Indoor Air Standards in Japan for Healthy Environment

Yoshika SekineSchool of Science, Tokai University, JapanSimon WattsBMS, Oxford Brookes University, UK

Page 2: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

2

Do you think ?

* The Last Samurai, Warner Bros.,2003** Sayuri, Columbia Pictures Industry, 2005

SAMURAIGEISHA

*

**

Page 3: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

3

Modern Japan

Economic power based on High-tech

Western style buildings

Page 4: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

4

Why Japanese companies are so good at making microchips?

M. Cross, New Scientist(1990)“…an important reason for Japan’s domination of the electronics market is that its people have a built-in “clean-room”mentality. It comes from the custom of changing shoes when stepping into another room.”

Page 5: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

5

Japanese climateJapanese climate

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12Month

Tem

pera

ture

( ℃)

20

30

40

50

60

70

80

Rel

ativ

e hu

mid

ity(%

)

Temp.RH

Page 6: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

6

SHOSO-IN Treasure House

An eighth century building specially constructed to prevent the natural damage caused by Japanese damp climate. The raised floor structure ensures sufficient ventilation underneath to keep the inside dry.

Page 7: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

7

Raised floor structure in modern house

“Clean Room” mentality

*http://www.misawa.co.jp/kodate/

*

Page 8: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

8

“Sick House Syndrome”

“Sick Building Syndrome”Majority of patients: housewives and children in newly-built housesTypical air pollutants- Formaldehyde (HCHO)- Volatile Organic Compounds (VOCs)Why it happened in a house and invited a great social concern?

Page 9: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

9

Renewal cycle of house

141

103

86

79

30

0 50 100 150

UK

USA

Fr

Ger

J

Renewal cycle (year)

Renewal cycle= No. of present houses /No. of newly-built houses per year

Page 10: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

10

Indoor air pollution by chemicals

Japanesehouse

Chemicalintolerance

Indoor airpollution

Use of chemicals

Large supply of houses

Air-tight

Saving energyAir change rate

< 0.2/h

Volatilization of chemicals

1970s~ 1990s~

Page 11: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

11

Case of a victim in Tokyo

Middle aged single womanIn Apr.1999, moving to a newly built apartment house in TokyoHealth disorder- eye mucus, throat pain, bronchus irritation, headache, unpleasant feeling with muscles, diarrhea, fatigue and failure of memoryPart-time librarian of a hospitalIn Mar.2000, diagnosis at hospital- Multiple Chemical Sensitivity

Page 12: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

12

Multiple Chemical Sensitivity

Medically unexplained symptom- different from allergy, acute poisoning

Damage on nerve system etc.Repeated and intermittent exposure to chemicals (non-specific structure, property)Cross-sensitization

- drugs, physical or psychological stressIn the case of Sick House Syndrome,most patients have been forced to move to another old house or replace building materials, sometimes at their expense.

Page 13: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

13

Efforts of reduction of chemicals(2)炭入り枕

Bamboo charcoal

Pillow filled with charcoal

PlantsAir cleaners

Door with air pathwayPassive sampler

Page 14: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

14

Concentration of formaldehyde

1999 2002

guideline

0

0.05

0.1

0.15

0.2

0.25

26 Sep. 7 Oct. 12 Oct.12 Mar. 18 May21 Aug. 15 Oct.

HC

HO

con

c.(

ppm

)

0

5

10

15

20

25

30

Roo

m te

mpe

ratu

re(

℃)

Page 15: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

15

Nation-wide survey

Questionnaire study for Japanese 4,000 adults (> age 20) (Uchiyama,2003)Quick Environmental Exposure and Sensitivity Inventory (QEESI)- developed by C. Miller (1998)Results- respondents: 2,851- suspected as chemical sensitivity: 0.74%Underestimate?- children: more sensitive to chemicals

Page 16: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

16

Governmental countermeasures

Setting Indoor Air Quality Guidelines of Chemicals (since 1997)Emission control and installation of ventilation system- Standard Building Law, 2003

Monitoring of indoor air concentrations ofchemicals in newly-built houses - Housing Quality Assurance Law , 2002

formaldehyde in buildings and school- Building Sanitation Law,2002

Page 17: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

17

Indoor Air Quality Guidelines- Ministry of Health, Labour and Welfare, Japan

date chemicals CAS No. concnetration

1997.6 formaldehyde 50-00-0 100µg/m3(0.08ppm)

2000.6 toluene 108-88-3 260µg/m3(0.07ppm)

xylene 1330-20-7 870µg/m3(0.20ppm)

p -dichlorobenzene 106-46-7 240µg/m3(0.04ppm)

2000.12 ethylbenzene 100-41-4 3800µg/m3(0.88ppm)

styrene 100-42-5 220µg/m3(0.05ppm)

chlorpyriphos 2921-88-2 1µg/m3(0.07ppb)

0.1µg/m3(0.007ppb)for infant

di-n-butylphthalate 84-74-2 220µg/m3(0.02ppm)

TVOC 400µg/m3 *2001.7.5 tetradecane 629-59-4 330µg/m3

(0.04ppm)di-2-ethylhexylphthalate 84-66-2 120µg/m3

(7.6ppb)diazinone 33-41-5 0.29µg/m3

(0.02ppb)nonanal 124-19-6 41µg/m3

(7.0ppb)*2002.1 acetaldehyde 75-07-0 48µg/m3

(0.03ppm)fenobucarb 3766-81-2 33µg/m3

(3.8ppb)( ): coverted at 25 degC, *Draft value

Page 18: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

18

Formaldehyde (HCHO)

Emission sourceadhesives used for - plywood, MDF, particle board, - vinyl wall paperIndoor concentrations

Survey for 4,600 housing units in 2000 (by MLIT)- average 0.071ppm- 27.3% of the units

> the guidelinePlywood used for flooring

Page 19: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

19

The amended Building Standard Law

Enforced in July, 2003Applied to every habitable room of all buildingsRegulation on Chlorpyrifos- The use of Chlorpyrifos is bannedRegulation of Formaldehyde (HCHO)- Area size of HCHO-emitting materials used for interior finishing is restricted- Installation of 24h-ventilation system is mandatory to keep >0.5 ACH

Page 20: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

20

HCHO-emitting materials

Formaldehydeemitting buildingmaterials

Emission rateRestrictions oninterior finishingmaterials

Type 4 up to 5µg/m2h No restrictions

Type 3 5~20µg/m2h Limited area

Type 2 20~120µg/m2h

Type 1 over 120µg/m2h Prohibited

Determined by a small chamber method (JIS A 1901,2003)

Page 21: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

21

Housing Quality Assurance Law- Ministry of Land, Infrastructure and Transport

IAQ : One of the housing performanceMeasurement of indoor concentrations included in fields of the Housing Performance Indication SystemBy request of the house purchaser, house builders have to make a monitoring of indoor air conc. of chemicals in a newly-built house.Sampling & analytical methods: Standard protocol prepared by MOHLW

Page 22: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

22

Monitoring of Chemicals

Target substances;formaldehydetoluene, xylene, styrene and ethylbenzene

Standard sampling methods1) Active samplings (30min)2) Passive samplings (24h)

Passive samplers are commonly used for IAQ monitoring

Passive samplers

Page 23: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

23

IAQ standard for museum

substance limit values frequencyPM 0.15mg/m3

CO2 1000ppmCO 10ppmtemperature 17 - 28℃relative humidity 40 - 70 %air stream 0.5m/s

HCHO 0.1mg/m3in summer afterbeing built, reformedand fitted up

bi-monthly

*HCHO was added in 2002.

Page 24: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

24

Yearly change of HCHO conc.

0

0.02

0.04

0.06

0.08

0.1

0.12

2000 2001 2002 2003 2004

Fiscal year

HC

HO

con

c.(p

pm)

0

5

10

15

20

25

30

35

Perc

enta

ge o

fex

ceed

ence

(%)

HCHO conc. exceedence

Indoor air concentrations of HCHO in newly-built houses (n=2,000)

http://www.skkm.org/houkoku/

Page 25: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

25

Air-cleaning materials based on “Clean-room” mentality

Air cleaner Air cleaning paint Air cleaning board

Page 26: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

26

Removal of airborne chemicalsprinciple methods/materials

physisorption activated charcoalporous ceramics

natural fiberschemisorption inorganic compounds

organic compoundsextracts

decomposition photocatalystozonolysis

catalytic decompositionmodified charcoalplasma discharge

minus ionsactivated oxygen

digestion bacterialblocking resins

Page 27: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

27

Passive air cleaning board

H2O+

CO2

HCHO

Pre-filter

MnO2 filterHCHO+2[O]→H2O+CO2

at room temperature

Page 28: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

28

Manganese dioxide

0

100

200

300

400

500

600

0 5 10 15 20Time(h)

HC

HO

con

c.(p

pm)

0

100

200

300

400

500

600

Prod

uced

CO

2(pp

m)

(MnO2:10g、PTFE Bag: 100L、21℃)

Page 29: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

29

Possible pathways

HCHO(g)+O(a)→ HCHOO(a) ……(1)

H C H O O ( a ) → H C O O ( a ) + H ( a )… … ( 2 )

H C O O ( a ) → C O 2 ( g ) + H ( a )… … ( 3 )

2 H ( a ) + O ( a ) → H 2 O… … ( 4 )

H C H O + 2 O → H 2 O + C O 2

… … ( 5 )Sekine,Y, Atmospheric Environment, 36,5543(2002)

Page 30: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

30

Field tests

Bath

Bedroom(b)

Bedroom(a)

Toilet

Kitchen

Living dining roomair-cleaning board total 9.8m2

air sampling site

Closet

N

1.5m2 1.0m2

0.8m2

1.5m2

3.0m2

1.0m2

1.0m2

Japanesestyle room

i Air-cleaning board

i Newly built and unoccupied apartment houses

i 3LDK(230m3)i N=0.15/hi May – Nov., 1998

Sekine,Y, et al. Atmospheric Environment, 35,2001(2001)

Page 31: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

31

Variation of HCHO concentrationIn

door

con

cent

ratio

n of

HC

HO

(ppm

)

0 30 60 90 120 150 180 2100.0

0.1

0.2

air conditioner off

house without the board

house with the board

Elapsed time(days)

guideline

Page 32: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

32

Air cleaning materials with legal basis

In the Standard Building Law,Exemption from the restrictions for HCHOHabitable room- equipped with centrally controlled air

conditioner- in which the HCHO concentration can be

maintained at no more than 0.1mg/m3

Air-cleaning materials can be used with approval of the Minister of MLIT

Page 33: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

33

On-site colorimetric detector of HCHO

Virgin sample

Exposed to HCHO

Put on the surface

HCHOemittingmaterials

Colorimetric reagent

Page 34: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One

34

User friendly technology