A Highly Efficient and Long Lasting Water Heater
Features■ Heavy Duty Construction
� Hydrastonecementliningprovideslongtanklife
� Copper-silicontappingscannotrustorcorrode
� Highimpactcompositejacketcannotrustorcorrodeandeliminatesdamage
■ High Efficiency� 2"thickpolyurethanefoaminsulation
reducesstandbyheatlossprovidingtheindustry'shighestefficiencyheater.
■ Advanced Heating Coil� Heatingcoilcanbeeasilyremovedfor
simplemaintenance� Heavygaugecopperfintubecoilprovides
maximumheattransfer
Utilize Existing Boiler Water Supply To Make Hot WaterTheHubbellTModelwaterheaterutilizesanexistingsupplyofboilerwatertoheatdomesticpotablewater.TheTransflowmodelstoragetankisfittedwithaspeciallydesigned,highefficiencyheatingcoilwhichtransfersheatfromtheboilerwatertothedomesticwaterinthetank.It’sadvanceddesignhasnomovingpartsanddoesnotrequireanyelectricalconnections,whilethehighqualitymaterials
usedinconstructionofitstankandheatingcoilensureslongservicelife.WhenyouspecifyandinstallaHubbellTransflowwaterheater,youwillhaveconfidenceinknowingthattheownerwillbeprovidedwithaqualityproductthatisatrouble-freeandlonglastingsourceforhotwater.
Applications TransFlow Model(Top Mount Model TT70C Shown)
The Hubbell TransFlow Water heater uses Boiler Water as the source for heating potable water.
TransFlow Model
NOGLASSLINING
NOGLASSLINING
■ Residential■ IndustrialFacilities
■ OfficeBuildings■ Schools
■ CommercialBuildings
Indirect Fired Water Heater35-119 Gallon Capacities
2
TransFlow Model Water Heater SpecificationsTank:
Capacities:Orientation:DrainSize:TankRating:CoilType:CoilMaterial:CoilRating:Approvals:Jacket:
Color:
HydrastoneCementLined Steel
35thru119Gallons Vertical3/4"HoseConnection 150psiWP,300psiTP RemovableCopperFinTube150psiWP,300psiTP cULus,AHRI,IBRHighImpactColorized CompositeWhiteandBlack
ThermostatOperation Voltage: 24VoltAC/DC(Constant)
Switching Relay: S.P.S.T,120Volt,10Ampmax.Temperature Range: 110-160°FDifferential: 2-20°F(Adjustable)
TankWarranty(Residential)TopMountModel: 10YearsSideMountModel: 7Years
TankWarranty(Commercial)TopMountModel: 5YearsSideMountModel: 3Years
Standard EquipmEnt■ 1/2"thickHydrastonecementlinedsteeltank■ Allcopper-siliconnon-ferroustankopenings■ Removableheatingcoil■ Highefficiencycopperfintubeheatingcoil■ Immersionadjustableelectronicthermostattocontroltheflowofboilerwaterthroughtheheatingcoil
■ ASMEratedtemperatureandpressurereliefvalvesetat150psi,210oF,200,000BTUmax
■ 2"thickpolyurethanefoaminsulationmeetsorexceedstherequirementsofANSI,ASHRAE,IESNA90.1-2007
■ Highimpactcolorizedcompositeprotectivejacket
OptiOnal EquipmEnt1. 11/2"MaleNPTinletandoutletwater
connections
2. Doublewallcopperheatingcoilwithaleakdetectionport
3. Integrallyweldedseismicattachmentpoints
4. Electricback-upheatingelementinvariouswattagesinsingleorthreephasevoltages(consultfactory).
5. Bulbandcapillarymechanicalthermostat(100-240°F)toaccept24-600VACoperationvoltage;SPSTswitch120Volt(16Amp),208Volt(9Amp),240Volt(8Amp).
Coil Pressure Drop ChartPlease note: Optional equipment may impact overall dimensions and weight. Please request submittal drawing from factory.
3
Outline Dimensions
FrontViewSideView
CBA
24"WithdrawalSpace
1"
CombinationColdWaterInletandDrain
HotWaterOutlet
T&PReliefValve
2"FoamInsulation
HeatingCoil
BoilerWaterOutlet
BoilerWaterInlet
ImmersionThermostatController
ProtectiveJacket
BaseModel
StorageCapacity(Gallons)
Standby Heat Loss°F/Hour
Dimensions (Inches) Inlet / OutletSize
(NPT)
ShippingWeight(Lbs)
OverallDiameter
OverallHeight
Inlet“A”
Coil“B”
Thermostat“C”
T&P Valve“D”
TS65 65 0.44 26 48 8 10 14 40 3/4" 308
TS80 80 0.41 26 58 8 10 14 51 3/4" 338
TS80C 80 0.41 26 58 8 10 14 51 1-1/2" 340
TS120 119 0.39 28 69.25 8 11 17 62 3/4" 420
TS120C 119 0.39 28 69.25 8 11 17 62 1-1/2" 425
Recovery ratings based upon the supply of 200°F boiler water to a single heating coil to heat domestic potable water from 50-140°F. For 180°F boiler water reduce recovery ratings by 25%.
Recovery ratings based upon one heating coil installed in tank. For additional coils, use the continuous demand rating.
SIDE MOUNT COIL
OptionalAdditionalCoil
OptionalAdditionalCoil
BaseModel
StorageCapacity(Gallons)
Coil Position Coil Type
Coil Model
No.
Coil Connection Size (NPT)
1st Hour Rating
(Gallons)
Continuous Demand Rating
(Gal/Hr)
Boiler Water Flow Rate
(GPM)
TS65 65 SideSingleWall 20S 1" 295 235 13
DoubleWall 10D 3/4" 142 82 11
TS80 TS80C 80 Side
SingleWall 20S 1" 307 235 13
DoubleWall 10D 3/4" 154 82 11
TS120 TS120C 119 Side
SingleWall 20S 1" 339 235 13
DoubleWall 10D 3/4" 186 82 11
Heating Coil Selection Chart with Recovery Ratings
RemovableHeatExchangeCoil
SideMount
HotWaterOutlet
T&PReliefValve45o
45o
CombinationColdWaterInletandDrain
ThermostatSensor
10o
Overall Dimensions
TankCrossSection
SteelPressureVessel
1/2"Hydrastone
D
4
3/4" Inlet and Outlet
1 1/2" Inlet and Outlet
BaseModel
StorageCapacity(Gallons)
Standby Heat Loss°F/Hour
Dimensions (Inches) Relief Valve Size
Inlet / OutletSize
(NPT)
Withdrawal Space
“E”
ShippingWeight(lbs.)
OverallDiameter
OverallHeight
Drain“A”
Inlet“B”
Thermostat“C”
T&P Valve“D”
TT35 35 0.72 22.75 39 8 Top 14 Top 3/4" 3/4" 36" 185
TT50 50 0.56 26 40 8 Top 14 Top 3/4" 3/4" 36" 238
TT70 70 0.45 28 46.5 8 Top 14 Top 3/4" 3/4" 41" 290
TT70C 70 0.45 28 46.5 8 8 14 38.5 3/4" 1-1/2" 41" 290
BaseModel
StorageCapacity(Gallons)
Coil Position
Coil Model Number Coil Type
CoilConnectionSize (NPT)
1st Hour Rating
(Gallons)
ContinuousDemand Rating
(Gal/Hr)
Boiler Water Flow Rate (GPM)
TT35 35 Top15S SingleWall 3/4" 230 203 6
15D DoubleWall 3/4" 124 94 4
TT50 50 Top15S SingleWall 3/4" 250 214 6
15D DoubleWall 3/4" 142 94 4
TT70 70 Top16S SingleWall 3/4" 335 271 6
16D DoubleWall 3/4" 175 111 4
TT70C 70 Top 19S SingleWall 1" 385 321 13
Heating Coil Selection Chart with Recovery Ratings
Recovery ratings based upon the supply of 200°F boiler water to the heating coil to heat domestic potable water from 50-140°F. For 180°F boiler water reduce recovery ratings by 25%.
FoamInsulation
TopView
ColdWaterInlet
Drain
HotWaterOutletandReliefValve
HeatingCoilInlet
(FromBoiler)
HeatingCoilOutlet(ToBoiler)
“E”WithdrawalSpace
TankCrossSection
SteelPressureVessel
1/2"
Drain
ImmersionThermowell
3/4"HotWaterOutlet
T&PReliefValve
A
C
8"
FoamInsulation
TopView
HeatingCoilOutlet(ToBoiler)
HotWaterOutlet
HeatingCoilInlet(FromBoiler)
11/2"MNPTColdWaterInlet
ImmersionThermowell
T&PReliefValve
3"
B
C
DTankCrossSection
A
Drain
SteelPressureVessel
1/2"
Hydrastone
Hydrastone
Outline Dimensions
TOP MOUNT COIL
ModelTT70COnly
Drain Inlet
Thermowell
ReliefValve
Overall Dimensions
30o30o20o10o
Top Mount Coil – Typical InstallationInstallationKeyShut-offValve
FlowCheckValve
CirculationPump
Drain
Union
T&P/ReliefValve&Brass"T"
ZoneValve
ExpansionTank
DielectricUnion
AirScoopwithExpansionTank
HotOuttoFixtures
ColdIn
BoilerSupplyMin.3/4"
Min.3/4"
BoilerReturn
BoilerReturn
Recommended
HotOuttoFixturesMin.
1-1/2"
BoilerSupply
Min.1"
BoilerReturnBoilerReturn
Recommended Recommended
ColdIn
Min.1-1/2"
BoilerReturnMin.1"
BoilerReturnMin.1"
BoilerSupplyMin.1"
ColdInMin.1-1/2"
Min.1-1/2"
HotOuttoFixturesMin.1-1/2"
HotOutMin.1-1/2"
Heating Coil Design — Top Mount Coil
Heatingsurfaceareapredominately
locatedinthecoldestpartofthetankfor
greatertemperaturedifferentialsresultinginsignificantlyimproved
heattransfer
O-ringgasketdesignprovidesreliableandtroublefreesealing
Plumbingconnectionslocatedinflangesimplifiesinstallationandimprovestanklongevity
Incoming cold water is distributed directly over the heating coils thereby significantly reducing mineral build up. Counter flow design increases heat transfer efficiency and hot water output.
5
Residential
Commercial Commercial with Additional Storage
The Electric Heater Company ■ P.O. Box 288 ■ Stratford, CT 06615-0288 ■ Phone: 203-378-2659 ■ Fax: [email protected] ■ www.hubbellheaters.com
ISO 9001:2008 ISO
Committed to continuous improvement...Continuing research results in product improvement; therefore specifications are subject to
change without notice. For the most updated information, consult the factory directly.
Made in the U.S.A.
Master Specification: TransFlow Model
GENERALProvideaquantityof Transflowwaterheater(s)ModelNo. asmanufacturedbyHUBBELLElectricHeaterCo.,Stratford,CT.Theentireunitistobecompletewithalloperatingcontrolsandrequiresonlyplumbingandelectricalserviceconnections.Thetankshallbeallweldedsteelcommercialconstructiondesignedfor150psiworkingpressureandcontain gallonsofstorage.ThetankshallbelinedwithseamlessHydrastonecementtoaminimumthicknessof¾"on100%ofallinteriortanksurfacesanddoesnotrequireanytypeofanodicprotection.Thetankshallbedesignedandfabricatedwithnon-ferrouscopper-siliconthreadedtappingsandnon-ferrousinletandoutletpipingformaximumcorrosionresistance.Steeltanktappingswillnotbeacceptable.Theentiretankistobeinsulatedwithaminimumof2"thickpolyurethanefoaminsulationandexceedthelatestASHRAEstandardforstand-byheatloss.Thecompleteheatershallbesuppliedwithahighimpactcolorizedcompositeprotectivejacketwhichcannotrustorcorrodeanddoesnotrequirepainting.Thecoldwaterinletshallbe¾"FemaleNPT( Optional Specification:11/2"MaleNPT)andincludeanon-corrosivestrata-flowdiffuserwhichpreventsincomingcoldwaterfrommixingtoorapidlywithhotwaterinthetank.A¾"hoseconnectiondrainissupplied.Thehotwateroutletshallbe¾"MaleNPT( Optional Specification:11/2"MaleNPT).AseparateFemaleNPTtappingistobeprovidedforreliefvalveinstallation.AnASMEratedautomaticreseatingcombinationtemperatureandpressuresafetyreliefvalvesetat150psiand210°Fshallbefactorysupplied.
HEATING COILThetankshallbefittedwithaheatingcoilwhichtransfersheatfromtheboilerwatertothedomesticwater.Boilerwatershallbeinthetubesanddomesticwaterinthetank.Theheatingcoilshallbeofsinglewall( Optional Specification:doublewall)copperfinetubeconstructionformaximumheattransferefficiencyandcoillongevity.Thecoilshallbefullyremovablefromthetanktoallowforperiodicinspectionandmaintenancewithouttheneedtomoveorliftthestoragetankfromitsinstalledposition.
BACk-UP ELECTRIC Thewaterheaterwillbesuppliedwithaback-upheater.Theback-upheatershallbeasingleelectricimmersionheat-ingelement( OptionalSpeci ication:119gallonmodelsonly:adualupperandlowerelement)ratedat KWeachanddesignedtooperateat
volts phase Hzwithallnecessaryoperatingcontrolsfactorymounted,wiredandtested.Theheatingelement(s)shallbecopperorincoloysheathelectricimmersiontypesizedtoobtaintheratedrecovery.Watertemperatureshallbecontrolledthroughanadjustable110-170oFsnapactionsurfacethermostat.Anover-temperaturemanualresetHi-Limitshallbefactoryinstalledtodisconnectallconductorstotheheatingelementintheeventofanovertemperatureconditioninthepressurevessel.
THERMOSTATThetankshallbefittedwithanimmersion110-160°Fadjustableelectronictemperaturecontrollertocontroltheflowofboilerwaterthroughtheheatingcoil.Thetemperaturecontrollerrequiresaconstant24voltpowersupplytooperate.TheswitchingrelayisaS.P.S.T.120volt10AmpMaxrelaywhichopensorclosesthecontrolcircuittothecirculationpumporzonevalve(byothers)inordertoregulatetheflowofboilerwaterthroughthecoilandtherebymaintainthedesiredwatertemperatureinthetank.
WARRANTYThewaterheatermanufacturershallwarrantyallcomponentsagainstdefectsinworkmanshipandmaterialforaperiodofone(1)yearfromdateofstart-upandthepressurevesselincludingtheheatingcoilforfive(5)yearsfromdateofstart-up,(residentialapplicationsseven(7)years)providedthattheunitisstartedwithinthree(3)monthsofdateofshipmentandinstalledandoperatedwithinthescopeofthetankdesignandoperatingcapability.Eachwaterheatershallbeshippedwithacompletesetofinstallationandoperatinginstructionsincludingsparepartslistandapproveddrawings.
Model TS Number Designation
■Step2StorageCapacity:Gallons65-119
■Step1BaseModel:TS=SideMount
tS■Step7Voltage/Phase/Hz:A = 120-1-60RS = 208-1-60S = 240-1-60W = 277-1-60T4S = 480-1-50/60
■Step6KWSelection:1.5-20KW
——
■Step8No.Elements:1=UpperPositionOnly(Single)
2=Upper&LowerPosition(Dual)
Complete this section only when specifying a back-up electric heating element.
■Step3#CoilsUpper:0,1,2
■Step4#CoilsLower:1,2
■Step5CoilModel#:SeeCoilSelectionChart
JOBNAME
REPRESENTATIVE
ENgINEER
CONTRACTOR
Model TT Number Designation
■Step2StorageCapacity:Gallons35-70
■Step1BaseModel:TT=TopMount
tt■Step5Voltage/Phase/Hz:A = 120-1-60RS = 208-1-60S = 240-1-60W = 277-1-60T4S = 480-1-50/60
■Step4KWSelection:1.5-20KW
——
■Step6No.Elements:1=UpperPositionOnly(Single)
2=Upper&LowerPosition(Dual)
Complete this section only when specifying a back-up electric heating element.
■Step3CoilModel#:SeeCoilSelectionChart
SIDEMOUNT
TOPMOUNT
— —
Rev C