industrial firefighting pool (ibp) ing. raymond bras special projects, unified industrial &...
TRANSCRIPT
![Page 1: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/1.jpg)
Industrial Firefighting Pool (IBP)
Ing. Raymond Bras
Special Projects, Unified Industrial & Harbour Fire Department
![Page 2: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/2.jpg)
Startings points
Decisive fire scenario’s:? “Largest possible tank surface” ?? “Largest possible tank surface” ?
Defined as:• Largest tank (mineral: d = 89 m; h = 22 m)• Largest tank (polar : d = 65 m; h = 30 m)
Existing equipment Unified Industrial & Harbour Fire Department insufficient:
Maximum capacity 3 industrial fire trucks + 3 large monitors insufficient: 45 meter diam. (18.000 l/min)
![Page 3: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/3.jpg)
Analysis
Mobile FiFi system with a capacity of:
• Mobile – large surface (NFPA 11): 10,4 liter/m2/min
• Mineral: 89 m 6221 m2 65 m3/minuut• Polar: 65 m 3318 m2 35 m3/minuut• Concentrate ind.: (3%) 2 m3/min 120 m3 (3%) +
100% spare
• Distance: 115 m to centre of tank at 22 m height • Transportation length: max. 1500 m from waterside
• And employable within 4 hours
![Page 4: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/4.jpg)
Finances
• Who?18 companys (by regulations of
environmental agency) Volunteers
• How?By membershipsThree types: A, B of C
A = Only foam concentrate
B = A + monitors (Fifi-units)
C = Total system
![Page 5: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/5.jpg)
Which companies
MOT
Neref
co E
uropoort
Shell E
uropoort
TEAM
KPE
Exxon R
OP
MET
VOPAK Euro
poort
VOPAK Chem
iehav
en
VOPAK TTR
ESSO
VOPAK Botle
k
Exxon R
AP
LBC
Odfjell
Shell S
NC
Shell S
NRNer
efco
Per
nis
![Page 6: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/6.jpg)
IBP
• Equipement– 3 Hoseretrievers– 1 Manifold-unit– 2 FiFi-units– 1 Hose-unit– 6 trailer with foam concentrate 20 m3
– 4 (5) quick foam concentrate containers 10 m3
• Organisation
![Page 7: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/7.jpg)
Hoseretriever
• 1.5 km transport length.
• 8 * 8” hoses at once.
![Page 8: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/8.jpg)
![Page 9: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/9.jpg)
Manifold-unit• Anchor point• T-junction• 24 connections for 8`` hoses
![Page 10: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/10.jpg)
• 2 units• 37.500 l/min per unit• Throw:115 meter
at 22 meter height
FiFi-unit
![Page 11: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/11.jpg)
Hose-unit
• Reels with ‘short’ hoses (10,15, 25, 40 en 50 meter)
• Barrows
![Page 12: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/12.jpg)
Foam concentrate trailers
• 6 trailers• 20 m3 foam concentrate• Moussol APS 3/3
![Page 13: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/13.jpg)
4 quick response containers
• 10 m3 foam concentrate• Moussol APS 3/3
![Page 14: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/14.jpg)
RPA
RPA
Ponton
Manifold
Foam concentrate
FiFi-unit
![Page 15: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/15.jpg)
Organisation
• Testresults very important for:– Pre-planning– Procedures– Education and training
• Logistics:– Agreement with transport company– Preparing special trucks– Maintenance– Smart storage
![Page 16: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/16.jpg)
Foam concentrate
• Tests to determine if our standard foam concentrate is usable;
• Method: Like Lastfire suited for IBP;– (Crude oil, leaded petrol);
• Good results with Moussol APS 3/3;– Also with 1% induction;
• 120 m3 bought.
![Page 17: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/17.jpg)
![Page 18: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/18.jpg)
Time line
• September 12th, official delivery;
• November 2006, IBP employable;
• Januari 1st 2007, personnel fully trained;
• Total system practice in April 2007.
![Page 19: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/19.jpg)
Area of employability
• First priority is the Rotterdam Harbour and Industry area;
• Afterwards examining if the IBP is useable outside this area.
![Page 20: Industrial Firefighting Pool (IBP) Ing. Raymond Bras Special Projects, Unified Industrial & Harbour Fire Department](https://reader031.vdocuments.site/reader031/viewer/2022032701/56649c7b5503460f9492eaa5/html5/thumbnails/20.jpg)
Questions?