influence of floor plenum on energy performance of

20
1 Influence of floor plenum on energy performance of buildings with 1 UFAD systems 2 Yan Xue 1 and Qingyan Chen 2,1* 3 4 1 School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907, USA 5 2 School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China 6 * Tel. (765)496-7562, Fax (765)494-0539, Email: [email protected] 7 8 Abstract 9 10 The heat transfer through the floor slab in buildings with Under-Floor Air Distribution (UFAD) 11 systems may have a negative impact on the energy performance of these buildings, although very 12 few studies have been reported in the literature. By using an energy simulation program, 13 EnergyPlus, this investigation compared the energy use in a Philadelphia office building with a 14 UFAD system to that with a well-mixed ventilation system. When the heat transfer through the 15 floor slab was taken into consideration, the thermal load of the building with the UFAD system 16 was higher than with the well-mixed system. On the other hand, the higher supply air 17 temperature of the UFAD system enables the use of more free-cooling. The annual energy 18 consumption by the chillers in the building with the UFAD system was 16%-27% lower than 19 with the well-mixed system, but energy consumption by the boiler was 12%-30% higher, and the 20 energy consumption by the fan was 22-50% higher, depending on the manner in which the heat 21 was supplied to the floor plenum. When the UFAD system was used with an un-ducted floor 22 plenum and without heating coils under the diffusers, it consumed slightly more energy than the 23 well-mixed system. 24 25 1. Introduction 26 27 Unlike conventional overhead well-mixed systems, UFAD systems provide directly conditioned 28 air to the occupied zone through diffusers in a raised floor, as shown in Figure 1. Thermal 29 buoyancy causes temperature stratification in the occupied zone, and the air temperature in the 30 lower part of the zone is lower than that in the upper part. Therefore, UFAD systems are believed 31 to use less energy for cooling [1,2]. In addition, the thermal stratification in a room with a UFAD 32 system can create better indoor air quality than in a room with a well-mixed air distribution 33 system [3,4]. A UFAD system also allows individual control of airflow rate in order to meet the 34 thermal comfort requirements of different occupants [5,6] and can thus provide a more 35 comfortable environment than overhead well-mixed systems [7]. However, if the air supply and 36 return in the plenums are un-ducted or un-insulated, the air temperature in the floor plenum is 37 very low during the cooling mode, while the ceiling plenum is very warm. The temperature 38 Xue, Y. and Chen, Q. 2014. “Influence of floor plenum on energy performance of buildings with UFAD systems,” Energy and Buildings, 79, 74-83.

Upload: others

Post on 20-Apr-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Influence of floor plenum on energy performance of

Influence of floor plenum on energy performance of buildings with 1 

UFAD systems 2 

Yan Xue1 and Qingyan Chen2,1* 3 

4 1School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907, USA 5 

2School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China 6 *Tel. (765)496-7562, Fax (765)494-0539, Email: [email protected] 

Abstract 9 

10 

The heat transfer through the floor slab in buildings with Under-Floor Air Distribution (UFAD) 11 

systems may have a negative impact on the energy performance of these buildings, although very 12 

few studies have been reported in the literature. By using an energy simulation program, 13 

EnergyPlus, this investigation compared the energy use in a Philadelphia office building with a 14 

UFAD system to that with a well-mixed ventilation system. When the heat transfer through the 15 

floor slab was taken into consideration, the thermal load of the building with the UFAD system 16 

was higher than with the well-mixed system. On the other hand, the higher supply air 17 

temperature of the UFAD system enables the use of more free-cooling. The annual energy 18 

consumption by the chillers in the building with the UFAD system was 16%-27% lower than 19 

with the well-mixed system, but energy consumption by the boiler was 12%-30% higher, and the 20 

energy consumption by the fan was 22-50% higher, depending on the manner in which the heat 21 

was supplied to the floor plenum. When the UFAD system was used with an un-ducted floor 22 

plenum and without heating coils under the diffusers, it consumed slightly more energy than the 23 

well-mixed system. 24 

25 

1. Introduction 26 

27 

Unlike conventional overhead well-mixed systems, UFAD systems provide directly conditioned 28 

air to the occupied zone through diffusers in a raised floor, as shown in Figure 1. Thermal 29 

buoyancy causes temperature stratification in the occupied zone, and the air temperature in the 30 

lower part of the zone is lower than that in the upper part. Therefore, UFAD systems are believed 31 

to use less energy for cooling [1,2]. In addition, the thermal stratification in a room with a UFAD 32 

system can create better indoor air quality than in a room with a well-mixed air distribution 33 

system [3,4]. A UFAD system also allows individual control of airflow rate in order to meet the 34 

thermal comfort requirements of different occupants [5,6] and can thus provide a more 35 

comfortable environment than overhead well-mixed systems [7]. However, if the air supply and 36 

return in the plenums are un-ducted or un-insulated, the air temperature in the floor plenum is 37 

very low during the cooling mode, while the ceiling plenum is very warm. The temperature 38 

Xue, Y. and Chen, Q. 2014. “Influence of floor plenum on energy performance of buildings 

with UFAD systems,” Energy and Buildings, 79, 74-83.

Page 2: Influence of floor plenum on energy performance of

2  

difference between the floor plenum and downstairs ceiling plenum leads to heat transfer across 39 

the floor slab, as shown in Figure 1,which may have an impact on energy use. 40 

41 

Studying the influence of the floor plenum on cooling load and energy use requires that the 42 

energy flow between the occupied zone and the floor plenum also be considered, so do the 43 

thermal stratification in the occupied zone [8]. Many previous researchers have analyzed the 44 

thermal stratification, and various models have been developed to predict the air temperature 45 

stratification in rooms with UFAD systems [9-15]. Air flow and heat transfer in the floor plenum 46 

contribute further complexity to the simulations. Linden [16] determined that there was a 47 

significant air temperature differential and air velocity variation in the floor plenum. These non-48 

uniform air temperature and flow distributions could affect heat transfer in the floor plenum. 49 

50 

In regard to the impact of the floor plenum on the energy performance of a UFAD system, 51 

Bauman et al. [17] found that the heat transfer in the floor plenum can be as high as 30%-40% of 52 

the room cooling load. However, this conclusion was made on the basis of a simplified first-law 53 

model that may not be accurate. Schiavon et al. [8] indicated that the presence of a raised floor 54 

changed the cooling load profile greatly, and the peak cooling load could vary in the range of −7 55 

to + 40% as compared to the load without the raised floor. However, their study did not address 56 

heating. Lee et al. [18] simulated a three-floor office building with a UFAD system on two 57 

design days: a summer day and a winter day. They found that thermal decay in the floor plenum 58 

could result in a higher supply airflow rate and greater use of energy by the fans and chiller. 59 

However, the non-uniform flow in the floor plenum was not taken into account in their study. 60 

The current investigation systematically studied the influence of heat transfer through a floor 61 

slab on the energy performance of an office building with a UFAD system. The objective was to 62 

accurately simulate the thermal load and energy use as influenced by the floor plenum and to 63 

assess the impact of non-uniform flow in the floor plenum on energy modeling. 64 

65 

2. Method 66 

67 

2.1. Load and energy simulations for an office building 68 

69 

To accurately study the impact of the floor plenum on energy performance, this investigation 70 

used EnergyPlus [19] as the main tool with the implementation of a room air stratification model. 71 

To simplify the study, this investigation simulated a typical middle floor, Floor N, in a multi-72 

floor building, as shown in Figure 2, rather than an entire building. Accurate simulations must 73 

take into account (1) the vertical air temperature stratification in the room air and (2) the non-74 

uniform air distribution in the floor plenum. 75 

76 

Page 3: Influence of floor plenum on energy performance of

3  

2.2. Vertical air temperature stratification in the simulated room 77 

78 

Because the EnergyPlus program did not calculate the room air distribution, the air temperature 79 

model from Lin et al. [12], implemented into the program by Liu et al. [20], was applied to 80 

calculate the vertical air temperature profiles in the room. The model predicts the vertical 81 

temperature profiles by simulating the buoyancy plumes from internal heat sources and the jets 82 

from air supply diffusers. The buoyancy plumes generate the air stratification and the jets lead to 83 

air mixing. 84 

85 

2.3. Non-uniform air distribution in the floor plenum 86 

87 

Along with the air temperature stratification in the room, non-uniform air velocity and air 88 

temperature in the floor plenum also contribute additional complexity to the simulation[16]. To 89 

simulate the non-uniform flow in the floor plenum, Computational Fluid Dynamics (CFD) can be 90 

used in combination with the energy calculation [21,22], but doing so is too computationally 91 

demanding. Instead, this investigation used a multizone model [23] to simulate the non-uniform 92 

air distribution in the floor plenum for coupling with EnergyPlus. The floor plenum was divided 93 

into several subzones according to the temperature distribution determined by CFD simulation. 94 

The air velocity and temperature differences among these subzones represented the non-uniform 95 

air temperature in the floor plenum. The simulation results of the multizone model were then 96 

compared to a single zone model in which the floor plenum had uniform air distribution. The 97 

difference between them could indicate the impact of the non-uniform air distribution on the 98 

energy modeling. 99 

100 

2.4. Validation of the computer models 101 

102 

The computer models described above use a number of approximations, and coupling them with 103 

EnergyPlus can lead to additional errors. The models needed to be validated before they could be 104 

used to simulate the cooling load and energy use in the building. This investigation used an 105 

environmental chamber as shown in Figure 3 to measure the air and surface temperatures in the 106 

floor plenum and the surface temperatures in the room. 107 

108 

This chamber had dimensions of 4.80 m in length, 4.20 m in width, and 2.73 m in height, 109 

including a floor plenum with a height of 0.30 m. The room contained several pieces of furniture, 110 

lighting fixtures, and heated boxes that were used to simulate internal loads such as electrical 111 

appliances, occupants, etc. The supply air duct was connected to the floor plenum, and two linear 112 

grille diffusers were installed in the floor. The walls and ceiling were well insulated with a 113 

thermal resistance of 5.45 m2-K/W. The raised floor panels were made of 0.1 m thick lightweight 114 

concrete with a thermal resistance of 0.16 m2-K/W. A double-glazed window with dimensions of 115 

Page 4: Influence of floor plenum on energy performance of

4  

4.65 m in width and 1.55 m in height and a thermal resistance of 0.25 m2-K/W was installed in 116 

the east wall of the chamber. Table 1 shows the power levels of the internal heat sources. 117 

 118 

Eight anemometers were placed in the middle of the floor plenum (0.15 m from the slab) for 119 

measuring air temperature and velocity in the plenum. Temperatures of the different surfaces of 120 

the floor plenum and room were measured by a number of T-type thermocouples. The 121 

experiment was conducted under steady-state conditions in summer. The inlet temperature was 122 

17.3°C, and the air change rate was 6 ACH. 123 

124 

3. Validation of the computer models and case setup 125 

126 

3.1. Validation of the computer models 127 

128 

The CFD simulations for this investigation were performed for the floor plenum using a 129 

commercial software program FLUENT [24]. The CFD results provided greater understanding of 130 

the temperature distribution in the floor plenum, which was the basis of the multizone model. 131 

Figures 4 and 5 show the air velocity and temperature profiles, respectively, in two sections of 132 

the floor plenum. The air supply was located on the bottom wall under Position 7, as shown in 133 

Figure 6, and therefore Positions 3 and 7 were located in the jet region. As a result, the air 134 

velocities measured at these positions were high, and the air temperatures were low. The 135 

agreement between the CFD results and experimental data for air velocity and temperature is 136 

quite good. Figure 6 shows a non-uniform air temperature distribution in the floor plenum. 137 

138 

Our EnergyPlus simulation divided the floor plenum into three subzones, as shown in Figure 6, 139 

for studying the impact of the non-uniform air temperature distribution on the load. Figure 5 140 

depicts the air temperature profiles calculated with the multizone model in the two sections of 141 

the floor plenum, and again they are in good agreement with the measured data. The results 142 

shown in Figures 5 and 6 have validated the computer models for calculating air temperature in 143 

the floor plenum. 144 

145 

Table 2 further compares the air temperature from the diffusers, air temperature at the exhaust, 146 

and EnergyPlus-simulated surface temperatures with the measured data. The columns of "Error" 147 

show the percentage difference between the experimental measurements and simulation results. 148 

Once again, agreement between the simulations and measurements is quite good. Therefore, the 149 

EnergyPlus program with the multizone air models can be used to predict thermal load and 150 

energy use in buildings. In addition, Table 2 shows the results obtained by EnergyPlus with the 151 

assumption of uniform air temperature in the floor plenum (one subzone). The air temperature 152 

with one subzone differed by only 0.5 K from that with three subzones, which was insignificant, 153 

although the air temperature between zones can differ by 2 K, as shown in Figure 6. Thus, the 154 

Page 5: Influence of floor plenum on energy performance of

5  

impact of the non-uniform air distribution in the floor plenum on the energy simulation was very 155 

limited and our subsequent simulations used only one zone for the floor plenum. 156 

157 

3.2. Case description for a building with UFAD systems in Philadelphia 158 

159 

Using the validated EnergyPlus model, this investigation conducted energy simulations for a 160 

mid-level floor of a multi-floor office building in Philadelphia. An office area with dimensions 161 

of 30 m 40 m 3.7 m, as shown Figure 7, was divided into five thermal zones: a central zone 162 

and four perimeter zones, because solar radiation would have a significant impact on the 163 

perimeter zones. The perimeter zones had a width of 5.0 m [25]. The construction and material 164 

information for the building envelope were taken from the default data for Chicago in 165 

EnergyPlus Version 7. Figure 8 shows the internal load profiles for weekdays and Saturdays. 166 

This study further assumed that the building was completely closed on Sundays, without an 167 

internal heat load. 168 

169 

This investigation simulated three different scenarios for the office building, as shown in Figure 170 

9: a well-mixed ventilation system, a UFAD system without heating coils in the diffusers, and a 171 

UFAD system with heating coils in the diffusers [26]. For each of the two UFAD scenarios, three 172 

cases were simulated with different floor plenum configurations: completely ducted floor 173 

plenums; partially ducted floor plenums (ducted floor plenums in the perimeter zones and an un-174 

ducted core zone); and completely un-ducted floor plenums. The arrangement led to a total of 175 

seven simulation cases, as shown in Table 3. All of the cases used the same HVAC system, 176 

which incorporated an electric chiller and a gas boiler. The system used variable-air-volume 177 

control and an economizer. The thermostat in the occupied zone was set at 21°C during the 178 

winter and 24°C during the summer. The minimum fresh air rate was 0.3 L/(s·m2), in accordance 179 

with ASHRAE Standard 62.1-2010 for indoor air quality [27]. For mixed ventilation, the supply 180 

air temperature was 13°C for cooling and 32°C for heating [28]. In the UFAD system without 181 

heating coils in the diffusers, the supply air temperature was 17°C [1,29] for cooling and 32°C 182 

for heating. In the UFAD system with heating coils, the air supply temperature from the HVAC 183 

system was 17oC all year round. When heating was called for, the air was heated to 32°C by the 184 

heating coils. The HVAC system operated from 6:00 to 22:00. 185 

186 

4. Results 187 

188 

In order to explain the effects of the heat transfer through slabs on the energy performance of 189 

buildings, this section will show the heat flux profiles across slabs and analyze their influence on 190 

the thermal loads. Then the year-round energy consumption results will be reported. 191 

192 

Page 6: Influence of floor plenum on energy performance of

6  

4.1. Thermal load simulations for the building 193 

194 

Figure 10 shows the heat flux at the two surfaces of the floor slab in the office building on July 195 

21, the summer design day in EnergyPlus. The sum of the heat transfer at the two surfaces is 196 

equal to the thermal storage in the slab. For cooling, the heating coils in the diffusers were not 197 

activated, and thus the two UFAD scenarios were identical. For the well-mixed system, from 198 

8:00 to16:00, heat was transferred from the occupied zone to the slab, as shown in Case 1 of 199 

Figure 10(a, b). In the perimeter zones as shown in Figure 10(a), this heat transfer was caused by 200 

the high level of radiation from the direct sunlight on the floor slab and the internal heat sources, 201 

With the UFAD systems, however, the radiation from the sun and the internal load had no direct 202 

impact on the slab. Thus, the heat transfer profiles in these cases were very different from those 203 

with the well-mixed system. In the thermal zones with ducted floor plenums, there was a small 204 

amount of heat transfer across the floor slabs. As for the un-ducted UFAD systems, cool air was 205 

supplied to the floor plenum, and the downstairs ceiling plenum was warm. The significant 206 

temperature difference between the two sides of the floor slab led to a high heat transfer rate 207 

from the downstairs ceiling plenum to the floor slab and further to the floor plenum. In the well-208 

mixed system, from 6:00 to 8:00 and 18:00 to 22:00, when the internal load and solar radiation 209 

were small, heat was transferred from the floor slab to the room air as a result of the high floor 210 

slab temperature. In the UFAD system, however, the total air supply was lower during these two 211 

periods than during the occupied hours, and thus the heat transfer from the floor plenum to the 212 

slab was smaller. 213 

214 

Despite the drastic difference in heat transfer profiles between the well-mixed ventilation and 215 

UFAD, the cooling loads of these systems had similar shapes on the summer design day, as 216 

shown in Figure 11.  217 

218 

For the winter heating, the heat transfer between the well-mixed system and UFAD system could 219 

be different but the heating load is also very similar as shown in the cooling scenario. Due to 220 

limited space in this paper, the detailed results are not presented here. 221 

222 

4.2. Annual energy consumptions of the building 223 

224 

Figures 12 and 13 illustrate the monthly energy consumption by the chiller and boiler, 225 

respectively, in the HVAC system in year-round simulations. With the well-mixed ventilation 226 

system, more energy was used by the chiller, especially during the shoulder seasons when the 227 

outdoor air temperature was suitable for free-cooling. In the two UFAD scenarios, the levels of 228 

electricity consumption by the chillers were almost identical. They were lower than that in the 229 

well-mixed system by 27% for the ducted cases (Cases 2 and 5), 23% for the partially ducted 230 

cases (Cases 3 and 6), and 16% for the un-ducted cases (Cases 4 and 7). The percentage numbers 231 

are based on the UFAD systems. However, the natural gas consumption levels by the boiler with 232 

Page 7: Influence of floor plenum on energy performance of

7  

the UFAD systems were higher than that with the well-mixed system. Without heating coils 233 

under the diffusers, the boiler energy consumption in the UFAD system was higher than that in 234 

the well-mixed system by 18% in the completely ducted case (Case 2), 21% in the partially 235 

ducted case (Case 3), and 30% in the un-ducted case (Case 4). When there were heating coils 236 

under the diffusers, the boiler energy consumption in the UFAD system was higher than that in 237 

the well-mixed system by 12% in the completely ducted case (Case 5) and by 18% in the 238 

partially ducted (Case 6) and the un-ducted (Case 7) cases.  239 

240 

The levels of electricity consumption by the fans in the building’s HVAC system were 22-50% 241 

higher with the UFAD systems than with the well-mixed system by using the energy use of the 242 

UFAD system as the reference, as shown in Figure 14. This difference occurred because the 243 

supply air temperature in the UFAD systems was higher than that in the well-mixed ventilation 244 

system, and a higher airflow rate is required in order to remove the same amount of heat. 245 

246 

A comparison of the different cases indicates that the ducting of floor plenums can reduce energy 247 

consumption by the chiller and the boiler, and that this effect is more significant in perimeter 248 

zones. Furthermore, during the heating mode, supplying warm air directly to the floor plenum 249 

without ducts is not recommended because heat flow in the plenum would cause significant 250 

energy loss. In addition to ducting of the floor plenums, the use of heating coils under the 251 

diffusers is recommended in order to reduce energy use by the boiler. 252 

253 

Using the energy consumption data, this investigation conducted a cost analysis for these cases 254 

with EnergyPlus. Table 4 shows the monthly price of natural gas [30]. The cost of electricity [30] 255 

was calculated using the block method shown in Table 5. The tax rate was 8%, and the monthly 256 

service fee for electricity was $8.81. Table 6 shows the annual electricity costs for the chiller and 257 

fans and the gas costs for the boiler. For the same building, the use of electricity by lights and 258 

electrical equipment was exactly the same with either the well-mixed ventilation or UFAD. 259 

Variations in energy consumption arose from the HVAC systems. 260 

261 

Because only the perimeter zones of the building required heating and natural gas was much 262 

cheaper than electricity, the gas costs for the boiler were much lower than the electricity costs for 263 

the chiller. As discussed above, energy consumption by the chiller was greater with the well-264 

mixed system than with the UFAD systems. Therefore, as shown in Table 6, chiller operation 265 

was more expensive in the well-mixed case (Case 1) than in the UFAD cases (Cases 2-6). 266 

Among the UFAD cases, those with un-ducted floor plenums (Cases 4 and 7) had higher 267 

electricity costs than the other cases. However, the addition of heating coils under the diffusers 268 

did not contribute significantly to the electricity costs. 269 

270 

Although chiller operation was cheaper in the UFAD cases, both the gas costs for the boiler and 271 

the electricity costs for the fan were higher with the UFAD systems than with the well-mixed 272 

Page 8: Influence of floor plenum on energy performance of

8  

system. These higher costs are consistent with the energy consumption levels shown in Figures 273 

13 and 14. In the UFAD cases, the addition of heating coils under the diffusers (Cases 5-7) 274 

reduced the gas cost for the boiler, especially in the cases with un-ducted floor plenums. The 275 

total energy cost for a building with a UFAD system could be lower than that with a well-mixed 276 

system if the floor plenum was ducted. Unfortunately, ducting of the floor plenum is not a 277 

common practice at present. 278 

279 

5. Conclusions 280 

281 

Using validated computer models, this investigation assessed the energy performance of a 282 

building in Philadelphia with several different UFAD systems and with a well-mixed ventilation 283 

system. The study led to the following major findings: 284 

The airflow and air temperature distribution in the floor plenum can be highly non-285 

uniform. The non-uniform air temperature distribution can be calculated with the use of a 286 

simple subzone model. By comparing the supply air temperature, exhaust air temperature, 287 

and enclosure surface temperatures between the multizone model and the single zone 288 

model, this study found that the impact of the non-uniform air temperature distribution on 289 

the energy modeling is small. 290 

In cooling situations, the temperature difference between the cold air in the floor plenum 291 

and the warm air in the downstairs ceiling plenum can result in significant heat transfer 292 

through the floor slab in a building with a UFAD system. This heat transfer leads to a 293 

slightly higher cooling load than with a well-mixed ventilation system. 294 

In heating situations, when a UFAD system is used in the building without heating coils 295 

in the air supply diffusers, the presence of warm air in the floor plenum can lead to a 296 

higher heating load than that with the well-mixed ventilation system. This increased heat 297 

load is again attributed to heat transfer from the plenum air to the floor slab. 298 

By conducting an annual energy analysis for the building, this investigation found that 299 

the chiller used 16%-27% less energy with the UFAD systems than with the well-mixed 300 

system because of the use of free cooling during the shoulder seasons. However, the 301 

boiler consumed 18%-30% more energy with the UFAD systems because of heat loss in 302 

the floor plenum. The use of heating coils in the air supply diffusers and/or the utilization 303 

of ducts for supplying air to the floor plenum can reduce energy use by the boiler. Finally, 304 

because the UFAD systems had a higher supply air temperature for cooling, the total 305 

supply airflow rate was higher than that with the well-mixed ventilation system. As a 306 

result, energy consumption by the fans in the UFAD systems was 22-50% higher. 307 

The total energy cost for a UFAD system with un-ducted floor plenums and without 308 

heating coils under the diffusers could be slightly higher than that for a well-mixed 309 

system. Either ducting the floor plenums or using the heating coils under the diffusers 310 

would reduce the energy cost. However, ducting the floor plenums would increase the 311 

Page 9: Influence of floor plenum on energy performance of

9  

initial investment and maintenance costs. Therefore, although the UFAD system with 312 

completely ducted floor plenums and with heating coils (Case 5) had the lowest energy 313 

costs, the partially ducted UFAD system with heating coils (Case 6) would be the most 314 

favorable one. 315 

316 

Acknowledgement 317 

318 

This research was funded partially by the Energy Efficient Building Hub led by the Pennsylvania 319 

State University and funded by the U.S. Department of Energy and other government agencies, 320 

where Purdue University was a subcontractor to the grant. 321 

322 

References 323 

324 

[1] F. Bauman, T. Webster, Outlook for Underfloor Air Distribution, ASHRAE Journal 43 (6) 325 

(2001) 18-27. 326 

[2] Y. Cheng, J. Niu, X. Liu, N. Gao, Experimental and Numerical Investigations on Stratified 327 

Air Distribution Systems with Special Configurations: Thermal Comfort and Energy Saving, 328 

Energy and Buildings 64 (2013) 154-161. 329 

[3] D. Faulkner, W.J. Fisk, D.P. Sullivan, Indoor Airflow and Pollutant Removal in a Room 330 

with Floor-Based Task Ventilation: Results of Additional Experiments, Building and 331 

Environment 30(3)(1995) 323-332. 332 

[4] C. Shen, N. Gao, T. Wang, CFD Study on the Transmission of Indoor Pollutants under 333 

Personalized Ventilation, Building and Environment 63 (2013) 69-78. 334 

[5] E.A. Arens, F.S. Bauman, L.P. Johnston, H. Zhang, Testing of Localized Ventilation 335 

Systems in a New Controlled Environment Chamber, Indoor Air 3 (1991) 263-281. 336 

[6] A. Hedge, A.T. Michael, S.L. Parmelee, Reactions of Office Workers and Facilities 337 

Managers to Underfloor Task Ventilation in Offices, Journal of Architectural and Planning 338 

Research 10(3) (1993) 203-218. 339 

[7] G. Kim, L. Schaefer, T.S. Lim, J.T. Kim, Thermal Comfort Prediction of an Underfloor Air 340 

Distribution System in a Large Indoor Environment, Energy and Buildings 64 (2013) 323-341 

331. 342 

[8] S. Schiavon, K.H. Lee, F. Bauman, T. Webster, Influence of Raised Floor on Zone Design 343 

Cooling Load in Commercial Buildings, Energy and Buildings 42 (2010) 1182-1191. 344 

[9] H. Ito, N. Nakahara, Simplified Calculation Model of Room Air Temperature Profile in 345 

Under-Floor Air-Conditioning System, Society of Heating, Air Conditioning and Sanitary 346 

Engineers of Japan, proceedings of the International Symposium on Room Air Convection 347 

and Ventilation Effectiveness (ISRACVE), held at the University of Tokyo(1992) 183-188. 348 

[10] J. Lau, Q. Chen, Floor-Supply Displacement Ventilation for Workshops, Building and 349 

Environment 42 (2007) 1718-1730. 350 

[11] K.S. Lee, Air Distribution Effectiveness and Thermal Stratification with Stratified Air 351 

Distribution Systems, Ph.D. thesis, Purdue University, West Lafayette, 2011. 352 

[12] Y.J.P. Lin, P.F Linden, A Model for an Under Floor Air Distribution System, Energy and 353 

Buildings 37 (2005) 399-409. 354 

Page 10: Influence of floor plenum on energy performance of

10  

[13] Q.A. Liu, P.F. Linden, The Fluid Dynamics of an Underfloor Air Distribution System, J. 355 

Fluid Mech 554 (2006) 323-341, Cambridge University Press, United Kingdom. 356 

[14] Q. Kong, B. Yu, Numerical Study on Temperature Stratification in a Room with Underfloor 357 

Air Distribution System, Energy and Buildings 40 (2008) 495-502. 358 

[15] G. Xue, K. Lee, Z. Jiang, Q. Chen, Q., Thermal Environment in Indoor Spaces with Under-359 

Floor Air Distribution Systems: Part 2. Determination of Design Parameters (1522-RP), 360 

HVAC&R Research 18:6 (2012) 1192-1201. 361 

[16] P.F. Linden, I. Kanda, D. Yamaguchi, Flow in an Underfloor Plenum, 2004 IBPSA-USA 362 

National Conference, Boulder, CO. 363 

[17] F. Bauman, H. Jin, T. Webster, Heat Transfer Pathways in Underfloor Air Distribution 364 

(UFAD) Systems, ASHRAE Transaction 112 (2006) Part 2. 365 

[18] K.H. Lee, S.Schiavon, F. Bauman, T. Webster, Thermal Decay in Underfloor Air 366 

Distribution (UFAD) Systems: Fundamentals and Influence on System Performance, 367 

Applied Energy 91 (2012) 197-207. 368 

[19] EnergyPlus, EnergyPlus Engineering Reference, University of Illinois and Ernest Orlando 369 

Lawrence Berkeley National Laboratory, 2012. 370 

[20] Q.A. Liu, P.F. Linden, The EnergyPlus UFAD Module, Third National Conference of 371 

IBPSA-USA, Berkeley, California, 2008. 372 

[21] Z. Zhai, Q. Chen, Numerical Determination and Treatment of Convective Heat Transfer 373 

Coefficient in the Coupled Building Energy and CFD Simulation, Building and 374 

Environment 36(8) (2004) 1000-1009. 375 

[22] H. Xu, J. Niu, Numerical Procedure for Predicting Annual Energy Consumption of the 376 

Under-Floor Air Distribution System, Energy and Buildings 38 (2006) 641-647. 377 

[23] G.N. Walton, Thermal Analysis Research Program Reference Manual, NBSSIR 83-2655, 378 

National Bureau of Standards, 1983. 379 

[24] FLUENT 6.3 Documentation, ANSYS Fluent Inc., Lebanon, NH, 2005. 380 

[25] O.T. Karaguzel, K.P. Lam, Development of Whole-Building Energy Performance Models 381 

as Benchmarks for Retrofit Projects, 2011 Winter Simulation Conference. 382 

[26] CBE, http://cbe.berkeley.edu/underfloorair/techoverview.htm (accessed Jan. 2014). 383 

[27] ASHRAE Standard 62.1-2010, Ventilation for Acceptable Indoor Air Quality, American 384 

Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA. 385 

[28] E.C. Montanya, Performance of Underfloor Air Distribution Systems. Temperature 386 

Stratification and Ventilation Effectiveness in the Child Development Centre, Master’s 387 

thesis, University of Calgary, Alberta, Canada, 2009. 388 

[29] K.H. Lee, Supply Air Temperature Impact in Underfloor Air Distribution Systems under 389 

Korean Climate Conditions: Energy, Humidity and Comfort, Energy and Buildings 58 390 

(2013) 363-371. 391 

[30] EnergyPlus Example File Generator, National Renewable Energy Laboratory (NREL), 2012. 392 

 393 

394 

Page 11: Influence of floor plenum on energy performance of

11  

Table 1.Power inputs of the lights and heated boxes. 395 

Number Power [W]

Lighting

1 43.0 2 44.0 3 26.5 4 43.5

Heated boxes for manikins 1 93.3 2 84.0

Heated boxes for equipment 1 65.0 2 65.0 3 65.0

396 

Table 2.Comparison of simulated and measured temperatures for the environmental chamber. 397 

Locations

Experimental measurements

E+ simulation with1-zone floor plenum

(uniform air temperature)

E+ simulation with 3-zone floor plenum (non-uniform air

temperature)

℃ ℃ Error (%) ℃ Error (%) Air at the diffusers 20.2 19.9 1.5 20.4 1.0 Air at the exhaust 24.2 24.4 0.8 24.2 0.0 Slab surface (facing floor plenum)

23.7 23.6 0.4 23.6 0.4

Ceiling surface 24.3 24.7 1.6 25.4 4.5 North wall of floor plenum 23.8 22.7 4.6 23.7 0.4 South wall of floor plenum 22.7 22.7 0.0 23.0 1.3 West wall of floor plenum 23.5 22.7 3.4 23.0 2.0 East wall of floor plenum 22.7 22.7 0.0 23.0 1.3 North wall of room 25.1 25.2 0.4 25.5 1.6 South wall of room 24.1 25.2 4.6 25.5 5.8 West wall of room 24.7 25.2 2.0 26.4 6.9 East wall of room 25.4 25.2 0.8 25.5 0.4

398 

Table 3.Simulated cases. 399 

Case Ventilation system Floor plenum configuration

Heating coils under diffusers

1 Well-mixed N/A N/A 2 UFAD Completely ducted No

3 UFAD Ducted perimeter zones

Un-ducted core zone No

4 UFAD Completely un-ducted No 5 UFAD Completely ducted Yes

6 UFAD Ducted perimeter zones

Un-ducted core zone Yes

7 UFAD Completely un-ducted Yes 400 

Page 12: Influence of floor plenum on energy performance of

12  

Table 4. Monthly natural gas price (unit: $/kWh). 401 

Jan Feb Mar Apr May Jun

0.344 0.343 0.343 0.346 0.371 0.400

Jul Aug Sep Oct Nov Dec

0.391 0.386 0.376 0.375 0.322 0.331

402 

Table 5.Electricity price (unit: $/kWh). 403 

Summer (Jun – Sep)and Winter (Oct - May) Charge Energy [$/kWh] Transition [$/kWh] Distribution [$/kWh]

< 80 hrs. 0.1088 0.0669 0.0344 80-160 hrs. Summer: 0.0592

Winter: 0.0428 Summer:0.0319 Winter: 0.0205

Summer:0.0162 Winter: 0.0103

160-400 hrs. 0.0428 0.0205 0.0103 > 400 hrs. 0.0275 0.0095 0.0046

404 

Table 6. Annual energy cost for the whole building in different cases. 405 

Case Electricity cost for the chiller

($)

Electricity cost for the fans

($)

Gas cost for the boiler

($)

Total cost as a percentage of Case 1

(%) 1 4275 369 244 100.0 2 3425 481 300 86.1 3 3553 660 320 92.7 4 3797 756 372 100.7 5 3424 481 274 85.7 6 3553 659 290 92.4 7 3814 744 297 99.6

406 

Page 13: Influence of floor plenum on energy performance of

13  

407 

408 

409 

410 

411 

412 

413 

414 

415 

416 

417 

Figure 1.Schematics of well-mixed (left) and UFAD (right) systems. 418 

419 

420 

421 

422 

423 

424 

425 

426 

427 

428 

429 

430 

431 

432 

433 

434 

435 

436 

Figure 2. Floor N in a multi-floor building with a UFAD system. 437 

 438 

439 

 

Floor plenum

Heat transfer 

 

Troom= Tplenum

Ceiling plenum

Occupied zone

Ceiling plenum

Floor slab

 

    

 

Floor plenum

Room

Return plenum

Floor plenum

Room

Floor plenum

Return plenum

Page 14: Influence of floor plenum on energy performance of

14  

1 2 3 4

5 6 7 8

0.00

0.40

0.80

1.20

1.60

0 1 2 3 4 5

U[m/s]

x[m]

Experiment Simulation

0.00

0.40

0.80

1.20

1.60

0 1 2 3 4 5

U[m/s]

x[m]

Experiment Simulation

440 

Figure 3.Schematic of the environmental chamber. 441 

442 

443 

444 

445 

446 

447 

448 

449 

450 

451 

452 

453 

454 

Figure 4. Comparison of CFD results with experimental data for air velocity in two sections of 455 

the floor plenum (horizontal cross-section of the plenum at 0.15m above the floor). 456 

457 

ExhaustLights 

Heated boxes 

for manikin and 

equipment 

Diffusers

Conditioned air inlet

Floor plenum

Desk

Room

North 

1 2

3

4

5 6

7

8 x

y

Page 15: Influence of floor plenum on energy performance of

15  

458 

Figure 5. Comparison of measured air temperature with that computed by CFD and by the 459 

multizone model in two sections of the floor plenum 460 

461 

462 Figure 6.Air temperature distribution at 0.15m above the floor slab as simulated by CFD, and 463 

division of the plenum into three subzones. 464 

465 

17

18

19

20

21

22

23

24

25

0 1 2 3 4 5

T[ ]

x[m]

CFD Experiment E+ (three subzones)

17

18

19

20

21

22

23

24

25

0 1 2 3 4 5

T[ ]

x[m]

Experiment CFD E+ (three subzones)

(K)

Page 16: Influence of floor plenum on energy performance of

16  

466 

467 

468 

469 

470 

471 

(a). Top view of thermal zone layout. 472 

473 

474 

475 

476 

477 

(b). Side view of thermal zone layout. 478 

Figure 7.Medium-sized office building in Philadelphia. 479 

480 

481 

482 

Figure 8.Internal heat load of the office building on weekdays (left) and Saturdays (right). 483 

484 

0

2

4

6

8

10

12

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

W/m2

Time/h

Internal heat on weekdaysElectric Lights Occupancy

0

1

2

3

4

5

6

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

W/m2

Time/h

Internal heat on SaturdaysElectric Lights Occupancy

Ceiling Plenum

Floor Plenum

Room

0.4m

3.0m

0.3m

N

W

S

E

40.0m

30.0m

5.0m

Central Zone

5.0m

5.0m

5.0m

Ceiling Plenum

Room

0.7m

3.0m

Page 17: Influence of floor plenum on energy performance of

17  

485 

486 

487 

488 

489 

490 

491 

492 

493 

494 

495 

(a) (b) (c) 496 

497 

Figure 9. Simulated scenarios: (1) well-mixed ventilation system, (2) UFAD system without 498 

heating coils in the diffusers, and (3) UFAD system with heating coils in the diffusers. 499 

500 

501 

      (a)            (b) 502 

-15

-10

-5

0

5

10

15

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Hea

t flu

x [W

/m2 ]

Time[h]

Perimeter zonesHeat flux from room/floor plenum to slab

1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (ducted perimeter zones)4/7.UFAD (completed un-ducted)

-15

-10

-5

0

5

10

15

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Hea

t flu

x [W

/m2 ]

Time[h]

Core zoneHeat flux from room/floor plenum to slab

1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (un-ducted core zone)4/7.UFAD (completed un-ducted)

 

 

Diffuser  Exhaust 

Supply air

Return air

 

 

 

Diffuser

Exhaust

Supply air

Return air

 

 

 

Diffuser

Exhaust 

Return air

Supply air Heating

coil

Page 18: Influence of floor plenum on energy performance of

18  

503       (c)            (d) 504 

Figure 10. Heat transfer across the floor slab of the office building on the summer design day - a 505 

weekday. Refer to Table 3 for case descriptions. (a) Heat flux from the room/floor plenum to the 506 

floor slab in perimeter zones, (b) Heat flux from the room/floor plenum to the floor slab in the 507 

core zone, (c) Heat flux from the downstairs ceiling plenum to the floor slab in perimeter zones, 508 

and (d) Heat flux from the downstairs ceiling plenum to the floor slab in core zones (right) 509 

510 

511 

512 (a) Perimeter zones (b) Core zone 513 

514 

Figure 11. Cooling loads on the summer design day for the office building with different 515 

ventilation systems. The numbers are for different cases as described in Table 3. 516 

-15

-10

-5

0

5

10

15

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Hea

t flu

x [W

/m2 ]

Time[h]

Perimeter zonesHeat flux from ceiling plenum to slab

1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (ducted perimeter zones)4/7.UFAD (completed un-ducted)

-15

-10

-5

0

5

10

15

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Hea

t flu

x [W

/m2 ]

Time[h]

Core zoneHeat flux from ceiling plenum to slab

1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (un-ducted core zone)4/7.UFAD (completed un-ducted)

0

10

20

30

40

50

60

70

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Coo

ling

load

[W

/m2 ]

Time[h]

Perimeter zones_cooling load1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (ducted perimeter zones)4/7.UFAD (completed un-ducted)

0

10

20

30

40

50

60

70

0:00

2:00

4:00

6:00

8:00

10:0

0

12:0

0

14:0

0

16:0

0

18:0

0

20:0

0

22:0

0

Coo

ling

load

[W

/m2 ]

Time[h]

Core zone_cooling load1.Well-mixed2/5.UFAD (completed ducted)3/6.UFAD (un-ducted core zone)4/7.UFAD (completed un-ducted)

Page 19: Influence of floor plenum on energy performance of

19  

517 

  518 

Figure 12.Monthly energy consumption by the chiller in the building’s HVAC system.The 519 

numbers are for different cases as described in Table 3. 520 

521 

522 Figure 13.Monthly energy consumption by the boiler in the building’s HVAC system. The 523 

numbers are for different cases as described in Table 3. 524 

 525 

526 

0

1000

2000

3000

4000

5000

6000

7000

8000

1 2 3 4 5 6 7 8 9 10 11 12

Ele

ctri

c C

onsu

mpt

ion

[kW

h]

Month

Chiller energy consumptionNo heating coils in diffusers

1.Well-mixed2.UFAD (completed ducted)3.UFAD (partially ducted)4.UFAD (completed un-ducted)

0

1000

2000

3000

4000

5000

6000

7000

8000

1 2 3 4 5 6 7 8 9 10 11 12

Ele

ctri

c C

onsu

mpt

ion

[kW

h]Month

Chiller energy consumptionWith heating coils in diffusers

1.Well-mixed5.UFAD (completed ducted)6.UFAD (partially ducted)7.UFAD (completed un-ducted)

0

500

1000

1500

2000

2500

3000

3500

4000

1 2 3 4 5 6 7 8 9 10 11 12

Gas

Con

sum

ptio

n [k

Wh]

Month

Boiler energy consumptionNo heating coils in diffusers

1.Well-mixed2.UFAD (completed ducted)3.UFAD (partially ducted)4.UFAD (completed un-ducted)

0

500

1000

1500

2000

2500

3000

3500

4000

1 2 3 4 5 6 7 8 9 10 11 12

Gas

Con

sum

ptio

n [k

Wh]

Month

Boiler energy consumptionWith heating coils in diffusers

1.Well-mixed5.UFAD (completed ducted)6.UFAD (partially ducted)7.UFAD (completed un-ducted)

Page 20: Influence of floor plenum on energy performance of

20  

527 Figure 14.Monthly energy consumption by the fans in the building’s HVAC system.The numbers 528 

are for different cases as described in Table 3. 529 

 530 

0

100

200

300

400

500

600

700

800

1 2 3 4 5 6 7 8 9 10 11 12

Ele

ctri

c C

onsu

mpt

ion

[kW

h]

Month

Fan energy consumptionNo heating coils in diffusers

1.Well-mixed2.UFAD (completed ducted)3.UFAD (partially ducted)4.UFAD (completed un-ducted)

0

100

200

300

400

500

600

700

800

1 2 3 4 5 6 7 8 9 10 11 12

Ele

ctri

c C

onsu

mpt

ion

[kW

h]

Month

Fan energy consumptionWith heating coils in diffusers

1.Well-mixed5.UFAD (completed ducted)6.UFAD (partially ducted)7.UFAD (completed un-ducted)