inspection of fire sprinkler systems - nfmtsprinkler maintenance- fitter sprinkler system tester...
TRANSCRIPT
Inspection of Fire
Sprinkler Systems
NFPA 25, Inspection, Testing
& Maintenance of Water Based
Fire Protection Systems
To insert your company logo
on this slide
• From the Insert Menu
• Select “Picture”
• Locate your logo file
• Click OK
To resize the logo
• Click anywhere inside the
logo. The boxes that appear
outside the logo are known
as “resize handles.”
• Use these to resize the
object.
• If you hold down the shift key
before using the resize
handles, you will maintain
the proportions of the object
you wish to resize.
Objective
To familiarize Facility
Managers with the process
of routine inspection of fire
sprinkler systems and to
recognize system
impairments.
Course Content
Applicable Codes
& Standards
Types of Systems
Key Components
What to Inspect
Documentation of
Inspections
Housekeeping
• Breaks
• Restrooms
• Open Atmosphere Ask Questions
• Hands on System
A look at Hotel Sprinkler Riser
State Codes
COMM 51.23(6)
• (a) All installed automatic
sprinkler systems, whether
required by this code or not, shall
be properly maintained for
efficient service pursuant to
NFPA 25.
Sprinklers Systems
Sprinklers are 92% - 98%
Effective
It is imperative that these
systems be maintained and
inspected
Factors that Affect
System Performance
Closed Valves
Damaged Components
Occupancy Change
Process and Material Changes
Building Renovations
Shutdown of Heating System
Water Supply Changes
Responsibility for Maintenance
Owners or operators
shall be responsible
for the condition of
their sprinkler
system and shall use
due diligence in
keeping the system
in good operating
condition.
COMM 51.23 (6)
Inspection of Records
Records of inspections, tests
and maintenance, as specified
in NFPA 25 shall be kept and
shall be made available, upon
request, to the department or
its authorized deputies.
Credentials for
Inspection and Testing
Fire sprinkler systems
shall be tested and
inspected at least once
a year by someone
holding one of the
following Dept. of
Commerce credentials. Other individuals can conduct the
daily, weekly, monthly,quarterly
or semi-annual inspection and
testing
Sprinkler Contractor
Journeyman Fitter
Fitter Apprentice
Sprinkler Contractor-
Maintenance
Sprinkler Maintenance-
Fitter
Sprinkler System Tester
National Standards
NFPA 25, Maintenance of Water
Based Fire Suppression System
Establishes the minimum
requirements for the periodic
inspection, testing, and
maintenance of fire sprinkler
systems.
What is a Sprinkler
System?
A sprinkler system is an integrated system of underground and overhead piping, designed in accordance with fire protection engineering standards, and connected to one or more automatic water supplies. The system is usually activated by heat from a fire, and the sprinkler heads then discharge water over the fire area. Sprinkler systems are nearly 100 percent effective.
"Fire Fighting," Microsoft® Encarta® Encyclopedia 2000. © 1993-1999
Microsoft Corporation. All rights reserved.
Types of Systems
• Wet System
• Dry System
• Pre-action System
• Deluge System
Wet Sprinkler System
A system that
employs a piping
containing water and
connected to a
water supply so that
water discharges
immediately from
sprinklers opened by
heat from a fire.
Wet Pipe System
Dry Pipe System
Includes automatic
sprinklers attached to a
piping system containing air
or nitrogen under pressure,
the release of which allows
the water pressure to open
the dry pipe valve allow
water to flow through the
system and out the open
sprinklers.
Pre-action Systems
• Sprinklers attached to a piping
system containing air that may be
under pressure, with a
supplemental detection system
installed in the same areas as the
sprinklers.
• Both the detection and the
sprinklers must be actuated prior
to the release of water.
Operation
If a smoke or heat detector operates, or a pull
station is activated...
The release panel will go into an alarm
condition.
The release circuit will energize.
This allows water to enter the sprinkler piping.
Water will be discharged only if a sprinkler
now opens.
Single Interlock Pre-action
Double Interlock Pre-action
Deluge System
A system employing open
sprinklers connected to
the water supply through
a valve that is opened by
by the operation of the
detection system. When
the valve opens, water is
discharged immediately
through all sprinklers.
What Do We Inspect?
Water Supply
Control Valves & Other Valves
Fire Department Connection
Alarm
Piping & Sprinklers
Inspectors Test
Water Supply
One or More Required per System
Municipal Water Main
Storage Reservoir
Pressure Tank
Gravity Tank
Inspecting the Underground
Cannot be Smaller than the Riser
Must be Protected Against
Freezing
Must be Flushed Before Connected
to Aboveground Piping
Must be Hydrostatically Tested
Aboveground
Ensure the
System Gauges
Shows Normal
Water Supply
Pressure
Weekly on Dry
Monthly on Wet
Gauges
Wet System: The pressure gauge
above and below the alarm valve
should be about the same. The one
above may be a little higher.
Dry System: The pressure above the
dry valve should be lower that the
reading on the gauge below the valve.
Typically close to a 6:1 ratio.
Outside Control Valves
Weekly if Valves are Sealed
Monthly if Electrically Supervised or Secured with Lock & Chain
Inside Control Valves
Isolation Control Valves
You may find these where the pipe goes
into an elevator pit or in stairwells where
the floor level can be isolated.
Fire Department
Connections
Visible & Accessible
Couplings & Swivels
not Damaged and
rotate smoothly
Plugs and Caps in
Place and Undamaged
Gaskets in Place and
Not Damaged
Fire Department
Connections
Identification
Sign in Place
Check Valve Not
Leaking
Automatic Drain
Valve in Place
and Operating
Properly
Waterflow Alarms
Required on all
systems having more
than 20 sprinklers.
Flow of water from a
single sprinkler of the
smallest orifice shall,
within 5 minutes,
result in an audible
signal on premises.
No Bells Outside?
NFPA 13 Section 3-10.3
Outside alarms can be omitted
where the sprinkler system is used
as part of a central station,
auxiliary, remote station, or
proprietary signaling fire alarm
system utilizing listed audible
inside alarm devices.
Waterflow Alarms
Paddle-type waterflow alarm indicators
shall be installed in wet systems only.
Sprinklers
Temperature of Sprinkler
Type of Sprinkler
Location of Sprinklers
Obstructions around Sprinklers
Physical Damage to Sprinklers
Painting or Coating of Sprinkler
Provide Extra Sprinklers
Temperature of Head
Color Code
Red
Temperature
Classification
Ordinary
Temperature Rating
135º to 170º
Max. Ceiling Temp.
100º
Temperature of Head
Color Code
Green
Temperature
Classification
Intermediate
Temperature Rating
175º to 225º
Max. Ceiling Temp.
150º
Sidewall Sprinkler
Upright or Pendent
Sprinkler
Special Sprinklers
Quick Response
Required in Light Hazard Occupancies
Sprinkler Spacing
Hazard Max. Distance
Between Sprinklers
Max. Square
Footage
Light 15 ft 225 ft
Ordinary 15 ft 130 ft
Extra 12 ft 100 ft
Sprinkler Spacing
Not to be closer than 4’ from each
other.
Sidewalls must be 4” to 6” down from
ceiling. (Manufacturer specification may allow
more)
Watch for occupancy changes.
NFPA 13, Section 2-1
Watch for height of storage.
NFPA 13, Section 10-5
Obstruction Around
Obstruction to Sprinkler
Discharge
NFPA 13, Section 5-5.5
Obstructions less than or equal to
18” below the deflector will
prevent pattern from fully
developing.
Sprinklers shall be installed under
fixed obstructions over 4ft.
Physical Damage
Sprinklers free of corrosion
Piping free of mechanical
damage
Piping properly lined
No external loads on piping
Hangers not damaged or loose
Painted Sprinklers
Sprinkler heads can only be
factory painted.
Ensure sprinklers are free of
paint.
Replace when painted.
Ensure they are not still taped or
covered
Spare Sprinklers
System with less
than 300 sprinklers,
not fewer than 6.
System with 300 to
1000 sprinklers, not
fewer than 12.
System with over
1000 sprinklers, not
fewer than 24.
Inspector’s Test
Method of Testing Sprinkler
System Alarms
Found on branch line usually at
the most remote point.
Flowing water through the test
connection ensures that water
is flowing through the entire
system.
Dry System Air
Compressor
The compressed air supply shall be
from a source available at all times
and have a capacity of restoring air
pressure in the system within 30
minutes. (NFPA 13 Section 4-2.6)
Air Maintenance Device
Drains on Dry Systems
Drum Drips must have upper valve
open and lower closed
When installing ensure everything is
pitched to drain
If there are low points, ensure there
is a low point drain.
All low points shall be drained
annually, prior to the onset of freezing
weather.
What Have We Inspected?
Water Supply
Control Valves & Other Valves
Fire Department Connection
Alarm
Piping & Sprinklers
Inspectors Test
REMEMBER
FIRE
SPRINKLER
SYSTEMS SAVE
LIVES