![Page 1: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/1.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126
Inspection Date:Friday June 7, 2019
Prepared For:Michael Knowd
Prepared By:Hindsight Inspection Services
223 East Owasso LaneShoreview, MN 55126
Report Number:2019-3
Inspector:Michael Heinze
![Page 2: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/2.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 3
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Report SummaryMajor Concerns
Upper roof was damp and had movement when stepped on near chimney. After further investigation in attic below it was discovered that daylight could be seen between chimney and flashing. Evidence of plywood rot in this area is apparent. Replacement of wood rot, correcting the flashing and adding cricket in front of the chimney would be solutions to resolve this issue. Recomend a roofing contractor evaluate this further.
Basement and garage windows are in poor condition and have fogged glass
In basement North and East walls have cracking and moisture intrusion. Some repairs have been made, but appear not to have resolved the issues. Ductwork below slab has standing water in it. Recommend further evaluation by a qualified contractor or licensed engineer. Steel bracing/ buttressing of wall, pouring/ patching, of wall locations, and installing a sump pump system around perimeter walls would be likely options for improvement.
Potential Safety HazardsGas range exhaust fan is vented directly into basement and has not yet been extended outside.
Water heater did not have a relief valve extension pipe and is located inside a garage space without a protection ballard and is mounted below 18" near a potential ignition source.
For inhanced safety recomend fire rated walls, doors, and ceiling be installed between lower garage and house if parking combustion vehicles in this space.
Recomend adding handrail to basement stairway.
Deferred Cost ItemsWater heater functioned properly, however it's age has exceeded the typical life expectancy for the average water heater, recomend budgeting for replacement.
Improvement ItemsRecomend adding spark arrestor cap to top of chimney.
Minor Concerns Recommend MaintenanceTrim was in need of normal painting maintenance in a handful of areas.
Recomend replacement of trim around basement windows.
Noticed east living room window did not stay hung upright when un-latched. Springs may need to be repaired or replaced on the right section looking towards the outside.
Recomend repairing weatherstripping on garage service door.
In upper main bathroom pop up drains in tub and sink areas would not hold water when closed. May need adjustment or
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 3: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/3.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 4
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Report SummaryMinor Concerns Recommend Maintenance
gaskets replaced.
In master bathroom sink strainer is missing rod clip, this will need to be installed/ adjusted in order to operate strainer from faucet.
Receptacle on west wall in basement has open ground connection.
Some roof vents on upper roof show signs of rust. Recomend repainting or replacing.
Additional ReferencesAttached with this report are the following illustrations which describe specific items mentioned in this report: Typical water heater installation requirements for a garage, fire separation requirements, and common foundation problems and repairs.
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 4: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/4.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 5
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Report OverviewScope of Inspection
All components designated for inspection in the ASHI Standards of Practice are inspected, except as may be noted in the "Limitations of Inspection" sections within this report. It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind. Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.
Main Entrance FacesEast
State of OccupancyOccupied
Weather ConditionsSunny
Recent RainNone
Ground CoverDry
Approximate Age41 years old
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 5: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/5.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 6
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
GroundsService Walks
None Not Visible
Material X Concrete Flagstone Gravel Brick Other:
Condition Satisfactory X Marginal Poor Trip hazard Typical cracks Pitched towards homeSettling cracks Public sidewalk needs repair
Comments
Photos
Rear service walk has some cracking
Driveway/Parking
None Not Visible
Material X Concrete Asphalt Gravel/Dirt Brick Other:
Condition X Satisfactory Marginal Poor Settling Cracks Typical cracks Pitched towards homeTrip hazard Fill cracks and seal
Comments
Stoops/Steps
None
Material Concrete X Wood Other: Composite Railing/Balusters recommended
Condition X Satisfactory Marginal Poor Safety Hazard Uneven risers Rotted/DamagedCracked Settled
Comments
Deck/Balcony
None Not Visible
Material Wood Metal X Composite Railing/Balusters recommended
Condition X Satisfactory Marginal Poor Wood in contact with soil
Finish Treated Painted/Stained Other: Safety Hazard Improper attachment to houseRailing loose X Not Applicable
Comments
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 6: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/6.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 7
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Grounds
Rear deck Front deck
Fence/Wall
Not evaluated None
Type X Brick Block Wood Metal Chain Link Rusted Vinyl
Condition X Satisfactory Marginal Poor Typical cracks Loose Blocks/Caps
Gate X N/A Satisfactory Marginal Poor Planks missing/damaged Operable: Yes No
Comments For inhanced safety railings could be installed in this location
Photos
Landscaping affecting foundation
N/A
Negative Grade East West North South X Satisfactory Recommend additional backfillRecommend window wells/covers X Trim back trees/shrubberiesWood in contact with/improper clearance to soil
Comments Recommend trimming trees/vegetation so it doesn not come into contact with the home
Hose bibs
N/A
Condition X Satisfactory Marginal Poor No anti-siphon valve Recommend Anti-siphon valve
Operable X Yes No Not Tested Not On
Comments
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 7: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/7.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 8
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Grounds
Typical hose bibb
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 8: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/8.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 9
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
RoofGeneral
Visibility None X All Partial Limited By:
Inspected From X Roof Ladder at eaves Ground With Binoculars
Style of Roof
Type X Gable Hip Mansard Shed Flat Other:
Pitch Low X Medium Steep Flat
Roof #1 - Lower Roof Type: Asphalt Layers: 1 Layer Age: 15-20+ Location: Garage
Roof #2 - Upper Roof NoneType: Asphalt Layers: 1 Layer Age: 15-20+ Location: House
Comments
Ventilation System
None N/A
Type X Soffit Ridge Gable X Roof Turbine Powered Other:
Comments Some roof vents on upper roof show signs of rust. Recomend repainting or replacing.
Photos
Roof Vents
Flashing
Material Not Visible X Galv/Alum Asphalt Copper Foam Rubber Lead Other:
Condition Not Visible Satisfactory Marginal X Poor Rusted MissingX Separated from chimney/roof Recommend Sealing Other:
Comments Roofing was damp and had movement when stepped on near chimney. After further investigation in attic it was discovered that daylight could be seen between chimney and flashing. Evidence of plywood rot in this area is apparent. Replacement of wood rot, correcting the flashing and adding cricket in front of the chimney would be solutions to resolve this issue. Recomend a roofing contractor evaluate this further.
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 9: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/9.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 10
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Roof
Gap between flashing and chimney
Location of wood rot below Daylight seen below and rot
Cricket installation to divert water around chimney
Condition of Roof Coverings
Roof #1 - Lower Roof Satisfactory X Marginal Poor Curling X Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping X Granules missing AlligatoringBlistering Missing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing X Recommend roofer evaluate Evidence of Leakage
Roof #2 - Upper Roof X N/A Satisfactory Marginal X Poor Curling X Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping X Granules missing AlligatoringBlistering Missing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing X Recommend roofer evaluate Evidence of Leakage
Comments
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 10: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/10.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 11
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Roof
Lower roof Upper roof
Skylights
N/A Not Visible
Condition Cracked/Broken X Satisfactory Marginal Poor
Comments
Photos
Skylight
Plumbing Vents
Not Visible Not Present
Condition X Satisfactory Marginal Poor
Comments
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 11: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/11.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 12
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
ExteriorChimney(s)
None
Location(s) Upper roof
Viewed From X Roof Ladder at eaves Ground (Inspection Limited) With Binoculars
Rain Cap/Spark Arrestor Yes X No X Recommended
Chase Brick Stone Metal X Blocks Framed
Evidence of Holes in metal Cracked chimney cap Loose mortar joints Flaking Loose brick RustX No apparent defects
Flue X Tile Metal Unlined Not Visible
Evidence of Scaling Cracks Creosote Not evaluated Have flue(s) cleaned and re-evaluatedX Recommend Cricket/Saddle/Flashing No apparent defects
Condition Satisfactory X Marginal Poor Recommend Repair
Comments Recomend adding spark arrestor cap to top of c himney . See roofing section for other recommended flashing and roof repairs.
Photos
Spark arrestor rain cap
Siding
Material Stone Slate Block/Brick Fiberboard Fiber-cement X Stucco EIFS* Not InspectedAsphalt Wood Metal/Vinyl Other: Typical cracks Peeling paint Monitor Wood rotLoose/Missing/Holes
Condition X Satisfactory Marginal Poor Recommend repair/painting
Comments
Trim
Material X Wood Fiberboard Aluminum/Steel X Vinyl X Stucco Recommend repair/paintingDamaged wood Other:
Condition Satisfactory X Marginal Poor
Comments Trim was in need of normal painting maintenance in a handful of areas. Recomend replacement of trim around basement windows.
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 12: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/12.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 13
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Exterior
Trim damaged above basement window
Painting maintenance
Soffit
None
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Fascia
None
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Flashing
None
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments
Caulking
None
Condition Satisfactory X Marginal PoorX Recommend around windows/doors/masonry ledges/corners/utility penetrations
Comments
Windows/Screens
Condition X Satisfactory Marginal X Poor Wood rot Recommend repair/paintingRecommend repair/replace damaged screens X Failed/fogged insulated glass
Material Wood X Metal Vinyl X Aluminum/Vinyl clad
Screens Torn Bent Not installed X Satisfactory
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 13: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/13.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 14
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
ExteriorWindows/Screens cont.
Comments Basement and garage windows are in poor condition and have fogged glass all other windows are in satisfactory condition. Noticed east living room window did not stay hung upright when un-latched. Springs may need to be repaired or replaced on the right section looking towards the outside. Dinning room windows were not opened, hardware is loose and may need ajustment.
Photos
Basement windows from inside Basement windows fogged glass Garage & basement windows fogged glass
Service Entry
Location X Underground Overhead
Condition X Satisfactory Marginal Poor Weather head/mast needs repair Overhead wires too low
Exterior receptacles X Yes No Operable: X Yes No Condition: X Satisfactory Marginal Poor
GFCI present X Yes No Operable: X Yes No Safety Hazard Reverse polarity Open ground(s)Recommend GFCI Receptacles
Comments All exterior and garage recepticles are controlled by a GFCI breaker in the main electrical panel.
Building(s) Exterior Wall Construction
Type Not Visible X Framed X Masonry Other:
Condition Not Visible X Satisfactory Marginal X Poor
Comments Wood framed walls not visible but appear satisfactory. Apparent movement and moisture in block foundation walls. See basement section for further details.
Exterior Doors
Main Entrance N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Sliding Doors To Deck N/A Weatherstripping: X Satisfactory Marginal Poor Missing ReplaceDoor condition: X Satisfactory Marginal Poor
Rear Basement Garage Door N/A Weatherstripping: Satisfactory X Marginal Poor Missing ReplaceDoor condition: X Satisfactory Marginal Poor
Garage Service Door N/A Weatherstripping: Satisfactory Marginal X Poor Missing X ReplaceDoor condition: Satisfactory X Marginal Poor
Comments Recomend repairing weatherstripping on garage service door.
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 14: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/14.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 15
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Exterior
Garage Service Door - Weatherstripping in need of repair
Exterior A/C - Heat pump #1
Unit #1 N/ALocation: West side of house Brand: Bryant Heating and Cooling Systems Model #: 265ANA030 Serial #: 3508E21523Approximate Age: 11 Years
Condition X Satisfactory Marginal Poor Cabinet/housing rusted
Energy source X Electric Gas Other:
Unit type Air cooled Water cooled Geothermal X Heat pump
Outside Disconnect X Yes No Maximum fuse/breaker rating (amps): 30 Fuses/Breakers installed (amps): 30Improperly sized fuses/breakers
Level X Yes No Recommend re-level unit
Condenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line X Satisfactory
Insulation X Yes No Replace
Improper Clearance (air flow) Yes X No
Comments
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 15: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/15.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 16
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Garage/CarportType
None
Type X Attached Detached 1-Car X 2-Car 3-Car 4-Car Carport
Comments
Photos
Main garage Lower garage
Automatic Opener
None N/A
Operation X Operable Inoperable
Comments
Safety Reverse
None N/A
Operation X Operable Not Operable Need(s) adjusting Safety hazardX Photo eyes and pressure reverse tested
Comments
Floor
Material X Concrete Gravel Asphalt Dirt Other: Spancrete
Condition X Satisfactory Typical cracks Large settling cracks Recommend evaluation/repairSafety hazard
Source of Ignition within 18" of the floor N/A X Yes X No
Comments Water heater located in lower garage space. This is a potential source of ignition. See water heater section for recommended requirements.
Overhead Door(s)
N/A
Material Wood Fiberglass Masonite X Metal Recommend repair
Condition X Satisfactory Marginal Poor Hardware loose Safety Cable RecommendedWeatherstripping missing/damaged Loose/missing
Recommend Priming/Painting Inside & Edges Yes X No
Comments
Electrical Receptacles
Yes No Not Visible Operable: Yes No
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 16: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/16.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 17
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Garage/CarportElectrical Receptacles cont.
Reverse polarity Yes X No
Open ground Yes X No Safety Hazard
GFCI Present X Yes No Operable: X Yes No Handyman/extension cord wiringRecommend GFCI Receptacles
Comments
Fire Separation Walls & Ceiling
N/A X Present Missing Recommend repair
Condition X Satisfactory Recommend repair Holes walls/ceiling X Safety hazard(s)
Moisture Stains Present Yes X No
Typical Cracks Yes X No
Fire door Not verifiable Not a fire door Needs repair X Satisfactory
Self closure N/A Satisfactory Inoperative X Missing
Comments Main garage is satisfactory. Lower garage in basement does not have a fire separation between the unfished basement and the family room floor above.
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 17: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/17.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 18
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
KitchenCountertops
Condition X Satisfactory Marginal Recommend repair/caulking
Comments
Photos
Kitchen
Cabinets
Condition X Satisfactory Marginal Recommend repair/adjustment
Comments
Plumbing
Faucet Leaks Yes X No
Pipes leak/corroded Yes X No
Sink/Faucet X Satisfactory Corroded Chipped Cracked Recommend repair
Functional drainage X Satisfactory Marginal Poor
Functional flow X Satisfactory Marginal Poor
Comments
Walls & Ceiling
Condition Satisfactory X Marginal Poor Typical cracks X Moisture stains
Comments Moisture stains were tested with moisture meter and apear inactive, stains are believed to be caused from old shower above that has sense been replaced.
Heating/Cooling Source
X Yes No
Comments
Floor
Condition X Satisfactory Marginal Poor Sloping Squeaks
Comments
Appliances
Disposal N/A Not tested Operable: X Yes No
Oven N/A Not tested Operable: X Yes No
Range N/A Not tested Operable: X Yes No
Dishwasher N/A X Not tested Operable: X Yes No
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 18: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/18.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 19
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
KitchenAppliances cont.
Exhaust fan N/A Not tested Operable: X Yes No
Refrigerator N/A Not tested Operable: X Yes No
Microwave N/A Not tested Operable: X Yes No
Dishwasher airgap X Yes No
Dishwasher drain line looped X Yes No
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI Receptacles: Yes NoPotential Safety Hazard(s)
Open ground/Reverse polarity: Yes X No Potential Safety Hazard
Comments Gas range exhaust fan is vented directly into basement and has not yet been extended outside. This is a potential safety hazard.
Photos
Range exhaust Range exhaust terminates in basement
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 19: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/19.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 20
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Laundry RoomLaundry
Laundry sink X N/A
Faucet leaks Yes X No
Pipes leak X Yes No Not Visible
Cross connections X Yes No Potential Safety Hazard
Heat source present X Yes No
Room vented X Yes No
Dryer vented N/A X Wall Ceiling Floor Not vented Plastic dryer vent not recommendedNot vented to exterior Recommend repair Safety hazard
Electrical Open ground/reverse polarity: Yes X No Safety hazard
GFCI present X Yes No Operable: X Yes No Recommend GFCI Receptacles
Appliances X Washer X Dryer Water heater Furnace/Boiler
Washer hook-up lines/valves X Satisfactory Leaking Corroded Not Visible
Gas shut-off valve X N/A Yes No Cap Needed Safety hazard Not Visible
Comments Discovered moisture in ceiling which is being contributed by the flashing roofing issues above next to the chimney. See further details in roofing section.
Photos
Moister above ceiling Laundry room
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 20: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/20.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 21
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Bathroom (1)Bath
Location Main floor
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window None X Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments
Photos
Main floor Bathroom
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 21: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/21.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 22
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Bathroom (2)Bath
Location Upper floor
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Tubs N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Shower/Tub area X Ceramic/Plastic Fiberglass Masonite Other: Condition: X Satisfactory MarginalPoor Rotted floors Caulk/Grouting needed: Yes X No
Where: N/A
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window None X Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments Pop up drains in tub and sink areas would not hold water when closed. May need adjustment or gaskets replaced
Photos
Pop up drain
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 22: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/22.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 23
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Bathroom (3)Bath
Location Upper floor Master Bathroom
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Tubs N/A Faucet leaks: Yes X No Pipes leak: Yes X No Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Shower/Tub area Ceramic/Plastic Fiberglass X Masonite Other: Tile Condition: X Satisfactory MarginalPoor Rotted floors Caulk/Grouting needed: Yes No
Where: N/A
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window None X Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: Yes No Noisy
Comments Sink strainer is missing rod clip, this will need to be installed/ adjusted in order to operate strainer from faucet.
Photos
Master Bathroom Strainer rod needs adjustment and clip
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 23: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/23.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 24
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Room (1)Room
Location Upper floor North West
Type Master Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor Satisfactory X Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan X None Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
Master Bedroom
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 24: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/24.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 25
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Room (2)Room
Location Upper floor North East
Type Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor Satisfactory X Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan X None Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
North East Bedroom
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 25: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/25.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 26
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Room (3)Room
Location Upper floor South East
Type Bedroom
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan X None Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
South East Bedroom
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 26: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/26.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 27
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
InteriorFireplace
None
Location(s) Main Floor and Basement
Type Gas X Wood Solid fuel burning stove Electric Ventless
Material X Masonry Metal (pre-fabricated) Metal insert Cast Iron
Miscellaneous Blower built-in Operable: Yes X No Damper operable: X Yes NoOpen joints or cracks in firebrick/panels should be sealed Fireplace doors need repair
Damper modified for gas operation X N/A Yes No Damper missing
Hearth extension adequate X Yes No
Mantel X N/A Secure Loose Recommend repair/replace
Physical condition X Satisfactory Marginal Poor Recommend having flue cleaned and re-examinedNot evaluated
Comments Note lower fire place has never been used. Fire place doors should be installed for lower fireplace to function safely.
Photos
Fireplace family room side Fireplace kitchen side
Stairs/Steps/Balconies
None
Condition X Satisfactory Marginal Poor Loose/Missing
Handrail Satisfactory Marginal Poor X Safety hazard X Hand Rail/Railing/Balusters recommended
Risers/Treads X Satisfactory Marginal Poor Risers/Treads uneven Trip hazard
Comments For inhanced safety recomend installing handrail on basement stairway
Photos
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 27: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/27.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 28
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Interior
Basement Stairway Missing Handrail
Smoke/Carbon Monoxide detectors
Smoke Detector X Present Not Present Operable: Yes No X Not tested Recommend additionalSafety Hazard
CO Detector X Present Not Present Operable: Yes No X Not tested Recommend additionalSafety Hazard
Comments
Attic/Structure/Framing/Insulation
N/A
Access Stairs Pulldown X Scuttlehole/Hatch No Access Other: Access limited by:
Inspected from X Access panel X In the attic Other
Location X Hallway Bedroom Closet X Garage Other
Flooring Complete Partial X None
Insulation Fiberglass X Batts Loose Cellulose Foam Other Vermiculite Rock woolDepth: 12" above house attic Damaged Displaced Missing Compressed
Recommend additional insulation
Installed in X Rafters/Trusses Walls Between ceiling joists Underside of roof deck Not Visible
Vapor barriers X Kraft/foil faced Plastic sheeting X Not Visible Improperly installed
Ventilation X Ventilation appears adequate Recommend additional ventilation Recommend baffles at eaves
Fans exhausted to Attic: Yes X No Recommend repair Outside: X Yes No Not Visible
HVAC Duct N/A X Satisfactory Damaged Split Disconnected Leaking Repair/ReplaceRecommend Insulation
Chimney chase N/A X Satisfactory Needs repair Not Visible
Structural problems observed Yes X No Recommend repair Recommend structural engineer
Roof structure X Rafters Trusses X Wood Metal Collar ties Purlins Knee wall Not Visible Other:
Ceiling joists X Wood Metal Not Visible
Sheathing X Plywood OSB Planking X Rotted X Stained Delaminated
Evidence of condensation Yes X No
Evidence of moisture X Yes No
Evidence of leaking X Yes No
Firewall between units N/A X Yes No Needs repair/sealing
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 28: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/28.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 29
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
InteriorAttic/Structure/Framing/Insulation cont.
Electrical X No apparent defects Open junction box(es) Handyman wiringKnob and tube covered with insulation Safety Hazard
Comments Attic above upper floor has leak and moisture intrusion at Chimney penetration through roof. See roofing section for further details. Lower attic above garage was in satisfactory condition.
Photos
Lower attic above garage Upper attic above upper floor
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 29: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/29.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 30
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
BasementFoundation
Condition Satisfactory Marginal X Have evaluated X Monitor Not Elevated
Material ICF Brick X Concrete block Stone Masonry Poured concrete wood
Horizontal cracks None X North South X East West
Step cracks None X North South East West
Vertical cracks X None North South East West
Covered walls None North South East X West
Movement apparent None X North South X East West
Indication of moisture X Yes No X Fresh Old stains
Comments North and East walls have cracking and moisture intrusion. Some repairs have been made, but appear not to have resolved the issues. Recommend further evaluation by a qualified contractor or licensed engineer. Steel bracing/ buttressing of wall, pouring/ patching, of wall locations, and installing a sump pump system around perimeter walls would be likely options for lmprovement.
Photos
North Wall step cracking and horizontal cracking
East wall horizontal cracking
Floor
Material X Concrete Dirt/Gravel Not Visible Other:
Condition X Satisfactory Marginal Poor X Typical cracks Not Visible
Comments
Girders/Beams
Not Visible
Condition X Satisfactory Marginal Poor Stained/Rusted
Material X Steel Wood Concrete LVL Not Visible
Comments
Columns
Not Visible
Condition X Satisfactory Marginal Poor Stained/Rusted
Material X Steel Wood Concrete Block Not Visible
Comments
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 30: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/30.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 31
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
BasementJoists
Not Visible
Condition X Satisfactory Marginal Poor
Material X Wood Steel Truss Not Visible 2x8 X 2x10 2x12 Engineered I-TypeSagging/altered joists
Comments
Subfloor
Not Visible
Condition X Satisfactory Marginal Poor Indication of moisture stains/rotting
Comments
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 31: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/31.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 32
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
PlumbingWater service
Main shut-off location Basement North wall
Water entry piping Not Visible X Copper/Galv. PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Lead Polyethylene
Lead other than solder joints Yes No X Unknown Service entry
Visible water distribution piping X Copper Galvanized PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Other:
Condition X Satisfactory Marginal Poor
Flow X Satisfactory Marginal Poor Water pressure over 80 psi Recommend plumber evaluateRecommend pressure regulator
Pipes Supply/Drain Corroded Leaking Valves broken/missing Dissimilar metal Cross connection: YesX No Safety Hazard Recommend repair Recommend a dielectric union X Satisfactory
Drain/Waste/Vent pipe Copper Cast iron Galvanized X PVC X ABS Brass
Condition X Satisfactory Marginal Poor
Support/Insulation X N/AType:
Traps proper P-Type X Yes No P-traps recommended
Drainage X Satisfactory Marginal Poor
Fuel line N/A X Copper Brass X Black iron Stainless steel CSST Not Visible GalvanizedRecommend CSST be properly bonded
Condition N/A X Satisfactory Marginal Poor Recommend plumber evaluate
Comments
Photos
Water Meter and Main Shutoff Valve
Main fuel shut-off location
N/A
Location Basement Near Furnace
Comments
Water heater #1
N/A
General Brand Name: AO Smith Model: KGA 40 860
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 32: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/32.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 33
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
PlumbingWater heater #1 cont.
General cont. Serial #: 86C-A-79-66651Capacity: 40 Gallon Approx. age: 33 years old
Type X Gas Electric Oil LP Other:
Combustion air venting present X Yes No N/A
Seismic restraints needed Yes No X N/A
Relief valve X Yes No Extension proper: Yes No X Missing X Recommend repairImproper material
Vent pipe N/A X Satisfactory Pitch proper Improper Rusted Recommend repair
Condition Satisfactory X Marginal Poor
Comments Water heater functioned properly, however it's age has exceeded the typical life expectancy for the average water heater, recomend budgeting for replacement. Tank drain valve on water heater has a slow drip. Water heater did not have a relief valve extension pipe and is located inside a garage space without a protection ballard and is mounted below 18" near a potential ignition source: Four wheelers, gas cans etc. These are potential safety hazards. See typical water heater installation for a garage space.
Photos
Drain valve drips, water heater is in garage space needs to be elevated 18" and have protective ballards
Missing Relief Valve Extension Typical water heater installation
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 33: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/33.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 34
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Heating SystemHeating system
Unit #1 Brand name: Bryant Approx. age: 11 Years
Unknown Model #: 355CAV0Y0100FASA Serial #: 2208A01449 X Satisfactory Marginal PoorRecommended HVAC technician examine
Energy source X Gas LP Oil Electric Solid fuel
Warm air system Belt drive X Direct drive Gravity Central system Floor/wall furnace
Heat exchanger N/A X Sealed X Not Visible Visual w/mirror Flame distortion RustedCarbon/soot buildup
Combustion air venting present N/A X Yes No
Controls Disconnect: X Yes No X Normal operating and safety controls observed Gas shut off valve:X Yes No
Distribution X Metal duct Insulated flex duct X Cold air returns Duct board Asbestos-like wrapSafety Hazard
Flue piping N/A X Satisfactory Rusted Improper slope Safety hazard Recommend repair/replace
Filter X Standard Electrostatic X Satisfactory Needs cleaning/replacement MissingElectronic (not tested)
When turned on by thermostat X Fired Did not fire Proper operation: X Yes No Not tested
Heat pump N/A Supplemental electric X Supplemental gas
Sub-slab ducts N/A Satisfactory Marginal X Poor Water/Sand Observed: X Yes No
System not operated due to X N/A Exterior temperature Other:
Comments Existing furnace filter was dirty, replaced with new furnace filter while onsite. (Filter size 20 x 24 x 4) Inside of furnace was clean, draft fan operation was satisfactory, condensate drain was inspected and showed no signs of leaks. Furnace was operated in cooling mode only. Heating mode was not tested. Heating mode runs the refrigeration loop in reverse utilizing the heat pump for supplemental heating, the natural gas heat exchanger will turn on when the heat pump can not keep up.
Photos
Inside Furnace 20 x 24 x 4 Filter replaced 5/7/19 Ductwork below slab has water in it
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 34: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/34.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 35
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Electric/Cooling SystemMain panel
Location Basement South Wall
Condition X Satisfactory Poor
Adequate Clearance to Panel X Yes No
Amperage/Voltage Unknown 60a 100a 150a X 200a 400a 120v/240v
Breakers/Fuses X Breakers Fuses
Appears grounded X Yes No Not Visible
GFCI breaker X Yes No Operable: X Yes No
AFCI breaker Yes X No Operable: Yes No Not Tested
Main wire Copper X Aluminum Not Visible Double tapping of the main wire Condition: X SatisfactoryMarginal Poor
Branch wire X Copper Aluminum Solid Branch Aluminum Wiring Not Visible Safety Hazard
Branch wire condition X Satisfactory Poor Recommend electrician evaluate/repair Romex BX cableConduit Knob/Tube Double tapping Wires undersized/oversized breaker/fusePanel not accessible Not evaluated
Reason:
Comments Receptacle on west wall in basement has open ground connection. Recomend qualified electrical contractor inspect/ reconnect ground wire behind receptacle.
Photos
Main electrical panel Open ground to receptacle west basement wall
Evaporator Coil Section Unit #1
N/A
General X Central system Wall unitLocation: Basement Age: 11 years
Evaporator coil Satisfactory X Not Visible Needs cleaning Damaged
Refrigerant lines Leak/Oil present Damage Insulation missing X Satisfactory
Condensate line/drain To exterior To pump X Floor drain Other:
Condition X Satisfactory Marginal Poor Recommend HVAC technician examine/clean/serviceNot operated due to exterior temperature
Comments
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 35: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/35.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 36
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Living RoomLiving Room
Location Main floor South of kitchen
Walls & Ceiling X Satisfactory Marginal Poor X Typical cracks Damage
Moisture stains X Yes NoWhere: South of chimney
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan X None Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments Moisture stains on ceiling were tested with moisture meter and have some active moisture. Likely cause is from leak on upper roof near chimney. See roofing section for further details
Photos
Living room
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
![Page 36: Inspection Date: Prepared For: Prepared By: Report Number ...€¦ · Major Concerns. Upper roof was damp ... Water heater functioned properly, however it's age has exceeded the typical](https://reader035.vdocuments.site/reader035/viewer/2022062606/5fdf223e2dd17b0d95129ace/html5/thumbnails/36.jpg)
3977 Woodbridge Ct., Vadnais Heights, MN 55126 Page 37
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services
Dining RoomDining Room
Location Main floor north of kitchen
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan X None Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Doors X None Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None Satisfactory X Marginal Poor Cracked glass Evidence of leaking insulated glassX Broken/Missing hardware
Comments See window section for additional comments regarding windows in the room.
Photos
Dinning room Dinning room
This confidential report is prepared exclusively for Michael Knowd©2020 Hindsight Inspection Services