Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter with HART ® Protocol

Upload: vuongdieu

Post on 24-Jul-2018

248 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start Guide00825-0100-4801, Rev NA

February 2018

00825-0100-4801_RevNA.fm Page 1 Friday, February 9, 2018 9:41 AM

Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter

®

with HART Protocol
Page 2: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 2 Friday, February 9, 2018 9:41 AM

NOTICEThis guide provides basic guidelines for Rosemount 3051S Series Pressure Transmitters. It also provides the basic electronic guidelines for the Rosemount 3051SFA Reference Manual, Rosemount 3051SFC Reference Manual, and Rosemount 3051SFP Reference Manual. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Rosemount 3051S HART Reference Manual for more instruction. This document is also available electronically on Emerson.com/Rosemount.

Explosions could result in death or serious injury.

Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of this guide for any restrictions associated with a safe installation.

Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.

In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.

Use appropriately rated Ex adaptors, blanking elements, or glands during installation.

Keep process insulation at least 1-in. (25 mm) from transmitter connection.Process leaks may cause harm or result in death.

Install and tighten process connectors before applying pressure.Electrical shock can result in death or serious injury.

Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.

Conduit/cable entries

Unless marked, the conduit/cable entries in the transmitter housing use a 1/2–14 NPT thread form. Entries marked “M20” are M20 � 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.

When installing in a hazardous location, use only appropriately listed or Ex certified plugs, adapters, or glands in cable/conduit entries.

Contents Mount the transmitter . . . . . . . . . . . . . . . . . . . . 3Consider housing rotation . . . . . . . . . . . . . . . . . 8Set switches and jumpers . . . . . . . . . . . . . . . . . . 8Connect wiring and power up . . . . . . . . . . . . . . 9

Verify configuration . . . . . . . . . . . . . . . . . . . . . 15Trim the transmitter . . . . . . . . . . . . . . . . . . . . . 18Safety instrumented systems installation . . . 19Product Certifications . . . . . . . . . . . . . . . . . . . . 20

2

Page 3: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 3 Friday, February 9, 2018 9:41 AM

1.0 Mount the transmitter

1.1 Liquid flow applications1. Place taps to the side of the line.2. Mount beside or below the taps.3. Mount the transmitter so the

drain/vent valves are oriented above the process.

1.2 Gas flow applications1. Place taps in the top or side of the line.2. Mount beside or above the taps.

1.3 Steam flow applications1. Place taps to the side of the line.2. Mount beside or below the taps.3. Fill impulse lines with water.

Flow

Flow

Flow

Flow

3

Page 4: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 4 Friday, February 9, 2018 9:41 AM

1.4 Using a mounting bracketIf the transmitter requires the use of a mounting bracket, use the images below for instructions on how to properly mount the transmitter using the Emerson™ provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts.

Panel mount Pipe mount

Coplanar flange

Traditional flange

In-line

4

Page 5: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 5 Friday, February 9, 2018 9:41 AM

1.5 Bolting considerationsIf the transmitter installation requires assembly of the process flanges, manifolds, or flange adaptors, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.

Figure 1. Common Transmitter Assemblies

A. Transmitter with coplanar flangeB. Transmitter with coplanar flange and optional flange adaptorsC. Transmitter with traditional flange and optional flange adaptorsD. Transmitter with coplanar flange and optional Rosemount Conventional Manifold and

flange adapters

Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1. If bolt material is not shown in Table 1, contact the local Emerson representative for more information.

Use the following bolt installation procedure:1. Carbon steel bolts do not require lubrication and the stainless steel bolts are

coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.

Housings

Plantweb™ Junction box Remote mount display

A

4 × 1.75-in. (44 mm)

D

4 × 1.75-in. (44 mm)

4 × 2.25-in. (57 mm)

C

4 × 1.75-in. (44 mm)

4 × 1.50-in. (38 mm)

B

4 × 2.88-in. (73 mm)

5

Page 6: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 6 Friday, February 9, 2018 9:41 AM

2. Finger-tighten the bolts.3. Torque the bolts to the initial torque value using a crossing pattern.

See Table 1 for initial torque value.4. Torque the bolts to the final torque value using the same crossing pattern.

See Table 1 for final torque value.5. Verify the flange bolts are protruding through the sensor module before

applying pressure.

Figure 2. Proper Bolt Installation

A. BoltB. Sensor module

Table 1. Torque Values for the Flange and Flange Adaptor Bolts

Bolt material Head markings Initial torque Final torque

Carbon Steel (CS) 300 in-lb 650 in-lb

Stainless Steel (SST) 150 in-lb 300 in-lb

AB

B7M

316316

316SW

316STM316

R

B8M

6

Page 7: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 7 Friday, February 9, 2018 9:41 AM

1.6 O-rings with flange adaptors

1.7 In-line gage transmitter orientationThe low side pressure port (atmospheric reference) on the in-line gage transmitter is located under the sensor module neck label. (See Figure 3.)

Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so any contaminants can drain away.

Figure 3. In-line Gage Transmitter

A. Low side pressure port (under neck label)

Failure to install proper flange adaptor O-rings may cause process leaks, which can result in death or serious injury. The two flange adaptors are distinguished by unique O-ring grooves. Only use the O-ring designed for its specific flange adaptor, as shown below:

A. Flange adaptorB. O-ringC. PTFE based (profile is square)D. Elastomer (profile is round)

Whenever the flanges or adaptors are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the O-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the O-rings.

A

B

CD

Rosemount 3051S/3051/2051/4088

A

7

Page 8: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 8 Friday, February 9, 2018 9:41 AM

2.0 Consider housing rotationTo improve field access to wiring or to better view the optional LCD display:1. Loosen the housing rotation set screw.2. First rotate the housing clockwise to the desired location. If the desired

location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360 degrees from thread limit).

3. Retighten the housing rotation set screw up to 30 in-lb.

Figure 4. Transmitter Housing Set Screw

A. Housing rotation set screw (3/32-in.)

3.0 Set switches and jumpersIf alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm “high” and the security “off”.

1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the transmitters is live, set the loop to manual and remove power.

2. Remove the electronics compartment cover. On the Plantweb housing the cover is opposite the field terminals side, or on the junction box housing remove the terminal block cover. Do not remove the housing cover in explosive environments.

3. On the Plantweb housing, slide the security and alarm switches into the preferred position by using a small screwdriver (An LCD display or an adjustment module must be in place to activate the switches). On the junction box housing pull the pins out and rotate 90° into desired position to set the security and alarm.

4. Reinstall the housing cover so metal contacts metal to meet explosion-proof requirements.

Plantweb Junction box

A A

8

Page 9: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 9 Friday, February 9, 2018 9:41 AM

Figure 5. Transmitter Switch and Jumper Configuration

A. Meter/adjustment moduleB. SecurityC. Alarm

4.0 Connect wiring and power upUse the following steps to wire the transmitter:1. Remove and discard orange conduit plugs.2. Remove the housing cover labeled “Field Terminals.” 3. Connect the positive lead to the “+” terminal, and the negative lead to the

“–” terminal.

NoteDo not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted pairs yield best results. Use 24–14 AWG wire and do not exceed 5,000 ft. (1,500 m). For single compartment housing (Junction Box housing), shielded signal wiring should be used in high EMI/RFI environments.

4. Plug and seal the unused conduit connection with the provided conduit plug.

5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.

6. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.

Plantweb Junction box

NOTICEWhen the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged.

A

B C

BC

9

Page 10: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 10 Friday, February 9, 2018 9:41 AM

The figures below show the wiring connections necessary to power a Rosemount 3051S and enable communications with a hand-held Field Communicator.

Figure 6. Transmitter Wiring

A. RL ≥ 250 ΩB. Power supply

NoteInstallation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051S case is properly grounded.

4.1 Signal wiring groundingDo not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations. See Step 2 for more information on how the cable shield should be grounded.1. Remove the Field Terminals housing cover.2. Connect the wiring pair and ground as indicated in Figure 7.

a. The cable shield should: Be trimmed close and insulated from touching the transmitter housing Continuously connect to the termination point Be connected to a good earth ground at the power supply end

Plantweb housing wiring Junction box housing wiring

A

B

A

B

10

Page 11: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 11 Friday, February 9, 2018 9:41 AM

Figure 7. Wiring

A. Insulate shieldB. Minimize distanceC. Connect shield back to the power supply groundD. Trim shield and insulateE. Safety ground

3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing.

4. Plug and seal the unused conduit connection with the provided conduit plug.

4.2 Remote display wiring and power up (if applicable)The remote mount display and Interface system consists of a local transmitter and a remote mount LCD display assembly. The local Rosemount 3051S assembly includes a Junction Box housing with a three-position terminal block integrally mounted to a sensor module. The remote mount LCD display assembly consists of a dual compartment Plantweb housing with a seven position terminal block. See Figure 8 on page 12 for complete wiring instructions. The following is a list of necessary information specific to the remote mount display system:

Each terminal block is unique for the remote display system. A 316 SST housing adaptor is permanently secured to the remote mount LCD

display Plantweb housing, providing an external ground and a means for field mounting with the provided mounting bracket.

A cable is required for wiring between the transmitter and remote mount LCD display. The cable length is limited to 100 ft.

50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring between the transmitter and remote mount LCD display. Option M7 does not include cable; see recommended specifications below.

Cable type

Recommend Madison AWM Style 2549 cable. Other comparable cable may be used as long as it has independent dual twisted shielded pair wires with an outer shield. The power wires must be 22 AWG minimum and the CAN communication wires must be 24 AWG minimum.

DP

C

AB

B

D E

11

Page 12: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 12 Friday, February 9, 2018 9:41 AM

Cable length

The cable length is up to 100 ft .depending upon cable capacitance.

Cable capacitance

The capacitance from the CAN communications line to the CAN return line as wired must be less than 5,000 picofarads total. This allows up to 50 picofarads per foot for a 100 foot cable.

Intrinsic safety consideration

The transmitter assembly with remote display has been approved with Madison AWM Style 2549 cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or control drawing in Appendix B of the Rosemount 3051S Reference Manual for remote cable IS requirements.

ImportantDo not apply power to the remote communications terminal. Follow wiring instructions carefully to prevent damage to system components.

Figure 8. Remote Mount Display Wiring Diagram

A. Remote mount displayB. Junction box housingC. 4–20 mA

A

B

C

(white) 24 AWG

(blue) 24 AWG

(black) 22 AWG

(red) 22 AWG

12

Page 13: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 13 Friday, February 9, 2018 9:41 AM

NoteWire colors provided on page 12 are per Madison AWM Style 2549 cable. Wire color may vary depending on cable selected.

Madison AWM Style 2549 cable includes a ground shield. This shield must be connected to earth ground at either the sensor module or the remote display, but not both.

4.3 Quick connect wiring (if applicable)As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately.

Figure 9. Rosemount 3051S Quick Connect Exploded View

ImportantIf Quick Connect is ordered as a Rosemount 300S spare housing or is removed from the sensor module, follow the instructions below for proper assembly prior to field wiring.

1. Place the Quick Connect onto the sensor module. To ensure proper pin alignment, remove coupling nut prior to installing quick connect onto the sensor module.

2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb (34 N-m).

3. Tighten the set screw up to 30 in-lb using a 3/32-in. hex wrench.

A. Straight field wireable connector(1)(3)

B. Right angle field wireable connector(2)(3)

C. Quick Connect housing

1. Order part number 03151-9063-0001.2. Order part number 03151-9063-0002.3. Field wiring supplied by customer

D. Cordset(4)

E. Coupling nutF. Quick Connect coupling nut

4. Supplied by cordset vendor.

A

B

DE

FC

A

B

DE

FC

13

Page 14: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 14 Friday, February 9, 2018 9:41 AM

4. Install cordset/field wireable connectors onto the Quick Connect. Do not over tighten.

Figure 10. Quick Connect Housing Pin-Out

A. GroundB. No connection

NoteFor other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions.

4.4 Conduit electrical connector wiring (option GE or GM)For Rosemount 3051S with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, non-incendive or FM FISCO Intrinsically Safe hazardous locations, install in accordance with Rosemount drawing 03151-1009. See Appendix B of the Rosemount 3051S Reference Manual.

4.5 Power supplyThe DC power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces.

Note The resistance of intrinsic safety barriers, if used, must be included.

A

B

“+”“-”

14

Page 15: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 15 Friday, February 9, 2018 9:41 AM

Figure 11. Load Limitation TransmitterMaximum loop resistance = 43.5 � (power supply voltage – 10.5)

The Field Communicator requires a minimum loop resistance of 250 Ω for communication.

5.0 Verify configurationUse any HART-compliant master to communicate with and verify configuration of the Rosemount 3051S.

5.1 Field Communicator user interfaceFast Key sequences vary with the device driver revision. The traditional interface Fast Key sequences apply to DD Rev. 8 or older and they can be found on page 16 The device dashboard Fast Key sequences apply to DD Rev. 9 or newer and they can be found on page 17.

Figure 12. Traditional Interface - Device Revision 6 or 7 and DD Revision 7

1387

1000

500

0

10.5 20 3042.4

Voltage (Vdc)

Load

(Ohm

s)

OperatingRegion

SAVE

3051:PT 93207Online1 Device setup2 PV 0.00 mbar3 Analog Output 4.000 mA 4 PV LRV 0.00 mbar5 PV URV 370.00 mbar

15

Page 16: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 16 Friday, February 9, 2018 9:41 AM

Figure 13. Device Dashboard - Device Revision 7 and DD Revision 9

A check () indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure.

Table 2. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence

Function Fast Key sequence

Alarm Level Configuration 1, 4, 2, 7, 7

Alarm and Saturation Levels 1, 4, 2, 7

Analog Output Alarm Direction 1, 4, 2, 7, 6

Analog Output Trim 1, 2, 3, 2

Burst Mode On/Off 1, 4, 3, 3, 3

Burst Options 1, 4, 3, 3, 4

Damping 1, 3, 6

Date 1, 3, 4, 1

Descriptor 1, 3, 4, 2

Digital To Analog Trim (4–20 mA Output) 1, 2, 3, 2, 1

Field Device Information 1, 4, 4, 1

LCD Display Configuration 1, 3, 7

Loop Test 1, 2, 2

Lower Sensor Trim 1, 2, 3, 3, 2

Message 1, 3, 4, 3

Number of Requested Preambles 1, 4, 3, 3, 2

Pressure Alert Configuration 1, 4, 3, 5, 3

Poll Address 1, 4, 3, 3, 1

Poll a Multidropped Transmitter Left Arrow, 3, 1, 1

SAVE

3051:PT 93207Online1 Overview2 Configure 3 Service Tools

16

Page 17: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 17 Friday, February 9, 2018 9:41 AM

Remapping 1, 4, 3, 6

Rerange- Keypad Input 1, 2, 3, 1, 1

Saturation Level Configuration 1, 4, 2, 7, 8

Scaled D/A Trim (4–20 mA Output) 1, 2, 3, 2, 2

Scaled Variable Configuration 1, 4, 3, 4, 7

Self Test (Transmitter) 1, 2, 1, 1

Sensor Information 1, 4, 4, 2

Sensor Temperature 1, 1, 4

Sensor Trim 1, 2, 3, 3

Sensor Trim Points 1, 2, 3, 3, 5

Status 1, 2, 1, 2

Tag 1, 3, 1

Temperature Alert Configuration 1, 4, 3, 5, 4

Transfer Function (Setting Output Type) 1, 3, 5

Transmitter Security (Write Protect) 1, 3, 4, 5

Units (Process Variable) 1, 3, 2

Upper Sensor Trim 1, 2, 3, 3, 3

Zero Trim 1, 2, 3, 3, 1

Table 3. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence

Function Fast Key sequence

Alarm and Saturation Levels 2, 2, 1, 7

Burst Mode Control 2, 2, 4, 2

Burst Option 2, 2, 4, 3

Custom Display Configuration 2, 1, 3

Damping 2, 2, 1, 5

Date 2, 2, 5, 4

Descriptor 2, 2, 5, 5

Digital to Analog Trim (4–20 mA Output) 3, 4, 2

Disable Zero & Span Adjustment 2, 2, 7, 2

Rerange with Keypad 2, 2, 1, 3, 1

Loop Test 3, 5, 1

Lower Sensor Trim 3, 4, 1, 2

Message 2, 2, 5, 6

Table 2. Traditional Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence

Function Fast Key sequence

17

Page 18: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 18 Friday, February 9, 2018 9:41 AM

6.0 Trim the transmitterTransmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit).

6.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled to the correct level. If zero offset is less than 3 percent of true zero, follow the Using the Field

Communicator instructions below to perform a zero trim. If zero offset is greater than 3 percent of true zero, follow the Using the

transmitter zero adjustment button instructions below to rerange. If hardware adjustments are not available, see the Rosemount 3051S

Reference Manual to perform a rerange using the Field Communicator.

Using the Field Communicator1. Equalize or vent the transmitter and connect Field Communicator.2. At the menu, input the Fast Key sequence (refer to Table 2 or Table 3).3. Follow the commands to perform a zero trim.

Range Values 2, 2, 1, 3

Scaled D/A Trim (4–20 mA Output) 3, 4, 2

Sensor Temperature/Trend (3051S) 3, 3, 3

Tag 2, 2, 5, 1

Transfer Function 2, 2, 1, 4

Transmitter Security (Write Protect) 2, 2, 7, 1

Units 2, 2, 1, 2

Upper Sensor Trim 3, 4, 1, 1

Zero Trim 3, 4, 1, 3

Table 3. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence

Function Fast Key sequence

18

Page 19: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 19 Friday, February 9, 2018 9:41 AM

Using the transmitter zero adjustment button

Push and hold the zero adjustment button for at least two seconds but no longer than ten seconds.

Figure 14. Transmitter Adjustment Buttons

A. ZeroB. Span

7.0 Safety instrumented systems installationFor safety certified installations, refer to the Rosemount 3051S Reference Manual for installation procedure and system requirements.

Plantweb Junction box

A BA B

19

Page 20: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 20 Friday, February 9, 2018 9:41 AM

8.0 Product CertificationsRev 1.15

8.1 European Directive InformationA copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

8.2 Ordinary Location CertificationAs standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

8.3 Installing Equipment in North AmericaThe US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

8.4 USAE5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)

Certificate: FM16US0090Standards: FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3616 - 2011, FM Class

3810 - 2005, ANSI/NEMA® 250 - 2003Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(–50 °C ≤ Ta ≤

+85 °C); Factory Sealed; Type 4X

I5 FM Intrinsic Safety (IS) and Nonincendive (NI)Certificate: FM16US0089XStandards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class

3810 - 2005, NEMA 250 - 2003Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0 AEx ia

IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +70 °C) [HART]; T4(–50 °C ≤ Ta ≤ +60 °C) [Fieldbus]; when connected per Rosemount drawing 03151-1006; Type 4X

Special Condition for Safe Use:1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains aluminum and is

considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.

NoteTransmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03151-1006.

20

Page 21: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 21 Friday, February 9, 2018 9:41 AM

IE FM FISCOCertificate: FM16US0089XStandards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class

3810 - 2005, NEMA 250 - 2003Markings: IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); when connected per

Rosemount drawing 03151-1006; Type 4X

Special Condition for Safe Use:1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains aluminum and is

considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.

8.5 CanadaE6 CSA Explosionproof, Dust-Ignitionproof, and Division 2

Certificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No.

30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 213-M1987, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05

Markings: Explosionproof Class I, Division 1, Groups B, C, D; Dust-Ignitionproof Class II, Division 1, Groups E, F, G; Class III; suitable for Class I, Zone 1, Group IIB+H2, T5; suitable for Class I, Division 2, Groups A, B, C, D; suitable for Class I, Zone 2, Group IIC, T5; when connected per Rosemount drawing 03151-1013; Type 4X

I6 CSA Intrinsically SafeCertificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No.

94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05

Markings: Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X

IF CSA FISCOCertificate: 1143113Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No.

94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05

Markings: FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X

21

Page 22: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 22 Friday, February 9, 2018 9:41 AM

8.6 EuropeE1 ATEX Flameproof

Certificate: KEMA 00ATEX2143XStandards: EEN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015Markings: II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta

≤ +80 °C)

Special Conditions for Safe Use (X):1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a

boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime

2. Flameproof joints are not intended for repair. 3. Non-standard paint options may cause risk from electrostatic discharge. Avoid

installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.

4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5°C greater than maximum specified temperature for location where installed.

I1 ATEX Intrinsic SafetyCertificate: BAS01ATEX1303XStandards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012Markings: 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)

Special Conditions for Safe Use (X):1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of

withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.

2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.

Temperature class Process temperature

T6 –60 °C to +70 °C

T5 –60 °C to +80 °C

T4 –60 °C to +120 °C

Model Ui Ii Pi Ci Li

SuperModule™ 30 V 300 mA 1.0 W 30 nF 0

3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0

3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0

3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;3051SAL…C… M7, M8, or M9

30 V 300 mA 1.0 W 12 nF 60 μH

3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH

3051SAL…M7, M8, or M93051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH

RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A

22

Page 23: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 23 Friday, February 9, 2018 9:41 AM

3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.

IA ATEX FISCOCertificate: BAS01ATEX1303XStandards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)

Special Conditions for Safe Use (X):1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of

withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation

2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529

3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.

ND ATEX DustCertificate: BAS01ATEX1374XStandards: EN 60079-0:2012, EN 60079-31:2009Markings: II 1 D Ex ta IIIC T105 °C T50095 °C Da, (–20 °C ≤ Ta ≤ +85 °C), Vmax = 42.4 V

Special Conditions for Safe Use (X):1. Cable entries must be used which maintain the ingress protection of the enclosure to

at least IP66.2. Unused cable entries must be filled with suitable blanking plugs which maintain the

ingress protection of the enclosure to at least IP66.3. Cable entries and blanking plugs must be suitable for the ambient temperature range

of the apparatus and capable of withstanding a 7 J impact test.4. The SuperModule(s) must be securely screwed in place to maintain the ingress

protection of the enclosure(s).N1 ATEX Type n

Certificate: BAS01ATEX3304XStandards: EN 60079-0: 2012+A11:2013, EN 60079-15: 2010Markings: II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C), Vmax = 45 V

Special Condition for Safe Use (X):1. The equipment is not capable of withstanding the 500 V insulation test required by

clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.

Parameter FISCO

Voltage Ui 17.5 V

Current Ii 380 mA

Power Pi 5.32 W

Capacitance Ci 0

Inductance Li 0

23

Page 24: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 24 Friday, February 9, 2018 9:41 AM

Note RTD Assembly is not included with the Rosemount 3051SFx Type n Approval.

8.7 InternationalE7 IECEx Flameproof and Dust

Certificate: IECEx KEM 08.0010X (Flameproof)Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C)

Special Conditions for Safe Use (X):1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take

into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

2. Flameproof joints are not intended for repair.3. Non-standard paint options may cause risk from electrostatic discharge. Avoid

installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.

4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5°C greater than maximum specified temperature for location where installed.

Certificate: IECEx BAS 09.0014X (Dust)Standards: IEC 60079-0:2011, IEC 60079-31:2008Markings: Ex ta IIIC T 105 °C T500 95 °C Da, (–20 °C ≤ Ta ≤ +85 °C), Vmax = 42.4 V

Special Conditions for Safe Use (X):1. Cable entries must be used which maintain the ingress protection of the enclosure to

at least IP66.2. Unused cable entries must be filled with suitable blanking plugs which maintain the

ingress protection of the enclosure to at least IP66.3. Cable entries and blanking plugs must be suitable for the ambient temperature range

of the apparatus and capable of withstanding a 7 J impact test.4. The Rosemount 3051S SuperModule must be securely screwed in place to maintain

the ingress protection of the enclosure.

I7 IECEx Intrinsic SafetyCertificate: IECEx BAS 04.0017XStandards: IEC 60079-0: 2011, IEC 60079-11:2011Markings: Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)

Temperature class Process temperature

T6 –60 °C to +70 °C

T5 –60 °C to +80 °C

T4 –60 °C to +120 °C

24

Page 25: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 25 Friday, February 9, 2018 9:41 AM

Special Conditions for Safe Use (X):1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of

withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.

2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.

3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.

I7 IECEx Intrinsic Safety - Group I - Mining (I7 with Special A0259)Certificate: IECEx TSA 14.0019XStandards: IEC 60079-0:2011, IEC 60079-11:2011Markings: Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)

Special Conditions for Safe Use (X):1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of

withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11:2011. This must be taken into account when installing the apparatus.

2. It is a condition of safe use that the above input parameters shall be taken into account during installation.

3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.

Model Ui Ii Pi Ci Li

SuperModule 30 V 300 mA 1.0 W 30 nF 0

3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0

3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0

3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;3051SAL…C… M7, M8, or M9

30 V 300 mA 1.0 W 12 nF 60 μH

3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH

3051SAL…M7, M8, or M93051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH

RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A

Model Ui Ii Pi Ci Li

SuperModule 30 V 300 mA 1.0 W 30 nF 0

3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0

3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0

3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;3051SAL…C… M7, M8, or M9

30 V 300 mA 1.0 W 12 nF 60 μH

3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH

3051SAL…M7, M8, or M93051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH

RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A

25

Page 26: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 26 Friday, February 9, 2018 9:41 AM

IG IECEx FISCOCertificate: IECEx BAS 04.0017XStandards: IEC 60079-0:2011, IEC 60079-11:2011Markings: Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)

Special Conditions for Safe Use (X):1. The Rosemount 3051S Transmitters fitted with transient protection are not capable of

withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.

2. The terminal pins of the Rosemount 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.

3. The Rosemount 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.

IG IECEx Intrinsic Safety – Group I - Mining (IG with Special A0259)Certificate: IECEx TSA 14.0019XStandards: IEC 60079-0:2011, IEC 60079-11:2011Markings: FISCO FIELD DEVICE Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)

Special Conditions for Safe Use (X):1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of

withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11:2011. This must be taken into account when installing the apparatus.

2. It is a condition of safe use that the above input parameters shall be taken into account during installation.

3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.

N7 IECEx Type nCertificate: IECEx BAS 04.0018XStandards: IEC 60079-0:2011, IEC 60079-15:2010Markings: Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C)

Parameter FISCO

Voltage Ui 17.5 V

Current Ii 380 mA

Power Pi 5.32 W

Capacitance Ci 0

Inductance Li 0

Parameter FISCO

Voltage Ui 17.5 V

Current Ii 380 mA

Power Pi 5.32 W

Capacitance Ci 0

Inductance Li 0

26

Page 27: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 27 Friday, February 9, 2018 9:41 AM

Special Condition for Safe Use (X):1. The equipment is not capable of withstanding the 500 V insulation test required by

clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.

8.8 BrazilE2 INMETRO Flameproof

Certificate: UL-BR15.0393XStandards: ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011,

ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1:2008

Markings: Ex d IIC T* Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C), IP66

Special Conditions for Safe Use (X):1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take

into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

2. For information on the dimensions of the flameproof joints, the manufacturer shall be contacted.

I2/IB INMETRO Intrinsic Safety/FISCOCertificate: UL-BR 15.0392XStandards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011, ABNT NBR IEC 60079-11:2009Markings: Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C), IP66

Special Condition for Safe Use (X):1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic

charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.2. The Model 701PBKKF Power Module may be replaced in a hazardous area. The Power

Module has a surface resistivity greater than 1 GΩ and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.

3. The 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in areas that requires EPL Ga.

Model Ui Ii Pi Ci Li

SuperModule 30 V 300 mA 1.0 W 30 nF 0

3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0

3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0

3051S…F…IB; 3051SF…F…IB 17.5V 380 mA 5.32 W 0 0

3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;3051SAL…C… M7, M8, or M9

30 V 300 mA 1.0 W 12 nF 60 μH

3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH

3051SAL…M7, M8, or M93051SAM…M7, M8, or M9 30 V 300 mA 1.0 W 12 nF 93 μH

RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A

27

Page 28: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 28 Friday, February 9, 2018 9:41 AM

8.9 ChinaE3 China Flameproof and Dust Ignition-proof

Certificate:3051S: GYJ16.1249X3051SFx: GYJ16.1466X3051S-ERS: GJY15.1406X

Standards: 3051S: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-20133051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB 12476.5-20133051S-ERS: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010

Markings: 3051S: Ex d IIC T6…T4; Ex tD A20 T105 °C T50095 °C; IP66 3051SFx: Ex d IIC T5/T6 Ga/Gb; DIP A20 TA105 °C; IP663051S-ERS: Ex d IIC T4~T6 Ga/Gb

Special Conditions for Safe Use (X):1. Only the pressure transmitters, consisting of Rosemount 3051SC Series, 3051ST

Series, 3051SL Series and 300S Series, are certified.2. Flameproof joints are not intended for repair.3. The ambient temperature range for the 3051S and 3051SFx in a dust environment is

–20 °C ≤ Ta ≤ 85 °C. 4. The relation between temperature class and maximum temperature of process

medium is as follows:

5. The earth connection facility in the enclosure should be connected reliably.6. During installation, use and maintenance of transmitter, observe the warning “Don’t

open the cover when the circuit is alive.”7. During installation, there should be no mixture harm to flameproof housing.8. Cable entry, certified by NEPSI with type of protection Ex d IIC in accordance with

GB3836.1-2000 and GB3836.2-2000, should be applied when installation in hazardous location. Five full threads should be in engagement when the cable entry is assembled onto the transmitter. When pressure transmitter is used in the presence of combustible dust, the ingress of protection of the cable entry should be IP66.

9. The diameter of cable should observe the instruction manual of cable entry. The compressing nut should be fastened. The aging of seal ring should be changed in time.

10. Maintenance should be done in non-hazardous location.11. End users are not permitted to change any components inside.

Table 4. Rosemount 3051S

Temperature class Ambient temperature (°C) Process temperature (°C)

T6 –60 °C ≤ Ta ≤ +70 °C –60 °C ≤ Ta ≤ +70 °C

T5 –60 °C ≤ Ta ≤ +80 °C –60 °C ≤ Ta ≤ +80 °C

T4 –60 °C ≤ Ta ≤ +80 °C –60 °C ≤ Ta ≤ +120 °C

28

Page 29: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 29 Friday, February 9, 2018 9:41 AM

12. When installation, use and maintenance of transmitter, observe following standards:GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”GB15577-1995 “Safe regulation for explosive dust atmospheres”GB12476.2-2006 “Electrical apparatus for use in the presence of combustible dust – Part 1-2: Electrical apparatus protected by enclosures and surface temperature limitation – Selection, installation and maintenance”

I3 China Intrinsic SafetyCertificate: 3051S: GYJ16.1250X[Mfg USA, China, Singapore]

3051SFx: GYJ16.1465X [Mfg USA, China, Singapore]3051S-ERS: GYJ16.1248X [Mfg USA, China, Singapore]

Standards: 3051S: GB3836.1-2010, GB3836.4-2010, GB3836.20-20103051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-20133051S-ERS: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010

Markings: 3051S, 3051SFx: Ex ia IIC T4 Ga3051S-ERS: Ex ia IIC T4

Special Conditions for Safe Use (X):1. Symbol “X” is used to denote specific conditions of use:

For output code A and F: This apparatus is not capable of withstanding the 500V r.m.s. insulation test required by Clause 6.4.12 of GB3836.4-2000.

2. The ambient temperature range is:

3. Intrinsically safe parameters:

4. The product should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.

Output code Ambient temperature

A –50 °C ≤ Ta ≤ +70 °C

F –50 °C ≤ Ta ≤ +60 °C

Output code

Housing code

Display code

Maximum input

voltage: Ui (V)

Maximum input

current: Ii (mA)

Maximum input power:

Pi (W)

Maximum internal

parameter: Ci (nF)

Maximum internal

parameter: Li (uH)

A =00 / 30 300 1 38 0

A ≠00 / 30 300 1 11.4 2.4

A ≠00 M7/M8/M9 30 300 1 0 58.2

F ≠00 / 30 300 1.3 0 0

FFISCO ≠00 / 17.5 500 5.5 0 0

29

Page 30: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 30 Friday, February 9, 2018 9:41 AM

5. The cable between this product and associated apparatus should be shielded cables (the cables must have insulated shield). The shield has to be grounded reliably in non-hazardous area.

6. The product complies to the requirements for FISCO field devices specified in IEC60079-27:2008. For the connection of an intrinsically safe circuit in accordance FISCO model, FISCO parameters of this product are as above.

7. End users are not permitted to change any components inside, but to settle the problem in conjunction with manufacturer to avoid damage to the product.

8. When installation, use and maintenance of this product, observe the following standards:GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”

N3 China Type nCertificate:3051S: GYJ17.1354X

3051SFX: GYJ17.1355XMarkings: Ex nL IIC T5 Gc

Special Condition for Safe Use (X):1. When transient protection board is chosen (Option Code T1), this apparatus

is not capable of withstanding the 500 V r.m.s insulation test, this must be taken into account when installing the component.

8.10 EAC – Belarus, Kazakhstan, RussiaEM Technical Regulation Customs Union (EAC) Flameproof

Certificate: RU C-US.AA87.B.00378Markings: Ga/Gb Ex d IIC T6…T4 X

Ex tb IIIC T105 °C T50095 °C Db XEx ta IIIC T105 °C T50095 °C Da X

IM Technical Regulation Customs Union (EAC) Intrinsic SafetyCertificate: RU C-US.AA87.B.00094 Markings: 0Ex ia IIC T4 Ga X

8.11 JapanE4 Japan Flameproof

Certificate: TC15682, TC15683, TC15684, TC15685, TC15686, TC15687, TC15688, TC15689, TC15690, TC17099, TC17100, TC17101, TC17102, TC18876 3051ERS: TC20215, TC20216, TC20217, TC20218, TC20219, TC20220, TC20221

Markings: Ex d IIC T6

30

Page 31: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 31 Friday, February 9, 2018 9:41 AM

8.12 Republic of KoreaEP Republic of Korea Flameproof

Certificate: 12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore]Markings: Ex d IIC T5 or T6

IP Republic of Korea Intrinsic SafetyCertificate: 12-KB4BO-0202X [HART – Mfg USA],

12-KB4BO-0204X [Fieldbus – Mfg USA], 12-KB4BO-0203X [HART – Mfg Singapore], 13-KB4BO-0296X [Fieldbus – Mfg Singapore]

Markings: Ex ia IIC T4

8.13 CombinationsK1 Combination of E1, I1, N1, and NDK2 Combination of E2 and I2K5 Combination of E5 and I5K6 Combination of E6 and I6K7 Combination of E7, I7, and N7KA Combination of E1, I1, E6, and I6KB Combination of E5, I5, E6, and I6KC Combination of E1, I1, E5, and I5KD Combination of E1, I1, E5, I5, E6, and I6KG Combination of IA, IE, IF, and IG

KM Combination of EM and IMKP Combination of EP and IP

8.14 Additional CertificationsSBS American Bureau of Shipping (ABS) Type Approval

Certificate: 00-HS145383-6-PDAIntended Use: Measure gauge or absolute pressure of liquid, gas or vapor

applications on ABS classed vessels, marine, and offshore installations.

SBV Bureau Veritas (BV) Type ApprovalCertificate: 31910/A0 BVRequirements: Bureau Veritas Rules for the Classification of Steel ShipsApplication: Class Notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS

SDN Det Norske Veritas (DNV) Type ApprovalCertificate: A-14186Intended Use: Det Norske Veritas’ Rules for Classification of Ships, High Speed

& Light Craft, and Det Norske Veritas’ Offshore Standards

31

Page 32: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 32 Friday, February 9, 2018 9:41 AM

Application:

SLL Lloyds Register (LR) Type ApprovalCertificate: 11/60002(E3)Application: Environmental categories ENV1, ENV2, ENV3, and ENV5

D3 Custody Transfer – Measurement Canada Accuracy Approval [3051S Only]Certificate: AG-0501, AV-2380C

Location classes

Type 3051S

Temperature D

Humidity B

Vibration A

EMC A

Enclosure D/IP66/IP68

32

Page 33: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 33 Friday, February 9, 2018 9:41 AM

Figure 15. Rosemount 3051S Declaration of Conformity

EU Declaration of Conformity No: RMD 1044 Rev. AA

Page 1 of 4

We,

Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA

declare under our sole responsibility that the product,

Rosemount 3051S Series Pressure Transmitters Rosmeount 3051SFx Series Flowmeter Transmitters

Rosemount 300S Housings manufactured by,

Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA

to which this declaration relates, is in conformity with the provisions of the European Union

Directives, including the latest amendments, as shown in the attached schedule.

Assumption of conformity is based on the application of the harmonized standards and, when

applicable or required, a European Union notified body certification, as shown in the attached

schedule.

(signature)

Vice President of Global Quality (function name - printed)

Chris LaPoint (name - printed)

13-April-2017

(date of issue)

33

Page 34: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 34 Friday, February 9, 2018 9:41 AM

EU Declaration of Conformity No: RMD 1044 Rev. AA

Page 2 of 4

EMC Directive (2014/30/EU)

Harmonized Standards:

EN 61326-1:2013, EN 61326-2-3:2013

PED Directive (2014/68/EU)

Rosemount 3051S Series Pressure Transmitters

Rosemount 3051S_CA4; 3051S_CD2, 3, 4, 5 (also with P0 & P9 option) PressureTransmitters

QS Certificate of Assessment – EC Certificate No. 59552-2009-CE-HOU-DNV

Module H Conformity Assessment

Evaluation standards:

ANSI / ISA 61010-1:2004

All other Rosemount 3051S Pressure TransmittersSound Engineering Practice

Transmitter Attachments: Diaphragm Seal, Process Flange, or ManifoldSound Engineering Practice

Rosemount 3051SFx Series Flowmeter Pressure TransmittersSee DSI 1000 Declaration of Conformity

34

Page 35: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 35 Friday, February 9, 2018 9:41 AM

EU Declaration of Conformity No: RMD 1044 Rev. AA

Page 3 of 4

ATEX Directive (2014/34/EU)

BAS01ATEX1303X – Intrinsic Safety Certificate Equipment Group II, Category 1 G

Ex ia IIC T4 Ga

Harmonized Standards Used:

EN 60079-0:2012+A11:2013, EN 60079-11:2012

BAS01ATEX3304X – Type n Certificate Equipment Group II, Category 3 G

Ex nA IIC T5 Gc

Harmonized Standards Used:

EN 60079-0:2012+A11:2013, EN 60079-15:2010

BAS01ATEX1374X – Dust Certificate Equipment Group II, Category 1 D

Ex ta IIIC T105°C T50095°C Da

Harmonized Standards Used:

EN 60079-0:2012+A11:2013

Other Standards Used:

EN 60079-31:2009 (a review against EN 60079-31:2014, which is

harmonized, shows no significant changes relevant to this equipment

so EN 60079-31:2009 continues to represent “State of the Art”)

BAS04ATEX0181X – Mining Certificate Equipment Group I, Category M1

Ex ia I Ma

Harmonized Standards Used:

EN 60079-0:2012, EN 60079-11:2012

BAS04ATEX0193U – Mining Certificate: Component Equipment Group I, Category M1

Ex ia I Ma

Harmonized Standards Used:

EN 60079-0:2012, EN 60079-11:2012

KEMA00ATEX2143X – Flameproof Certificate Equipment Group II, Category 1/2 G

Ex db IIC T6…T4 Ga/Gb

Harmonized Standards:

EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015

35

Page 36: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

February 2018Quick Start Guide

00825-0100-4801_RevNA.fm Page 36 Friday, February 9, 2018 9:41 AM

EU Declaration of Conformity No: RMD 1044 Rev. AA

Page 4 of 4

PED Notified Body

Rsoemount 3051S Series Pressure Transmitters

DNV GL AS [Notified Body Number: 0575]

Veritasveien 1, N-1322

Hovik, Norway

ATEX Notified Bodies for EU Type Examination Certificate

DEKRA Certification B.V. [Notified Body Number: 0344]

Utrechtseweg 310

Postbus 5185

6802 ED Arnhem

Netherlands

SGS Baseefa Limited [Notified Body Number: 1180]

Rockhead Business Park, Staden Lane

Buxton, Derbyshire SK17 9RZ

United Kingdom

ATEX Notified Body for Quality Assurance

SGS Baseefa Limited [Notified Body Number: 1180]

Rockhead Business Park, Staden Lane

Buxton, Derbyshire SK17 9RZ

United Kingdom

36

Page 37: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

Quick Start GuideFebruary 2018

00825-0100-4801_RevNA.fm Page 37 Friday, February 9, 2018 9:41 AM

China RoHS Rosemount 3051SList of Rosemount 3051S Parts with China RoHS Concentration above MCVs

Part Name

/ Hazardous Substances

Lead(Pb)

Mercury(Hg)

Cadmium(Cd)

Hexavalent Chromium

(Cr +6)

Polybrominated biphenyls

(PBB)

Polybrominated diphenyl ethers

(PBDE)

Electronics Assembly

X O O O O O

Housing Assembly

X O O X O O

Sensor Assembly

X O O X O O

SJ/T11364This table is proposed in accordance with the provision of SJ/T11364.

O: GB/T 26572O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement ofGB/T 26572.

X: GB/T 26572X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.

37

Page 38: Install Guide: Rosemount 3051S (HART?) - Emerson€¦ · Quick Start Guide 00825-0100-4801, Rev NA February 2018 Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF

*00825-0100-4801*

00825-0100-4801_RevNA.fm Page 38 Friday, February 9, 2018 9:41 AM

Global HeadquartersEmerson Automation Solutions6021 Innovation Blvd.Shakopee, MN 55379, USA

+1 800 999 9307 or +1 952 906 8888+1 952 949 7001 [email protected]

North America Regional OfficeEmerson Automation Solutions8200 Market Blvd.Chanhassen, MN 55317, USA

+1 800 999 9307 or +1 952 906 8888

+1 952 949 7001

[email protected]

Latin America Regional OfficeEmerson Automation Solutions1300 Concord Terrace, Suite 400Sunrise, FL 33323, USA

+1 954 846 5030

+1 954 846 5121

[email protected]

Linkedin.com/company/Emerson-Automation-Solutions

Twitter.com/Rosemount_News

Facebook.com/Rosemount

Youtube.com/user/RosemountMeasurement

Google.com/+RosemountMeasurement

Emerson Terms and Conditions of Sale are available upon requestThe Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.© 2018 Emerson. All rights reserved.

Europe Regional OfficeEmerson Automation SolutionsNeuhofstrasse 19a P.O. Box 1046CH 6340 BaarSwitzerland

+41 (0) 41 768 6111

+41 (0) 41 768 6300

[email protected]

Asia Pacific Regional OfficeEmerson Automation Solutions1 Pandan CrescentSingapore 128461

+65 6777 8211

+65 6777 0947 [email protected]

Middle East and Africa Regional OfficeEmerson Automation SolutionsEmerson FZE P.O. Box 17033Jebel Ali Free Zone - South 2Dubai, United Arab Emirates

+971 4 8118100

+971 4 [email protected]

Quick Start Guide00825-0100-4801, Rev NA

February 2018