506253-01 Issue 0912 Page 1 Save these instructions for future reference INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner TABLE OF CONTENTS INSTALLATION ...................................... 2 START-UP ............................................ 12 OPERATION ........................................ 16 MAINTENANCE ................................... 20 CONNECTION DIAGRAM ................... 22 WARRANTY ......................................... 23 Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical com- ponents. Only trained and qualified service personnel should install or service this equip- ment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death. WARNING Risk of electrical shock. Disconnect all remote power supplies before installing or servicing any portion of the system. Failure to disconnect power supplies can result in property damage, personal injury, or death. WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation technicians. Improper installation, modification, service, or use can cause electrical shock, fire, explosion, or other conditions which may cause personal injury, death, or property damage. Use appropriate safety gear including safety glasses and gloves when installing this equipment. WARNING Sharp metal edges can cause injury. When installing the unit, use care to avoid sharp edges. WARNING *48442L005* Manufactured By Allied Air Enterprises Inc. A Lennox International Inc. Company 215 Metropolitan Drive West Columbia, SC 29170

Upload: others

Post on 07-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 1

Save these instructions for future reference

INSTALLATION AND MAINTENANCEINSTRUCTIONS

4SCU16LT SeriesSplit System Air Conditioner

TABLE OF CONTENTS

INSTALLATION ...................................... 2

START-UP ............................................ 12

OPERATION ........................................ 16

MAINTENANCE ................................... 20

CONNECTION DIAGRAM ................... 22

WARRANTY......................................... 23

Installation and servicing of air conditioningequipment can be hazardous due to internalrefrigerant pressure and live electrical com-ponents. Only trained and qualified servicepersonnel should install or service this equip-ment. Installation and service performed byunqualified persons can result in propertydamage, personal injury, or death.

WARNING

Risk of electrical shock. Disconnect allremote power supplies before installing orservicing any portion of the system. Failureto disconnect power supplies can result inproperty damage, personal injury, or death.

WARNING

The equipment covered in this manual is to be installed by trained and experiencedservice and installation technicians. Improper installation, modification, service, oruse can cause electrical shock, fire, explosion, or other conditions which may causepersonal injury, death, or property damage. Use appropriate safety gear includingsafety glasses and gloves when installing this equipment.

WARNING

Sharp metal edges can cause injury. Wheninstalling the unit, use care to avoid sharpedges.

WARNING

*48442L005*

Manufactured ByAllied Air Enterprises Inc.

A Lennox International Inc. Company215 Metropolitan Drive

West Columbia, SC 29170

Page 2: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 2 Issue 0912 506253-01

INSTALLATION Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possibleshipping damage. If damage is found, it should be notedon the carrier’s freight bill. Take special care to examinethe unit inside the carton if the carton is damaged. Anyconcealed damage discovered should be reported to thelast carrier immediately, preferably in writing, and shouldinclude a request for inspection by the carrier’s agent.If any damages are discovered and reported to the carrierDO NOT INSTALL THE UNIT, as claim may be denied.

Check the unit rating plate to confirm specificationsare as ordered.

Location of Unit

Refer to Figure 1 for installation clearances.

General

Read this entire instruction manual, as well as theinstructions supplied in separate equipment, beforestarting the installation. Observe and follow all warn-ings, cautions, instructional labels, and tags. Failureto comply with these instructions could result in anunsafe condition and/or premature component failure.

These instructions are intended as a general guide onlyfor use by qualified personnel and do not supersede anynational or local codes in any way. The installation mustcomply with all provincial, state, and local codes as well asthe National Electrical Code (U.S.) or Canadian ElectricalCode (Canada). Compliance should be determined priorto installation.

4SCU16LT condensing units use R410A which is anozone-friendly HFC refrigerant. The unit must be installedwith a matching indoor coil and line set. 4SCU16LT unitsare designed for use in expansion valve (TXV) systemsonly. The TXV expansion valve must be ordered sepa-rately from the manufacturer. A filter drier approved foruse with 410A is installed in the unit.

IMPORTANT: This product has been designed and manu-factured to meet ENERGY STAR criteria for energy effi-ciency when matched with appropriate coil components.However, proper refrigerant charge and proper air flow arecritical to achieve rated capacity and efficiency. Installationof this product should follow the manufacturer’s refrigerantcharging and air flow instructions. Failure to confirmproper charge and airflow may reduce energy effi-ciency and shorten equipment life.

When servicing or repairing HVAC components, ensurethe fasteners are appropriately tightened. Table 1 showstorque values for fasteners.

Slab Mounting

When installing unit at grade level, install on level slabhigh enough so that water from higher ground will notcollect around unit (see Figure 2).

Roof Mounting

Install unit at a minimum of 4" above surface of the roof.Care must be taken to ensure weight of unit is properlydistributed over roof joists and rafters. Either redwood orsteel supports are recommended.

Torque Table

Table 1

renetsaF euqroT

spaCmetS .sbl.tf8

spaCtroPecivreS .sbl.tf8

swercSlateMteehS .sbl.ni61

swercSenihcaM8# .sbl.ni61

swercSenihcaM01# .sbl.ni82

stloBrosserpmoC .sbl.ni09

Figure 1

Installation Clearances

* A service clearance of 30" must be maintained onone of the sides adjacent to the control box.Clearance to one of the other three sides must be36". Clearance to one of the remaining two sidesmay be 12" and the final side may be 6".

A clearance of 24" must be maintained between units.

48" clearance required on top of unit. Maximum soffitoverhang is 36".

36 *�

36�

36�36 *�

Page 3: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 3

Electrical Wiring

All field wiring must be done in accordance with theNational Electrical Code (NEC) recommendations,Canadian Electrical Code (CEC) and CSA Standards, orlocal codes, where applicable.

Refer to the furnace or blower coil Installation Instructionsfor additional wiring application diagrams and refer to unitrating plate for minimum circuit ampacity and maximumovercurrent protection size.

1. Install line voltage power supply to unit from a properlysized disconnect switch. Any excess high voltage fieldwiring should be trimmed or secured away from thelow voltage field wiring.

2. Ground unit at unit disconnect switch or to an earthground. To facilitate conduit, a hole is in the bottom ofthe control box. Connect conduit to the control boxusing a proper conduit fitting. Units are approved foruse only with copper conductors. 24V Class II circuitconnections are made to the low voltage pigtails. Acomplete unit wiring diagram is located inside the unitcontrol box cover (see also page 22 of this instruction).

3. Install room thermostat on an inside wall that is notsubject to drafts, direct sunshine, or other heat sources.

4. Install low voltage wiring from outdoor to indoor unit andfrom thermostat to indoor unit (see Figure 3).

Unit must be grounded in accordance withnational and local codes. Failure to ground unitproperly can result in personal injury or death.

WARNING

5. Do not bundle any excess 24V control wire inside controlbox. Run control wire through installed wire tie and tightenwire tie to provide low voltage strain relief and to maintainseparation of field-installed low and high voltage circuits.

Refrigerant Piping

Figure 2

Slab Mounting

Discharge Air

Mounting Slab

Ground Level

BuildingStructure

Thermostat Designations

Figure 3

See unit wiring diagram for power supply connections.If the indoor unit is not equipped with a blower relay,one must be field supplied and installed.Do not connect C (common) connection betweenindoor unit and thermostat except when required bythe indoor thermostat. Refer to thermostat installationinstructions. C (common) connection between indoorunit and outdoor unit required for proper operation.

Power

Indoor UnitThermostat Outdoor Unit

Heat

Cooling

Indoor Blower

R

W1

Y

G

C

R

W

Y

G

C

Y2 Y2

R

W

Y

G

C

Y2

If the 4SCU16LT unit is being installed with a new indoorcoil and line set, the refrigerant connections should bemade as outlined in this section. If an existing line set and/or indoor coil will be used to complete the system, refer tothis section as well as the section that follows entitledFlushing Existing Line Set and Indoor Coil.

If this unit is being matched with an approved line set orindoor coil which was previously charged with R22 refriger-ant, the line set and coil must be flushed prior to installation.If the unit is being used with an existing indoor coil whichwas equipped with a liquid line which served as a meteringdevice (RFCI), the liquid line must be replaced prior to theinstallation of the 4SCU16LT unit.

Field refrigerant piping consists of liquid and suction linesfrom the outdoor unit (sweat connections) to the indoorcoil (flare or sweat connections).

Refrigerant can be harmful if inhaled. Refrigerantmust always be used and recovered responsibly.Incorrect or irresponsible use of refrigerant canresult in personal injury or death.

WARNING

Page 4: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01Page 4 Issue 0912

Select line set diameters from Table 2 to ensure that oil returnto the compressor. Size vertical suction riser to maintainminimum velocity at minimum capacity. Recommended linelength is 50’ or less. If more than 50’ line set is required,contact Technical Services.

Table 2 shows the diameters for line sets up to 100’ althoughvertical lift applications and trapping requirements need tobe reviewed with Technical Services for line sets over 50’.

Installing Refrigerant Line

During the installation of an air conditioning system, it isimportant to properly isolate the refrigerant line to preventunnecessary vibration. Line set contact with the structure(wall, ceiling, or floor) may cause objectionable moise whenvibration is translated into sound. As a result, more energyor vibration can be expected. Close attention to line setisolation must be observed. If refrigeration lines are routedthrough a wall, seal and isolate the opening so vibration isnot transmitted to the building.

Following are some points to consider when placing andinstalling a high-efficiency outdoor unit:

Placement

Be aware that some localities are adopting sound ordinancesbased on how noisy the unit is at the neighbor’s home, notat the original installation. Install the unit as far as possiblefrom the property line. When possible, do not install the unitdirectly outside a bedroom window. Glass has a very highlevel of sound transmission. Figure 4 shows how to placethe outdoor unit and line set to reduce line set vibration.

Line Set Isolation

Illustrations on the following pages demonstrate procedureswhich ensure proper refrigerant line set isolation. Figure 5shows how to install line sets on horizontal runs. On page6, Figure 6 shows how to make a transition from horizontalto vertical and Figure 7 shows how to install line sets onvertical runs.

Brazing Connection Procedure

1. Cut ends of refrigerant lines square (free from nicks ordents). Debur the ends. The pipe must remain round; donot pinch end of line.

2. Before making line set connections, use dry nitrogen topurge the refrigerant piping. This will help to preventoxidation and the introduction of moisture into the system.

3. Use silver alloy brazing rods (5% or 6% silver alloy forcopper-to-copper brazing or 45% silver alloy for

Refrigerant Line Set Diameters (in.)

For installations exceeding 50’, contactTechnical Services.

Table 2

S uction L ine

B T UHL ine S et Length and S ize

12 ft. 25 ft. 50 ft. 75 ft. 100 ft.

3/4 3/424,000 7/8

36,000

7/8

7/8

7/8

1-1/8

7/8

7/8

1-1/848,000

7/87/8

7/8

1-1/8

1-1/8

60,000 1-1/8

1-1/8

7/8

1-1/8 1-1/8

L iquid L ine

B T UHL ine S et Length and S ize

12 ft. 25 ft. 50 ft. 75 ft. 100 ft.

3/8 3/8 3/8 3/8 3/824,000

3/8 3/8 3/8 3/8

3/8 3/8 3/8 1/2

36,000

3/8 3/8 3/8 1/2

48,000

60,000 1/2

1/2

1/2

Polyolester (POE) oils used with R-410A refrigerantabsorb moisture very quickly. It is very important thatthe refrigerant system be kept closed as much aspossible. DO NOT remove line set caps or service valvestub caps until ready to make connections.

WARNING

Page 5: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 5

Outside Unit Placementand Installation

Figure 4

Install unit awayfrom windows

Two 90° elbows installed in linesetwill reduce lineset vibration

copper-to-brass or copper-to-steel brazing) which arerated for use with R410A refrigerant.

4. Remove the Schrader core assemblies before brazingto protect them from damage due to extreme heat.Replace the cores when brazing is complete.

5. Remove light maroon washers from service valves andshield light maroon stickers to protect them duringbrazing. Wrap a wet cloth around the valve body andcopper tube stub to protect it from heat damage.

6. Braze the line set to the service valve. Quench the jointswith water or a wet cloth to prevent heat damage to thevalve core and opening port. The tube end must staybottomed in the fitting during final assembly toensure proper seating, sealing, and rigidity.

7. Install a thermal expansion valve (which is soldseparately and which is approved for use with R410Arefrigerant) in the liquid line at the indoor coil (seeRefrigerant Metering Device on page 8).

Figure 5

To hang line set from joist or rafter,use either metal strapping materialor anchored heavy nylon wire ties.

Strapping Material(around vapor line only)

8’

8’

Tape or Wire Tie

Strap the vapor line to the joist or rafterat 8 intervals then strap the liquid lineto the vapor line.

Floor Joist orRoof Rafter

Metal Sleeve

Floor Joist or Roof Rafter

Tape or Wire Tie

Wire Tie(around vapor line only)

Refrigerant Line Sets: Installing Horizontal Runs

Page 6: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 6 Issue 0912 506253-01

Figure 6

Refrigerant Line Sets: Transition from Vertical to Horizontal

AnchoredHeavy Nylon

Wire Tie

WallStud

Metal SleeveVapor Line Wrapped

in Armaflex–

Liquid Line

WallStud

AutomotiveMuffler-Type

Hanger

Strap LiquidLine to VaporLine

Metal SleeveVapor Line Wrapped

in Armaflex–

Liquid Line

Strap LiquidLine to VaporLine

Figure 7

Refrigerant Line Sets: Installing Vertical Runs (new construction shown)

Outside Wall

Wood BlockBetween Studs

IMPORTANT: Refrigerantlines must not contact wall.

Vapor Line Liquid Line

Wire Tie

Inside Wall

Strap

Sleeve

Wire Tie

Wire Tie

Strap

Wood Block

Sleeve

Vapor Line Wrappedwith Armaflex

Liquid Line

Caulk

PVC Pipe FiberglassInsulation

Outside WallIMPORTANT:

Refrigerantlines must not

contact structure.

NOTE: Similar installation practicesshould be used if line set is to beinstalled on exterior of outside wall.

Page 7: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 7

Flushing Existing Line Set and Indoor Coil

This procedure should not be performed on systemswhich contain contaminants, such as compressorburn out.

Flushing Procedure

IMPORTANT: The line set and/or indoor coil must beflushed with at least the same amount of refrigerant thatpreviously charged the system. Check the charge in theflushing cylinder before flushing the unit.

1. Remove existing R22 refrigerant using the appropriateprocedure.

If the existing outdoor unit is not equipped with shutoffvalves, or if the unit is not operational AND the existingR22 refrigerant will be used to flush the system:

Disconnect all power to the existing outdoor unit.Connect the existing unit, a clean recovery cylinder, andthe recovery machine according to the instructionsprovided with the recovery machine. Remove all R22refrigerant from the existing system. Refer to thegauges after shutdown to confirm that the entire systemis completely void of refrigerant. Disconnect the liquidand suction lines from the existing outdoor unit.

If the existing outdoor unit is equipped with manualshutoff valves AND new R22 refrigerant will be usedto flush the system:

Start the existing R22 refrigerant system in cooling modeand close the liquid line valve. Pump all the existing R22refrigerant back into the outdoor unit.

Required Equipment

The following equipment is needed to flush the existingline set and indoor coil (see Figure 8): Two clean R22recovery bottles, an oil-less recovery machine with a“pump down” feature, and two sets of gauges (one for usewith R22 and one for use with R410A).

Figure 8

Flushing Connections

Note: The inverted R22 cylinder must containat least the same amount of refrigerantas was recovered from the existingsystem.

When flushing existing line set and/or indoorcoil, be sure to empty all existing traps. Residualmineral oil can act as an insulator, preventingproper heat transfer. It can also clog the thermalexpansion valve, reducing system performanceand capacity. Failure to properly flush system asexplained in these instructions will void warranty.

CAUTION

Page 8: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 8 Issue 0912 506253-01

(It may be necessary to bypass the low pressureswitches to ensure complete refrigerant evacuation.)

When the low side system pressures reach 0 psig, closethe suction line valve. Disconnect all power to theexisting outdoor unit. Refer to the gauges after shutdownto confirm that the valves are not allowing refrigerant toflow back into the low side of the system. Disconnect theliquid and suction lines from the existing outdoor unit.

2. Remove the existing outdoor unit. Set the new R410Aunit and follow the brazing connection procedureoutlined previously on this page to make line setconnections. Do not install the R410A thermalexpansion valve at this time.

3. Make low voltage and line voltage connections to thenew outdoor unit. Do not turn on power to the unit oropen the outdoor unit service valves at this time.

4. Remove the existing R-22 refrigerant flow controlorifice or thermal expansion valve before continuingwith flushing procedures. R-22 flow control devicesare not approved for use with R410A refrigerant andmay prevent proper flushing. Use a field-providedfitting to reconnect the lines.

5. Remove the pressure tap valve cores from the4SCU16LT unit’s service valves. Connect an R-22cylinder with clean refrigerant to the suction servicevalve. Connect the R-22 gauge set to the liquid linevalve and connect a recovery machine with an emptyrecovery tank to the gauge set.

6. Set the recovery machine for liquid recovery and startthe recovery machine. Open the gauge set valves toallow the recovery machine to pull a vacuum on theexisting system line set and indoor coil.

7. Invert the cylinder of clean R-22 and open its valve toallow liquid refrigerant to flow into the system throughthe suction line valve. Allow the refrigerant to passfrom the cylinder and through the line set and theindoor coil before it enters the recovery machine.

8. After all of the liquid refrigerant has been recovered,switch the recovery machine to vapor recovery so thatall of the R-22 vapor is recovered. Allow the recoverymachine to pull a vacuum on the system.

NOTE: A single system flush should remove all of themineral oil from the existing refrigerant lines and indoorcoil. A second flushing may be done (using cleanrefrigerant) if insufficient amounts of mineral oil wereremoved during the first flush. After each systemflush, allow the recovery machine to pull a vacuumon the system at the end of the procedure.

9. Close the valve on the inverted R22 cylinder and thegauge set valves. Pump the remaining refrigerant outof the recovery machine and turn the machine off.

10. Use nitrogen to break the vacuum on the refrigerant linesand indoor coil before removing the recovery machine,gauges, and R22 refrigerant drum. Re-install pressure tapvalve cores into the 4SCU16LT unit’s service valves.

11. Install a thermal expansion valve approved for use withR410A refrigerant in the liquid line at the indoor coil.

Refrigerant Metering Device

4SCU16LT units are designed for use with TXV systems only.

Expansion valves equipped with Chatleff-type fittings areavailable from the manufacturer. See Table 3 for properTXV for each unit.

To install an expansion valve (see Figure 9):

1. Separate the distributor assembly and remove thepiston orifice and used teflon seal. Insert nozzle end ofthe expansion valve along with a new teflon seal into thedistributor and tighten to 20 – 30 ft. lbs. Use backupwrench on all wrench flats. Overtightening will crushthe teflon seal and may cause a leak.

2. Attach liquid line portion of distributor assembly alongwith new teflon seal to the inlet of the expansionvalve. Tighten to 20 – 30 ft. lbs. Use backup wrenchon all wrench flats. Overtightening will crush theteflon seal and may cause a leak.

3. Connect the external equalizer line to the equalizerport on the suction line and tighten to 8 ft. lbs.

4. Strap the superheat sensing bulb to the suction header.

If installing an expansion valve on an indoor coil thatpreviously used a fixed orifice, be sure to remove theexisting fixed orifice. Failure to remove a fixed orificewhen installing an expansion valve to the indoor coil willresult in improper operation and damage to the system.

Table 3

TXV Data

ledoM rebmuNtraP

63-,42-TL61UCS4 10VXT4A

TL61UCS4 84- 20VXT4A

TL61UCS4 06- 30VXT4H

Page 9: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 9

To Close Liquid or Suction Line Service Valve:

1. Remove the stem cap with an adjustable wrench.

2. Use a service wrench with a hex-head extension to turnthe stem clockwise to seat the valve. Tighten firmly.

3. Replace the stem cap. Tighten finger tight, thentighten an additional 1/6 turn.

Suction Line (Ball Type) Service Valve

Suction line (ball type) service valves function the sameway as the other valves; the difference is in the construc-tion (see Figure 11 on page 10).

The ball valve is equipped with a service port with afactory-installed Schrader valve. A service port capprotects the Schrader valve from contamination andserves as the primary seal.

Manifold Gauge Set

Manifold gauge sets used with systems charged withR410A refrigerant must be capable of handling the highersystem operating pressures. The gauges should be ratedfor use with pressures 0 – 800 on the high side and a lowside of 30" vacuum to 250 psi with dampened speed to500 psi. Gauge hoses must be rated for use at up to 800psi of pressure with a 4000 psi burst rating.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves and serviceports are used for leak testing, evacuating, charging, andchecking charge.

Each valve is equipped with a service port which has afactory-installed Schrader valve (see Figure 10). A serviceport cap protects the Schrader valve from contaminationand serves as the primary leak seal.

To Access the Schrader Port:

1. Remove the service port cap with an adjustable wrench.

2. Connect gauge to the service port.

3. When testing is completed, replace service port cap.Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1. Remove stem cap with an adjustable wrench.

2. Use a service wrench with a hex-head extension toback the stem out counterclockwise as far as it willgo. Use a 3/16" hex head extension for liquid lineservice valves and a 5/16" extension for suction lineservice valves.

3. Replace the stem cap. Tighten finger tight, thentighten an additional 1/6 turn.

Metering Device Installation

Figure 9

Figure 10

Service Valve

Valve Closed

Valve Open

Page 10: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 10 Issue 0912 506253-01

Leak Testing

After the line set has been connected to the indoor andoutdoor units, the line set connections and indoor unitmust be checked for leaks.

Figure 11

2. With both manifold valves closed, connect the cylin-der of R410A refrigerant. Open the valve on theR410A cylinder (vapor only).

3. Open the high pressure side of the manifold to allowR410A into the line set and indoor unit. Weigh in atrace amount of R410A. (A trace amount is a maxi-mum of 2 oz. of refrigerant or 3 lbs. pressure.) Closethe valve on the R410A cylinder and the valve on thehigh pressure side of the manifold gauge set. Discon-nect the R410A cylinder.

4. Connect a cylinder of nitrogen with a pressure regulat-ing valve to the center port of the manifold gauge set.When using high pressure gas such as nitrogenfor this purpose, be sure to use a regulator thatcan control the pressure down to 1 or 2 psig.

5. Adjust nitrogen pressure to 150 psig. Open the valveon the high side of the manifold gauge set to pressur-ize the line set and the indoor coil.

6. After a short period of time, open a refrigerant port tomake sure that an adequate amount of refrigerant hasbeen added for detection (refrigerant requirements willvary with lengths). Check all joints for leaks. Purgenitrogen and R410A mixture. Correct any leaks andrecheck.

Evacuation

Evacuating the system of noncondensables is critical forproper operation of the unit. Noncondensables are definedas any gas that will not condense under temperatures andpressures present during operation of an air conditioningsystem. Noncondensables and water vapor combine withrefrigerant to produce substances that corrode copperpiping and compressor parts.

Using an Electronic Leak Detector

1. Connect the high pressure hose of the manifoldgauge set to the suction valve service port. (Normallythe high pressure hose is connected to the liquid lineport; however, connecting it to the suction ports helpsto protect the manifold gauge set from damagecaused by high pressure.)

Use a thermocouple or thermistor electronic vacuumgauge that is calibrated in microns. Use an instrument thatreads down to 50 microns.

1. Connect the manifold gauge set to the service valveports as follows:

• Low pressure gauge to suction line service valve• High pressure gauge to liquid line service valve

Do not use a compressor to evacuate a sys-tem. Avoid deep vacuum operation. Extremelylow vacuums can cause internal arcing andcompressor failure. Danger of equipmentdamage. Damage caused by deep vacuumoperation will void warranty.

WARNING

Ball Type Service Valve(Valve Open)

Use adjustable wrench. To open, rotate stemcounterclockwise 1/4 turn (90°). To close, rotatestem clockwise 1/4 turn (90°).

Fire, Explosion, and Personal Safety Hazard.

Failure to follow this warning could result indamage, personal injury, or death.

Never use oxygen to pressurize or purgerefrigeration lines. Oxygen, when exposed toa spark or open flame, can cause damage byfire and/or an explosion, that could result inpersonal injury or death.

WARNING

Page 11: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 11

2. Connect micron gauge.

3. Connect the vacuum pump (with vacuum gauge) tothe center port of the manifold gauge set.

4. Open both manifold valves and start vacuum pump.

5. Evacuate the line set and indoor unit to a minimum of 500microns or lower. During the early stages of evacuation, itis desirable to close the manifold gauge valve at leastonce to determine if there is a rapid rise in pressure. Arapid rise in pressure indicates a relatively large leak. Ifthis occurs, the leak testing procedure must be repeated.

6. When 500 microns or lower is maintained, close themanifold gauge valves, turn off the vacuum pump, anddisconnect the manifold gauge center port hose fromthe vacuum pump. Attach the manifold gauge centerport hose to a nitrogen cylinder with pressure regulatorset to 150 psig and purge the hose. Open the manifoldgauge valves to break the vacuum in the line set andindoor unit. Close the manifold gauge valves.

7. Shut off the nitrogen cylinder and remove the manifoldgauge hose from the cylinder. Open the manifoldgauge valves to release the nitrogen from the line setand indoor unit.

8. Reconnect the manifold gauge to the vacuum pump,turn the pump on, and continue to evacuate the lineset and indoor unit until 500 microns is maintainedwithin a 20-minute period after shutting off thevacuum pump and closing the manifold gauge valves.

9. When the requirements above have been met,disconnect the manifold hose from the vacuum pump.Open the service valves to break the vacuum in theline set and indoor unit.

Page 12: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 12 Issue 0912 506253-01

If the system is void of refrigerant, clean the system usingthe procedure described below.

1. Use dry nitrogen to pressurize the system and checkfor leaks. Repair leaks, if possible.

2. Evacuate the system to remove as much of themoisture as possible.

3. Use dry nitrogen to break the vacuum.

4. Evacuate the system again.

5. Weigh the appropriate amount of R410A refrigerant(listed on unit nameplate) into the system.

6. Monitor the system to determine the amount ofmoisture remaining in the oil. Use a test kit to verifythat the moisture content is within the kit’s dry colorrange. It may be necessary to replace the filter drierseveral times to achieve the required dryness level. Ifsystem dryness is not verified, the compressorwill fail in the future.

The outdoor unit should be charged during warm weather.However, applications arise in which charging must occurin the colder months. The method of charging is deter-mined by the outdoor ambient temperature.

Measure the liquid line temperature and the outdoorambient temperature as outlined below:

1. Connect the manifold gauge set to the service valveports as follows:

• Low pressure gauge to suction line service valve• High pressure gauge to liquid line service valve

START-UP

1. Rotate fan to check for frozen bearings or binding.

2. Inspect all factory and field-installed wiring for looseconnections.

3. After evacuation is complete, open liquid line andsuction line service valves to release refrigerantcharge (contained in outdoor unit) into system.

4. Replace the stem caps and secure finger tight, thentighten an additional 1/6 of a turn.

5. Check voltage supply at the disconnect switch. Thevoltage must be within the range listed on the unitnameplate. If not, do not start equipment until thepower company has been consulted and the voltagecondition corrected.

6. Set thermostat for cooling demand, turn on power toindoor blower and close the outdoor unit disconnectswitch to start the unit.

7. Recheck unit voltage with unit running. Power must bewithin range shown on unit nameplate.

Refrigerant Charging

This system is charged with R410A refrigerant whichoperates at much higher pressures than R22. The liquid linedrier provided with the unit is approved for use with R410A.Do not replace it with one designed for use with R22. Thisunit is NOT approved for use with coils which usecapillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored. Refriger-ant should be added through the vapor valve in theliquid state.

Certain R410A cylinders are identified as beingequipped with a dip tube. These allow liquid refriger-ant to be drawn from the bottom of the cylinderwithout inverting the cylinder. Do not turn this type ofcylinder upside down to draw refrigerant.

Units are factory charged with the amount of R410Arefrigerant indicated on the unit rating plate. This charge isbased on a matching indoor coil and outdoor coil with 15'line set. For varying lengths of line set, refer to Table 4 forrefrigerant charge adjustment.

If unit is equipped with a crankcase heater, itshould be energized 24 hours before unitstart-up to prevent compressor damage as aresult of slugging.

CAUTION

Mineral oils are not compatible with R410A. Ifoil must be added, it must be a polyol ester oil.

IMPORTANT

Refrigerant Charge Adjustment

* If line length is greater than 15 ft., add this amount.If line length is less than 15 ft., remove this amount.

Table 4

teSeniLdiuqiLretemaiD

tsujda.tf5rep.zO*tesenil.tf51morf

.ni8/3 .tf5rep.zo3

Page 13: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 13

2. Close manifold gauge set valves. Connect the centermanifold hose to an upright cylinder of R410A.

3. If room temperature is below 70°F, set the room thermo-stat to call for heat. This will create the necessary loadfor properly charging the system in the cooling cycle.

4. Use a digital thermometer to record the outdoorambient temperature.

5. When the heating demand has been satisfied, switchthe thermostat to cooling mode with a set point of68°F. When pressures have stabilized, use a digitalthermometer to record the liquid and suction linetemperatures.

6. The outdoor temperature will determine which charg-ing method to use. Proceed with the appropriatecharging method.

Charge Using Weigh-In Method

If the system is void of refrigerant, or if the outdoor ambienttemperature is cool, first locate and repair any leaks thenuse the weigh-in method to charge the unit.

1. Recover the refrigerant from the unit.

2. Conduct a leak check, then evacuate as previouslyoutlined.

3. Weigh in the charge according to the total amountshown on the unit nameplate.

If weighing facilities are not available, use one of thefollowing procedures to charge the unit.

Charge Using Subcooling Method –Outdoor Temperatures Below 65°F

When the outdoor ambient temperature is below 65°F, thesubcooling method can be used to charge the unit. It maybe necessary to restrict the air flow through the outdoorcoil to achieve pressures in the 200-250 psig range.These higher pressures are necessary for checking thecharge. Block equal sections of air intake panels andmove obstructions sideways until the liquid pressure is inthe 200-250 psig range (see Figure 12).

1. With the manifold gauge hose on the liquid serviceport and the unit operating stably, use a digital ther-mometer to record the liquid line temperature.

2. At the same time, record the liquid line pressure reading.

3. Use the temperature/pressure chart (Table 5 on page 14)to determine the saturation temperature for the liquid linepressure reading.

4. Subtract the liquid line temperature from the satura-tion temperature (according to the chart) to determinesubcooling.

_____ ° Saturation Temperature °F

_____ ° Liquid Line Temperature °F

_____ ° Subcooling Value °F

=

5. Compare the subcooling value with those shown inTable 6 on page 14. If subcooling is greater thanshown, recover some refrigerant. If subcooling is lessthan shown, add some refrigerant.

Charge Using Approach Method –Outdoor Temperatures 65°F or Above

The following procedure is intended as a general guideand is for use on expansion valve systems only. For bestresults, indoor temperature should 70°F to 80°F. Monitorsystem pressures while charging.

1. Record outdoor ambient temperature using a digitalthermometer.

2. Attach high pressure gauge set and operate unit forseveral minutes to allow system pressures to stabilize.

3. Compare stabilized pressures with those provided inTable 8 on page 15. Minor variations in these pres-sures may be expected due to differences in installa-tions. Significant differences could mean that thesystem is not properly charged or that a problemexists with some component in the system.Pressures higher than those listed indicate that thesystem is overcharged. Pressures lower than thoselisted indicate that the system is undercharged. Verifyadjusted charge using the approach method.

4. Use the same digital thermometer to check liquid linetemperature.

5. Subtract the outdoor ambient temperature from theliquid line temperature to determine the approachtemperature.

Figure 12

Outdoor coil should beblocked one side at a timewith cardboard or plasticsheet until proper testingpressures are reached.

Blocking Outdoor Coil

Cardboard or Plastic Sheet

Page 14: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 14 Issue 0912 506253-01

_____ ° Liquid Line Temperature °F

_____ ° Outdoor Ambient Temperature °F

_____ ° Approach Temperature °F

=

6. Compare the approach value with those shown inTable 7. If the values to do not agree with thoseprovided in Table 7, add refrigerant to lower theapproach temperature or recover refrigerant from thesystem to increase the approach temperature.

Check Charge Using Normal Operating Pressures

Use Table 8 to perform maintenance checks. Table 8 isnot a procedure for charging the system. Minor variationsin these pressures may be due to differences in installa-tions. Significant deviations could mean that the system isnot properly charged or that a problem exists with somecomponent in the system.

R410A Temperature/Pressure Chart

Table 5

.pmeTF°

erusserPgisP

23 8.001

33 9.201

43 0.501

53 1.701

63 2.901

73 4.111

83 6.311

93 8.511

04 0.811

14 3.021

24 6.221

34 0.521

44 3.721

54 7.921

64 2.231

74 6.431

84 1.731

94 6.931

05 2.241

15 8.441

25 4.741

35 1.051

45 8.251

55 5.551

65 2.851

75 0.161

85 9.361

95 7.661

06 6.961

16 6.271

26 5.571

36 5.871

46 6.181

56 3.481

66 7.781

76 9.091

86 1.491

96 3.791

07 6.002

17 9.302

27 2.702

37 6.012

.pmeTF°

erusserPgisP

47 0.412

57 4.712

67 9.022

77 4.422

87 0.822

97 6.132

08 3.532

18 0.932

28 7.242

38 5.642

48 3.052

58 1.452

68 0.852

78 0.262

88 0.662

98 0.072

09 1.472

19 2.872

29 3.282

39 5.682

49 8.092

59 1.592

69 4.992

79 8.303

89 2.803

99 7.213

001 2.713

101 8.123

201 4.623

301 0.133

401 7.533

501 5.043

601 3.543

701 1.053

801 0.553

901 0.063

011 0.563

111 0.073

211 1.573

311 2.083

411 4.583

511 7.093

.pmeTF°

erusserPgisP

611 0.693

711 3.104

811 7.604

911 2.214

021 7.714

121 2.324

221 8.824

321 5.434

421 2.044

521 9.544

621 8.154

721 6.754

821 5.364

921 5.964

031 6.574

131 6.184

231 8.784

331 0.494

431 2.005

531 5.605

631 9.215

731 3.915

831 8.525

931 4.235

041 0.935

141 6.545

241 3.255

341 1.955

441 9.565

541 8.275

641 8.975

741 8.685

841 8.395

941 0.106

051 1.806

151 4.516

251 7.226

351 1.036

451 5.736

551 0.546

Subcooling Values

Table 6

ledoM 42- 63- 84- 06-

F°.pmeT 5 6 6 9

Approach Values for TXV Systems

Approach value is the liquid line temperatureminus the outdoor ambient temperature (±1°F).NOTE: For best results, use the same digitalthermometer to check both outdoor ambient andliquid temperatures.

Table 7

ledoM 42- 63- 84- 06-

F°.pmeT 8 01 8 4

Page 15: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 15

Normal Operating Pressures

L = Liquid S = Suction

Table 8

Values provided above are typical pressures. Indoor unit matchup, indoor air quality, and indoor load will causepressures to vary.

foerutarepmeTgniretnEriAehtlioCroodtuOeht

ledoM

42- 63- 84- 06-

L S L S L S L S

1 ts )yticapaCwoL(egatS

F°56 442 631 832 331 742 031 052 521

F°57 382 831 872 531 182 431 192 721

F°58 623 141 423 731 523 731 433 031

F°59 673 241 473 931 683 931 383 331

F°501 824 441 924 241 824 141 434 631

F°511 684 641 005 441 584 441 984 931

2 dn )yticapaChgiH(egatS

F°56 942 621 152 921 942 321 342 711

F°57 882 331 192 531 682 921 582 321

F°58 133 831 433 931 823 331 923 921

F°59 973 341 383 341 273 731 673 431

F°501 524 741 534 741 914 141 724 731

F°511 184 051 094 051 574 541 584 141

Page 16: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 16 Issue 0912 506253-01

OPERATION

Outdoor unit and indoor blower cycle on demand from theroom thermostat. When the thermostat blower switch ismoved to the ON position, the indoor blower operatescontinuously.

System Diagnostic Module

4SCU16LT units contain a diagnostic module for trouble-shooting air conditioning system failures. By monitoringand analyzing data from the compressor and thermostatdemand, the module can accurately detect the cause ofelectrical and system related failure without any sensors.If a system problem occurs, a flashing LED indicatorcommunicates the failure code.

LED Description

POWER LED (Green) indicates voltage is present at thepower connection of the module.

ALERT LED (Yellow) communicates an abnormal systemcondition through a unique flash code. The ALERT LEDwill flash a number of times consecutively, pause, andthen repeat the process. The number of consecutiveflashes correlates to a particular abnormal condition.

TRIP LED (Red) indicates there is a demand signal fromthe thermostat but no current to the compressor is de-tected by the module. The TRIP LED typically indicatesthe compressor protector is open or may indicate missingsupply power to the compressor.

Interpreting the Diagnostic LEDs

When an abnormal system condition occurs, the diagnosticmodule displays the appropriate ALERT and/or TRIP LED.The yellow ALERT LED will flash a number of timesconsecutively, pause, and then repeat the process. Toidentify a flash code number, count the number of consecu-tive flashes. Refer to Table 9 on page 17 and Table 10 onpage 18 for information on the flash codes.

Every time the module powers up, the last ALERT LEDflash code that occurred prior to shutdown is displayed for60 seconds. The module will continue to display theprevious flash code until the condition returns to normal or24VAC is removed from the module. TRIP and ALERTLEDs flashing at the same time means control circuitvoltage is too low for operation.

24VAC Power Wiring

The diagnostic module requires a constant nominal 24VACpower supply. The wiring to the module’s R and C terminalsmust be directly from the indoor unit or thermostat.

Thermostat Demand Wiring

The diagnostic module requires a thermostat demandsignal to operate properly. The thermostat demand signalinput, labeled Y on the module, should always be con-nected to the compressor contactor coil so that when thecoil is energized, the demand signal input is 24VAC. Whenthe coil is not energized, the demand signal input should beless than 0.5VAC.

Miswired Module Codes

Depending on the system configuration, some ALERTflash codes may not be active. The presence of safetyswitches affects how the system alerts are displayed bythe module.

Miswiring the diagnostic module will cause false LEDcodes. Table 11 on page 19 describes LED operationwhen the module is miswired and what troubleshootingaction is required to correct the problem.

Page 17: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 17

Flash Codes

Table 9

DELsutatS

noitpircseDtluaF noitamrofnIgnitoohselbuorT

REWOP)neerG(

rewopsaheludoM slanimreteludomtatneserpsiegatlovylppuS

PIRT)deR(

dnamedtatsomrehT,tneserpsi1Ylangis

rosserpmocehttubgninnurtonsi

neposirotcetorprosserpmoC.1erusserpdaehhgihrofkcehC*

egatlovylppusrosserpmockcehC*nepositcennocsidrewoptinuroodtuO.2

neposi)s(esufrorekaerbtiucricrosserpmoC.3tcatnocgnikamtonsirotcennocroeriwnekorB.4

metsysnitneserpfinepohctiwserusserpwoL.5nepodeliafsahrotcatnocrosserpmoC.6

TRELA)wolleY(

hsalF1edoC

miTnuRgnoL eeeeesirosserpmoC

gninnurnurgnolylemertxe

selcyc

egrahctnaregirferwoL.1gninnurtonsirewolbrotaropavE.2

stcatnocdnaliocyalerrewolbkcehC*roticapacrotomrewolbkcehC*

egakcolbroeruliafrofrotomrewolbkcehC*rotcennocdnagniriwrewolbrotaropavekcehC*

draoblortnocrewolbroodnikcehC*tiucricneporofgniriwtatsomrehtkcehC*

nezorfsiliocrotaropavE.3erusserpnoitcuswolrofkcehC*

gnittestatsomrehtwolylevissecxerofkcehC*)retlifrianruterrosegakcolblioc(wolfriarotaropavekcehC*

egakcolbrofsretsigerrokrowtcudkcehC*ecivedgniretemytluaF.4

)tcatnocdna,noitacol,ezis(noitallatsniblubVXTkcehC*evitcefedrodesolckcutssiecifirodexif/VXTfikcehC*

ytridsiliocresnednoC.5)metsysnitneserpfidekcolbreirdretlif(noitcirtserenildiuqiL.6

gninoitcnuflamsitatsomrehT.7tiucrictrohsrofgniriwroesab-bustatsomrehtkcehC*

)level,noitacol(noitallatsnitatsomrehtkcehC*

TRELA)wolleY(

hsalF2edoC

metsySpirTerusserP

noitcusroegrahcsiDerusserp

rostimilfotuorosserpmoc

dedaolrevo

erusserpdaehhgiH.1metsysnitneserpfihctiwserusserphgihkcehC*tnaregirferhtiwdegrahcrevosimetsysfikcehC*

metsysnielbasnednoc-nonrofkcehC*)degamad,dekcolb,ytrid(noitalucricriaroopliocresnednoC.2

gninnurtonsinafresnednoC.3roticapacnafkcehC*

srotcennocdnagniriwnafkcehC*egakcolbroeruliafrofrotomnafkcehC*

egakaellaitnatsbussahtcudrianruteR.4ofni1edoChsalFkcehc,metsysnitneserphctiwserusserpwolfI.5

Page 18: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 18 Issue 0912 506253-01

Flash Codes (cont.)

Table 10

DELsutatS

noitpircseDtluaF noitamrofnIgnitoohselbuorT

TRELA)wolleY(

hsalF3edoC

gnilcyCtrohSsirosserpmoC

gninnurylfeirbylno

tnettimretnisilangisdnamedtatsomrehT.1evitcefeddraoblortnocroyaleryaledemiT.2

ofni2edoChsalFotog,tneserphctiwserusserphgihfI.3ofni1edoChsalFotog,tneserphctiwserusserpwolfI.4

TRELA)wolleY(

hsalF4edoC

rotoRdekcoL

deliafsahroticapacnuR.1)wolsitcennocsidtaegatlovfiytilitutcatnoc(egatlovenilwoL.2

snoitcennocgniriwkcehC*rosserpmocnitnaregirferdiuqilevissecxE.3

dezieserasgniraebrosserpmoC.4levelliorosserpmocerusaeM*

TRELA)wolleY(

hsalF5edoC

tiucriCnepO

nepositcennocsidrewoptinuroodtuO.1neposi)s(esufrorekaerbtiucricrosserpmoC.2

nepodeliafsahrotcatnocrosserpmoC.3srotcennocdnagniriwrotcatnocrosserpmockcehC*

)neporo,dettip,denrub(eruliafrotcatnocrosserpmocrofkcehC*rosserpmocdnaylppusneewtebsrotcennocdnagniriwkcehC*

liocrotcatnocrosserpmoctaegatlovtolipwolrofkcehC*teserlaunamseriuqerdnaneposihctiwserusserphgiH.4snoitcennocrogniriwylppusrosserpmocnitiucricnepO.5

erutarepmettneibmaemertxeoteudemitteserrotcetorprosserpmocgnolyllausunU.6degamaderasgnidniwrosserpmoC.7

ecnatsisergnidniwrotomrosserpmockcehC*

TRELA)wolleY(

hsalF6edoC

tiucriCtratSnepOnurniylnotnerruC

tiucric

deliafsahroticapacnuR.1snoitcennocrogniriwtratsrosserpmocnitiucricnepO.2

lanimretSrosserpmocehtdnaylppusneewtebsrotcennocdnagniriwkcehC*degamadsignidniwtratsrosserpmoC.3

ecnatsisergnidniwrotomrosserpmockcehC*

TRELA)wolleY(

hsalF7edoC

tiucriCnuRnepOtratsniylnotnerruC

tiucric

snoitcennocrogniriwnurrosserpmocnitiucricnepO.1lanimretRrosserpmocehtdnaylppusneewtebsrotcennocdnagniriwkcehC*

degamadsignidniwnurrosserpmoC.2ecnatsisergnidniwrotomrosserpmockcehC*

TRELA)wolleY(

hsalF8edoC

rotcatnoCdedleWsyawlarosserpmoC

snur

desolcdeliafsahrotcatnocrosserpmoC.1eludomotdetcennoctonlangisdnamedtatsomrehT.2

TRELA)wolleY(

hsalF9edoC

egatloVwoLsseltiucriclortnoC

CAV71naht

dedaolrevosiremrofsnarttiucriclortnoC.1)wolsitcennocsidtaegatlovfiytilitutcatnoc(egatlovenilwoL.2

snoitidnocgniriwkcehC*

Page 19: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 19

Table 11

Miswired Module Troubleshooting

noitacidnIeludoMderiwsiM noitcAgnitoohselbuorTdednemmoceR

,notonsiDELneerG.purewoptonseodeludom

tneserpsiegatlovyfireV.detcennoceraslanimreteludomCdnaRhtobfienimreteDrof61egapnonoitcesgniriWrewoPCAV42weiveR.slanimretCdnaRs'eludomta

.gniriwCdnaR

,tnettimretniDELneerGylnopusrewopeludom.snurrosserpmocnehw

CdnaRs'eludomyfireV.esrevernideriweraslanimretYdnaRfienimreteD61egapnonoitcesgniriWrewoPCAV42weiveR.ecruostnatsnocaevahslanimret

.gniriwCdnaRrof

metsystubnosiDELPIRT.KOkcehcrosserpmocdna

rotcatnoctaegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV.ffonehwCAV5.0wolebsllafslioc

DELTRELAdnaDELPIRT.rehtegotgnihsalf

.CAV82-91htiwdeilppuseraslanimretCdnaRyfireV

3edoChsalFTRELA)gnilcyCtrohSrosserpmoC(

.yltcerrocnideyalpsid

rotcatnoctaegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV.ffonehwCAV5.0wolebsllaflioc

7ro,6,5edoChsalFTRELAtratSnepO,tiucriCnepO(

)tiucriCnuRnepOro,tiucriC.yltcerrocnideyalpsid

gnisnestnerrucs'eludomhguorhteraseriwtratsdnanurrosserpmoctahtkcehCtaegatlovyfireV.liocrotcatnoctaCAV42otdetcennocsilanimretYyfireV.seloh

.ffonehwCAV5.0wolebsllafliocrotcatnoc

6edoChsalFTRELA)tiucriCtratSnepO(7edoCrofdeyalpsidtiucriCnuRnepO(

.asrevecivro

eludomtcerrochguorhtdetuoreraseriwtratsdnanurrosserpmoctahtkcehC.selohgnisnes

8edoChsalFTRELA)rotcatnoCdedleW(.yltcerrocnideyalpsid

taCAV42otdetcennocsilanimretYyfireV.detcennocsilanimretYs'eludomfienimreteDsilangisdnamedtatsomrehtnehwCdnaYssorcatneserpsiCAV42yfireV.liocrotcatnoc

wolebsllafliocrotcatnoctaegatlovyfireV.deriwesrevereraCdnaR,tonfI.tneserp.gniriwCdnaYrof61egapnogniriWdnameDtatsomrehTweiveR.ffonehwCAV5.0

Page 20: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 20 Issue 0912 506253-01

4. Check all wiring for loose connections.

5. Check for correct voltage at unit (with unit operating).

6. Check amp-draw on blower motor.

Unit nameplate _________ Actual _________

Maintenance and service must be performed by a quali-fied installer or service agency.

At the beginning of each cooling season, the systemshould be checked as follows:

1. Clean and inspect condenser coil. Coil may beflushed with a water hose. Be sure the power is offbefore using water to clean the coil.

2. Outdoor fan motor is pre-lubricated and sealed. Nofurther lubrication is needed.

3. Visually inspect connecting lines and coils for evi-dence of oil leaks.

4. Check wiring for loose connections.

5. Check for correct voltage at unit (with unit operating).

6. Check amp-draw outdoor fan motor.

Unit nameplate _________ Actual _________

NOTE – If owner complains of insufficient cooling, theunit should be gauged and refrigerant charge checked.Refer to the Refrigerant Charging section on page 12.

Indoor Coil

1. Clean coil, if necessary.

2. Check connecting lines and coils for evidence of oilleaks.

3. Check condensate pan line and clean, if necessary.

Indoor Unit

1. Clean or change filters.

2. Adjust blower speed for cooling. Measure the pressuredrop over the coil to determine the correct blower CFM.

3. Belt drive blowers: Check belt for wear and propertension.

MAINTENANCE

Before performing maintenance operations onsystem, turn the electric power to unit OFF atdisconnect switch(es). Unit may have multiplepower supplies. Electrical shock could causepersonal injury or death.

WARNING

Page 21: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 21

Start-Up and Performance Checklist

Job Name _______________________________ Job No. ________________ Date ______________

Job Location _____________________________ City ___________________ State ______________

Installer _________________________________ City ___________________ State ______________

Unit Model No.______________ Serial No. ___________________

Service Technician ________________________________________ Nameplate Voltage ______________

Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________

Maximum Fuse or Circuit Breaker________________________

Electrical Connections Tight? Indoor Filter Clean? Supply Voltage (Unit Off) ________________

Indoor Blower RPM _____________ S.P. Drop Over Indoor (Dry) ____________

Outdoor Coil Entering Air Temperature _____________ Voltage with Compressor Operating _____________

Discharge Pressure___________ Vapor Pressure ____________

Refrigerant Charge Checked? Outdoor Fan Checked?

Refrigerant Lines: Leak Checked? Properly Insulated?

Service Valves: Fully Opened? Caps Tight?

Thermostat: Calibrated? Properly Set? Level?

Page 22: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

Page 22 Issue 0912 506253-01Figure 13

Wiring Diagram P/N 48440-002

OUTDOORFAN

F C H

R S C

H C F

C

EQUIPMENTGROUND

HR1

L2

208-230/60/1

L1

K1-1

BLACK

YELLOW

RED

RE

D

C12

BLACK

ORANGE

B4

PURPLE

K1

S4 S24

Y1 C

S4 HIGHPRESSURE

SWITCH

S24 LOSSOF CHARGE

SWITCH

B1

GROUNDLUG

GROUND

L2

L1208-230/60/1

C Y1

TO 24 VACPOWER SOURCE20 VA MINIMUMNEC CLASS 2

DUALCAPACITOR

RE

D

CO

MP

RE

SS

OR

CO

NTA

CTO

R

BLACK

COMPRESSORCRANKCASE HEATER

(IF USED)

PURPLEBLACK

ORANGE

YELLOW

1 S R

Y2 R CL Y1

Y2

RCL

Y1

RY2

LT BLUE

RE

DR

Y2BLUE

RED

YE

LLO

W

A132

TO 24 VACPOWER SOURCE20 VA MINIMUMNEC CLASS 2

DESCRIPTIONKEY COMPONENTA4 CONTROL - TIMED OFF

B1 COMPRESSORB4 MOTOR - OUTDOOR FAN

C12 CAPACITOR - DUALHR1 HEATER - COMPRESSORK1-1 CONTACTOR - COMPRESSORS4 SWITCH - HIGH PRESSURE

S24 SWITCH - LOSS OF CHARGE

FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT RATINGPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENTPROTECTION SIZE.

WARNING--ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH.UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONALAND LOCAL CODES.

LINE VOLTAGE FACTORY INSTALLED

1

LINE VOLTAGE FIELD INSTALLED

24 VOLT FACTORY INSTALLED

CLASS II VOLTAGE FIELD INSTALLED

A132 DIAGNOSTIC MODULE

Page 23: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Page 23Issue 0912

ALLIED AIR ENTERPRISESEQUIPMENT LIMITED WARRANTYAPPLIES IN U.S.A. AND CANADA ONLY

FAILURE TO MAINTAIN YOUR EQUIPMENT WILL VOID THIS WARRANTY

COVERED EQUIPMENTThe following Allied Air Enterprises heating and cooling equipment is covered by the Limited Warranty,

Condensing Units: 2SCU13, 4SCU13, 4SCU14, 4SCU16, 4SCU18, 2AC13, 2AC14, 4AC13Heat Pumps: 2SHP13, 4SHP13, 2SHP14, 4SHP14, 4SHP16, 4SHP18, 2HP13, 2HP14, 4HP13Gas Furnaces: G1N80, G1D80, G2D80, G1D91, G1D93, G2D93, G2D95, FPBB, CG80, CG90, CG92, CG93Oil Furnace: LBR80, LBF80, LHF80, LUF80, LHF80, RLUF, RLBF, RLBR, RLBU, RLHF, RLHRElectric Furnace: EFC, EFVEvaporator Coils: EC, EU, EH, EMAir handlers: BCS2, RBCS2Package Equipment: 2PCE13, 4PCE13, 4PCE15, 2PGE13, 4PGE13, 4PGE15, 2PHP13, 4PHP13, 4PHP15, 2SG13, 2SH13, 2SA13, RGE13, RPGE13, RHP13, RCE13, RPHP13, RPCE13

PARTS and COMPRESSOR COVERAGEThe covered equipment and covered parts and compressor are warranted by Allied Air for a period of five (5) years from the date of the original installation, when installed in a residential application(which includes homes, duplexes, apartments and condominiums). The covered equipment and covered parts and compressor are warranted by Allied Air for a period of one (1) year from the date of theoriginal installation, when installed in non-residential applications. If, during this period, a covered component fails because of a manufacturing defect, Allied Air will provide a free replacement part tothe owner through a licensed service contractor utilizing an Allied Air distributor. You must pay shipping charges and all other costs of warranty service. Allied Air will not pay labor involved in diagnosticcalls or in removing, repairing, servicing or replacing parts. Such cost may be covered by a separate warranty provided by the installer.

HEAT EXCHANGER EXTENDED COVERAGEAll covered heat exchangers are warranted by Allied Air for a period of twenty (20) years from the date of original installation.Heat Exchanger Availability: If a replacement heat exchanger is no longer available for a unit covered by this warranty, Allied Air will allow a credit toward the purchase of an equivalent Allied Air furnace(at the current suggested distributor’s cost).

NOTE: if the date of original installation cannot be verified, the warranty period will be deemed to begin ninety (90) days after the date of manufacture.

EXCLUDED COMPONENTSThe following components are not covered by this warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles, unit accessories and any parts notaffecting unit operation

CARE OF EQUIPMENTYour new Allied Air unit must be properly installed, operated and maintained in accordance with the unit installation, operation and maintenance instructions provided with each Allied Air unit. Failure toprovide maintenance per Allied Air instructions will void this warranty.

WARRANTY PROCEDUREWhen service or warranty parts are required:

1. Call your local licensed service dealer or contractor 2. If the installing dealer is unable to provide warranty service, check online at www.alliedair.com. 3. Be prepared to furnish the following information:

a. complete model and serial numberb. proof of required periodic maintenance, installation date and locationc. an accurate description of the problem

WARRANTY LIMITATIONS1. This warranty is void if the covered equipment is removed from the original installation site.2. This warranty does not cover damage or defect resulting from:

a. flood, wind, fire, lightning, mold, or installation and operation in a corrosive atmosphere, or otherwise in contact with corrosive materials (chorine, fluorine, salt, recycled wastewater, urine, fertilizers, or other damaging substances or chemicals); accident, or neglect or unreasonable use or operation of the equipment including operation of electricalequipment at voltages other than the range specified on the unit nameplate (includes damages caused by brownouts).

b. modification, change or alteration of the equipment, except as directed in writing by Allied Air.c. operation with system components (indoor unit, outdoor unit and refrigerant control devices) which are not an ARI match or meet the specifications recommended by Allied Air.d. operation of furnaces with return air temperatures of less than 60ºF (16ºC) or operation of a furnace field installed downstream from a cooling coil.e. use of contaminated or refrigerant not compatible with the unit.

The installation of replacement parts under the terms of this warranty does not extend the original warranty period.

Allied Air makes no express warranties other than the warranty specified above. All implied warranties, including the implied warranties of merchantability and fitness for a particularpurpose, are excluded to the extent to a period legally permissible. Should such exclusion or limitation of the warranty be unenforceable, such implied warranties are in any event limitedto a period of one (1) year. Liability for incidental and consequential damages is excluded. Some states do not allow limitation of incidental damages, so the limitations or exclusions maynot apply to you. Allied Air will not pay electricity or fuel costs, or increases in electricity or fuel costs, for any reason whatsoever, including additional or unusual use of supplementalelectric heat. This warranty does not cover lodging expenses or labor charges.

Allied Air shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control.

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

NOTE TO CUSTOMER:Please complete information below and retain this warranty for your records and future reference.

Outside Unit Model Number: ____________________________________________________ Serial Number: _______________________________________ Installed Date: ________________

Furnace / Air Handler: _________________________________________________________ Serial Number: _______________________________________ Installed Date: ________________

Indoor Coil Model Number: _____________________________________________________ Serial Number: _______________________________________ Installed Dare: ________________

Installing Company Name: ___________________________________________________________________________________ Phone: _____________________________________________

Installing Company Address: _____________________________________________________________ State/Province: _______________________________ Zip/Postal Code: _____________

215 Metropolitan Drive - West Columbia - SC - 29170© 2008 Allied Air Enterprises Litho U.S.A. FORM W-2008-2 (3/10/2009)

Page 24: INSTALLATION AND MAINTENANCE …...However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should

506253-01 Issue 0912 Page 24

Allied Air Enterprises, Inc. (“Allied”) provides its air conditioning and heating products with a standard five-year parts warranty. This limited extended parts warranty is in addition to andis intended to supplement Allied’s standard 5-year parts warranty. As such, this limited extended warranty provides for a total of 10-years of limited warranty coverage (Standard 5-YearLimited Parts Warranty plus Additional 5-Year Limited Extended Parts warranty).

EXTENDED COVERAGE -

PARTS/COMPRESSORSThe covered equipment and parts are warranted by Allied for a total of 10 YEARS (standard 5 Year Limited Parts Warranty) from installation, except as provided below.

HEAT EXCHANGERSThe covered residential heating equipment’s heat exchanger is warranted by Allied for a Limited Lifetime (standard 20 Year Limited Warranty) from date of original installation, exceptas provided below.

This warranty applies only to the original purchaser of the unit and cannot be transferred. If during this period, a covered part fails because of a defect in materials or workmanship undernormal use and maintenance, Allied will provide a free replacement part to the purchaser through an Armstrong Air, Air Ease, Ducane or Concord dealer or other licensed servicecontractor through an authorized Allied distributor. The purchaser must pay shipping costs, including labor, of the warranty service.

EXCLUDED COMPONENTS -The following components are expressly not covered by this limited warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts, wiring, fuses, oil nozzles,and unit accessories, R-22 compressors, and any parts not affecting unit operation.

If this extended warranty does not apply, then parts are warranted for the standard warranty period of 5 YEARS and all heat exchangers for 20 YEARS. If the standard warrantyperiods differ from the original warranty certificate, the periods stated on the original warranty certificate apply.

This limited extended warranty does not apply to, and no warranty is offered by Allied, on any unit ordered over the internet. Proof of purchase may be required.

Any part replaced pursuant to this limited extended warranty is warranted only for the unexpired portion of the limited extended warranty term applying to the original part. Theinstallation of replacement parts under the terms of this limited extended warranty does not extend the warranty period.

This limited extended warranty is an extension of Allied’s standard warranty. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSEON THIS PRODUCT IS LIMITED IN DURATION TO THE TERM OF THIS LIMITED EXTENDED WARRANTY. Some states and provinces do not allow limitations on how long animplied warranty lasts, so the above limitation may not apply to you.

ALLIED SHALL IN NO EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO EXTRA UTILITY EXPENSES OR DAMAGESTO PROPERTY. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

Allied is not responsible for:1. Damage or repairs required as a result of flood, fire, wind, lightening strike (to the home or unit), corrosive atmosphere, contact with corrosive material (Chlorine, fluorine, salt,

recycled waste water, fertilizers or other damaging substances) or other conditions beyond the control of Allied;2. Use of parts, accessories, or refrigerant not compatible with the unit;3. Modification, change or alteration of the unit, except as expressly directed in writing by Allied;4. Improper use, accident, neglect or unreasonable use or operation of the unit, including operation of electrical equipment at voltages other than the range specified on the unit

nameplate;5. Operation with system parts (indoor unit, outdoor unit and refrigerant control devices) which are not ARI matched or do not meet the specifications recommended by Allied;6. Damage or repairs required as a consequence of faulty or installation or application;7. Normal maintenance as described in the installation and operating manual, such as cleaning of coils, filter cleaning and/or replacement and lubrication; and8. Changes in the appearance or sound of the unit that do not affect its performance.

The parties intend this writing as a final expression of their agreement with respect to warranties. Allied makes no other warranty beyond that which is expressly containedin this writing.

Allied shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control, including the unavailability of replacement parts.

This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.

Steps for getting replacement parts under this limited extended warranty:If you suspect a defect in your equipment, please contact the installer of the unit to obtain assistance. If unsuccessful, please contact an Allied dealer or distributor inyour area. If unable to obtain local assistance, refer to Allied’s website (www.alliedair.com) or contact Allied at 800-448-5872.

1 Excludes residents of states or provinces where registration requirements are prohibited, such as California and Quebec. Residents of these states or provinces may either register as noted above orprovide proof of when the unit was purchased and installed, such as an original invoice from the contractor with the Owner’s name, address, purchase date, serial and model number.

LIMITED EXTENDED PARTS WARRANTY

1. The unit is an Armstrong Air, Air ease, Ducane, or Concord branded unit;2. The unit is installed in a residential application, which is an owner-occupied single-family residence. No commercial applications are allowed;3. The unit is properly registered at (www.alliedair.com) with Allied Air Enterprises within 60-days after the original date of installation oroccupancy.1 To register follow the directions and complete the on line warranty registration at (www.alliedair.com). For customer inquiriescontact Allied Air at 1-800-448-5872.4. The unit is part of a complete ARI matched system and installed by a state certified or licensed contractor in accordance with the unit installation,operation, and maintenance instructions provided with the unit.5. Coils and air handlers are covered only when they are branded Armstrong Air, Air ease, Ducane, or Concord and are purchased and installed as asystem along with a qualifying unit. (Third party coils are not covered).6. Installation takes place on or after October 3, 2008.

COVERAGE REQUIREMENTS -