G HTD

230V Parts (Not Shown)

Page 19: Installation and Service Instructions Unipower MPG Series

Midco® International Inc. - 4140 West Victoria Street - Chicago, Illinois 60646 - toll free: 866 705 0514tel: 773.604.8700 - fax: 866.580.8700 - web: www.midcointernational.com - e-mail: [email protected]

MADE in the USA

4Printed in USA

ISO9001

COMPANY

RE

GISTER

ED

418 8472 95

Cartridge Assemblies - MPG 1.5G & MPG 2.5G

HAMPION

52

3

HAMPION2

3

7

4B4A

6B6A

8B8A

9B9A10A

10B10C

10D

1B1C

1D

1A

1A 5238-30 MPG 1.5 FR Cartridge Assembly 11B 5239-30 MPG 2.5 FR Cartridge Assembly 11C 5238-90 MPG 1.5 FR Cartridge Assembly (On-Off ) 11D 5239-90 MPG 2.5 FR Cartridge Assembly (On-Off ) 12 7122-90 Peep Sight Assembly 13 5238-49 Spark Plug 14A 5238-20 Pilot Weldment-Flame Rod (MPG 1.5/2.5) Two Slots (High Low 3″ Full Mod) 14B 5238-62 Pilot Weldment-Flame Rod (MPG 1.5/2.5) Single Slot (On- Off ) 15 5236-18 Flame Rod Assembly 16A 5238-09 MPG 1.5 FR Cartridge Weldment Swirlier 16B 5239-09 MPG 2.5 FR Cartridge Weldment Swirlier 17 8428-05 UV Scanner 18A 5238-84 Pilot Weldment - UV (MPG 1.5/2.5) Two Slots 18B 5238-51 Pilot Weldment UV(MPG 1.5/2.5) Three Slots (10 to 1) 19A 5238-82 MPG 1.5 UV Cartridge Weldment Swirlier 1 9B 5239-82 MPG 2.5 UV Cartridge Weldment Swirlier 110A 5238-02 MPG 1.5 UV Cartridge Assembly 110B 5239-02 MPG 2.5 UV Cartridge Assembly 110C 5238-61 MPG 1.5 UV Cartridge Assembly 10 to 1 110D 5239-83 MPG 2.5 UV Cartridge Assembly 10 to 1 1

Item Part # Description Qty

Cartridge Assemblies

Flame Rod (FR) Cartridge

UV Cartridge

4

5

2 3

1

67

8

7

1

1 8450-94 Crank Arm Shrt 22 5243-30 MPG Gas Valve Shaft 13 5243-32 MPG Gas Valve Indicator 14 5243-38 MPG Belimo Assembly 15 5243-39 MPG Belimo Anti-Rotation Bracket 16 5243-31 MPG Actuator Holder 17 8450-18 5/16″ Ball Joint 28 7180-25 14″ Long Connecting Rod 1

Item Part # Description Qty

Gas Flow Controlfor Two-Stage and Full Modulating 3-1 Burners

Not Shown 5243-34 Butterball Valve (MPG 1.5) 5243-35 Butterball Valve (MPG 2.5) 8419-09 Belimo Actuator Repair Kit 8447-28 Transformer Full Mod/Hi-Lo (120/208/240-24V 40VA)

Not Shown

5238-42 Ignition Wire - MPG 1.5/2.5

8457-21 Cable Wrap Black (UV Cartridge Assemblies)

8506-38 Flame Rod Wire MPG 1.5/2.5

(FR Cartridge Assemblies)