impact of transformer core size on the reactive power requirement of power transformers due to gic

36
DEGREE PROJECT, IN , SECOND LEVEL STOCKHOLM, SWEDEN 2014 Impact of transformer core size on the reactive power requirement of power transformers due to GIC CLAUDIA BERGSÅKER KTH ROYAL INSTITUTE OF TECHNOLOGY KTH ELECTRICAL ENGINEEING

Upload: others

Post on 11-Sep-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

DEGREE PROJECT, IN , SECOND LEVEL

STOCKHOLM, SWEDEN 2014

Impact of transformer core size on thereactive power requirement of powertransformers due to GIC

CLAUDIA BERGSÅKER

KTH ROYAL INSTITUTE OF TECHNOLOGY

KTH ELECTRICAL ENGINEEING

Page 2: Impact of transformer core size on the reactive power requirement of power transformers due to GIC
Page 3: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Abstract

Geomagnetiskt inducerade strömmar (GIC) är ett naturfenomen som uppstår till följd av solstor-mar. Vid en solstorm kastas stora mängder magnetiserad plasma ut från solens yta, och när dennaplasma når jorden uppstår uktuationer i det jordmagnetiska fältet. Detta kan leda till att DC-strömmar induceras i långa transmissionsledsningar. Dessa överströmmar påverkar kraftsystemetpå era olika sätt, bland annat har de en stor påverkan på transformatorer. Då överströmmenyter genom transformatorlindningarna ökar det reaktiva eektuttaget för transformatorn, vilketkan leda till spänningsinstabilitet i systemet. En fråga som legat till grund för detta projekt är hu-ruvida en ökning av transformatorkärnans storlek gör transformatorns reaktiva eektuttag mindrekänsligt för GIC. För att undersöka detta har en ny transformatormodell använts; den såkalladehybridmodellen som kombinerar dualitetsprincipen med en matrisrepresentation av transformatorn.Denna modell, som nyligen implementerats i simuleringsprogrammet PSCAD, har använts för attsimulera GIC i transformatorer med kärnor av olika storlekar. Resultaten från dessa simuleringarindikerar att större transformatorkärna medför mindre förändring av det reaktiva eektuttaget närtransformatorn utsätts för GIC. Det är även tydligt att det reaktiva eektuttaget som funktion avGIC är en icke-linjär funktion när hybridmodellen används. Denna funktion har tidigare ansettsvara linjär.

Geomagnetically induced currents (GIC) are a natural phenomenon which arises due to solarstorms. During a solar storm, large amounts of magnetized plasma are ejected from the surfaceof the sun. When this plasma reaches earth, it causes uctuations in the geomagnetic eld. Suchuctuations may induce DC over-currents in long transmission lines. These currents aect thetransmission system several dierent ways; In particular high voltage transformers are sensitive toGIC. When the over-current ows through the transformer windings the reactive power absorptionof the transformer increases, which may lead to voltage instability in the power system. For thisproject, the main issue has been to determine whether or not an increase in the size of the trans-former core leads to the reactive power absorption being less sensitive to GIC. In order to investigatethis issue a recently developed transformer model has been used; the Hybrid transformer model.This model combines the principle of duality with a matrix representation of the transformer. TheHybrid transformer model, which has recently been implemented in the power system simulationssoftware PSCAD, has been used to simulate GIC events in transformers of varying core sizes. Theresults from these simulations indicate that a larger transformer core is associated with a smallerincrease in reactive power absorption during a GIC event. It is also clear that the reactive powerabsorption as a function of GIC magnitude is a non-linear function when the Hybrid transformermodel is applied. This function has previously been considered a linear function.

1

Page 4: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Acknowledgments

First of all I would like to thank the Norwegian Transmission System Operator, Statnett, for fundingthis Master's Degree Project. In particular, I want to thank Jan-Ove Gjerde for giving me this greatopportunity, and Trond M. Ohnstad who has been my supervisor during this project.

I would also like to thank Dr. Nicola Chiesa for answering the questions I had regarding theXFMR transformer model for GIC studies in PSCAD. Furthermore, I want to thank Prof. GöranEngdahl at KTH for showing me a great deal of patience and understanding. I would also like tothank my supervisor at KTH, Seyed-Ali Mousavi, for providing me with useful information anddoing his best to help me despite the distance.

Finally I want to thank Dr. Luigi Vanfretti. Without your help and support this project couldnot have happened.

2

Page 5: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Contents

1 Introduction 4

1.1 Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.2 Problem Denition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.3 Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.4 Overview of the report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 The GIC Phenomenon 6

2.1 Geomagnetically Induced Currents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.2 GIC impact on the power transformers . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.2.1 Reactive power losses due to GIC . . . . . . . . . . . . . . . . . . . . . . . . . 72.2.2 The dierence between ve-limb and three-limb cores . . . . . . . . . . . . . 8

2.3 Historical solar storms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

3 Transformer Modeling 11

3.1 The Hybrid Transformer Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123.2 Hybrid Transformer Model for GIC phenomena . . . . . . . . . . . . . . . . . . . . . 14

4 Simulations 15

4.1 Simulation environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.2 Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4.2.1 Transformer T1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184.2.2 Transformers T2 and T3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

4.3 Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.4 Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

5 Conclusions and further studies 30

3

Page 6: Impact of transformer core size on the reactive power requirement of power transformers due to GIC
Page 7: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

1 Introduction

1.1 Background

Geomagnetically Induced Currents (GIC) are near-DC currents owing in transmission lines due todisturbances in the geomagnetic eld. These currents are a natural phenomenon which may posea threat to the power system, and it arises as an eect of solar storms; eruptions of plasma andcharged particles from surface of the sun. The solar activity follows an 11-year cycle, and the years2012-2014 have been associated with a solar activity peak - meaning an enhanced probability ofsolar eruptions. For this reason, the interest in solar activity and the consequences it may have onsociety has been high during the last couple of years, with articles in e.g. National Geographic andIEEE Spectrum providing speculations regarding the potential dangers of solar storms and GIC. Inthe power system, the most vulnerable component to GIC impact is the power transformer. One ofthe eects of GIC on the power transformer is that reactive power absorption dramatically increasesduring a GIC event, which could lead to voltage instability and power outages. In order to make ascientic, reliable assessment of the risks associated with GIC, the behavior of power transformerswhen exposed to GIC must be studied.

1.2 Problem Denition

The key to studying GIC eects on the power system is transformer modeling. When simulating aGIC event in a transformer a complex model is required, a model which incorporates the non-linearcharacteristics of the transformer core. GIC can be described as a slow transient, for which reasonan electromagnetic transient simulation software must be used. A transformer model suitable forGIC studies called the Hybrid Transformer Model has recently been developed. The purpose ofthis thesis is to use the Hybrid Transformer Model to study the increase of reactive power demandof large power transformers due to GIC. The modeling approach is presented in [1]. The focus ofthe thesis is core design impact on reactive power losses due to GIC. The main problems are

To determine how the increased reactive power demand depends on GIC magnitude accordingto the Hybrid Transformer Model

To determine if increased cross-sectional areaal area of the transformer core makes the trans-former less sensitive to GIC

This thesis project is limited to the study of high voltage three-phase power transformers.

1.3 Objectives

The following objectives were set for the thesis:

Perform a literature review on GIC and transformer modeling in general and the HybridTransformer Model in particular

Learn how to use PSCAD for transient simulation

Use the implementation of the Hybrid Transformer Model in PSCAD to simulate GIC eventsand record reactive power absorption

Find a method for varying the transformer core cross-sectional area and record how theincrease in reactive power demand depends on core cross-sectional area.

4

Page 8: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

1.4 Overview of the report

This report begins with a short introduction to the GIC phenomenon, and how power transformersare aected when subjected to GIC during solar storm events.

Section 3 describes transformer models for electromagnetic transients studies in general, andthe XFMR transformer model in particular. In section 4 the GIC simulations carried out in thisproject are presented and discussed.

Finally, section 5 provides conclusions to be drawn from the results presented in section 4, andsuggestions for further studies.

5

Page 9: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

2 The GIC Phenomenon

2.1 Geomagnetically Induced Currents

Geomagnetically induced currents (GIC) is a phenomenon related to solar activity. It arises dueto so-called solar eruptions or solar ares in which the sun ejects plasma and radiation from itssurface. An image of a solar are is shown in Fig. 1. Solar eruptions lead to solar storms, which arelarge streams of magnetized plasma traveling through interplanetary space. The magnetospheresurrounding our planet protects us from the major part of this plasma ow. However, chargedparticles can enter the magnetosphere in the polar regions, where the geomagnetic eld has a verticaldirection, and reach the earth's atmosphere. These high-energy particles give rise to auroras, andcause uctuations in the geomagnetic eld. Disturbances in the geomagnetic eld cause changesin the currents in the ionosphere, which in turn may cause electric potential dierences at theearth's surface. Such potential dierences cause near-DC (0.01-0.001 Hz) currents to ow in theground[14]. These currents ow through loops consisting of overhead-lines, power transformers,grounded neutrals and ground, and are known as Geomagnetically Induced Currents (GIC). GIClevels up to a few hundred amperes have been observed[14].

The transformer is considered the most vulnerable transmission system component primarilyaected by GIC. The DC current owing in the transformer windings during a GIC event gives riseto an oset in the magnetization characteristic of the transformer core, which causes the transformerto saturate each half cycle of the system frequency. The transition from the unsaturated state tothe saturated state is associated with a change in inductance of the transformer core by severalorders of magnitude. As a result of the variation in core inductance the exciting current drawnfrom the supply is dramatically increased. Since the exciting current lags the system voltage by90º, this leads to a rise in reactive power demand of the transformer. Unless there is sucientreactive power compensation in the system, this can lead to voltage instability, and in the worstcase scenario voltage collapse.

Another eect of half-cycle saturation is increased harmonic content in exciting currents, whichmay lead to false relay tripping. Also, overheating of transformers as a consequence of saturationcaused by GIC has been observed.

2.2 GIC impact on the power transformers

Frequently discussed risks associated with GIC events are overheating of transformers, false relaytripping caused by increased harmonic content of line currents, and voltage instability due toincreased reactive power (var) absorption of the transformer. Previous work has mainly beenfocused on the rst two; temperature rise in transformers and false relay tripping. There havebeen wild speculations regarding the risks of transformers being damaged due to overheating asa consequence of GIC. The risk of overheating depends on the magnitude and duration of theGIC. Typically, a GIC event can be seen as high magnitude DC peaks of short duration (order of10 minutes), separated by relatively low magnitude periods (order of 60 minutes). The durationof each peak is normally not great enough to increase the temperature of the transformer to aharmful level. In [12] two experiments on the eects of DC injection on temperature of windingsand structural parts of power transformers are described, one performed by Hydro Quebec and theother by Fingrid. In these experiments, single and three-phase power transformers were injectedat no load with high levels of DC; 75 A/phase up to one hour, and 200/3 A/phase for 20 minutes,

6

Page 10: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Figure 1: Solar eruption on June 20, 2013. Image from NASA/SDO

respectively. The temperature rise in windings and structural parts were measured, and bothexperiments reported small temperature rise in windings and moderate rise in structural parts,compared to the IEEE Standard C57.91 temperature limits. It was concluded that at the GIClevels injected, no transformer damage would occur.[12]

False relay tripping due to GIC has been reported on various occasions. When the transformeris operating in the saturated state, the harmonic content of line currents increases. Relays maythen react to the harmonics as to an over current, and trip falsely. The most severe incident tookplace in Quebec, Canada, in 1989.

Another concern is voltage instability due to increased var losses. The voltage stability dependson the operation point of the system. If the operation point is already close to a collapse, aGIC event could lead to voltage collapse. If a GIC event drives the system into a near collapsestate, operators may be forced to disconnect load in order to avoid collapse. The stability of thepower system depends on many dierent factors. Increased reactive power absorption in powertransformers, combined with loss of reactive compensation equipment and failure to disconnectshunt inductances could lead to instability.

2.2.1 Reactive power losses due to GIC

When the geomagnetically induced DC-current ows through the transformer windings it generatesa DC-ux in the transformer core. The DC-ux strength depends on the magnitude of the GIC,the number of transformer winding turns and the reluctance of the core. The DC-ux changes theoperating point of the transformer on the hysteresis curve (the characteristics of the ferromagneticcore material). During normal conditions the transformer operates in the linear region of thehysteresis curve. The DC-ux generated by GIC causes an oset, so that the transformer reachesthe saturated region of the hysteresis curve every half-period of the system frequency. Fig. 2shows the shift in the operating point. The exciting current drawn from the supply is dramaticallyincreased when the transformer operates in the saturated state. Also the harmonic content of the

7

Page 11: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Figure 2: Oset in magnetic characteristics caused by DC excitation. The DC ux is added to theAC ux during one half-period, and substracted from the AC ux during the other half-period.This leads to core ux densities in the saturated region. Figure from [3].

current is increased. The exciting current lags the system voltage by 90º, and is therefore associatedwith reactive (var) losses.

In [1] it is stated that only the fundamental lagging current components have a signicant impacton the system voltage prole. The fundamental component of the reactive power can be calculatedas:

Q(1) =√

3 · V 2I(1) − P 2 (1)

where V is the line-to-line voltage, I(1) is the rms value of the fundamental component of theline current, and P is the active power consumed by the transformer. It is here assumed that thevoltage has no harmonic distortion.[1]

In previous work [1, 12], it has been concluded that the reactive power absorbed by the trans-former when subjected to GIC is directly proportional to the GIC level. The results presented inthis thesis will suggest that the relationship between reactive power absorption and GIC level isnon-linear.

2.2.2 The dierence between ve-limb and three-limb cores

The transformer core of a three-phase transformer has either ve or three limbs. In a ve-limbtransformer, the outer limbs serve as return paths for the ux generated in the core legs. Fig. 3shows a ve-limb transformer core. A three-limb transformer core, shown in Fig. 4, has no outerlimbs and the DC-ux generated by by the DC current owing in the windings must close throughthe tank walls and air surrounding the core. Air and the non-magnetic tank material have ordersof magnitude higher magnetic reluctance than the ferromagnetic core material. This means that ina three-limb transformer the ux must pass through a very high reluctance return path in order toclose, which means that the change in ux due to GIC is smaller for a three-limb transformer.[3]Three-limb transformers have proven to be less sensitive to GIC than ve-limb transformers [15]. Inthe Norwegian transmission system, ve-limb core transformers are common at high voltage levels.Approximately 75% of the transformers at 400 kV are ve-limb. [8]

8

Page 12: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Leg Leg Leg

Outer limb Outer limb

Figure 3: Core dimensions for a ve-limb transformer

Figure 4: Three limb transformer core

9

Page 13: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

2.3 Historical solar storms

The strongest solar storm ever recorded took place in 1859 and is known as the Carrington event, after the British amateur astronomer Richard Carrington. Between August 28 and September 4,1859, powerful auroras were observed around the world. This phenomenon which normally onlytakes place near the polar regions was observed in North- and South America, Europe, Asia andAustralia. Auroras appeared as far south of the North Pole as Hawaii and the Caribbean, andas far north of the South Pole as Santiago, Chile. Geomagnetic irregularities were also observed;magnetometer traces were driven o scale and the telegraph networks all over the world sueredmajor disruptions.[13]

On September 1, Carrington observed, with his unaided eye, on the sun's surface two patchesof intensely bright and white light [13] from a large group of sunspots (Sunspots are areas of lowertemperature than the surroundings, for this reason they appear darker on the solar disc). This is therst recorded observation of the phenomenon now known as solar ares; eruptions of intensiedradiation, plasma and charged particles from the sun. Although no connection between the solarare and the peculiar magnetic disturbances were made at the time, the Carrington event wouldlater contribute to the understanding of space weather and solar storms. In 1859, there was nopower system to be aected by the powerful magnetic disturbances. One frequently discussed issueis what consequences a solar storm of the same proportions as the 1859 event would have on societytoday. Although it is unclear exactly how strong the 1859 solar storm was, it is agreed upon thatit was stronger than any solar storm observed in modern time. Since there is only one known eventof this proportion, it is dicult to estimate how often they occur. The most common estimation isthat a solar storm of this strength appears once in 500 years.[15]

The most severe GIC event of modern time occurred in Quebec, Canada, in March 1989. It wascaused by a coronal mass ejection occurring March 19, 1989. Two days later voltage variations inHydro Quebec's transmission grid were detected. Early in the morning of March 13 ve 735 kVtransmission lines were disconnected as a result of false relay tripping, which caused the systemvoltage to collapse. Nine hours later, 17% of the system load was still disconnected from the powergrid [15]. The solar storm of March 1989 aected the power grid also in other parts of NorthAmerica. In Manitoba, Canada, Manitoba Hydro observed a dramatic increase in reactive powerconsumed by synchronous capacitors at one of their substations. The total reactive power demandfrom the substation increased by 420 MVar within a few minutes time span. [8] In Virginia, U.S.,at a substation in the Allegheny Power System a 350 MVA auto transformer was removed fromservice because of high levels of gas in the transformer oil (a byproduct of internal heating). Theoverheating was believed to be caused by GIC. [8]

As previously mentioned, wild speculations regarding the consequences of a strong solar stormhave been seen in the last few years. In the February 2012 issue of IEEE Spectrum John Kap-penman concludes that it is reasonable to assume that a solar storm of the same proportions asthe Carrington event, or even stronger, will happen again. Kappenman describes the consequencesof such an event as a veritable doomsday scenario; It will lead to a massive planetary blackout,which in turn will cause severe damage on infrastructure, food and drinking water shortages, andhealthcare failures. Kappenman states that the fatalities in case of such an event may reach millionsof human lives. He concludes that a solar storm of such proportions would amount to one of theworst disasters in recorded history. It is however pointed out in [12] that articles such as thesedo not oer a scientic and engineering analysis of the many complex issues that determine powersystem impacts.

10

Page 14: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

3 Transformer Modeling

There are numbers of dierent approaches for modeling and simulating electromagnetic transients inpower system transformers. Typically, the choice of model depends on the character and frequencyof the transient to be simulated. Very few transformer models can be applied to all power systemtransients for a complete frequency range. The frequency of the transient in question also determineswhich simplications are in order. A GIC event can be described as a low frequency transient.

One of the challenges when modeling the transformer for GIC studies is the modeling of the corenon-linearity. For the ferromagnetic material of the core, the relationship between the magneticeld strength H, generated by the magnetizing (exciting) current of the windings, and the uxdensity B is non-linear and history-dependent, and follows the hysteresis loop. Magnetic saturationrefers to a state where the ux density B reaches a maximum value, and an increase in magneticeld strength no longer produces an increased ux density. In the saturated state, the permeabilityof the iron core is lower than in normal operation which means that more ampere-turns will berequired in order to produce the same amount of ux. In transformer models, the core non-linearityis generally represented by a non-linear inductance characterized by the relationship between uxlinkage and current.

Another important parameter when modeling low frequency transients such as GIC events isleakage inductance. Leakage inductance represents magnetic ux owing outside the core, in airand inside and between the transformer windings.

The simplest transformer models for simulation of low-frequency transients consist of matrixrepresentation of the branch impedances, where the elements of the matrices are found from short-circuit tests. This approach does not include the non-linear eects of the transformer core that arecrucial to GIC studies. Non-linear elements representing the core may be attached externally tosuch a model. However, an externally added core is not necessarily topologically correct. [7, 9]

A topologically correct core representation can be achieved from duality-based transformer mod-els. Such models are based on magnetic circuit theory. Magnetic circuit theory states that magneticparameters can be transformed into electric parameters. Each component in a magnetic circuit hasa corresponding electric circuit component. In a magnetic circuit, the ampere-turns drive a mag-netic ux through a ux path characterized by a certain reluctance, in the same way that a voltagesource drives a current through a conductor of a certain resistance. The node equations of themagnetic circuit are duals of the electrical equivalent node equations [7].

GIC impacts on transformers have previously been modeled using either FEM (the Finite Ele-ment Method) or magnetic circuit theory. For power system studies the latter is often preferred,due to the great computational burden of FEM analysis. [1]

A new transformer modeling approach, presented in [5], is the Hybrid Transformer Model. Thismodel is based on a magnetic circuit representation of the transformer, which is transformed intoits electric dual. The model is then separated into a core model and an inverse impedance matrixrepresentation of the leakage uxes. The winding losses and coil capacitances are added at thetransformer terminals. One of the main advantages of this model is that it includes a non-linear,topologically correct core model. The Hybrid Transformer Model is implemented in the softwareATPDraw, and is there called XFMR. [5]

11

Page 15: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

3.1 The Hybrid Transformer Model

The Hybrid Transformer Model is based on a combination of two modeling approaches; a short-circuit model given by an admittance matrix representing leakage inductance, and a non-linearduality based core representation. The model incorporates frequency-dependent winding resistancesand capacitive eects. A detailed description of the Hybrid Transformer Model can be found in[9, 10, 5]. Here, a brief summary will be given.

The core is modeled according to the following. A ctitious, innitely thin N+1th winding(where N is the number of physical windings) is assumed for the connection between the coreequivalent and the short-circuit model. The N+1th winding is thought to be located at the surfaceof the core leg, between the innermost winding (normally low-voltage) and the core. Each leg andyoke of the core is represented by a core-loss resistance in parallel with a non-linear magnetizinginductance, as shown in Fig. 5. The behavior of the magnetizing inductance is modeled by theFrolich equation (2), which is an approximation of the B-H relationship of the core material. Themagnetizing characteristic of the core is thus determined by the parameters a and b , which arespecic to the core material. The magnetizing inductances of the legs and yokes are estimatedindividually based on the relative cross-sectional area and length of each part. [10]

B =H

a+ b · |H|(2)

Equation (2) is reformulated into a relationship between ux linkage and current, Ψ− i , in thefollowing manner [5]: the ux linkage is introduced as Ψ = B ·A ·N , and the current i = H · l/N .Here, N is the number of turns of the innermost winding, A is the cross-sectional area, and l is thelength of the core section in question. This gives:

Ψ =i ·A ·N2/l

a+ b · |i| ·N/l(3)

If the B-H characteristics, the absolute dimensions of the transformer core A and l, and thenumber of turns N are known, (3) and (2) can be used directly to nd Ψ − i pairs for each limb,which are used to describe the non-linear magnetizing inductance. However, these data are seldomlyprovided by transformer manufacturers. In order to use test report data to obtain Ψ− i pairs, (3)is re-written into:

Ψ =Ar · i

a′ · lr + b′ · |i|(4)

where the substitutionsa′ = a · lL/

(N2 ·AL

)(5)

andb′ = b/ (N ·AL) (6)

have been made. Here, AL and lL are the absolute values of cross-sectional area and length of thecore leg, and Ar and lr are the relative cross-sectional area and length of the core section to bemodeled relative to the leg, i.e. Ar = Asection

ALand lr = lsection

lL. The absolute dimensions are thus

eliminated, and only the relative dimensions of the core are required. The parameters a′ and b′ arefound as functions of (VRMS , IRMS) pairs, available from factory test reports, which are converted

12

Page 16: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Ry

Rl

Ry

RlRl

L l L lL l

L o L oL y

L y RoRo

Figure 5: Core model for a ve-leg transformer

into the corresponding Ψ−i pairs for each limb. A description of the parameter estimation method,which involves an optimization process, can be found in [10].

The core loss resistances consist of hysteresis losses, eddy-current losses and anomalous losses,which are lumped together into one core loss resistance for each limb [9]. The core losses areassumed to be proportional to the core volume, so that the outer leg and yoke resistances (Ro andRy) can be set as proportional to the leg resistance Rl. The total core loss is inversely proportionalto the leg resistance, according to equation (7). K3/5 is a constant whose value depends on the coregeometry. [5]

Ploss =V 2

Rl·K3/5 (7)

The leakage ux of the transformer is modeled by a short-circuit admittance matrix, [A]. Leakageux refers to the part of the magnetic ux that leaks out of the core, and ows inside and betweenwindings, and in the air surrounding the core. It may also ow through the transformer tank,or other metallic parts. Some leakage ux is always present, in all magnetic circuits, since thepermeability is only 103 − 104 times larger for ferromagnetic materials than for air.

The leakage ux can be investigated by means of short-circuit tests. In such tests one measuresthe voltage required to produce rated current in one of the windings (two in case of a three-windingtransformer) while the other winding is short-circuited. The voltage drop over the examined windingwill then consist of two components: one resistive component corresponding to load losses, and onereactive component corresponding to leakage ux. [6]

The admittance matrix used in the Hybrid Transformer Model has dimension (Nw + 1)Np ,where Nw is the number of physical windings and Np is the number of phases. The (Nw + 1)winding represents the ctitious core winding, as mentioned earlier. The admittance matrix is builtaccording to the procedure presented in [2], section 6.5. For GIC analysis it is important to considerthe air-path inductances, i.e. the transformed magnetic reluctance of the ux owing outside thecore. This feature is not included in the Hybrid Model.

13

Page 17: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

ZTV

LVZgZ

Figure 6: System topology

3.2 Hybrid Transformer Model for GIC phenomena

In recent work by Sintef Energy Research, NTNU and Statnett, the Hybrid Transformer Modelwas implemented for GIC phenomena in PSCAD. The model was expanded to also include air-pathinductances. The modeling approach used is presented in [1]. In this study, a 300 MVA ve-legpower transformer was used. The topology of the analyzed system is shown in Fig. 6. The GICevent is represented by a DC voltage source on the HV neutral point of the transformer, with theDC voltage applied as a ramp between 2 and 10 s. The magnitude of the GIC is determined by:

IGIC =VDC

Re Zg+RW(8)

where VDC is the applied DC voltage, Zg is a resistive series source impedance and RW is theHV winding resistance. In this study the reactive power absorption is found to be a linear functionof GIC magnitude.

The paper focuses on the impact of air-path inductances. These are calculated by 3D-FEM,and it is reported in the paper that neglecting air-path impedances leads to an underestimation oforder 10-20% for the increase of reactive power demand due to GIC.

14

Page 18: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

4 Simulations

In order to investigate the relation between reactive power losses and GIC magnitude, two ve-limb and one three-limb power transformer have been used for simulation of GIC in PSCAD. Theimplementation of XFMR in PSCAD is the same as presented in [1]. The transformers most likelyto be exposed to GIC are step-up/step-down transformers connected to long transmission lines,for which reason transformers with nominal voltage around 400 kV are of particular interest forGIC simulations. Also, for this project transformers with the ve-limb core conguration are themost relevant to use for simulations, since this conguration dominates at high voltage levels in theNorwegian power system.

As mentioned in the previous section there are two ways of obtaining the Ψ− i pairs describingthe core non-linearity; either from transformer design data or factory test reports. The moststraightforward way to study the core size dependence of reactive power losses would be to usedesign data as input, since the Ψ− i relation then directly depends on the absolute dimensions ofthe core. However, the implementation of the XFMR model uses test report data as input, sincedesign data for transformer cores rarely are available. In the method for using test report data asinput, the absolute size dependence has been eliminated, according to equation (4). In this projectthree dierent transformers in the Norwegian power grid have been used for GIC simulations. Alist of simulated transformers is given in table 1. All transformers are three-phase, three-windingunits with Y-connected primary and secondary windings, and delta-connected tertiary windings.Transformers T1 is a ve-limb core transformer for which test report data was given, and T2 isnewly produced ve-limb core transformer for which design data was available (but not test reportdata). Transformer T3 is a three-limb core transformer for which design data was available. Thedata of transformers T1-T3 are property of Statnett and cannot be presented in detail here.

In order to use transformers T2 and T3 to study the core size dependence of the relation betweenreactive power losses and GIC magnitude, a method for using transformer design data as input to themodel had to be established. Also, a method for re-introducing the absolute dimensions dependencewhen using test report data is input had to be established, in order to use transformer T1 for thestudy.

Transformer Rated power Core type Available data

T1 300/300/100 MVA Five-limb Test report

T2 300/300/100 MVA Five-limb Complete design data

T3 100/100/30 MVA Three-limb Complete design data

Table 1: Transformers

4.1 Simulation environment

The GIC simulations of this thesis project have been carried out using the power system simulationsoftware PSCAD (version 4.5.1) where the XFMR model has been implemented for the purposeof relay testing. A base simulation model for GIC analysis was available for the project, and astand-alone MATLAB application calculating the model parameters from test report data. Theimplementation of the XFMR model and the parameters calculations applications have been de-

15

Page 19: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

veloped by Sintef for Statnett, in accordance with [1]. The application requires the following inputdata:

Main transformer ratings and conguration

For calculating the impedance: transformer short-circuit test report data

For calculating the core characteristics (Ψ − i relation): Open circuit test report data andrelative dimensions of the core

Transformer capacitances are not supported by the PSCAD model. The application calculatesthe transformer winding resistances and the admittance matrix based on short-circuit test reportdata, and generates the transformer core saturation curve expressed as ux-linkage as a function ofcurrent, based on positive sequence no-load test report data and relative dimensions of the core bycalculating parameters a′ and b′ in equation (4). The application generates an optional number ofux linkage - current pairs. The XFMR model in PSCAD allows for up to 10 − i pairs as input.Only three-phase units are supported by the model, with two or three windings and a number ofdierent winding congurations. The model supports ve-limb and three-limb transformer cores.

The main obstacle of the thesis project has been that neither the parameters calculation appli-cation or the XFMR model in PSCAD could be changed. They can be seen as two black boxeswhose content cannot be seen or manipulated. The parameters calculation application generatesa data le containing the transformer parameters, which is used as an input to the XFMR model.The data le containing the input for the transformer model is the only part where changes can bemade. In order to study the core size dependence of the reactive power losses, the core characteris-tics must be calculated externally, for dierent core sizes, and then placed in the data le which isused as input to the XFMR model in PSCAD. The idea is shown in Fig. 7. The data le containsthe following transformer parameters:

General settings; number of windings and core conguration

Non-linear core representation; Ψ− i pairs

Zero-sequence inductance and core loss resistance

The winding resistance in matrix form

The winding admittance in matrix form

All simulations have been carried out using the system topology shown in Fig. 6, with a durationof 90 s and a solution time step of 25 µs, which is the recommended time step for the model. Fig. 8shows the network model in PSCAD, which is identical to the network model used in [1]. The GICis represented as a DC voltage source at the HV neutral point, with the voltage applied as a rampof 8 seconds from 0 V to the nal value. The DC voltage level corresponding to a certain GIC levelis calculated from equation (8).

The voltage source in Fig. 8 is an ideal source, with zero internal impedance. The 0.02Ωresistance in series with the source represents a negligible resistive series source impedance. All linecurrents and voltages have been monitored, as well as the current owing through the high voltageneutral, core ux, air ux and core current. As mentioned above, capacitive eects have beenneglected, which is reasonable since according to [9] such eects are negligible for low frequencytransients.

16

Page 20: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Figure 7: Process of changing the input method of the model

The fundamental component of the reactive power Q consumed by the transformer was calcu-lated from equation (1). In the system shown in Fig. 8, Lload is small (0.1 mH), which means thereactive power drawn from the supply will be equal to the reactive power drawn from the trans-former. I(1) was obtained by using Fast Fourier Transform on the primary side line current, and Pwas obtained by placing the Real Power Meter component in PSCAD at the primary side line. Fora system where the transformer is loaded with a higher inductive or capacitive load, the reactivepower drawn from the transformer must be calculated as QHV − (QLV +QTV ).

4.2 Transformers

The transformers used for simulations in this project have been chosen on account of their voltageand power ratings, and congurations. As explained earlier ve-limb core transformers are of thehighest relevance. However, one three-limb core transformer has been included in the study inorder to to investigate if similar core size dependence on reactive power demand appears for thethree-limb core conguration as for the ve-limb core. Since there are two dierent approaches tore-introduce the core size dependence, depending on the type of input data available, two ve-limbcore transformers have been used, one for each approach.

In order to investigate how the reactive power absorption depends on the size (absolute dimen-sions) of the transformer core, the core saturation curve must be expressed as a function of absolutelength and cross section of the core. If all design data, including B-H characteristics, absolutedimensions of the core and number of turns of the innermost winding are known, the saturationcurve can be calculated by means of tting the B-H curve to the Frolich equation (2), obtainingparameters a and b, and calculating ux-linkage as a function of current from equation (4).

When only test report data is available, the core size impact can be studied by calculating a′

and b′ in equation (4) based on test report data, assuming values for length and cross-sectional areaof the core and number of turns of the innermost winding, and then calculating a and b in equation(3). Then, equation (3) can be used in order to generate any number of ux linkage - current pairs,for dierent core sizes. Both methods will be presented below.

17

Page 21: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Figure 8: System for GIC simulations with XFMR transformer model

4.2.1 Transformer T1

The transformer T1 is a 300 MVA ve-limb transformer. Short-circuit and no-load test report datawere available, so the parameters calculation application could be used as intended to obtain theparameters a′ and b′ in equation (4) and generating a data le containing the parameters for theXFMR model. In order to vary the size of the transformer core, initial values of the absolute coredimensions had to be assumed. The relative core dimensions were known, and could be maintained.The parameters a and b in (3) could be calculated by use of equations (5) and (6) using assumedvalues for lL and AL and an assumed value of N . For lL and AL, the length and cross-sectional areaof a transformer with similar power rating as T1 was used. When assuming the number of turnsof the innermost winding N , a rule of thumb is that each transformer winding turn corresponds to300 V1.

Next, nine Ψ−i pairs were calculated from equation (3) using MATLAB and put into a data le inorder to be used as input to the XFMRmodel in PSCAD. This set of Ψ−i pairs is now approximatelyequal to the Ψ − i pairs originally calculated by the parameters calculation application. For thechange in core size, the relative dimensions of the core were maintained, i.e. the ratios lY

lL, lO

lL, AY

AL,

AO

ALwere kept constant. Also the relation between the length of the leg lL and the cross-sectional

area of the leg AL was maintained. In this manner the change in core size can be expressed by thechange in the length of the leg lL. How the length of the leg was measured is shown in Fig. 3. Thelengths lL1 = 1.00 · lL, lL2 = 1.05 · lL, lL3 = 1.10 · lL and lL4 = 1.20 · lL were used. The length of the

1From correspondence with supervisor S. Mousavi

18

Page 22: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 2 4 6 8150

200

250

300

350

400

450

500

current [A]

Flu

x lin

kage [

Wb

turn

s]

Figure 9: T1: Leg ux for four core sizes

core leg was thus increased by 5, 10 and 20%. These four core sizes will be referred to as 100, 105,110 and 120%. For each core size, nine Ψ− i pairs were calculated and put into data les otherwiseequal to the parameters le originally generated by the parameters calculation application. Onlythe Ψ − i pairs of each limb were changed. This is a simplication which means that the changein core size only aects the Ψ − i relation, and not the core loss resistance of the transformer. Inreality increased core size leads to increased active core losses, according to (7). For this project,the dependence of core geometry on the constant K in (7) was unknown and therefore had to beomitted. Fig.9 shows Ψ(i) of the transformer leg for the dierent core sizes. Figs. 10 and 11 showΨ(i) of the yoke and outer limb, respectively.

As can be seen in Figs. 9-11, increasing the core size gives a higher maximum ux linkage,i.e. moves the point of saturation upwards. This creates a margin for the DC-excited transformerto reach the saturated state. It is therefore expected that the larger core sizes will be associatedwith smaller reactive power demand compared to the smaller core size for the same GIC levels; i.e.that the transformer with larger core will display less sensitivity to GIC in terms of reactive powerabsorption. Simulations in PSCAD were carried out as described in the previous section. For eachcore size (100, 105, 110 and 120% of the original size) the fundamental component of the reactivepower drawn from the supply was calculated according to (1) for 12 dierent GIC levels between0-525 A.

4.2.2 Transformers T2 and T3

The transformer T2 is a recently manufactured 300 MVA ve-limb power transformer. Completedesign data for this transformer were available, including absolute core dimensions, number of turnsof the innermost winding and the B-H characteristics. In order to obtain the Ψ− i relation for thistransformer, the B-H data set was tted to the Frolich equation (2) in MATLAB and the parametersa and b were obtained. The original B-H curve of T2 and the Frolich t are shown in Fig. 12. Sincethe length and cross-sectional area of each core section were known, as well as the number of turns

19

Page 23: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 2 4 6 850

100

150

200

250

300

current [A]

Flu

x lin

kage [

Wb

turn

s]

Size1(100%)

Size2(105%)

Size3(110%)

Size4(120%)

Figure 10: T1: Yoke ux for four core sizes

0 2 4 6 850

100

150

200

250

300

current [A]

Flu

x lin

kage [

Wb

turn

s]

Size1(100%)

Size2(105%)

Size3(110%)

Size4(120%)

Figure 11: T1: Outer limb ux for four dierent core sizes

20

Page 24: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 100 200 300 400 500 600 7000

0.5

1

1.5

2

2.5

H [A/m]

B [

T]

Figure 12: T2: B-H curve (blue) and t to the Frolich equation (red)

of the innermost winding, the ux linkage - current relation could be obtained from (3) directly,from which nine Ψ− i pairs could be extracted. Four sets of Ψ− i pairs for dierent core sizes, (100,105, 110 and 120%) could then be calculated by varying the limb lengths and cross-sectional areasin (3). The core was scaled in the same manner as transformer T1, described in the previous section.Fig. 13 shows the Ψ− i relation of the core leg, for the four dierent sizes of the transformer core.As can be seen in the gure an increase in core size is associated with a margin of the saturationcurve. The yoke and outer limb uxes show very similar core size dependence as the leg ux. It canbe noted that the maximum ux linkage level for T2 is much lower than that of T1. T2 is thereforeexpected to display an enhanced vulnerability to GIC in terms of reactive power increase comparedto the transformer T1.

PSCAD simulations and calculations of the fundamental component of reactive power absorptionwere carried out in the same manner as described in the previous section. Simulations for four coresizes at GIC levels between 0-150 A were carried out. The reason for the dierence in GIC rangesimulated as compared to T1 is that T2 reaches the saturated state at much lower GIC levels thanT1.

The transformer T3 is a recently manufactured three-limb transformer. Design data, includingB-H curve and core dimensions were available. However, short-circuit losses and zero-sequenceimpedance were not available, for which reason they had to be assumed. These assumptions weremade using test reports from transformers with similar rating as T3 as a reference. These assump-tions will aect active and reactive power demand in steady state (when no GIC is present) as wellas during a GIC event.

The same procedure as for transformer T2 was followed in order to obtain the Ψ−i characteristicsof transformer T3. Fig. 4 shows the core dimensions The t of the B-H data to the Frolich equation(2) is shown in Fig. 14. The core size was again scaled into four sizes; 100, 105, 110 and 120%.The Ψ− i relations for the leg and yoke of the transformer are shown in Fig.15. GIC levels between0-500 A were simulated.

21

Page 25: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 20 40 60 80 10010

20

30

40

50

60

70

80

90

100

current [A]

Flu

x lin

kage [

Wb

turn

s]

Figure 13: T2: Leg ux for four dierent core sizes

0 100 200 300 4000

0.5

1

1.5

2

2.5

H [A/m]

B [

T]

Figure 14: T3: B-H curve (solid) and t to Frolich (dotted)

22

Page 26: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 20 40 60 80 100 12020

30

40

50

60

70

80

current [A]

Flu

x lin

kage [

Wb

turn

s]

Size 100%

Size 105%

Size 110%

Size 120%

Figure 15: T3: Leg ux for four dierent core sizes

4.3 Results

From each simulation of GIC events for transformer T1-T3, Q(1) was calculated from equation (1).Q(1) as a function of IGIC for the three transformers, and for four dierent core sizes, are shownin Figs. 16-18. The function Q(IGIC) is apparently nonlinear for all three transformers. Q(1)

increases linearly with IGIC up to some certain level Qmax. The increase rate and the maximumlevel Qmaxare however dierent for the three dierent transformers.

From Figs. 16-18 it is clear that a larger transformer core leads to decreased reactive powerabsorption of the transformer during a GIC event.

4.4 Discussion

The results shown in Figs. 16, 17 and 18 indicate that the reactive power demand of a powertransformer during a GIC event decreases with increased core size. For all three transformersthe function Q(IGIC) is nonlinear, with a linear increase in a certain interval. The increase in Qthen declines towards a maximum value Qmax. The core size impact seems to increase with GICmagnitude, i.e. a larger transformer core seems to be associated with a smaller slope in the linearregion of Q(IGIC). This can be further investigated by calculating the ratio Qx

Q100for dierent levels

of GIC. Here, Qx is reactive power demand of core sizes 105, 110 and 120%, Q100 is the reactivepower demand for the original core size. Figs. 19-21 show the ratio Qx

Q100for transformers T1-T3.

As can be seen in the gures, the overall core size dependence seems to increase with increased GICmagnitude for all three transformers.

Transformers T1 and T2 are both ve-limb transformers, and have similar power ratings. Theyare therefore expected to display similar behavior when exposed to GIC. However, from Figs. 16 and17 it is apparent that transformer T2 reaches much higher Q levels for lower GIC magnitude thanT1, and that the maximum value Qmax,T2 is lower than Qmax,T1, although initially T1 and T2 havealmost identical reactive power demands. This dierence in behavior is due to the dierence in coreux characteristics, shown in Figs.9 and 13. The ux characteristics of the original size are given by

23

Page 27: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 100 200 300 400 500 6000

20

40

60

80

100

120

GIC, A

Q,

MV

ar

size1(100%)

size2(105%)

size3(110%)

size4(120%)

Figure 16: T1: Reactive power as a function of GIC for four dierent core sizes

0 50 100 150

20

40

60

80

100

GIC [A]

Q [

MV

ar]

size1(100%)

size2(105%)

size3(110%)

size4(120%)

Figure 17: T2: Reactive power as a function of GIC for four dierent core sizes

24

Page 28: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 100 200 300 400 50050

60

70

80

90

100

110

120

GIC [A]

Q [

MV

ar]

size1(100%)

size2(105%)

size3(110%)

size4(120%)

Figure 18: T3: Reactive power demand as a function of GIC for four core sizes

equation (3) for transformer T2 and by equation (4) for transformer T1. The parameters a′ and b′

in (4) can dier between the two transformers due to a dierence in core cross-sectional area, corelength and number of turns, as well as in the Frolich parameters a and b representing the magneticproperties of the core material. Since these parameters are unknown for T1 (only a′ and b′areknown) it is not possible to determine wherein the dierence lays. However, one can use equation(3) to nd an indication of which parameters are most signicant for the ux characteristics. Theparameters that were used for the Ψ− i characteristics of T1 and T2 are presented in table 2. Fig.22 shows a simple comparison of the impact of the dierent parameters. As can be seen in thegure, the dierence in the Frolich parameters a and b gives a relatively small deviation of Ψ(i).The dierence in parameters l,A, and N have a greater impact on the deviation. In particular, itappears that the number of turns N causes the two Ψ(i) curves to dier.

As mentioned earlier, the assumed length, cross-sectional area and number of turns for T1are based on the geometry of another transformer core, from a transformer with power and voltageratings similar to T1, and the rule of thumb that each transformer winding corresponds to 300 volts,and the assumption that the innermost winding is the secondary winding. Since these parametervalues dier from the parameters of T2, in particular with respect to number of turns N , they maynot be realistic. However, the l, A and N dependence of the ux characteristics of T1 is includedin the parameters a′ and b′ in (4). The reason that there is a dierence between T1 and T2 maybe that

There is, in reality, a great dierence in the Frolich parameters a and b, i.e. the magneticcharacteristics of the core material given by (2).

The methods for obtaining the Frolich parameters (optimization process from test report datavs tting the B-H data to the Frolich equation) give very dierent result, leading to a greatdierence in a and b.

The two transformers are in fact very dierent in terms of core geometry and number of turnsof the innermost winding.

25

Page 29: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

T1 T2a 2.3460 7.5240b 0.5210 0.4845

lleg[m] 3.119 2.621Aleg[m2] 0.5041 0.8963

N 409 44

Table 2: Parameters of T1 and T2

Figure 19: Relative reactive power demand for transformer T1

The dierence in ux characteristics between T1 and T2 may of course also be due to a combinationof the proposed explanations above.

As can be seen in Figs.16, 17 and 18, the reactive power as a function of GIC, Q(IGIC) , isnon-linear for all three transformers simulated. This diers from what is reported in [1] and [12],where the reactive power absorption is given as a linear function of GIC magnitude. However, [4]reports similar ndings. The study described in [4] has been carried out on a larger system, withseveral transformers. The non-linear saturation curve used for transformer characteristics in thisstudy was based on eld test measurements. It is reported that that the relation between GICmagnitude and reactive power losses is non-linear. The relation between GIC and reactive powerlosses ∆Q

IGICis in [4] reported to vary between 0.32 and 0.50 MVAR/A. The corresponding ratios

for the simulations of transformers T1-T3 above are as follows. For T1, ∆QIGIC

varies between 0.19and 0.35 MVAR/A, for T2 between 0.19 and 0.66 MVAR/A, and for three-limb transformer T3between 0.08 and 0.15 MVAR/A.

The results presented in the previous section give a clear indication that increased transformercore size makes the transformer less sensitive to GIC exposure in terms of reactive power losses.One important simplication that has been made for the size dependence study is neglecting thechange in active core losses when the core size is increased, as described in section 4.2.1. In reality,the active core losses (eddy current losses and hysteresis losses) are expected to increase when the

26

Page 30: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

Figure 20: Relative reactive power demand for transformer T2

Figure 21: Relative reactive power demand for transformer T3

27

Page 31: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

0 20 40 60 800

200

400

600

I [A]

Psi [W

btu

rns]

0 20 40 60 800

200

400

600

I [A]

Psi [W

btu

rns]

0 20 40 60 800

200

400

600

I [A]

Psi [W

btu

rns]

0 20 40 60 800

200

400

600

800

I [A]

Psi [W

btu

rns]

Figure 22: Comparison of transformer parameters impact on ux-current relation. Upper left gure:The original ux-current characteristics of T1 (blue, solid line) and T2 (red, dotted line). Upperright gure: Flux-current with the dierence in a and b maintained, l, A and N equal. Lower leftgure: Flux-current with the dierence in a, b, and N maintained, l and A equal. Lower rightgure: Flux-current with the dierence in a, b, l, and A maintained, N equal.

28

Page 32: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

core size is increased. This means that the reactive power losses are decreased. Taking the changein Ploss into account is therefore expected to further decrease the reactive power losses for enhancedcore sizes.

Increasing the core size is associated with a dramatic increase in production cost, since the costof the core material is proportional to the volume of the core. A scale wise core size increase of 20%thus leads to a price increase of 73%, since the volume is proportional to l3. For the simulationsabove, the core length and cross-sectional area have been equally increased (not scale wise); anincrease to core size 4 in the simulations above is thus associated with a volume increase of 44%.Also the costs of transportation are increased if the transformer core size is increased. Therefore,one should not necessarily start manufacturing larger transformer cores in order to protect thepower system from damage caused by GIC.

A number of other precautions for power system protection have been suggested. In [15] and [12]the importance of space weather forecasts and the communication of such forecasts to transmissionsystem operators is stressed. In [12] it is pointed out that monitoring and assessment procedures canprepare transmission system operators for responses in case of a GIC event. It is here recommendedthat, among other things, unusual swings in voltage or reactive power be monitored, as well asabnormal temperature rise in transformers. Also reactive power reserves should be monitored.Operators must also be prepared for possible disruptions of telecommunications systems during aGIC event, which may cause false energy management system indications. In case of a severe GICevent operators must be prepared to remove transformers and transmission lines from service. Itis however pointed out in [12] that removal of equipment from service may increase loading onother equipment, putting the system in a less secure state. Since operators may be required toevaluate trade-os such as these with very limited information at hand, the importance of carryingout studies ahead of time is emphasized.

In general, all investments in power system protection from GIC must of course be evaluatedin relation to the expected frequency of these events, and the monetary losses associated withthem. Since there is currently no consensus regarding either the risk of a strong solar storm (ofthe same proportions as the 1989 Quebec event described in section 2.3 or greater) or the expectedconsequences associated with such an event, this is not an easy task. Apart from the monetary lossessuered during a large blackout, the opinion of the public must also be taken into consideration.Large, long-lasting power outages are generally associated with great discontent among consumersdirected towards operators, ocial agencies and politicians. Consequences such as these must ofcourse also be taken into account when discussing potential threats to the power system, andinvestments in system protection.

29

Page 33: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

5 Conclusions and further studies

The results presented in the previous section indicate that increased transformer core cross-sectionalarea leads to smaller increase in reactive power demand during GIC events.

It is also noted that the the relation between GIC and reactive power demand is non-linear.It is apparent that this relation depends on the B-H characteristics of the the core, which is aproperty of the core material. The reactive power - GIC relation therefore diers between dierenttransformers, even if the power ratings are the same. Since the results presented in the previoussection give a clear indication that a larger transformer core leads to smaller increase in reactivepower drawn from the supply, it can be concluded that a transformer with a larger core is lesssensitive to GIC disturbances, in terms of reactive power absorption. It can also be concluded thatwhen using an advanced simulation model, incorporating non-linear elements, the relation betweenreactive power absorption and GIC magnitude is non-linear. Since the core size dependence ofreactive power absorption diers greatly between transformer T1 and T2, no formulation of thefunction Q(IGIC) for ve-leg core transformers may be attempted based on the work presented inthis thesis.

For future studies of the core size dependence of reactive power absorption increase due toGIC, simulations of GIC with design data as input method must be properly implemented inan electromagnetic transients software. The method that has been used in order to obtain theB-H characteristics of the transformer core based on design data in this thesis requires manualmanipulation of a data le, which is time consuming and impractical. Also, as mentioned earlier,the impact of transformer core size on the active power absorption has been omitted for this project.Future studies should include this property.

In this thesis project, the core size dependence of reactive power absorption as a function of GIClevel for single phase transformers and auto transformers have not been investigated. Attempts tosimulate GIC events in auto transformer have been made, but no satisfying adaptions of the XFMRmodel in PSCAD to auto transformers have been achieved. It is therefore suggested that futurestudies incorporate implementations of the XFMR model for single phase transformers and autotransformers. It is also clear that in order to draw conclusions of the impact of GIC events on thepower system stability, simulations of larger networks including several power transformers mustbe performed.

When simulating a larger network, the XFMR transformer model used in this project shouldbe combined with a ground conductivity model representing expected GIC level depending ongeographic location of the transformer substation. Also, when studying large networks includingseveral transformer substations, the results presented in [4] regarding the impact on geomagneticstorm orientation on the DC current levels owing in the transformer neutral should be taken intoconsideration. According to [4], the topology of the power system in relation to the orientationof the geomagnetic storm has a great impact on the DC current levels injected in the transformerneutral. In the simulations presented in [4] only substations in the extreme ends of the systemsexperience saturation due to GIC.

In this project, only transformers with small inductive load have been simulated. In furtherstudies, simulations of transformer with larger inductive and capacitive loading should be performed,since no relation between loading and change in reactive power absorption of the transformer havebeen investigated here.

30

Page 34: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

References

[1] N. Chiesa, L. Abbas, H. K. Hoidalen, B. Mork, O. Rui, and T. Ohnstad. Five-leg transformermodel for gic studies. In International Conference on Power System Transients, (IPST2013),Vancouver, July 2013.

[2] H.W. Dommel. Electromagnetic Transients Program Theory Book. BPA, 1987.

[3] R. Girgis, K. Vedante, and K. Gramm. Eects of geomagnetically induced currents on powertransformers and power systems. Technical report, Cigré, Paris, 2012.

[4] L. Gérin-Lajoie, J. Guillon, J. Mahseredjian, and O. Saad. Impact of transformer saturationfrom gic on power system voltage regulation. In International Conference on Power SystemsTransients (IPST2013), Vancouver, July 2013.

[5] H. K. Hoidalen, B.A. Mork, F. Gonzalez, D. Ishchenko, and N. Chiesa. Implementation andverication of the hybrid transformer model in atpdraw. Electric Power Systems Research,79(3):454 459, 2009.

[6] F. León, P. Gómez, J.A. Martinez-Velasco, and M. Rioual. Power System Transients: Param-eter Determination. CRC Press, 2009.

[7] J.A. Martinez and B.A. Mork. Transformer modeling for simulation of low-frequency transients.In Power Engineering Society General Meeting, 2003, IEEE, volume 2, pages 1225 Vol. 2,2003.

[8] Metatech. Evaluation of the vulnerability of the statnett and svenska kraftnat transmissionnetworks to the eects of geomagnetic storms. Technical report, Metatech, 2000.

[9] B.A. Mork, F. Gonzalez, D. Ishchenko, D.L. Stuehm, and J. Mitra. Hybrid transformer modelfor transient simulation mdash;part i: Development and parameters. Power Delivery, IEEETransactions on, 22(1):248255, 2007.

[10] B.A. Mork, D. Ishchenko, F. Gonzalez, and S.D. Cho. Parameter estimation methods for ve-limb magnetic core model. Power Delivery, IEEE Transactions on, 23(4):20252032, 2008.

[11] S. A. Mousavi. Electromagnetic modelling of power transformers with dc magnetization, 2012.QC 20121121.

[12] IEEE PES Technical Counsil Task Force on Geomagnetic Disturbances. Geomagnetic distur-bances. IEEE Power and Energy Magazine, 11(4):7178, July 2013.

[13] Committee on the Societal and National Research Council Economic Impacts of Severe SpaceWeather Events: A Workshop. Severe Space Weather EventsUnderstanding Societal andEconomic Impacts:A Workshop Report. The National Academies Press, 2008.

[14] P. R. Price. Geomagnetically induced current eects on transformers. Power EngineeringReview, IEEE, 22(6):6262, June.

[15] SvK. Skydd mot geomagnetiska stormar. Report, http://www.svk.se/rapporter, SvenskaKraftnät, March 2012.

31

Page 35: Impact of transformer core size on the reactive power requirement of power transformers due to GIC
Page 36: Impact of transformer core size on the reactive power requirement of power transformers due to GIC

TRITA TRITA XR-EE-ETK 2014:16

www.kth.se