information for Distribution-Network-Operators 11 20 www.kries.com With partial discharge detection in CAPDIS (R5), the partial discharge level of equipment and sys- tems can be permanently monitored and partial discharges can be detected at a stage before they lead to stationary faults and thus cause con- sequential damage or power failures. if a partial discharge is detected by the CAPDis (r5), the system can be examined in detail using an online diagnostic procedure to locate the partial discharge source.. Some errors in the Distribution network are obvious.. Measurement procedures for partial discharge detection differ not only in methodology but also in their suitability for the respective measurement location and the operating condition of the mea- surement object. in switchgear production, PD testing serves as a quality standard for the insula- tion strength of a new system and is tested under laboratory conditions, whereas such tests cannot be performed on systems in operation. Tempo- rary PD measurements of plants in operation pro- vide only a momentary picture, but are often not sufficient for a general risk assessment. CAPDis (r5) with Parital-Discharge Detection .. for others you need the right detecting devices Partial discharges are the most common cause of faults in medium and high voltage systems. Our solution: CAPDIS (R5) Measurement procedures for partial discharge detection differ not only in methodology but also in their suitability for the respective measurement location and the operating condition of the mea- surement object. In switchgear production, PD testing serves as a quality standard for the insula- tion strength of a new system and is tested under laboratory conditions, whereas such tests cannot be performed on systems in operation. Tempo- rary PD measurementsof plants in operation pro- vide only a momentarypicture, but are often not sufficient for a general risk assessment. With partial discharge detection in CAPDIS (R5), the partial discharge level of equipment and sys- tems can be permanently monitored and partial discharges can be detected at a stage before they lead to stationary faults and thus cause con- sequential damage or power failures. If a partial discharge is detected by the CAPDIS (R5), the system can be examined in detail using an online diagnostic procedure to locate the partial discharge source..

Upload: others

Post on 22-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: information for Distribution-Network-Operators

information for

Distribution-Network-Operators

1120

www.kries.com

With partial discharge detection in CAPDIS (R5),

the partial discharge level of equipment and sys-

tems can be permanently monitored and partial

discharges can be detected at a stage before

they lead to stationary faults and thus cause con-

sequential damage or power failures.

if a partial discharge is detected by the CAPDis

(r5), the system can be examined in detail using

an online diagnostic procedure to locate the partial

discharge source..

Some errors in the

Distribution network are obvious..

Measurement procedures for partial discharge

detection differ not only in methodology but also

in their suitability for the respective measurement

location and the operating condition of the mea-

surement object. in switchgear production, PD

testing serves as a quality standard for the insula-

tion strength of a new system and is tested under

laboratory conditions, whereas such tests cannot

be performed on systems in operation. Tempo-

rary PD measurements of plants in operation pro-

vide only a momentary picture, but are often not

sufficient for a general risk assessment.

CAPDis (r5) with Parital-Discharge Detection

.. for others you need

the right detecting devices

Partial discharges are the most common cause of faults in medium

and high voltage systems. Our solution: CAPDIS (R5)

Measurement procedures for partial discharge

detection differ not only in methodology but also

in their suitability for the respective measurement

location and the operating condition of the mea-

surement object. In switchgear production, PD

testing servesas a quality standard for the insula-

tion strength of a new system andis tested under

laboratory conditions, whereas such tests cannot

be performed on systems in operation. Tempo-

rary PD measurementsof plants in operation pro-

vide only a momentarypicture, but are often not

sufficient for a general risk assessment.

With partial discharge detection in CAPDIS (R5),

the partial discharge level of equipment and sys-

tems can be permanently monitored and partial

discharges can be detected at a stage before

they lead to stationary faults and thus cause con-

sequential damage or powerfailures.

If a partial discharge is detected by the CAPDIS

(R5), the system can be examined in detail using

an online diagnostic procedure to locate the partial

discharge source..

Page 2: information for Distribution-Network-Operators

www.kries.com2

Main causes for partial discharges in medium and

high voltage systems are

• Assembly errors during installation (e.g. loose

connections, incorrectly installed terminations, ...),

• insulation losses in the insulation materials (ear-

ly failures due to air inclusions in casting resins,

missing oil in terminations, sleeve defects due to

ageing)

• environmental influences (moisture and dust)

While partial discharges due to environmental influen-

ces occur less frequently in sF6 switchgear, they can

be observed and in some cases even eliminated, espe-

cially in older air- or solid-insulated systems, provided

that they are detected in time..

in gas-insulated systems, on the other hand, there are

often installation failures but also the loss of insula-

ting gas, which can lead to an increase of the partial

discharge level.

Partial-Discharge Sources

For the decoupling of the voltage and partial discharge

signal, various capacitive coupling electrodes are avai-

lable.

in factory-made Gis switchgear these can be the alrea-

dy existing bushings which are also used for voltage

testing.

For PD detection on transformers or for retrofitting

voltage testing systems on switchgear, adapter sets

for elbow connectors are used, which also allow volta-

ge testing and partial discharge detection.

in air-insulated switchgear, capacitive dividers are of-

ten installed, which capacitively decouple the voltage

signal in addition to their static function. These are also

well suited for PD detection.

if no capacitive coupling electrodes are available and

a voltage test with or without PD detection is to be

retrofitted, we offer either retrofittable coupling elec-

trodes or capacitive sensors which can be installed on

unshielded terminations.

It is recommended to provide partial discharge de-

tection as well as voltage testing in each field of a

switchgear. A partial discharge usually spreads over

several fields in an installation and can usually be as-

signed to one field by selective switching operations.

The ieee Gold Book Table 36 provides a

percentage evaluation for individual com-

ponents of their failures due to insulation

failures caused by aging, environmental

influences and wear and tear, and lack of

maintenance.

Percentage of components that have failed

due to insulation failure:

• Transformers 84 %

• Circuit breaker 21

• Disconnect switch 15

• insulated busbars 95%

• Bushings 90%

• Cable 89%

• Cable sleeves 91%

• Cable terminations 87%

PD can be detected at capacitive dividers and bushings

retrofit of capacitive sensors at terminations and

elbow-plugs

Capacitive decoupling by combined sensors for V and i

Capacitive signal decoupling for partial discharge detection with CAPDIS-Sx (R5)

6d

Partial-Discharge Sources

Main causes for partial discharges in medium and

high voltage systems are

e Assembly errors during installation (e.g. loose

connections,incorrectly installed terminations, ...},

e Insulation losses in the insulation materials (ear-

ly failures due to air inclusions in casting resins,

missing oil in terminations, sleeve defects due to

ageing)

¢ Environmentalinfluences (moisture and dust)

While partial discharges due to environmentalinfluen-

ces occurless frequently in SF6 switchgear, they can

be observed and in some caseseveneliminated, espe-

cially in older air- or solid-insulated systems, provided

that they are detectedin time..

In gas-insulated systems, on the other hand,there are

often installation failures but also the loss of insula-

ting gas, which can lead to an increase of the partial

dischargelevel.

The IEEE Gold Book Table 36 provides a

percentage evaluation for individual com-

ponents of their failures due to insulation

failures caused by aging, environmental

influences and wear and tear, and lack of

maintenance.

Percentage of components that havefailed

due to insulation failure:

Transformers 84 %

Circuit breaker 21

Disconnect switch 15

Insulated busbars 95%

Bushings 90%

Cable 89%

Cable sleeves 91%

Cable terminations 87%

Capacitive signal decoupling for partial discharge detection with CAPDIS-Sx (R5)

For the decoupling of the voltage and partial discharge

signal, various capacitive coupling electrodesare avai-

lable.

In factory-made GIS switchgearthese can be thealrea-

dy existing bushings which are also used for voltage

testing.

For PD detection on transformers or for retrofitting

voltage testing systems on switchgear, adapter sets

for elbow connectorsare used, whichalso allow volta-

ge testing andpartial discharge detection.

In air-insulated switchgear, capacitive dividers are of-

ten installed, which capacitively decouple the voltage

signal in addition to their static function. These are also

well suited for PD detection.

If no Capacitive coupling electrodes are available and

a voltage test with or without PD detection is to be

retrofitted, we offer either retrofittable coupling elec-

trodes or capacitive sensors which can beinstalled on

unshielded terminations.

It is recommended to provide partial discharge de-

tection as well as voltage testing in each field of a

switchgear.A partial discharge usually spreads over

severalfields in an installation and can usually be as-

signed to onefield by selective switching operations.

2 www.kries.com

PD can be detectedat capacitive dividers and bushings

Retrofit of capacitive sensors at terminations and

elbow-plugs

Capacitive decoupling by combined sensorsfor V and|

Page 3: information for Distribution-Network-Operators

4

Partial-Discharge Detection according DIN EN 60270 (VDE 0434)

4

The PD measurement method in CAPDis is derived

from eN 60270 (VDe 0434) and, like the voltage mea-

surement in CAPDis, is based on the capacitive de-

coupling of the signals via a coupling capacitor Ck. Ho-

wever, the partial discharge signal is a high-frequency

signal (30 kHz to some MHz), which is superimposed

on the 50 Hz (60 Hz) useful signal for voltage testing.

The coupling capacitor Ck is the capacitive tap (also

known as C1), which also decouples the voltage test

signal. since this coupling capacitor is system-specific

and can be designed between approx. 1 pF and 100 pF

in practice, the PD signal also has a different strength.

in order not to react too sensitively to uncritical distur-

bances, four pick-up ranges have proven to be useful.

These can be successively adjusted in CAPDis (r5) to

be less sensitive if a PD display occurs without obvious

error.

The CAPDis family with the standard devices CAP-

Dis-s1 (r4.5) and CAPDis-s2 (r4.5) without partial

discharge detection is extended by the family members

CAPDis-s1_55 (r5) and CAPDis-s2_55 (r5) with PD

detection. Also available are the high voltage devices

CAPDis-s1_HV (r5) and CAPDis-s2_HV (r5) with PD

detection.

All CAPDis devices feature the three-stage voltage test

as well as the integrated maintenance test; i.e. the de-

vices are exempt from cyclic maintenance testing.

No auxiliary power or battery is required for partial

discharge detection and indication on the LC display.

The energy for partial discharge detection and display

is taken exclusively from the 50Hz (60Hz) measure-

ment signal.

in the CAPDis-s2_xy (r5) versions, the partial discharge

is indicated on the LC display as with the CAPDis-s1_xy

(r5). in addition, the fault message function is activated

in the CAPDis-s2_xy (r5) when partial discharge is de-

tected. This collective fault can be transmitted directly

to a scada-system or by iki-23 / iki-50 also via Mod-

bus. Auxiliary power is required for remote transmissi-

on of the PD information.

Comparison to PD-Detecting acc. eN

602770

Z = Filter corresponds to cable network

Ca = plant capacity

Ck = C1 = Coupling capacitance

CD = Coupling unit integrated in CAPDis

CC = Connection line to CAPDis

The CAPDIS-Family

CAPDis-s1 (r4.5) CAPDis-s2 (r4.5)

CAPDis-s1_55 (r5) CAPDis-s2_55 (r5)

CAPDis-s1_HV (r5) CAPDis-s2_HV (r5)

iki-23 CAPDis-s2_55(r5)

Partial-Discharge Detection according DIN EN 60270 (VDE 0434)

The PD measurement method in CAPDIS is derived

from EN 60270 (VDE 0434)and,like the voltage mea- Lz]surement in CAPDIS, is based on the capacitive de-

coupling of the signals via a coupling capacitor Ck. Ho- C C

wever, the partial discharge signal is a high-frequency y — s

signal (80 kHz to some MHZ}, which is superimposed cc

on the 50 Hz (60 Hz) useful signal for voltage testing.

The coupling capacitor Ck is the capacitive tap (also

known as C1), which also decouples the voltage test

signal. Since this coupling capacitor is system-specific = Schaltanlage / Switch Gear

and can be designed between approx. 1 pF and 100 pF

in practice, the PD signal also has a different strength.

In order not to react too sensitively to uncritical distur-

bances, four pick-up ranges have proven to be useful.

These can be successively adjusted in CAPDIS (R5) to

be less sensitive if a PD display occurs without obvious

error.

Comparison to PD-Detecting acc. EN

602770

Z = Filter corresponds to cable network

Ca = plant capacity

Ck = C1 = Coupling capacitance

CD = Coupling unit integrated in CAPDIS

CC = Connection line to CAPDIS

The CAPDIS-Family

The CAPDIS family with the standard devices CAP-

DIS-S1 (R4.5) and CAPDIS-S2 (R4.5) without partial

discharge detection is extendedby the family members

CAPDIS-S1_55 (R5) and CAPDIS-S2_55 (R5) with PD

detection. Also available are the high voltage devices

CAPDIS-S1_HV (R5) and CAPDIS-S2_HV (R5) with PD

detection.

All CAPDIS devices feature the three-stage voltage test

as well as the integrated maintenance test; i.e. the de-

vices are exempt from cyclic maintenancetesting.

No auxiliary power or battery is required for partial

discharge detection and indication on the LC display.

The energy for partial discharge detection and display

is taken exclusively from the 5QHz (60Hz) measure-

mentsignal.

Inthe CAPDIS-S2_xy(R5) versions,the partial discharge

is indicated on the LC display as with the CAPDIS-S1_xy

(R5). In addition, the fault message functionis activated

in the CAPDIS-S2_xy (R5) whenpartial discharge is de-

tected. This collective fault can be transmitted directly

to a Scada-System orby IKl-23 / IKI-50 also via Mod-

bus. Auxiliary power is required for remote transmissi-

on of the PD information. —

IKI-23 CAPDIS-S2_55(R5)

CAPDISS1_HV(R5} CAPDISS2_HV [R5]

Page 4: information for Distribution-Network-Operators

Retrofit of CAPDIS (R5)

5 www.kries.com 5

Universal adapter for retrofitting

Furthermore, we have attached importance to

easy retrofitting. The CAPDis (r5) can of course

be used instead of existing CAPDis. For retrofit-

ting to Hr or LrM interfaces, we offer an univer-

sal retrofit adapter that takes into account all sys-

tem configurations known to us.

The universal adaption capacity on the back of all

CAPDis units allows easy adaptation of the se-

condary capacity to the primary capacity without

any calculation or preliminary calculation. This is

particularly helpful for retrofitting. The value is set

so that three full flash arrows are visible on the

display when the nominal voltage is present. if

only half of the arrow appears, the adaption capa-

city must be reduced, if a framed arrow appears,

the adaption capacity must be increased.

.

Why CAPDIS (R5)?

The use of CAPDIS (R5) increases personal sa-

fety and the safety of the switchgear, whose

insulation can be monitored with PD detection.

if the CAPDis (r5) is retrofitted to an existing Hr

or LrM interface, its service life is extended by

the permanent load impedance. in addition, the

cyclic maintenance test for voltage detecting sys-

tems, which is already integrated in all CAPDis

and permanently performed, is no longer neces-

sary.

CAPDis (r5) does not replace a PD diagnosis, as

specific PD diagnosis systems offer, but it does

provide an indication when such a PD diagnosis is

urgently recommended.

in addition, the PD display in the field-related CAP-

Dis devices can be used to quickly determine the

panel affected by the partial discharge. A corres-

ponding procedure is shown in the adjacent flow

chart from the operating instructions.

ExtractfromManual:Schemeforpre-localizationofPD

kries

Retrofit of CAPDIS (R5)

CAPDIS mitUniversal-Adapteraufgesteckt auf

Universal adapterforretrofitting Settle PhasoL2

Furthermore, we have attached importance to

easy retrofitting. The CAPDIS (R5) can of course

be used instead of existing CAPDIS.For retrofit-

ting to HR or LRM interfaces, we offer an univer-

sal retrofit adapter that takes into accountall sys-

tem configurations knownto us.

The universal adaption capacity on the backofall

CAPDIS units allows easy adaptation of the se-

condary capacity to the primary capacity without

any calculation or preliminary calculation. This is

particularly helpful for retrofitting. The value is set

so that three full flash arrows are visible on the

display when the nominal voltage is present.If

only half of the arrow appears,the adaption capa-

city must be reduced,if a framed arrow appears,

the adaption capacity mustbe increased.

CAPDIS-Sx

U

LRM: 14mm.

L3 u4

PD-Detection activated in CAPDIS R65;all CAPDIS R65haveto be adjusted to the mostsensitive PD-pickup-level

Switch Gear powered with nominal voltage and all CAPDIS R65show threefull arrows

PD-Detection (blinking or permanent)Why CAPDIS (R5)? at one or more CAPDIS R5

y 10 sec after last switching operation?es)

No

The use of CAPDIS (R5) increases personal sa- d. Single feeders are separated from the busbar;i.e. disconnected

fety and the safety of the switchgear, whose [ until the PDnication canbe pinpointed to one dedicated feeder- |Devices with permanentindication are closer to the PD-source

insulation can be monitored with PD detection.

onesingle feederof the switch-gear? No

If the CAPDIS (R95)is retrofitted to an existing HR (

or LRM interface, its service life is extended by

Thesetting of the bluecircuit capacitor on the backof the devicemay have to be reduced byonevalue to avoid PDdetection by noise.

. 7 —_—: Nothe permanent load impedance.In addition, the Yes PD indication stil present? a,

cyclic maintenance test for voltage detecting sys- Thefurther measuresrefer only to feeders, which might be the PD-source: : : : In these feeders it must be checked whetherthe termintations are correctly mounted and

tems, which is already integrated in all CAPDIS there are noexternal conspicuous features or noises. If no abnormalitiesare recognizable, then continue in the scheme;otherwise, correct the recognized errors

and permanently performed,is no longer neces-

sary. ‘PD-pick-up onelevel less sensitive

. . Pick-up level adjustment DIP 3 4CAPDIS (R5]) does not replace a PD diagnosis, as Pick-up 1 (very sensve: Of of

es . . . ick-up nspecific PD diagnosis systemsoffer, but it does Pick-up 3 . Off On

Pick-up 4 (unsensitive): On On

provide an indication when such a PD diagnosisis

urgently recommended.

PDindicationstill present?

In addition, the PD display in the field-related CAP-

DIS devices can be used to quickly determine the aller 1aedays

panel affected by the partial discharge. A corres-

ponding procedure is shown in the adjacent flowYes

PD-indication appears again?

chart from the operating instructions. | Diagnosis required Yes No

——

Extract from Manuat Scheme for pretocalization of PD

Checking the indication

www.kries.com 5

Page 5: information for Distribution-Network-Operators

6kries-energietechnik GmbH & Co. kG, sandwiesenstr. 19, 71334 Waiblingen

Telefon +49 7151 96932-0, e-Mail: [email protected], internet: kries.com

Waiblingen in November 2020

Distribution network operators, who have recognized that their greatest capital and skills are buried in

the distribution networks, have also learned that the networks must be digitized for the energy turna-

round. in order to cope with this, leading distribution network operators worldwide have now opted for a

combination of remote-controlled stations (digitization level k3) and remote-monitored stations (digitiza-

tion level k2).

Here, the remote control technology together with CAPDis, iki-5x and PsU-Hy-

brid is consistently used in new motorized switching systems, while exis-

ting systems are retrofitted with monitoring systems like CAPDis, iki-2x or iki-5x.

A target network planning, which provides for sufficient retrofitting of voltage and fault de-

tection systems with remote transmission in existing switch gears, enables the interaction

with the new remote controlled switch gears. This allows for rapid fault location and selecti-

ve activation, which reduces sAiDi and increases availability and personal and switch gear safety.

in order to detect system faults before they cause a power failure, partial discharge detection has proven

its worth in practice. Partial discharges are the harbingers of failures in medium and high voltage systems.

There are different types of partial discharges (internal and external discharges), but

they have one thing in common: a breakdown of an insulation section, i.e. there is no di-

rect contact between two electrodes (phase-phase or phase-earth), but insulation is reduced.

6D

Waiblingen in November 2020

Distribution network operators, who have recognized that their greatest capital and skills are buried in

the distribution networks, have also learned that the networks mustbe digitized for the energy turna-

round. In order to cope withthis, leading distribution network operators worldwide have now opted for a

combination of remote-controlled stations (digitization level K3) and remote-monitoredstations(digitiza-

tion level K2).

Here, the remote control technology together with CAPDIS, IKI-Sx and PSU-Hy-

brid is consistently used in new motorized switching systems, while exis-

ting systems are retrofitted with monitoring systems like CAPDIS, IKl-2x or IKI-x.

A target network planning, which provides for sufficient retrofitting of voltage and fault de-

tection systems with remote transmission in existing switch gears, enables the interaction

with the new remote controlled switch gears. This allows for rapid fault location and selecti-

ve activation, which reduces SAIDI and increases availability and personal and switch gear safety.

saling

K4 :

Distribution-Protection| Automatic Transfer Switch ATS

Digi

tali

zati

o

‘High-Availability

Distribution Network Availability

Outage-Time

<1

Minu

te

focus on power presence>

In order to detect system faults before they cause a powerfailure, partial discharge detection has proven

its worthin practice. Partial discharges are the harbingersoffailures in medium and high voltage systems.

There are different types of partial discharges (internal and external discharges), but

they have one thing in common: a breakdown of an insulation section, ie. there is no di-

rect contact between two electrodes (phase-phase or phase-earth), but insulation is reduced.

KRIES-Energietechnik GmbH & Co. KG, Sandwiesenstr. 19, 71334 Waiblingen 6

Telefon +49 7151 969382-0, E-Mail: [email protected], Internet: kries.com

Page 6: information for Distribution-Network-Operators

3

Partial discharges do not cause a tripping from the

protection relay and therefore often remain undetec-

ted. We have made it our task in the new CAPDis (r5)

to detect these nevertheless.

The insulation loss is caused by an increased field

strength concentration, which leads to a parti-

al breakdown of the insulation. This process is ra-

rely reversible and often turns into a static fault

over time if it is not detected and stopped early.

The partial discharge detection in CAPDis (r5) is reali-

zed with an active bandpass whose gain can be adjusted.

The detected partial discharge level depends

on the decoupling capacity of the switchge-

ar C1 and the set threshold in the device.

Typical PD detection thresholds that are reached

are between 300 pC and 1000 pC. Weak parti-

al discharges are indicated by a flashing signal,

stronger partial discharges by a continuous signal.

The threshold value for partial discharge detecti-

on in CAPDis can be set by means of a DiP switch

accessible on the rear of the device. Alternatively

the partial discharge detection can be deactivated.

Tests on systems in nominal operation have shown

that partial discharges in the medium voltage cab-

le are also detected. However, the sensitivity of PD

detection decreases rapidly along the medium vol-

tage cable. Already at a distance of 3 m only partial

discharges larger than 1000 pC can be detected.

if a remote transformer is to be monitored as well, it is re-

commended to provide voltage and PD detection direct-

ly at the medium voltage connection of the transformer.

Diagnosis of the cause of PD

A diagnostic socket is available on CAPDis (r5). The

diagnostic socket allows a more detailed examination

of the partial discharge.

in addition, there are mobile PD diagnostic systems

from various suppliers as well as specialized service

providers who can perform advanced PD diagnosis.

even an oscilloscope diagnosis can determine which

conductor is actually affected and whether it is an in-

ternal or external discharge or an external disturban-

ce.

Partial-Discharge Detection with CAPDIS (R5) in Practice

PD-Diagnosis with scope

6D

Partial-Discharge Detection with CAPDIS (R5) in Practice

Partial discharges do not cause a tripping from the

protection relay and therefore often remain undetec-

ted. We have madeit our task in the new CAPDIS (R5)

to detect these nevertheless.

The insulation loss is caused by an increasedfield

strength concentration, which leads to a_ parti

al breakdown of the insulation. This process is ra-

rely reversible and often turns into a static fault

over time if it is not detected and stopped early.

The partial discharge detection in CAPDIS (R35)is reali-

zed with an active bandpass whosegain can be adjusted.

The detected partial discharge level depends

on the decoupling capacity of the switchge-

ar C1 and the set threshold in the device.

Typical PD detection thresholds that are reached

are between 300 pC and 1000 pC. Weak parti

al discharges are indicated by a flashing signal,

stronger partial discharges by a continuous signal.

The threshold value for partial discharge detecti-

on in CAPDIS can be set by means of a DIP switch

accessible on the rear of the device. Alternatively

the partial discharge detection can be deactivated.

Tests on systems in nominal operation have shown

that partial discharges in the medium voltage cab-

le are also detected. However, the sensitivity of PD

detection decreases rapidly along the medium vol-

tage cable. Already at a distance of 3 m only partial

discharges larger than 1000 pC can be detected.

Ifa remote transformeristo be monitored as well, itis re-

commendedtoprovide voltage and PD detectiondirect-

lyatthe medium voltage connection of the transformer.

TE-Diagnose-Buchse geeignetfur Oszilloskop

PD-Diagnostic-socet suitable

for Oscilloscope

Diagnosis of the cause of PD

A diagnostic socket is available on CAPDIS (R5). The

diagnostic socket allows a more detailed examination

of the partial discharge.

In addition, there are mobile PD diagnostic systems

from various suppliers as well as specialized service

providers who can perform advanced PD diagnosis.

Even an oscilloscope diagnosis can determine which

conductoris actually affected and whetherit is anin-

ternal or external discharge or an external disturban-

ce.

External DischargesCorona-Discharges Internal Discharges || | | | | | | | |

General pisturbances| | |||] |]] | ||] [| HALAL TALL

PD-Diagnosis with Scope